SPECIAL INSPECTION REPORTSnCedar WA 980 6636511 o Lynnwood, A ES TES TI G ENGINEERS 425-742-9360 n 1rereaoa;l7 COMPANY LABORATORY COMPACTION CHARACTERISTICS OF SOIL REPORT Report Number: M7191337.0005A Service Date: 03/25/20 Report Date: 03/27/20 Task: Client Project City of Edmonds WA City of Edmonds Waterfront Redevelopment Attn: Henry Schroder 220 Railroad Avenue Public Works Dept Edmonds, WA 121 Fifth Ave N Edmonds, WA 98020 Project No. M7191337 Laboratory Reference # 4467 Sample Description: 5/8" crushed gravel Sample Location: Jobsite stockpile Date Sampled: 3/25/2020 Date Delivered: 3/25/20 Sampled By: K. Pauly Delivered By: K. Pauly Test Results: Test Method: ASTM D-1557 Method C / C 127 / D 4718 (if needed) 133.4 pcf @ 6.1 % See attached analysis sheet Material sampled in accordance with aooroariate standard. (ASTM D75. AASHTO T2) Services: Special Inspection/Materials Testing Tested By: Molly Strain Report Distribution (1) City of Edmonds WA, Henry Schroder (1) City of Edmonds WA, Eric Carter /� p� ywgvrt u �b{t ice+ (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Nic Morin Reviewed By: 4 // (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz Zenaida Revilla (1) Reid Middleton, Blaine McRae Laboratory Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CT0002, 10-16-13, Rev.a Page 1 of 1 MAYES TESTING ENGINEERS, INC. Alferracon COMPANY 20225 Cedar Valley Road, Suite 110 Ph 425-742-9360 Moisture Density Relationship Test Lynnwood, WA 98036 Fax 425-745-1737 Client: City of Edmonds, WA Report Date: 3/27/2020 Edmonds, WA Date Tested: 3/26/2020 Project: City of Edmonds Waterfront Redevelopment Project Number: M7191337 Test Method: ASTM D-1557 Method C / C 127 / D 4718 (if needed) Lab Number: 4467 Mechanical X Wet Preparation F-] Test Results Dry Preparation Hand Tamper Optimum Water Content % 1 6.1 Date Received: 3/25/2020 Max Dry Density lbs/ft'l 133.4 Source of Sample: Sieve Analysis Description of Sample: 5/8" crushed gravel Sieve Size Percent Retained 3/4 0% ero Void line plotted at an assumed SpG of: 2.65 3/8 22% ax. Density Uncorrected: 133.4 #4 51 % Water Content, % of dry Weight Tested By: M. Strain Information in this report applies only to the actual samples tested and shall not be reproduced except in full, without the approval of Mayes Testing Engineers, Inc. M7191337.0005A.1/3/27/2020 MTE Form # 149, Rev 2, 6/02 GROUT COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0003A Service Date: 09/09/19 Report Date: 09/18/19 Revision 1 - add strength requirement Task: Client 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project - M7191427 Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Mix ID: 5G55149 Supplier: Cadman Batch Time: 0630 Plant: 32 Truck No.: 376 Ticket No.: 674906 Field Test Data Test Result Slump (in): 11 Grout Temp. (F): 73 Ambient Temp. (F): 61 Laboratory Test Data Set Specimen Date Date No. ID Received Tested 1 a 09/10/19 09/16/19 1 b 09/10/19 10/07/19 1 c 09/10/19 10/07/19 1 d 09/10/19 10/07/19 1 e 09/10/19 Initial Cure: Outside Plastic Lids Comments: Specification Arerra[On c...A., Sample Date: 09/09/19 Sample Time: 0930 Sampled By: Earl Uy Weather Conditions: Cloudy Accumulative Yards: 18 Batch Size: 9 Sample Size: Sample Location: Placement Location: Pile 631 Form Material: Plastic Mold No. Units: 5 Samples Plumb: Yes Temperature Range: Maximum Compressive Age Area Load Strength Fracture Tested (days) (sq in) (lbs) (psi) Type By 7 3.08 17,870 5,800 2 JHK 28 28 28 Hold Final Cure: Moist Room Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Earl Uy Reported To: Contractor: WG Clark Construction Co. Report Distribution: (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) WG Clark Construction Co, Jim Bray Reviewed By: Heath Defoor, PE Senior Project Field Manager Test Methods: ASTM C 31, ASTM C39, ASTM C109, ASTM C138, ASTM C143, ASTM C1019, ASTM C1064 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CRoo09, 11-16-12, Rev.6 Page 1 of 1 GROUT COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0003A Service Date: 09/09/19 Report Date: 10/08/19 Revision 2 - 28-day results Task: Client 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project - M7191427 Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Arerra[On c...A., Specified Strength: 4,000 psi @ 28 days Sample Date: 09/09/19 Sample Time: 0930 Sampled By: Earl Uy Mix ID: 5G55149 Weather Conditions: Cloudy Supplier: Cadman Accumulative Yards: 18 Batch Size: 9 Batch Time: 0630 Plant: 32 Sample Size: 2x4" Truck No.: 376 Ticket No.: 674906 Sample Location: Placement Location: Pile 631 Field Test Data Form Material: Plastic Mold No. Units: 5 Test Result Specification Samples Plumb: Yes Slump (in): 11 Temperature Range: Grout Temp. (F): 73 Ambient Temp. (F): 61 Laboratory Test Data Maximum Compressive Set Specimen Date Date Age Area Load Strength Fracture Tested No. ID Received Tested (days) (sq in) (lbs) (psi) Type By 1 a 09/10/19 09/16/19 7 3.08 17,870 5,800 2 JHK 1 b 09/10/19 10/07/19 28 3.14 24,090 7,670 2 HRB 1 c 09/10/19 10/07/19 28 3.11 23,610 7,590 4 HRB 1 d 09/10/19 10/07/19 28 3.11 24,510 7,880 4 HRB 1 e 09/10/19 10/07/19 28 3.11 23,880 7,680 4 HRB Average (28 days) 7,700 Initial Cure: Outside Plastic Lids Final Cure: Moist Room Comments: Average compressive strength of 28 day Cylinder complies with the specified strength. Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Earl Uy Reported To: Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Senior Project Field Manager Test Methods: ASTM C 31, ASTM C39, ASTM C109, ASTM C138, ASTM C143, ASTM C1019, ASTM C1064 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cRoo09, 11-16-12, Rev.6 Page 1 of 1 Distribution Page Report Number: M7191427.0003A Service Date: 09/09/19 Report Date: 10/08/19 Revision 2 - 28-day results Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 GROUT OBSERVATIONS REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0004 Service Date: 09/10/19 Report Date: 09/16/19 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds. WA 98020 Permit No.: BLD2018-1658 Samples: (5) 2x4" cylinders On site for the following inspections: 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmond, WA Project No. Weather: M7191427 Drizzle, 60°F 1) Reinforcement and grout placement of (54) cubic yards Cadman mix 5G55149 for auger -cast piles #602, 626, 627, 629, 603 and 625 at SW end of site. The piles are 18" diameter x 50' or 60' deep. Verified reinforcement — (6) #6 verticals with #4 spiral at 4-1/2" pitch (3" pitch at top 12'), per details on 18/S3.2 (wheel spacers for clearance). The grout was placed via pump hose. Cast (5) 2x4" cylinders for compressive strength testing (4000 psi at 28 days required). Contractor requested extra cylinder. 2) Reinforcing steel for total of (33) cages for 50' and 60' deep auger -cast piles. Verified reinforcing steel number, size and spacing, per details on 18/S3.2. Note: General contractor stated that there are another (55) reinforcing steel cages still to be delivered to site. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Charles Solway Reported to: WG Clark Construction Company Contractor: WG Clark Construction Co. Report Distribution: (1) Edmonds Senior Center, Daniel (1) City of Edmonds WA, Leif Bjorback Johnson (1) City of Edmonds WA, Milton (1) Environmental Works, Inc., Sally Reviewed By: Thompson Knodell 4 a e —� (1) Mayes Testing Engineers, Inc, (1) Mayes Testing Engineers, Inc, Heath Defoor, PE Donna Pollard Todd Wirtz (1) WG Clark Construction Co, Jim Senior Project Field Manager Brav The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CT000t, 10-16-13, Rev.10 Page 1 of 1 GROUT COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0004A Service Date: 09/10/19 Report Date: 09/18/19 Task: Client 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project - M7191427 Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Mix ID: 5G55149 Supplier: Cadman Batch Time: 0644 Plant: 32 Truck No.: 366 Ticket No.: 675316 Field Test Data Test Result Slump (in): 9 Grout Temp. (F): 67 Ambient Temp. (F): 60 Laboratory Test Data Specification Sample Date: Sampled By: Weather Conditions: Accumulative Yards: Sample Size: Sample Location: Placement Location: Form Material: Samples Plumb: Temperature Range: Arerra[On c...A., 09/10/19 Sample Time:0920 Charles Solway Drizzle 54 Batch Size: 9 2"x4" Pile 627 Augercast piles 602, 626, 627, 629, 603, 625 Plastic Mold No. Units: Yes Maximum Compressive Set Specimen Date Date Age Area Load Strength Fracture Tested No. ID Received Tested (days) (sq in) (lbs) (psi) Type By 1 1 09/11/19 09/17/19 7 3.11 16,520 5,310 2 KWB 1 2 09/11/19 10/08/19 28 1 3 09/11/19 10/08/19 28 1 4 09/11/19 10/08/19 28 1 5 09/11/19 10/08/19 28 Initial Cure: Cure Box Final Cure: Moist Room Min Temp: 64 Max Temp: 64 Comments: Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Charles Solway Reported To: Contractor: WG Clark Construction Co. Report Distribution: (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) WG Clark Construction Co, Jim Bray Reviewed By: Heath Defoor, PE Senior Project Field Manager Test Methods: ASTM C 31, ASTM C39, ASTM C109, ASTM C138, ASTM C143, ASTM C1019, ASTM C1064 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CRoo09, 11-16-12, Rev.6 Page 1 of 1 GROUT COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0004A Service Date: 09/10/19 Report Date: 10/09/19 Revision 1 - 28-day results Task: Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project - M7191427 Edmonds Senior Center Activity Center 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Mix ID: 5G55149 Supplier: Cadman Batch Time: 0644 Truck No.: 366 Plant: 32 Ticket No.: 675316 Field Test Data Test Result Slump (in): 9 Grout Temp. (F): 67 Ambient Temp. (F): 60 Laboratory Test Data Specification Arerra[On c...A., Sample Date: 09/10/19 Sample Time:0920 Sampled By: Charles Solway Weather Conditions: Drizzle Accumulative Yards: 54 Batch Size: 9 Sample Size: 211x4" Sample Location: Pile 627 Placement Location: Augercast piles 602, 626, 627, 629, 603, 625 Form Material: Plastic Mold No. Units: Samples Plumb: Yes Temperature Range: Maximum Compressive Set Specimen Date Date Age Area Load Strength Fracture Tested No. ID Received Tested (days) (sq in) (lbs) (psi) Type By 1 1 09/11/19 09/17/19 7 3.11 16,520 5,310 2 KWB 1 2 09/11/19 10/08/19 28 3.11 23,320 7,500 2 HRB 1 3 09/11/19 10/08/19 28 3.11 23,550 7,570 4 HRB 1 4 09/11/19 10/08/19 28 3.14 23,660 7,530 4 HRB 1 5 09/11/19 10/08/19 28 3.11 22,970 7,390 4 HRB Average (28 days) 7,500 Initial Cure: Cure Box Final Cure: Moist Room Min Temp: 64 Max Temp: 64 Comments: Average compressive strength of 28 day Cylinder complies with the specified strength. Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Charles Solway Reported To: Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Senior Project Field Manager Test Methods: ASTM C 31, ASTM C39, ASTM C109, ASTM C138, ASTM C143, ASTM C1019, ASTM C1064 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cRoo09, 11-16-12, Rev.6 Page 1 of 1 Distribution Page Report Number: M7191427.0004A Service Date: 09/10/19 Report Date: 10/09/19 Revision 1 - 28-day results Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 GROUT OBSERVATIONS REPORT Report Number: M7191427.0005 Service Date: 09/11/19 Report Date: 09/16/19 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Samples: (5) 2x4" cylinders MAYES TESTING ENGINEERS nlrerracan cmernxv 20225 Cedar Vallev Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmond, WA Project No. Weather: M7191427 Clear Pile Inspection and Grout Inspected the reinforcement and grout placement of (60) cubic yards of Cadman concrete mix 5G55149 for (11) auger -cast piles #637, 639, 641, 606, 607, 622, 621, 643, 613, 617 and 645. The reinforcement of the piles was verified in reference to the approved project documents and structural plans found on schedule 18/S3.2. The grout was placed via hose pump and deposited into each of the auger -cast piles. There were (5) 2x4" grout cylinders cast for compressive strength testing with a required f'c of 4000 psi at (28) days. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Erik Tichenor Reported to: WG Clark Construction Co. Contractor: WG Clark Construction Co. Report Distribution: (1) Edmonds Senior Center, Daniel (1) City of Edmonds WA, Leif Bjorback Johnson (1) City of Edmonds WA, Milton (1) Environmental Works, Inc., Sally Reviewed By: Thompson Knodell 4 a e —� (1) Mayes Testing Engineers, Inc, (1) Mayes Testing Engineers, Inc, Heath Defoor, PE Donna Pollard Todd Wirtz (1) WG Clark Construction Co, Jim Senior Project Field Manager Brav The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CT000t, 10-16-13, Rev.10 Page 1 of 1 GROUT COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0005A Service Date: 09/11/19 Report Date: 09/20/19 Task: Client 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project - M7191427 Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Mix ID: 5G55149 Supplier: Cadman Batch Time: 0850 Plant: 32 Truck No.: 347 Ticket No.: 676004 Field Test Data Test Result Specification Slump (in): Grout Temp. (F): 74 Ambient Temp. (F): 58 Laboratory Test Data Set Specimen Date No. ID Received 1 1 09/16/19 1 2 09/16/19 1 3 09/16/19 1 4 09/16/19 1 5 09/16/19 Initial Cure: Outside Comments: Arerra[On c...A., Sample Date: 09/11/19 Sample Time:1020 Sampled By: Erik Tichenor Weather Conditions: Clear Accumulative Yards: 36 Batch Size: 9 Sample Size: Sample Location: Truck chute Placement Location: Augercast piles Form Material: Plastic Mold No. Units: Samples Plumb: Yes Temperature Range: 62 - 62 Maximum Compressive Date Age Area Load Strength Fracture Tested Tested (days) (sq in) (lbs) (psi) Type By 09/18/19 7 3.11 18,770 6,030 4 HRB 10/09/19 28 10/09/19 28 10/09/19 28 Hold Final Cure: Moist Room Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Erik Tichenor Reported To: Contractor: WG Clark Construction Co. Report Distribution: (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) WG Clark Construction Co, Jim Bray Reviewed By: Heath Defoor, PE Senior Project Field Manager Test Methods: ASTM C 31, ASTM C39, ASTM C109, ASTM C138, ASTM C143, ASTM C1019, ASTM C1064 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CRoo09, 11-16-12, Rev.6 Page 1 of 1 GROUT COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0005A Service Date: 09/11/19 Report Date: 10/11/19 Revision 1 - 28-day results Task: Client 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project - M7191427 Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Arerra[On c...A., Specified Strength: 4,000 psi @ 28 days Sample Date: 09/11/19 Sample Time:1020 Sampled By: Erik Tichenor Mix ID: 5G55149 Weather Conditions: Clear Supplier: Cadman Accumulative Yards: 36 Batch Size: 9 Batch Time: 0850 Plant: 32 Sample Size: 2x4" Truck No.: 347 Ticket No.: 676004 Sample Location: Truck chute Placement Location: Augercast piles Field Test Data Form Material: Plastic Mold No. Units: Test Result Specification Samples Plumb: Yes Slump (in): Temperature Range: 62 - 62 Grout Temp. (F): 74 Ambient Temp. (F): 58 Laboratory Test Data Maximum Compressive Set Specimen Date Date Age Area Load Strength Fracture Tested No. ID Received Tested (days) (sq in) (lbs) (psi) Type By 1 1 09/16/19 09/18/19 7 3.11 18,770 6,030 4 HRB 1 2 09/16/19 10/09/19 28 3.11 24,210 7,780 2 KWB 1 3 09/16/19 10/09/19 28 3.11 24,210 7,780 2 KWB 1 4 09/16/19 10/09/19 28 3.11 24,970 8,030 2 KWB 1 5 09/16/19 10/09/19 28 3.11 24,910 8,010 2 KWB Average (28 days) 7,900 Initial Cure: Outside Final Cure: Moist Room Comments: Average compressive strength of 28 day Cylinder complies with the specified strength. **NP = Not Performed Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Erik Tichenor Reported To: Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Senior Project Field Manager Test Methods: ASTM C 31, ASTM C39, ASTM C109, ASTM C138, ASTM C143, ASTM C1019, ASTM C1064 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cRoo09, 11-16-12, Rev.6 Page 1 of 1 Distribution Page Report Number: M7191427.0005A Service Date: 09/11 /19 Report Date: 10/11/19 Revision 1 - 28-day results Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 GROUT OBSERVATIONS REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0006 Service Date: 09/12/19 Report Date: 09/16/19 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds. WA 98020 Permit No.: BLD2018-1658 Samples: (5) 2x4" cylinders On site for the following inspections: 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmond, WA Project No. Weather: M7191427 630F 1) Reinforcement and grout placement of (63) cubic yards Cadman mix 5G55149 for auger -cast piles. The piles are 18" diameter x 50' or 60' deep. Today's piles installed are #'s 647, 608, 610, 615, 609, 614, 619, 620, 616, 649, 651 and 618 (12 total). Verified reinforcement — (6) #6 verticals with #4 spiral at 4-1/2" pitch (3" pitch a top 12'), per details on 18/S3.2. For clearance, 3" wheel spacers installed on cage. The grout was placed via pump hose. Cast (5) 2x4" cylinders for compressive strength testing (4000 psi at 28 days required). Contractor requested extra cylinder. 2) Reinforcement for additional (26) cages delivered to site. Verified reinforcing steel number, size and spacing, and cage length, per details on 18/S3.2. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Charles Solway Reported to: WG Clark Construction Company Contractor: WG Clark Construction Co. Report Distribution: (1) Edmonds Senior Center, Daniel (1) City of Edmonds WA, Leif Bjorback Johnson (1) City of Edmonds WA, Milton (1) Environmental Works, Inc., Sally Reviewed By: Thompson Knodell 4 a e —� (1) Mayes Testing Engineers, Inc, (1) Mayes Testing Engineers, Inc, Heath Defoor, PE Donna Pollard Todd Wirtz (1) WG Clark Construction Co, Jim Senior Project Field Manager Brav The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CT000t, 10-16-13, Rev.10 Page 1 of 1 GROUT COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0006A Service Date: 09/12/19 Report Date: 09/20/19 Task: Client 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project - M7191427 Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Mix ID: 5G55149 Supplier: Cadman Batch Time: 0748 Plant: 32 Truck No.: 312 Ticket No.: 676577 Field Test Data Test Result Slump (in): 11 Grout Temp. (F): 68 Ambient Temp. (F): 63 Laboratory Test Data Specification Sample Date: Sampled By: Weather Conditions: Accumulative Yards: Sample Size: Sample Location: Placement Location: Form Material: Samples Plumb: Temperature Range: Arerra[On c...A., 09/12/19 Sample Time:1000 Charles Solway Lower 60's 63 Batch Size: 9 2x4" Pile #610 Augercast Pile #'s 647, 608, 610, 615, 609, 614, 619, 620, 616, 649, 651, 618 Plastic Mold No. Units: Yes Maximum Compressive Set Specimen Date Date Age Area Load Strength Fracture Tested No. ID Received Tested (days) (sq in) (lbs) (psi) Type By 1 1 09/13/19 09/19/19 7 3.14 14,700 4,680 4 ZAJ 1 2 09/13/19 10/10/19 28 1 3 09/13/19 10/10/19 28 1 4 09/13/19 10/10/19 28 1 5 09/13/19 10/10/19 28 Initial Cure: Cure Box Final Cure: Moist Room Min Temp: 60 Max Temp: 60 Comments: Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Charles Solway Reported To: Contractor: WG Clark Construction Co. Report Distribution: (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) WG Clark Construction Co, Jim Bray Reviewed By: Heath Defoor, PE Senior Project Field Manager Test Methods: ASTM C 31, ASTM C39, ASTM C109, ASTM C138, ASTM C143, ASTM C1019, ASTM C1064 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CRoo09, 11-16-12, Rev.6 Page 1 of 1 GROUT COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0006A Service Date: 09/12/19 Report Date: 10/14/19 Revision 1 - 28-day results Task: Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project - M7191427 Edmonds Senior Center Activity Center 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Mix ID: 5G55149 Supplier: Cadman Batch Time: 0748 Truck No.: 312 Plant: 32 Ticket No.: 676577 Field Test Data Test Result Slump (in): 11 Grout Temp. (F): 68 Ambient Temp. (F): 63 Laboratory Test Data Specification Arerra[On c...A., Sample Date: 09/12/19 Sample Time:1000 Sampled By: Charles Solway Weather Conditions: Lower 60's Accumulative Yards: 63 Batch Size: 9 Sample Size: 2x4" Sample Location: Pile #610 Placement Location: Augercast Pile #'s 647, 608, 610, 615, 609, 614, 619, 620, 616, 649, 651, 618 Form Material: Plastic Mold No. Units: Samples Plumb: Yes Temperature Range: Maximum Compressive Set Specimen Date Date Age Area Load Strength Fracture Tested No. ID Received Tested (days) (sq in) (lbs) (psi) Type By 1 1 09/13/19 09/19/19 7 3.14 14,700 4,680 4 ZAJ 1 2 09/13/19 10/10/19 28 3.11 22,400 7,200 4 HRB 1 3 09/13/19 10/10/19 28 3.08 22,850 7,420 4 HRB 1 4 09/13/19 10/10/19 28 3.08 23,260 7,550 4 HRB 1 5 09/13/19 10/10/19 28 3.08 20,800 6,760 2 HRB Average (28 days) 7,230 Initial Cure: Cure Box Final Cure: Moist Room Min Temp: 60 Max Temp: 60 Comments: Average compressive strength of 28 day Cylinder complies with the specified strength. Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Charles Solway Reported To: Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Senior Project Field Manager Test Methods: ASTM C 31, ASTM C39, ASTM C109, ASTM C138, ASTM C143, ASTM C1019, ASTM C1064 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cRoo09, 11-16-12, Rev.6 Page 1 of 1 Distribution Page Report Number: M7191427.0006A Service Date: 09/12/19 Report Date: 10/14/19 Revision 1 - 28-day results Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 GROUT COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0007A Service Date: 09/13/19 Report Date: 09/24/19 Task: Client 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project - M7191427 Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Mix ID: 5G55149 Supplier: Cadman Batch Time: 0903 Plant: 32 Truck No.: 429 Ticket No.: 677282 Field Test Data Test Result Specification Slump (in): Grout Temp. (F): 75 Ambient Temp. (F): 52 Laboratory Test Data Set Specimen Date Date No. ID Received Tested 1 1 09/19/19 09/20/19 1 2 09/19/19 10/11/19 1 3 09/19/19 10/11/19 1 4 09/19/19 10/11/19 1 5 09/19/19 Initial Cure: Outside Plastic Lids Comments: Arerra[On c...A., Sample Date: 09/13/19 Sample Time:1030 Sampled By: Erik Tichenor Weather Conditions: Clear Accumulative Yards: 36 Batch Size: 9 Sample Size: 211x4" Sample Location: Truck chute Placement Location: Augercast piles Form Material: Plastic Mold No. Units: Samples Plumb: Yes Temperature Range: Maximum Compressive Age Area Load Strength Fracture Tested (days) (sq in) (lbs) (psi) Type By 7 3.11 17,030 5,480 2 HRB 28 28 28 Hold Final Cure: Moist Room Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Erik Tichenor Reported To: Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Senior Project Field Manager Test Methods: ASTM C 31, ASTM C39, ASTM C109, ASTM C138, ASTM C143, ASTM C1019, ASTM C1064 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cRoo09, 11-16-12, Rev.6 Page 1 of 1 Distribution Page Report Number: M7191427.0007A Service Date: 09/13/19 Report Date: 09/24/19 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams-Wolle MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 GROUT COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0007A Service Date: 09/13/19 Report Date: 10/14/19 Revision 1 - 28-day results Task: Client 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project - M7191427 Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Arerra[On c...A., Specified Strength: 4,000 psi @ 28 days Sample Date: 09/13/19 Sample Time:1030 Sampled By: Erik Tichenor Mix ID: 5G55149 Weather Conditions: Clear Supplier: Cadman Accumulative Yards: 36 Batch Size: 9 Batch Time: 0903 Plant: 32 Sample Size: 211x4" Truck No.: 429 Ticket No.: 677282 Sample Location: Truck chute Placement Location: Augercast piles Field Test Data Form Material: Plastic Mold No. Units: Test Result Specification Samples Plumb: Yes Slump (in): Temperature Range: Grout Temp. (F): 75 Ambient Temp. (F): 52 Laboratory Test Data Maximum Compressive Set Specimen Date Date Age Area Load Strength Fracture Tested No. ID Received Tested (days) (sq in) (lbs) (psi) Type By 1 1 09/19/19 09/20/19 7 3.11 17,030 5,480 2 HRB 1 2 09/19/19 10/11/19 28 3.05 21,630 7,100 2 ZAJ 1 3 09/19/19 10/11/19 28 3.08 22,370 7,270 2 ZAJ 1 4 09/19/19 10/11/19 28 3.08 23,020 7,480 2 ZAJ 1 5 09/19/19 10/11/19 28 3.08 19,590 6,360 2 ZAJ Average (28 days) 7,050 Initial Cure: Outside Plastic Lids Final Cure: Moist Room Comments: Average compressive strength of 28 day Cylinder complies with the specified strength. **NP = Not Performed Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Erik Tichenor Reported To: Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Senior Project Field Manager Test Methods: ASTM C 31, ASTM C39, ASTM C109, ASTM C138, ASTM C143, ASTM C1019, ASTM C1064 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cRoo09, 11-16-12, Rev.6 Page 1 of 1 Distribution Page Report Number: M7191427.0007A Service Date: 09/13/19 Report Date: 10/14/19 Revision 1 - 28-day results Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 GROUT OBSERVATIONS REPORT Report Number: M7191427.0008 Service Date: 09/16/19 Report Date: 09/19/19 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds, WA 98020 Permit No.: BLD-2018-1658 Samples: (5) 2x4" cylinders MAYES TESTING ENGINEERS nlrerracan cmernxv 20225 Cedar Vallev Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmond, WA Project No. Weather: M7191427 Overcast Pile Inspection and Grout Inspected the reinforcement and grout placement of (63) cubic yards of Cadman concrete mix 5G55149 for (11) auger -cast piles #633, 671, 708, 632, 670, 637, 635, 634, 668, 705 and 709. The reinforcement of the piles was verified in reference to the approved project documents and structural plans found on 18/S3.2. The grout was placed via hose pump and deposited into each of the auger -cast piles. There were (5) 2x4" grout cylinders cast for compressive strength testing with a required f'c of 4000 psi at (28) days. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Erik Tichenor Reported to: WG Clark Construction Co. Contractor: WG Clark Construction Co. Report Distribution: (1) Edmonds Senior Center, Daniel (1) City of Edmonds WA, Leif Bjorback Johnson (1) City of Edmonds WA, Milton (1) Environmental Works, Inc., Sally Reviewed By: Thompson Knodell 4 a e —� (1) Mayes Testing Engineers, Inc, (1) Mayes Testing Engineers, Inc, Heath Defoor, PE Donna Pollard Todd Wirtz (1) WG Clark Construction Co, Jim Senior Project Field Manager Brav The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CT000t, 10-16-13, Rev.10 Page 1 of 1 GROUT COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0008A Service Date: 09/16/19 Report Date: 09/24/19 Task: Client 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project - M7191427 Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Mix ID: 5G55149 Supplier: Cadman Batch Time: 0903 Plant: 32 Truck No.: 433 Ticket No.: 677896 Field Test Data Test Result Specification Slump (in): Grout Temp. (F): 75 Ambient Temp. (F): 53 Laboratory Test Data Arerra[On c...A., Sample Date: 09/16/19 Sample Time:1140 Sampled By: Erik Tichenor Weather Conditions: Clear Accumulative Yards: 36 Batch Size: 9 Sample Size: 2x4" Sample Location: Truck chute Placement Location: Augercast piles Form Material: Plastic Mold No. Units: Samples Plumb: Yes Temperature Range: Maximum Compressive Set Specimen Date Date Age Area Load Strength Fracture Tested No. ID Received Tested (days) (sq in) (lbs) (psi) Type By 1 1 09/17/19 09/23/19 7 3.11 15,240 4,900 2 HRB 1 2 09/17/19 10/14/19 28 1 3 09/17/19 10/14/19 28 1 4 09/17/19 10/14/19 28 1 5 09/17/19 10/14/19 28 Initial Cure: Cure Box Final Cure: Moist Room Min Temp: 58 Max Temp: 61 Comments: Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Erik Tichenor Reported To: Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Senior Project Field Manager Test Methods: ASTM C 31, ASTM C39, ASTM C109, ASTM C138, ASTM C143, ASTM C1019, ASTM C1064 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cRoo09, 11-16-12, Rev.6 Page 1 of 1 Distribution Page Report Number: M7191427.0008A Service Date: 09/16/19 Report Date: 09/24/19 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams-Wolle MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 GROUT COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0008A Service Date: 09/16/19 Report Date: 10/16/19 Revision 1 - 28-day results Task: Client 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project - M7191427 Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Mix ID: 5G55149 Supplier: Cadman Batch Time: 0903 Plant: 32 Truck No.: 433 Ticket No.: 677896 Field Test Data Test Result Specification Slump (in): Grout Temp. (F): 75 Ambient Temp. (F): 53 Laboratory Test Data Arerra[On c...A., Sample Date: 09/16/19 Sample Time:1140 Sampled By: Erik Tichenor Weather Conditions: Clear Accumulative Yards: 36 Batch Size: 9 Sample Size: 2x4" Sample Location: Truck chute Placement Location: Augercast piles Form Material: Plastic Mold No. Units: Samples Plumb: Yes Temperature Range: Maximum Compressive Set Specimen Date Date Age Area Load Strength Fracture Tested No. ID Received Tested (days) (sq in) (lbs) (psi) Type By 1 1 09/17/19 09/23/19 7 3.11 15,240 4,900 2 HRB 1 2 09/17/19 10/14/19 28 3.14 21,540 6,860 2 KWB 1 3 09/17/19 10/14/19 28 3.11 20,870 6,710 4 KWB 1 4 09/17/19 10/14/19 28 3.11 22,520 7,240 4 KWB 1 5 09/17/19 10/14/19 28 3.11 21,300 6,850 2 KWB Average (28 days) 6,910 Initial Cure: Cure Box Final Cure: Moist Room Min Temp: 58 Max Temp: 61 Comments: Average compressive strength of 28 day Cylinder complies with the specified strength. **NP = Not Performed Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Erik Tichenor Reported To: Contractor: WG Clark Construction Co. Report Distribution: Reviewed B See attached distribution list. y: Timothy G. Beckerle, PE Principal Test Methods: ASTM C 31, ASTM C39, ASTM C109, ASTM C138, ASTM C143, ASTM C1019, ASTM C1064 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cRoo09, 11-16-12, Rev.6 Page 1 of 1 Distribution Page Report Number: M7191427.0008A Service Date: 09/16/19 Report Date: 10/16/19 Revision 1 - 28-day results Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 GROUT OBSERVATIONS REPORT Report Number: M7191427.0009 Service Date: 09/17/19 Report Date: 09/23/19 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds, WA 98020 Permit No.: BLD-2018-1658 Samples: (5) 2x4" cylinders MAYES TESTING ENGINEERS nlrerracan cmernxv 20225 Cedar Vallev Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmond, WA Project No. Weather: M7191427 Overcast Pile Inspection and Grout Inspected the reinforcement and grout placement of (63) cubic yards Cadman concrete mix 5G55149 for (9) auger -cast piles #669, 704, 667, 705, 702, 702 (re -drill) 701, 673 and 665. The reinforcement of the piles was verified in reference to approved project documents and structural plans found on 18/S3.2. The grout was placed via hose pump and deposited into each of the auger -cast piles. There were (5) 2x4" grout cylinders cast for compressive strength testing with a required f'c of 4000 psi at (28) days. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Erik Tichenor Reported to: WG Clark Construction Co. Contractor: WG Clark Construction Co. Report Distribution: (1) Edmonds Senior Center, Daniel (1) City of Edmonds WA, Leif Bjorback Johnson (1) City of Edmonds WA, Milton (1) Environmental Works, Inc., Sally Reviewed By: Thompson Knodell 4 a e —� (1) Mayes Testing Engineers, Inc, (1) Mayes Testing Engineers, Inc, Heath Defoor, PE Donna Pollard Todd Wirtz (1) WG Clark Construction Co, Jim Senior Project Field Manager Brav The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CT000t, 10-16-13, Rev.10 Page 1 of 1 GROUT COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0009A Service Date: 09/17/19 Report Date: 09/26/19 Task: Client 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project - M7191427 Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Mix ID: 5G55149 Supplier: Cadman Batch Time: 0831 Plant: 32 Truck No.: 446 Ticket No.: 678241 Field Test Data Test Result Specification Slump (in): Grout Temp. (F): 78 Ambient Temp. (F): 49 Laboratory Test Data Set Specimen Date No. ID Received 1 1 09/18/19 1 2 09/18/19 1 3 09/18/19 1 4 09/18/19 1 5 09/18/19 Initial Cure: Outside Comments: Arerra[On c...A., Sample Date: 09/17/19 Sample Time: 1015 Sampled By: Erik Tichenor Weather Conditions: Clear Accumulative Yards: 36 Batch Size: 9 Sample Size: 2x4" Sample Location: Truck chute Placement Location: Augercast piles Form Material: Plastic Mold No. Units: Samples Plumb: Yes Temperature Range: Maximum Compressive Date Age Area Load Strength Fracture Tested Tested (days) (sq in) (lbs) (psi) Type By 09/24/19 7 3.08 16,230 5,270 3 ZAJ 10/15/19 28 10/15/19 28 10/15/19 28 10/15/19 28 Final Cure: Moist Room Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Erik Tichenor Reported To: Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Senior Project Field Manager Test Methods: ASTM C 31, ASTM C39, ASTM C109, ASTM C138, ASTM C143, ASTM C1019, ASTM C1064 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cRoo09, 11-16-12, Rev.6 Page 1 of 1 Distribution Page Report Number: M7191427.0009A Service Date: 09/17/19 Report Date: 09/26/19 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams-Wolle MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 GROUT COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0009A Service Date: 09/17/19 Report Date: 10/16/19 Revision 1 - 28-day results Task: Client 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project - M7191427 Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Arerra[On c...A., Specified Strength: 4,000 psi @ 28 days Sample Date: 09/17/19 Sample Time: 1015 Sampled By: Erik Tichenor Mix ID: 5G55149 Weather Conditions: Clear Supplier: Cadman Accumulative Yards: 36 Batch Size: 9 Batch Time: 0831 Plant: 32 Sample Size: 2x4" Truck No.: 446 Ticket No.: 678241 Sample Location: Truck chute Placement Location: Augercast piles Field Test Data Form Material: Plastic Mold No. Units: Test Result Specification Samples Plumb: Yes Slump (in): Temperature Range: Grout Temp. (F): 78 Ambient Temp. (F): 49 Laboratory Test Data Maximum Compressive Set Specimen Date Date Age Area Load Strength Fracture Tested No. ID Received Tested (days) (sq in) (lbs) (psi) Type By 1 1 09/18/19 09/24/19 7 3.08 16,230 5,270 3 ZAJ 1 2 09/18/19 10/15/19 28 3.14 22,540 7,170 2 KWB 1 3 09/18/19 10/15/19 28 3.11 23,170 7,450 2 KWB 1 4 09/18/19 10/15/19 28 3.11 22,310 7,170 4 KWB 1 5 09/18/19 10/15/19 28 3.11 18,900 6,080 4 KWB Average (28 days) 6,970 Initial Cure: Cure Box Final Cure: Moist Room Comments: Average compressive strength of 28 day Cylinder complies with the specified strength. **NP = Not Performed Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Erik Tichenor Reported To: Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Michael S. Dolder, PE Senior Principal Test Methods: ASTM C 31, ASTM C39, ASTM C109, ASTM C138, ASTM C143, ASTM C1019, ASTM C1064 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cRoo09, 11-16-12, Rev.6 Page 1 of 1 Distribution Page Report Number: M7191427.0009A Service Date: 09/17/19 Report Date: 10/16/19 Revision 1 - 28-day results Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams-Wolle MAYES TESTING ENGINEERS i� Alrerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 GROUT OBSERVATIONS REPORT Report Number: M7191427.0010 Service Date: 09/18/19 Report Date: 09/23/19 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds, WA 98020 Permit No.: BLD-2018-1658 Samples: (4) 2x4" cylinders MAYES TESTING ENGINEERS nlrerracan cmernxv 20225 Cedar Vallev Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmond, WA Project No. Weather: M7191427 Overcast Pile Inspection and Grout Inspected the reinforcement and grout placement of (7,2) cubic yards of Cadman concrete mix 5G55149 for (13) auger -cast piles #703, 672, 699, 700, 674, 664, 698, 697, 676, 695, 690, 680 and 661. The reinforcement of the piles was verified in reference to approved project documents and structural plans found on 18/S3.2. The grout was placed via hose pump and deposited into each of the augercast piles. There were (4) 2x4" grout cylinders cast for compressive strength testing with a required f'c of 4000 psi at (28) days. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Erik Tichenor Reported to: WG Clark Construction Co. Contractor: WG Clark Construction Co. Report Distribution: (1) Edmonds Senior Center, Daniel (1) City of Edmonds WA, Leif Bjorback Johnson (1) City of Edmonds WA, Milton (1) Environmental Works, Inc., Sally Reviewed By: Thompson Knodell 4 a e —� (1) Mayes Testing Engineers, Inc, (1) Mayes Testing Engineers, Inc, Heath Defoor, PE Donna Pollard Todd Wirtz (1) WG Clark Construction Co, Jim Senior Project Field Manager Brav The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CT000t, 10-16-13, Rev.10 Page 1 of 1 GROUT COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0010A Service Date: 09/18/19 Report Date: 09/26/19 Task: Client 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project - M7191427 Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Mix ID: 5G55149 Supplier: Cadman Batch Time: 0715 Plant: 32 Truck No.: 347 Ticket No.: 678598 Field Test Data Test Result Specification Slump (in): Grout Temp. (F): 72 Ambient Temp. (F): 51 Laboratory Test Data Set Specimen Date No. ID Received 1 1 09/19/19 1 2 09/19/19 1 3 09/19/19 1 4 09/19/19 1 5 09/19/19 Initial Cure: Outside Comments: Arerra[On c...A., Sample Date: 09/18/19 Sample Time: 0955 Sampled By: Erik Tichenor Weather Conditions: Clear Accumulative Yards: 27 Batch Size: 9 Sample Size: 2x4" Sample Location: Truck chute Placement Location: Augercast piles Form Material: Plastic Mold No. Units: Samples Plumb: Yes Temperature Range: Maximum Compressive Date Age Area Load Strength Fracture Tested Tested (days) (sq in) (lbs) (psi) Type By 09/25/19 7 3.08 17,440 5,660 2 ZAJ 10/16/19 28 10/16/19 28 10/16/19 28 10/16/19 28 Final Cure: Moist Room Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Erik Tichenor Reported To: Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Senior Project Field Manager Test Methods: ASTM C 31, ASTM C39, ASTM C109, ASTM C138, ASTM C143, ASTM C1019, ASTM C1064 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cRoo09, 11-16-12, Rev.6 Page 1 of 1 Distribution Page Report Number: M7191427.0010A Service Date: 09/18/19 Report Date: 09/26/19 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams-Wolle MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 GROUT OBSERVATIONS REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0011 Service Date: 09/19/19 20225 Cedar Vallev Rd Ste 110 Report Date: 09/23/19 Lynnwood, WA 98036-6365 425-742-9360 Client Project Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Project No.: M7191427 Permit No.: BLD-2018-1658 Weather: Overcast Samples: (4) 2x4" cylinders Pile Inspection and Grout Inspected the reinforcement and grout placement of (72) cubic yards of Cadman concrete mix 5G55149 for (15) auger cast piles #675, 696, 693, 692, 663, 678, 662, 694, 691, 684, 658, 656, 683, 685 and 681. The reinforcement of the piles was verified in reference to the approved project documents and structural plans found on 18/S3.2. The grout was placed via hose pump and deposited into each of the auger -cast piles. There were (4) 2x4" grout cylinders cast for compressive strength testing with a required f'c of 4000 psi at (28) days. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Erik Tichenor Reported to: WG Clark Construction Co. Contractor: WG Clark Construction Co. Report Distribution: (1) Edmonds Senior Center, Daniel (1) City of Edmonds WA, Leif Bjorback Johnson (1) City of Edmonds WA, Milton (1) Environmental Works, Inc., Sally Reviewed By: Thompson Knodell 4 a e —� (1) Mayes Testing Engineers, Inc, (1) Mayes Testing Engineers, Inc, Heath Defoor, PE Donna Pollard Todd Wirtz (1) WG Clark Construction Co, Jim Senior Project Field Manager Brav The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CT000t, 10-16-13, Rev.10 Page 1 of 1 GROUT COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0011A Service Date: 09/19/19 Report Date: 09/30/19 Task: Client 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project - M7191427 Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Mix ID: 5G55149 Supplier: Cadman Batch Time: 0807 Plant: 32 Truck No.: 442 Ticket No.: 679062 Field Test Data Test Result Specification Slump (in): Grout Temp. (F): 78 Ambient Temp. (F): 59 Laboratory Test Data Sample Date: Sampled By: Weather Conditions: Accumulative Yards: Sample Size: Sample Location: Placement Location: Form Material: Samples Plumb: Temperature Range: Arerra[On c...A., 09/19/19 Sample Time: 0930 Erik Tichenor Clear 36 Batch Size: 9 2"x4" Truck chute (15) Augercast piles Plastic Mold No. Units: Yes Maximum Compressive Set Specimen Date Date Age Area Load Strength Fracture Tested No. ID Received Tested (days) (sq in) (lbs) (psi) Type By 1 1 09/20/19 09/26/19 7 3.14 16,700 5,320 2 KWB 1 2 09/20/19 10/17/19 28 1 3 09/20/19 10/17/19 28 1 4 09/20/19 10/17/19 28 Initial Cure: Cure Box Final Cure: Moist Room Min Temp: 61 Max Temp: 61 Comments: Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Erik Tichenor Reported To: Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Senior Project Field Manager Test Methods: ASTM C 31, ASTM C39, ASTM C109, ASTM C138, ASTM C143, ASTM C1019, ASTM C1064 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cRoo09, 11-16-12, Rev.6 Page 1 of 1 Distribution Page Report Number: M7191427.0011A Service Date: 09/19/19 Report Date: 09/30/19 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams-Wolle MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 GROUT COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0011A Service Date: 09/19/19 Report Date: 10/18/19 Revision 1 - 28-day results Task: Client 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project - M7191427 Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Mix ID: 5G55149 Supplier: Cadman Batch Time: 0807 Plant: 32 Truck No.: 442 Ticket No.: 679062 Field Test Data Test Result Specification Slump (in): Grout Temp. (F): 78 Ambient Temp. (F): 59 Laboratory Test Data Sample Date: Sampled By: Weather Conditions: Accumulative Yards: Sample Size: Sample Location: Placement Location: Form Material: Samples Plumb: Temperature Range: Arerr.... c...A., 09/19/19 Sample Time: 0930 Erik Tichenor Clear 36 Batch Size: 9 2"x4" Truck chute (15) Augercast piles Plastic Mold No. Units: Yes Maximum Compressive Set Specimen Date Date Age Area Load Strength Fracture Tested No. ID Received Tested (days) (sq in) (lbs) (psi) Type By 1 1 09/20/19 09/26/19 7 3.14 16,700 5,320 2 KWB 1 2 09/20/19 10/17/19 28 3.11 19,690 6,330 2 KWB 1 3 09/20/19 10/17/19 28 3.14 21,580 6,870 2 KWB 1 4 09/20/19 10/17/19 28 3.11 22,070 7,100 2 KWB Average (28 days) 6,770 Initial Cure: Cure Box Final Cure: Moist Room Min Temp: 61 Max Temp: 61 Comments: Average compressive strength of 28 day Cylinder complies with the specified strength. **NP = Not Performed Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Erik Tichenor Reported To: Contractor: WG Clark Construction Co. - - Report Distribution: See attached distribution list. Reviewed By: . Michael S. Dolder, PE Senior Principal Test Methods: ASTM C 31, ASTM C39, ASTM C109, ASTM C138, ASTM C143, ASTM C1019, ASTM C1064 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cRoo09, 11-16-12, Rev.6 Page 1 of 1 Distribution Page Report Number: M7191427.0011A Service Date: 09/19/19 Report Date: 10/18/19 Revision 1 - 28-day results Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams-Wolle MAYES TESTING ENGINEERS i� Alrerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 GROUT OBSERVATIONS REPORT Report Number: M7191427.0012 Service Date: 09/20/19 Report Date: 09/25/19 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds, WA 98020 Permit No.: BLD-2018-1658 Samples: (4) 2x4" cylinders MAYES TESTING ENGINEERS nlrerracan cmernxv 20225 Cedar Vallev Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmond, WA Project No. Weather: M7191427 Overcast Pile Inspection and Grout Inspected the reinforcement and grout placement of (54) cubic yards of Cadman concrete mix 5G55149 for (11) auger -cast piles #677, 679, 689, 686, 683, 682, 681, 655, 657, 654 and 660. The reinforcement of the piles was verified in reference to approved project documents and structural plans found on 18/S3.2. The grout was placed via hose pump and deposited into each of the auger -cast piles. There were (4) 2x4" grout cylinders cast for compressive strength testing with a required f'c of 4000 psi at (28) days. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Erik Tichenor Reported to: WG Clark Construction Co. Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Senior Project Field Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000t, 10-16-13, Rev.lo Page 1 of 1 Distribution Page Report Number: M7191427.0012 Service Date: 09/20/19 Report Date: 09/25/19 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams-Wolle MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 GROUT COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0012A Service Date: 09/20/19 Report Date: 09/30/19 Task: Client 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project - M7191427 Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Mix ID: 5G55149 Supplier: Cadman Batch Time: 0602 Plant: 32 Truck No.: 429 Ticket No.: 679583 Field Test Data Test Result Specification Slump (in): Grout Temp. (F): 76 Ambient Temp. (F): 50 Laboratory Test Data Arerra[On c...A., Sample Date: 09/20/19 Sample Time:0800 Sampled By: Erik Tichenor Weather Conditions: Clear Accumulative Yards: 9 Batch Size: 9 Sample Size: 2x4" Sample Location: Truck chute Placement Location: Augercast piles Form Material: Plastic Mold No. Units: Samples Plumb: Yes Temperature Range: Maximum Compressive Set Specimen Date Date Age Area Load Strength Fracture Tested No. ID Received Tested (days) (sq in) (lbs) (psi) Type By 1 1 09/24/19 09/27/19 7 3.08 17,580 5,710 2 ZAJ 1 2 09/24/19 10/18/19 28 1 3 09/24/19 10/18/19 28 1 4 09/24/19 10/18/19 28 Initial Cure: Cure Box Final Cure: Moist Room Comments: Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Erik Tichenor Reported To: Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Senior Project Field Manager Test Methods: ASTM C 31, ASTM C39, ASTM C109, ASTM C138, ASTM C143, ASTM C1019, ASTM C1064 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cRoo09, 11-16-12, Rev.6 Page 1 of 1 Distribution Page Report Number: M7191427.0012A Service Date: 09/20/19 Report Date: 09/30/19 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 GROUT OBSERVATIONS REPORT Report Number: M7191427.0013 Service Date: 09/23/19 Report Date: 09/26/19 MAYES TESTING ENGINEERS nlrerracan cmernxv 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Client Project Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Project No.: M7191427 Permit No.: BLD-2018-1658 Samples: (4) 2x4" cylinders Weather: Overcast Pile Inspection and Grout Inspected the reinforcement and grout placement of (18) cubic yards of Cadman concrete mix 5G55149 for (3) auger -cast piles and the topping off of piles placed in prior weeks. The piles drilled and placed were #688, 659 and 657. The reinforcement of the piles was verified in reference to approved project documents and structural plans found on 18/S3.2. The grout was placed via hose pump and deposited into each of the auger -cast piles. There were (4) 2x4" grout cylinders cast for compressive strength testing (f'c of 4000 psi at 28 days). To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Erik Tichenor Reported to: WG Clark Construction Co. Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Senior Project Field Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000t, 10-16-13, Rev.lo Page 1 of 1 Distribution Page Report Number: M7191427.0013 Service Date: 09/23/19 Report Date: 09/26/19 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams-Wolle MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 GROUT COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0013A Service Date: 09/23/19 Report Date: 10/02/19 Task: Client 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project - M7191427 Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Mix ID: 5G55149 Supplier: Cadman Batch Time: 0630 Plant: 32 Truck No.: 347 Ticket No.: 680340 Field Test Data Test Result Specification Slump (in): Grout Temp. (F): 75 Ambient Temp. (F): Laboratory Test Data Arerra[On c...A., Sample Date: 09/23/19 Sample Time: Sampled By: Erik Tichenor Weather Conditions: Overcast Accumulative Yards: 9 Batch Size: 9 Sample Size: Sample Location: Augercast Piles Placement Location: Augercast Piles Form Material: Plastic Mold No. Units: 4 Samples Plumb: Yes Temperature Range: Maximum Compressive Set Specimen Date Date Age Area Load Strength Fracture Tested No. ID Received Tested (days) (sq in) (lbs) (psi) Type By 1 A 09/24/19 09/30/19 7 3.08 16,630 5,400 2 ZAJ 1 B 09/24/19 10/21/19 28 8.00 1 C 09/24/19 10/21/19 28 8.00 1 D 09/24/19 10/21/19 28 8.00 Initial Cure: Cure Box Final Cure: Moist Room Comments: Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Erik Tichenor Reported To: Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Senior Project Field Manager Test Methods: ASTM C 31, ASTM C39, ASTM C109, ASTM C138, ASTM C143, ASTM C1019, ASTM C1064 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cRoo09, 11-16-12, Rev.6 Page 1 of 1 Distribution Page Report Number: M7191427.0013A Service Date: 09/23/19 Report Date: 10/02/19 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 GROUT COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0013A Service Date: 09/23/19 Report Date: 10/22/19 Revision 1 - 28-day results Task: Client 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project - M7191427 Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Arerr.... c...A., Specified Strength: 4,000 psi @ 28 days Sample Date: 09/23/19 Sample Time: Sampled By: Erik Tichenor Mix ID: 5G55149 Weather Conditions: Overcast Supplier: Cadman Accumulative Yards: 9 Batch Size: 9 Batch Time: 0630 Plant: 32 Sample Size: Truck No.: 347 Ticket No.: 680340 Sample Location: Augercast Piles Placement Location: Augercast Piles Field Test Data Form Material: Plastic Mold No. Units: 4 Test Result Specification Samples Plumb: Yes Slump (in): Temperature Range: Grout Temp. (F): 75 Ambient Temp. (F): Laboratory Test Data Maximum Compressive Set Specimen Date Date Age Area Load Strength Fracture Tested No. ID Received Tested (days) (sq in) (lbs) (psi) Type By 1 A 09/24/19 09/30/19 7 3.08 16,630 5,400 2 ZAJ 1 B 09/24/19 10/21/19 28 3.05 23,110 7,580 2 ZAJ 1 C 09/24/19 10/21/19 28 3.08 21,890 7,110 4 ZAJ 1 D 09/24/19 10/21/19 28 3.11 20,690 6,650 2 ZAJ Average (28 days) 7,110 Initial Cure: Cure Box Final Cure: Moist Room Comments: Average compressive strength of 28 day Cylinder complies with the specified strength. **NP = Not Performed Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Erik Tichenor Reported To: Contractor: WG Clark Construction Co. - - Report Distribution: See attached distribution list. Reviewed By: . Michael S. Dolder, PE Senior Principal Test Methods: ASTM C 31, ASTM C39, ASTM C109, ASTM C138, ASTM C143, ASTM C1019, ASTM C1064 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cRoo09, 11-16-12, Rev.6 Page 1 of 1 Distribution Page Report Number: M7191427.0013A Service Date: 09/23/19 Report Date: 10/22/19 Revision 1 - 28-day results Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams-Wolle MAYES TESTING ENGINEERS i� Alrerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 GROUT OBSERVATIONS REPORT Report Number: M7191427.0014 Service Date: 09/24/19 Report Date: 09/26/19 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds, WA 98020 Permit No.: BLD-2018-1658 Samples: None MAYES TESTING ENGINEERS nlrerracan cmernxv 20225 Cedar Vallev Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmond, WA Project No. Weather: M7191427 Overcast Item 1: Pile Inspection Inspected the reinforcement and grout placement height of the previously placed auger -cast piles of Cadman concrete mix 5G55149. The auger -cast piles from prior weeks were verified and stub -out reinforcement also has been verified. The auger -cast piles were verified in reference to approved project documents and structural plans found on 18/S3.2. Item 2: Cylinder Pick-up Picked up the (4) 2x4" cylinders cast yesterday for compressive strength testing and transported them to Mayes Testing Engineers Lynwood, WA laboratory. Placed the cylinders in the vapor -controlled mist room. The cylinders will be tested at (7) and (28) days. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Erik Tichenor Reported to: WG Clark Construction Co. Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Senior Project Field Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000t, 10-16-13, Rev.lo Page 1 of 1 Distribution Page Report Number: M7191427.0014 Service Date: 09/24/19 Report Date: 09/26/19 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams-Wolle MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 GROUT OBSERVATIONS REPORT Report Number: M7191427.0015 Service Date: 09/25/19 Report Date: 11 /04/19 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds, WA 98020 Permit No.: BLDG-2018-1658 Samples: N/A MAYES TESTING ENGINEERS nlrerracan cmernxv 20225 Cedar Vallev Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmond, WA Project No. Weather: M7191427 Clear On site to monitor and sample the grout from auger cast piles. Upon arrival, it was found that there were no more piles to be grouted. Crane was being disassembled and no concrete was on site. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Erik Tichenor Reported to: WG Clark Construction Co. Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list Reviewed By: Timothy G. Beckerle, PE Principal The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000l, 10-16-13, Rev.10 Page 1 of 1 Distribution Page Report Number: M7191427.0015 Service Date: 09/25/19 Report Date: 11/04/19 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 CONCRETE OBSERVATION REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0016 Service Date: 10/11/19 Report Date: 10/16/19 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds. WA 98020 Permit No.: BLD2018-1658 Samples: (4) 4x8" cylinders 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmond, WA Project No. Weather: M7191427 450 F On site for inspection of reinforcement and concrete placement — (80) cubic yards CalPortland mix 61818 at elevator foundation, shown on schedule S1.1, at grid lines C to C.5/8.7 to 9.5. Foundation consists of (2) grade beams (east and west sides), slab -on -grade, sump and (4) walls. Each grade beam sits on top of (2) piles. Verified (6) hooked dowels on top of each pile. Verified grade beams per reinforcement in details 17/S3.1 and 16/S3.2, and reinforcing steel placement drawing R01. Verified slab -on -grade reinforcement and reinforcement for 16" thick and 8" thick wall dowels, per S3.2 details and drawing R01. Foundation dimensions are 14'x11'x28" deep. Verified reinforcement for 30" wide x 18" high grade beams at grid lines A/2 to 12, A.5/2 to 12, B/2 to 12, B.2/2.5 to 3, 2/A to B and 2.5/13 to C. Verified reinforcement per details 9, 19, 20/S3.2 and drawing R01. The reinforcement sits on top of vapor barrier. The concrete was placed via pump hose and vibrated for consolidation. Cast (4) 4x8" cylinders for compressive strength testing (5000 psi at 28 days required). To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Charles Solway Reported to: WG Clark Construction Company Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list Reviewed By: Timothy G. Beckerle, PE Principal The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000l, 10-16-13, Rev.10 Page 1 of 1 Distribution Page Report Number: M7191427.0016 Service Date: 10/11 /19 Report Date: 10/16/19 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 CONCRETE COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0016A Service Date: 10/11/19 Report Date: 11/11/19 Revision 1 - 28-day results Task: Client Project - M7191427 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Airf«-con CO"A" Specified Strength: 5,000 psi @ 28 days Sample Date: 10/11/19 Sample Time: 1100 Sampled By: Charles Solway Mix ID: 61818 Weather Conditions: Mid 40's Supplier: CalPortland Accumulative Yards: 80 Batch Size (cy): 9 Batch Time: 1000 Plant: 260 Placement Method: Pump hose Truck No.: 7428 Ticket No.: 2203760 Water Added Before (gal): Field Test Data Water Added After (gal): Sample Location: Elevator foundation Test Result Specification Placement Location: Elevator foundation and grade beams Slump (in): 6 1/2 at grids A/2-12, A.5/2-12, B/2-12, Air Content (%): 5.7 B.2/2.5-3, 2/A-B, 2.5/13-C Concrete Temp. (F): 68 Ambient Temp. (F): 45 Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Laboratory Test Data Age at Maximum Compressive Set Specimen Avg Diam. Area Date Date Test Load Strength Fracture Tested No. ID (in) (sq in) Received Tested (days) (lbs) (psi) Type By 1 1 3.98 12.44 10/14/19 10/18/19 7 64,710 5,200 5 KWB 1 2 3.97 12.38 10/14/19 11/08/19 28 82,880 6,700 2 HRB 1 3 3.98 12.44 10/14/19 11/08/19 28 82,960 6,670 2 HRB 1 4 3.99 12.5 10/14/19 11/08/19 28 81,950 6,550 2 HRB Average (28 days) 6,640 Initial Cure: Cure Box Final Cure: Moist Room Min Temp: 61 Max Temp: 61 Comments: Average compressive strength of 28 day cylinders complies with the specified strength. Not tested for plastic unit weight. Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Charles Solway Reported To: Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Senior Project Field Manager Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cR000t, 11-16-12, Rev.6 Page 1 of 1 Distribution Page Report Number: M7191427.0016A Service Date: 10/11 /19 Report Date: 11/11/19 Revision 1 - 28-day results Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 CONCRETE OBSERVATION REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0017 Service Date: 10/18/19 Report Date: 10/25/19 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds. WA 98020 Permit No.: BLD2018-1658 Samples: N/A 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmond, WA Project No. Weather: M7191427 Cloudy After arriving on site was informed the inspection was cancelled. Spoke with the superintendent about the grade beams not being completed. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: David Schmutzler Reported to: WG Clark Construction Co. Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list Reviewed By: Timothy G. Beckerle, PE Principal The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000l, 10-16-13, Rev.10 Page 1 of 1 Distribution Page Report Number: M7191427.0017 Service Date: 10/18/19 Report Date: 10/25/19 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 CONCRETE OBSERVATION REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0018 Service Date: 10/22/19 Report Date: 10/29/19 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds. WA 98020 Permit No.: BLD2018-1658 Samples: N/A 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmond, WA Project No. Weather: M7191427 Please find attached the report by Jeremy Christensen with AAR Testing and Inspection, Inc. for work performed on site for the above -noted project. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Jeremy Christensen Reported to: WG Clark Construction Co. Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list Reviewed By: Timothy G. Beckerle, PE Principal The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000l, 10-16-13, Rev.10 Page 1 of 1 DAILY FIELD REPORT AAR TESTING AND INSPECTION, INC. 7126 180th Ave NE, Suite C101 Redmond, WA 98052 425-881-5812 Inspection Date 10/22/2019 Report Number JCC102219 CLIENT INFORMATION PROJECT INFORMATION Contact Jill Rouse - Mayes Project No. 19-600 Greg - WG Construction Company Mayes Testing Project Name Edmonds Community Center - M7191427 Address 20225 Cedar Valley Rd #110 Address 220 Railroad Avenue City Lynnwood City Edmonds Contractor WG Construction Co. Permit No. B18-0447 INSPECTION TYPE(S) STRUCTURE(S) / LOCATION(S) Reinforced Concrete Grade beams: A/1-12, A-D/12, D/1-12, C-D/1-12, A-D/2.5 O Other Weather Temperature (°F) Start Time End Time Cloudy 52 Approved plans - S0.1-0.2, S3.1-3.2, R.01 Approved permit #1318-0447 Approved mix design #61818 DRAWINGS / DOCUMENTS REFERENCED INSPECTION OBSERVATION / REMARKS Arrived onsite as requested to inspect concrete reinforcement for grade beams in locations previously noted in this report. Verified placement of reinforcement in corners and intersections as shown on R.01 and S3.1-3.1 all clearances were observed to be a minimum of 3" on all sides. CALPORTLAND supplied approximately 100cys of mix design #61818. Concrete was placed via boom pump and consolidated by mechanical vibration. AAR sampled and tested concrete, one set of five cylinders were, see concrete test report #JCC102219 for results. Samples were left onsite in Mayes cure box for initial curing. To the best of my knowledge work observed meets project plans and specifications. Items inspected are in conformance with approved plans, specifications and jurisdictional requirements Jeremy Christensen 10/22/2019 Teajalam (TJ) Gounden D1C59C4F-38E4-4E94-B335-CF67F9FF7AC0 ARI vim• _ _ ?off. - - LL riAMMSRU auk ma a19 77 M Distribution Page Report Number: M7191427.0018 Service Date: 10/22/19 Report Date: 10/29/19 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 CONCRETE COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0018A Service Date: 10/22/19 Report Date: 10/30/19 Task: Client Project - M7191427 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Specified Strength: 5,000 psi @ 28 days Mix ID: 61818 Supplier: CalPortland Batch Time: 1206 Plant: 260 Truck No.: 687 Ticket No.: 2210991 Field Test Data Test Slump (in): Air Content (%): Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Laboratory Test Data Set Specimen Avg Diam. No. ID (in) 1 1 3.99 1 2 1 3 1 4 1 5 Initial Cure: Cure Box Result Specification 7 5 -7 6.9 4.5 - 7.5 70 54 Sample Date: Sampled By: Weather Conditions: Accumulative Yards: Placement Method: Water Added Before (gal): Water Added After (gal): Sample Location: Placement Location: Age at Maximum Area Date Date Test Load (sq in) Received Tested (days) (lbs) 12.5 10/23/19 10/29/19 7 54,730 10/23/19 11/19/19 28 10/23/19 11/19/19 28 10/23/19 11/19/19 28 10/23/19 Hold Final Cure: Moist Room Comments: Not tested for plastic unit weight. Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Jeremy Christensen Reported To: Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Airf«-con CO"A" 10/22/19 Sample Time: 1304 Jeremy Christensen Showers 10 of 100 Batch Size (cy): 10 Grade beam, grid line A/2 Compressive Strength Fracture Tested (psi) Type By 4,380 2 KWB Reviewed By: �Ii�laJ c' S. Dolder, PE Senior Project Field Manager Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cR000t, 11-16-12, Rev.6 Page 1 of 1 Distribution Page Report Number: M7191427.0018A Service Date: 10/22/19 Report Date: 10/30/19 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams-Wolle MAYES TESTING ENGINEERS i� Alrerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 CONCRETE COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0018A Service Date: 10/22/19 Report Date: 11/21/19 Revision 1 - 28-day results Task: Client Project - M7191427 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Airf«-con CO"A" Specified Strength: 5,000 psi @ 28 days Sample Date: 10/22/19 Sample Time: 1304 Sampled By: Jeremy Christensen Mix ID: 61818 Weather Conditions: Showers Supplier: CalPortland Accumulative Yards: 10 of 100 Batch Size (cy): 10 Batch Time: 1206 Plant: 260 Placement Method: Truck No.: 687 Ticket No.: 2210991 Water Added Before (gal): Field Test Data Water Added After (gal): Sample Location: Test Result Specification Placement Location: Grade beam, grid line A/2 Slump (in): 7 5 -7 Air Content (%): 6.9 4.5 - 7.5 Concrete Temp. (F): 70 Ambient Temp. (F): 54 Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Laboratory Test Data Age at Maximum Compressive Set Specimen Avg Diam. Area Date Date Test Load Strength Fracture Tested No. ID (in) (sq in) Received Tested (days) (lbs) (psi) Type By 1 1 3.99 12.5 10/23/19 10/29/19 7 54,730 4,380 2 KWB 1 2 3.98 12.44 10/23/19 11/19/19 28 82,000 6,590 2 HRB 1 3 4.00 12.57 10/23/19 11/19/19 28 78,440 6,240 2 HRB 1 4 4.00 12.57 10/23/19 11/19/19 28 79,940 6,360 2 HRB 1 5 3.99 12.5 10/23/19 11/19/19 28 80,890 6,470 2 HRB Average (28 days) 6,420 Initial Cure: Cure Box Final Cure: Moist Room Comments: Average compressive strength of 28 day cylinders complies with the specified strength. Not tested for plastic unit we Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Jeremy Christensen Reported To: Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Senior Project Field Manager Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cR000l, 11,16-12, Rev.6 Page 1 of 1 Distribution Page MAYES TESTING ENGINEERS Report Number: M7191427.0018A nlrerracon COMPANY Service Date: 10/22/19 20225 Cedar Valley Rd Ste 110 Report Date: 11/21/19 Revision 1 - 28-day results Lynnwood, WA 98036-6365 Task: 425-742-9360 Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe CONCRETE OBSERVATION REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0019 Service Date: 10/29/19 Report Date: 11 /01 /19 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds. WA 98020 Permit No.: BLD2018-1658 Samples: (4) 4x8" cylinders 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmond, WA Project No. Weather: M7191427 Clear Observed the placement of (5) cubic yards of CalPortland concrete mix 61818 into the grade beam at grid lines C to D/8.5. The concrete was placed via mixer truck chute and consolidated via internal mechanical vibration. There were (4) 4x8" lab -cure cylinders cast for compressive strength testing (5000 psi at 28 days required). The reinforcing steel for this element was verified prior to placement and conformed to detail 20 on S3.2. Verified cover and clearances of reinforcement. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Samuel Larson Reported to: WG Clark Construction Co. Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list Reviewed By: Timothy G. Beckerle, PE Principal The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000l, 10-16-13, Rev.10 Page 1 of 1 Distribution Page Report Number: M7191427.0019 Service Date: 10/29/19 Report Date: 11 /01 /19 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 CONCRETE COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0019A Service Date: 10/29/19 Report Date: 11/07/19 Task: Client Project - M7191427 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Specified Strength: 5,000 psi @ 28 days Mix ID: 61818 Supplier: CalPortland Batch Time: 1247 Plant: 260 Truck No.: 7665 Ticket No.: 2217092 Field Test Data Test Slump (in): Air Content (%): Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Result Specification 5 6.2 63 45 Sample Date: Sampled By: Weather Conditions: Accumulative Yards: Placement Method: Water Added Before (gal): Water Added After (gal): Sample Location: Placement Location: Airf«-con CO"A" 10/29/19 Sample Time: 1345 Samuel Larson Clear 5 Batch Size (cy): 5 Chute 5 Grade beam at grids C to D/8.5 Laboratory Test Data Age at Maximum Compressive Set Specimen Avg Diam. Area Date Date Test Load Strength Fracture Tested No. ID (in) (sq in) Received Tested (days) (lbs) (psi) Type By 1 a 3.98 12.44 10/30/19 11/05/19 7 51,560 4,140 2 HRB 1 b 10/30/19 11/26/19 28 1 c 10/30/19 11/26/19 28 1 d 10/30/19 11/26/19 28 Initial Cure: Cure Box Final Cure: Moist Room Min Temp: 52 Max Temp: 61 Comments: Not tested for plastic unit weight. Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Samuel Larson Reported To: WG Clark Construction Company Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: _ Heath Defo Senior Project Field Manager Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CR000t, 11-16-12, Rev.6 Page 1 of 1 Distribution Page Report Number: M7191427.0019A Service Date: 10/29/19 Report Date: 11/07/19 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 POST -INSTALLED ANCHORS REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0020 Service Date: 11/04/19 Report Date: 11 /07/19 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds. WA 98020 Permit No.: BLD2018-1658 Samples: N/A 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmond, WA Project No. Weather: M7191427 Cloudy, 41 °F Please find attached the Post -Installed Anchors Report from AAR Testing and Inspection, Inc. for work performed on 11 /04/19 for the above project. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Tony Dalzell Reported to: WG Clark Construction Co. Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Senior Project Field Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000t, 10-16-13, Rev.lo Page 1 of 1 DAILY FIELD REPORT AAR TESTING AND INSPECTION, INC. 7126 180th Ave NE, Suite C101 Redmond, WA 98052 425-881-5812 Inspection Date 11/04/2019 Report Number TJD110419A CLIENT INFORMATION PROJECT INFORMATION Contact Jill Rouse Project No. 19-600C Company Mayes Testing Engineers; Inc. Project Name Edmonds Senior Center Activity Center (Mayes Project #M7191427) Address 20225 Cedar Valley Road; Suite 110 Address 220 Railroad Ave City Lynnwood City Edmonds Contractor WGClark Permit No. BLD 20181658 INSPECTION TYPE(S) STRUCTURE(S) / LOCATION(S) Proprietary Anchors - Epoxy #5 dowels placed with epoxy into footing Weather Temperature (°F) Start Time End Time Cloudy 41 0PAII11901 DRAWINGS / DOCUMENTS REFERENCED RFI #37 #5 bar Holes, 9-1/4 inch embedment ILlI[1Iill�ul INSPECTION OBSERVATION / REMARKS Arrived on site as requested to inspect (14) #5 rebar dowels, placed with Simpson Strong -Tie AT-XP Acrylic, 9.4 fl oz, Exp 9/19/20 with code AT-XP10 lot #1000056406. Holes had been bottle brushed and blown before epoxy placement. Items inspected are in conformance with approved plans, specifications and jurisdictional requirements Inspectors Name Report Date Reviewed By Reviewed Date Tony Dalzell 11/04/2019 G�Teajalam (TJ) 11/05/2019 Gounden 5270e64939402c42-1572902620122 M DAILY FIELD REPORT Inspection Date11/04/2019 r AAR TESTING AND INSPECTION, INC. 7126 180th Ave NE, Suite C101 Report Number Redmond, WA 98052 TJD110419A 425-881-5812 PHOTOS —• ti ,.ems-. I J-1F -- #5 bar placed with epoxy ;.j Close up of footing with #5 bar Inspectors Name Report Date Reviewed By Reviewed Date Tony Dalzell 11/04/2019 G�Teajalam (TJ) 11/05/2019 Gounden 5270e64939402c42-1572902620122 Distribution Page Report Number: M7191427.0020 Service Date: 11 /04/19 Report Date: 11/07/19 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 REINFORCING STEEL OBSERVATIONS REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0021 Service Date: 11/13/19 Report Date: 11 /20/19 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds. WA 98020 Permit No.: BLD2018-1658 Samples: N/A 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmond, WA Project No. Weather: M7191427 Partly cloudy Conducted an inspection of the reinforcing steel for the slab -on -grade at grids A to D/1 to 12, including dropped slab areas, for size, grade, spacing, quantity and placement. The reinforcing steel conformed to notes on S2.1 and associated details for curbs, hold-downs and HSS supports. Prior to placement, the following items to be verified: • Clearances between mats of reinforcement • Clearance underneath dropped slab reinforcement at grids A/11 • Finish curbs on D-Line per detail 20 on S3.2 PRELIMINARY INSPECTION Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Samuel Larson Reported to: WG Clark Construction Co. Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Senior Project Field Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000t, 10-16-13, Rev.lo Page 1 of 1 Distribution Page Report Number: M7191427.0021 Service Date: 11 /13/19 Report Date: 11/20/19 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 CONCRETE COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0022A Service Date: 11/20/19 Report Date: 12/20/19 Revision 1 - 28-day results Task: Client Project - M7191427 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Airf«-con CO"A" Specified Strength: 4,000 psi @ 28 days Sample Date: 11/20/19 Sample Time: 0810 Sampled By: Charles Solway Mix ID: 60941 Weather Conditions: 390F Supplier: CalPortland Accumulative Yards: 136 Batch Size (cy): 9.5 Batch Time: 0746 Plant: 260 Placement Method: pump hose Truck No.: 5348 Ticket No.: 2233312 Water Added Before (gal): Field Test Data Water Added After (gal): Sample Location: Test Result Specification Placement Location: Slab -on -grade, grid Ines A to D/1 Slump (in): 6 1/2 to12 Air Content (%): Concrete Temp. (F): 66 Ambient Temp. (F): 39 Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Laboratory Test Data Age at Maximum Compressive Set Specimen Avg Diam. Area Date Date Test Load Strength Fracture Tested No. ID (in) (sq in) Received Tested (days) (lbs) (psi) Type By 1 1 3.98 12.44 11/21/19 11/27/19 7 84,850 6,820 2 HRB 1 2 3.98 12.44 11/21/19 12/18/19 28 113,480 9,120 1 KWB 1 3 3.97 12.38 11/21/19 12/18/19 28 110,560 8,930 5 KWB 1 4 3.98 12.44 11/21/19 12/18/19 28 115,210 9,260 5 KWB Average (28 days) 9,100 Initial Cure: Cure Box Final Cure: Moist Room Comments: Average compressive strength of 28 day cylinders complies with the specified strength. Not tested for plastic unit weight. Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Charles Solway Reported To: Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cR000t, 11-16-12, Rev.6 Page 1 of 4 CONCRETE COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0022A Service Date: 11/20/19 Report Date: 12/20/19 Revision 1 - 28-day results Task: Client Project - M7191427 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Airf«-con CO"A" Specified Strength: 4,000 psi @ 28 days Sample Date: 11/20/19 Sample Time: 0920 Sampled By: Charles Solway Mix ID: 60941 Weather Conditions: 41 OF Supplier: CalPortland Accumulative Yards: 174 Batch Size (cy): 9.5 Batch Time: 0802 Plant: 260 Placement Method: pump hose Truck No.: 7675 Ticket No.: 2233335 Water Added Before (gal): 20 Field Test Data Water Added After (gal): Sample Location: Test Result Specification Placement Location: Slab -on -grade, grid Ines A to D/1 Slump (in): 7 1/2 to12 Air Content (%): Concrete Temp. (F): 67 Ambient Temp. (F): 41 Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Laboratory Test Data Age at Maximum Compressive Set Specimen Avg Diam. Area Date Date Test Load Strength Fracture Tested No. ID (in) (sq in) Received Tested (days) (lbs) (psi) Type By 2 1 3.98 12.44 11/21/19 11/27/19 7 73,890 5,940 3 HRB 2 2 3.97 12.38 11/21/19 12/18/19 28 108,180 8,740 5 KWB 2 3 3.97 12.38 11/21/19 12/18/19 28 105,680 8,540 1 KWB 2 4 3.97 12.38 11/21/19 12/18/19 28 108,040 8,730 2 KWB Average (28 days) 8,670 Initial Cure: Cure Box Final Cure: Moist Room Comments: Average compressive strength of 28 day cylinders complies with the specified strength. Not tested for plastic unit weight. 7.5" slump after water added Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Charles Solway Reported To: Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cR000t, 11-16-12, Rev.6 Page 2 of 4 CONCRETE COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0022A Service Date: 11/20/19 Report Date: 12/20/19 Revision 1 - 28-day results Task: Client Project - M7191427 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Airf«-con CO"A" Specified Strength: 4,000 psi @ 28 days Sample Date: 11/20/19 Sample Time: 1000 Sampled By: Charles Solway Mix ID: 60941 Weather Conditions: 41 OF Supplier: CalPortland Accumulative Yards: 319.5 Batch Size (cy): 9.5 Batch Time: 0908 Plant: 260 Placement Method: pump hose Truck No.: 7647 Ticket No.: 2233471 Water Added Before (gal): 20 Field Test Data Water Added After (gal): Sample Location: Test Result Specification Placement Location: Slab -on -grade, grid Ines A to D/1 Slump (in): 7 to12 Air Content (%): Concrete Temp. (F): 67 Ambient Temp. (F): 41 Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Laboratory Test Data Age at Maximum Compressive Set Specimen Avg Diam. Area Date Date Test Load Strength Fracture Tested No. ID (in) (sq in) Received Tested (days) (lbs) (psi) Type By 3 1 3.98 12.44 11/21/19 11/27/19 7 70,750 5,690 2 HRB 3 2 3.97 12.38 11/21/19 12/18/19 28 93,530 7,560 5 KWB 3 3 3.97 12.38 11/21/19 12/18/19 28 98,430 7,950 5 KWB 3 4 3.97 12.38 11/21/19 12/18/19 28 99,020 8,000 2 KWB Average (28 days) 7,840 Initial Cure: Cure Box Final Cure: Moist Room Comments: Average compressive strength of 28 day cylinders complies with the specified strength. Not tested for plastic unit weight. 7" slump after water added Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Charles Solway Reported To: Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cR000t, 11-16-12, Rev.6 Page 3 of 4 CONCRETE COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0022A Service Date: 11/20/19 Report Date: 12/20/19 Revision 1 - 28-day results Task: Client Project - M7191427 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Airf«-con CO"A" Specified Strength: 4,000 psi @ 28 days Sample Date: 11/20/19 Sample Time: 1125 Sampled By: Charles Solway Mix ID: 60941 Weather Conditions: 41 OF Supplier: CalPortland Accumulative Yards: 475 Batch Size (cy): 10 Batch Time: 1012 Plant: 260 Placement Method: pump hose Truck No.: 7687 Ticket No.: 2233608 Water Added Before (gal): 10 Field Test Data Water Added After (gal): Sample Location: Test Result Specification Placement Location: Slab -on -grade, grid Ines A to D/1 Slump (in): 6 1/2 to12 Air Content (%): Concrete Temp. (F): 67 Ambient Temp. (F): 41 Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Laboratory Test Data Age at Maximum Compressive Set Specimen Avg Diam. Area Date Date Test Load Strength Fracture Tested No. ID (in) (sq in) Received Tested (days) (lbs) (psi) Type By 4 1 4.00 12.57 11/21/19 11/27/19 7 67,090 5,340 2 HRB 4 2 3.97 12.38 11/21/19 12/18/19 28 103,470 8,360 1 KWB 4 3 3.98 12.44 11/21/19 12/18/19 28 102,770 8,260 5 KWB 4 4 3.98 12.44 11/21/19 12/18/19 28 87,260 7,010 1 KWB Average (28 days) 7,880 Initial Cure: Cure Box Final Cure: Moist Room Comments: Average compressive strength of 28 day cylinders complies with the specified strength. Not tested for plastic unit weight. 6.5" slump after water added Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Charles Solway Reported To: Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Senior Project Field Manager Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cR000t, 11-16-12, Rev.6 Page 4 of 4 Distribution Page Report Number: M7191427.0022A Service Date: 11 /20/19 Report Date: 12/20/19 Revision 1 - 28-day results Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 POST -INSTALLED ANCHORS REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0024 Service Date: 12/11/19 Report Date: 12/17/19 20225 Cedar Vallev Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Client Project Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Project No.: M7191427 Permit No.: BLD2018-1658 Weather: Overcast Samples: N/A Monitored epoxy grouting of deformed reinforcing steel into the existing exterior slab -on -grade at the northwest corner of the building for entry stairs curbs. Verified per the approved General Notes on S0.2. The holes were drilled and cleaned prior to epoxy installation using Simpson AT-XP10 (Lot 1000059074, expiration 10/2020) per the manufacturer's written instructions. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Mark Schrader Reported to: WG Clark Construction Co. Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Senior Project Field Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000t, 10-16-13, Rev.lo Page 1 of 1 Distribution Page Report Number: M7191427.0024 Service Date: 12/11 /19 Report Date: 12/17/19 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 CONCRETE OBSERVATION REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0025 Service Date: 12/16/19 Report Date: 12/27/19 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds. WA 98020 Permit No.: BLD2018-1658 Samples: (4) 4x8" cylinders 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmond, WA Project No. Weather: M7191427 Cloudy Performed reinforcing steel inspection for the vestibule 8" stem walls at the Level 1 vestibule at grid lines A.5/11. Verified the reinforcing steel and hold-downs were placed per the approved contract documents, details S2.1, S5.1 and S6.6, and per specifications. Observed the placement of (2) cubic yards of CalPortland concrete mix 61818 for the vestibule 8" stem walls noted above. The concrete was placed via direct discharge and mechanically vibrated for consolidation. A sample was taken with (1) set of (4) 4x8" cylinders cast for compressive strength testing (4000 psi at 28 days required). To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Additional Inspector on site: Jacob Lee Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Randal Dohrman Reported to: WG Clark Construction Co. Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Senior Project Field Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000t, 10-16-13, Rev.lo Page 1 of 1 Distribution Page Report Number: M7191427.0025 Service Date: 12/16/19 Report Date: 12/27/19 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 CONCRETE COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0025A Service Date: 12/16/19 Report Date: 01/15/20 Revision 1 - 28-day results Task: Client Project - M7191427 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Mix ID: 61818 Supplier: CalPortland Batch Time: 0800 Plant: 260 Truck No.: 8457 Ticket No.: 2248912 Field Test Data Test Result Air Content (%): Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Specification 3 -7 55-90 Sample Date: Sampled By: Weather Conditions: Accumulative Yards: Placement Method: Water Added Before (gal): Water Added After (gal): Sample Location: Placement Location: Airf«-con CO"A" 12/16/19 Sample Time: 0900 Randal Dohrman Cloudy 2 Batch Size (cy): 2 Direct Discharge truck chute 8" curb walls at the vestibule Laboratory Test Data Age at Maximum Compressive Set Specimen Avg Diam. Area Date Date Test Load Strength Fracture Tested No. ID (in) (sq in) Received Tested (days) (lbs) (psi) Type By 1 1 3.98 12.44 12/18/19 12/23/19 7 60,450 4,860 2 KWB 1 2 3.98 12.44 12/18/19 01/13/20 28 79,320 6,380 2 MRS 1 3 3.99 12.5 12/18/19 01/13/20 28 80,370 6,430 3 MRS 1 4 3.99 12.5 12/18/19 01/13/20 28 78,440 6,270 2 MRS Average (28 days) 6,360 Initial Cure: Cure Box Final Cure: Moist Room Min Temp: 58 Max Temp: 60 Comments: Average compressive strength of 28 day cylinders complies with the specified strength. Not tested for plastic unit weight. Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Randal Dohrman Reported To: Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Senior Project Field Manager Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cR000t, 11-16-12, Rev.6 Page 1 of 1 Distribution Page MAYES TESTING ENGINEERS Report Number: M7191427.0025A nlre'rracon COMPANY Service Date: 12/16/19 20225 Cedar Valley Rd Ste 110 Report Date: 01/15/20 Revision 1 - 28-day results Lynnwood, WA 98036-6365 Task: 425-742-9360 Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Greg Jackson (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe WOOD FRAME OBSERVATIONS REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0027 Service Date: 01/17/20 Report Date: 01 /21 /20 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds. WA 98020 Permit No.: BLD2018-1658 Samples: N/A 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmond, WA Project No. Weather: M7191427 Cloudy Inspected diaphragm nailing of shear walls for nail size, nail spacing, sheeting size and sheeting grade, from slab -on -grade to Level 2 at grid lines B to D/1 to 12 and A to D/1 to 2, per schedule S2.2 and detail 20/S6.3. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Harold Edmonds Reported to: WG Clark Construction Co. Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Senior Project Field Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000t, 10-16-13, Rev.lo Page 1 of 1 Distribution Page MAYES TESTING ENGINEERS Report Number: M7191427.0027 nlre'rracon COMPANY Service Date: 01/17/20 20225 Cedar Valley Rd Ste 110 Report Date: 01/21/20 Lynnwood, WA98036-6365 Task: 425-742-9360 Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe WOOD FRAME OBSERVATIONS REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0028 Service Date: 01/22/20 Report Date: 01 /27/20 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds. WA 98020 Permit No.: BLD2018-1658 Samples: N/A On site for the following. 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmond, WA Project No. Weather: M7191427 Rain Verified sheathing, nailing and stud pack nailing of (2) shear walls (Type 4) on the 2nd level at grid lines 1/B.2 to D. Walls inspected were laying horizontal on the deck as they will be sheathed with DensGlass®. Verified that walls were per schedule of 20/S6.0. Verified 2nd floor diaphragm sheathing, nailing and straps at grid lines 1 to 12/13.3 to D. Per note 2 of S2.3, 3/4" rated tongue -and -groove sheathing with 10d nails at 4" on center at supported edges and 12" on center field. Diaphragm perimeter nailing is 2" on center staggered. During inspection, any areas found lacking nails were completed prior to departure. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: David Bernier Reported to: WG Clark Construction Co. Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Senior Project Field Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000t, 10-16-13, Rev.lo Page 1 of 1 Distribution Page Report Number: M7191427.0028 Service Date: 01 /22/20 Report Date: 01 /27/20 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 WOOD FRAME OBSERVATIONS REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0029 Service Date: 02/10/20 Report Date: 02/16/20 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds. WA 98020 Permit No.: BLD2018-1658 Samples: N/A 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmond, WA Project No. Weather: M7191427 Clear Inspection of diaphragm, blocked diaphragm and drag strut strapping. Diaphragm, blocked diaphragm and strapping are installed per plan. Location: L2 diaphragm at grid lines A to B from 1 to 10. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Barry Tuttle Reported to: WG Clark Construction Company Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Department Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000t, 10-16-13, Rev.lo Page 1 of 1 Distribution Page Report Number: M7191427.0029 Service Date: 02/10/20 Report Date: 02/16/20 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 GENERAL OBSERVATION REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0030 Service Date: 02/18/20 Report Date: 02/24/20 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds. WA 98020 Permit No.: BLD2018-1658 Samples: N/A 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmond, WA Project No. Weather: M7191427 Clear Monitored epoxy grouting of deformed reinforcing steel bars into the existing footing at the south building perimeter curbs for the walkway. Verified per the approved General Notes on S0.2 and 17/S3.2. The holes were drilled and cleaned, and epoxy installed per the manufacturers instructions. The epoxy used was Simpson SET-XP22 (lot #1000062075, expiration 11/11/21). Verified the diaphragm nailing on the shiplap layer on the roof diaphragm. The diaphragm was verified between grid lines D to C/1 to 12 and found to be in general conformance with the approved plans. Verified per Note 4 on plan page S2.4 and RFI 88. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Mark Schrader Reported to: WG Clark Construction Company Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list Reviewed By: Timothy G. Beckerle, PE Principal The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000l, 10-16-13, Rev.10 Page 1 of 1 Distribution Page Report Number: M7191427.0030 Service Date: 02/18/20 Report Date: 02/24/20 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 CONCRETE OBSERVATION REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0031 Service Date: 02/21/20 Report Date: 02/27/20 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds. WA 98020 Permit No.: BLD2018-1658 Samples: (4) 4x8" cylinders 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmond, WA Project No. Weather: M7191427 Sunny Performed final reinforcing steel inspection for the South Alley slab -on -grade perimeter wall. Verified the reinforcing steel was placed per the approved contract documents details 4/A1.2, 17/S3.2 and per specifications. Observed placement of (13.5) cubic yards of CalPortland concrete mix 3344 for the South Alley slab -on -grade perimeter wall noted above. Concrete was placed by concrete pump truck and mechanically vibrated for consolidation. A sample was taken with a set of (4) 4x8" cylinders cast for compressive strength testing (4,000 psi at 28 days required). Field test results as follows: Ambient Temperature — 50°F Concrete Temperature — 640F Slump — 5.5" Air Content — 5.5% To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Randal Dohrman Reported to: WG Clark Construction Co Contractor: WG Clark Construction Co Report Distribution: See attached distribution list. Reviewed By: -emu Kevin Graham Senior Project Field Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000t, 10-16-13, Rev.lo Page 1 of 1 Distribution Page Report Number: M7191427.0031 Service Date: 02/21 /20 Report Date: 02/27/20 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS Alrerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 CONCRETE COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0031A Service Date: 02/21/20 Report Date: 03/03/20 Task: Client Project - M7191427 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmond, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Mix ID: 3344 Supplier: CalPortland Batch Time: 1330 Plant: 260 Truck No.: 7665 Ticket No.: 2288020 Field Test Data Test Slump (in): Air Content (%): Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Result Specification 5 1/2 67 48 Sample Date: Sampled By: Weather Conditions: Accumulative Yards: Placement Method: Water Added Before (gal): Water Added After (gal): Sample Location: Placement Location: Airf«-con CO"A" 02/21/20 Sample Time: 1430 Randal Dohrman Sunny 9.5 Batch Size (cy): 9.5 Pump truck chute South Alley slab -on -grade perimeter wall Laboratory Test Data Age at Maximum Compressive Set Specimen Avg Diam. Area Date Date Test Load Strength Fracture Tested No. ID (in) (sq in) Received Tested (days) (lbs) (psi) Type By 1 1 3.99 12.5 02/22/20 02/28/20 7 53,810 4,300 2 ZAJ 1 2 02/22/20 03/20/20 28 1 3 02/22/20 03/20/20 28 1 4 02/22/20 03/20/20 28 Initial Cure: Cure Box Final Cure: Moist Room Min Temp: 52 Max Temp: 60 Comments: Not tested for plastic unit weight. Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Randal Dohrman Reported To: Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Senior Project Field Manager Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cR000t, 11-16-12, Rev.6 Page 1 of 1 Distribution Page Report Number: M7191427.0031A Service Date: 02/21 /20 Report Date: 03/03/20 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 WOOD FRAME OBSERVATIONS REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0032 Service Date: 03/05/20 Report Date: 03/09/20 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds. WA 98020 Permit No.: BLD2018-1658 Samples: N/A 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmond, WA Project No. Weather: M7191427 Cloudy Roof sheathing diaphragm between grid lines B and D from 1 to 12, reference S2.4, regarding fastening of 19/32 sheathing over 3X tongue and groove car decking. Verified minimum required CMST14 or CMST12 strapping and A35 connectors for 8x8 members at the skylight openings, meeting RFI 315. Observed screw fastening and 10d nail fastening to follow note 4/S2.4, less the contractor was asked by this inspector to clarify with the engineer -of -record if sheathing panel edge nailing only of 6" on center done in the field is adequate but unable to get response from engineer -of -record, outside of struts, shear walls and at perimeter. Note: On standby time to verify corrections of missing Simpson 1/4" diameter x 6" long SIDS screws at 3" on center staggered and shear walls and struts resolved, as well as missing diaphragm perimeter edge nailing at 2-1/2" on center resolved this visit. PRELIMINARY INSPECTION This field report is preliminary pending engineer -of -record review for atypical sheathing panel edge nailing. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Todd Wirtz Reported to: WG Clark Construction Company Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Department Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000t, 10-16-13, Rev.lo Page 1 of 1 Distribution Page Report Number: M7191427.0032 Service Date: 03/05/20 Report Date: 03/09/20 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 WOOD FRAME OBSERVATIONS REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0033 Service Date: 03/06/20 Report Date: 03/16/20 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds. WA 98020 Permit No.: BLD2018-1658 Samples: N/A 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmonds, WA Project No. Weather: M7191427 Rain, 41 °F On site for inspection of roof diaphragm installed on top of 3" tongue -and -groove decking. Diaphragm consists of 5/8" APA-rated tongue -and -groove plywood with 10d nailing (.148 x 2-1/4") with 12" on center field nailing, per note 4/S2.4. RFI 119 confirms that the edge nailing should be 3" on center at all panel edges. Note 4/S2.4 also calls for 1/4" x 6" SDS screws at 3" on center staggered at diaphragm boundary, interior and exterior shear walls and on top of struts. Today, all sheathing, nailing and screws were verified in the area of grid lines B to D/1 to 12. Preliminary Item. In the area of grid lines A to B/1 to 12, contractor ran out of sheathing for approximately last 6' along A -line. Of the sheathing installed, verified nailing and nailing patterns. SDS screws still need to be installed along north, south and west boundaries, and on top of exterior shear walls and struts. CORRECTIVE ACTIONS TAKEN This report clears Mayes Testing Engineers report M7191427.0032, service date 03/05/20. PRELIMINARY INSPECTION Pending completion of sheathing. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Charles Solway Reported to: WG Clark Construction Co. Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Department Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000t, 10-16-13, Rev.lo Page 1 of 1 Distribution Page Report Number: M7191427.0033 Service Date: 03/06/20 Report Date: 03/16/20 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 WOOD FRAME OBSERVATIONS REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0034 Service Date: 03/09/20 Report Date: 03/16/20 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds. WA 98020 Permit No.: BLD2018-1658 Samples: N/A 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmonds, WA Project No. Weather: M7191427 Sunny Reviewed report 0033 and continued inspection of the floor diaphragm nailing and installation of 1/4" diameter x 6" long SIDS screws and found per plans and RFI's. Inspected the CMST12 straps (CMST14 was required) and the A35 clips into the 8x8 timber framing for the skylights and found per RFI 105. Inspected the parapet walls at grid lines D/6.8 to 8.5, 12/13 to C and 1/13.2 to C. Inspected the Simpson DTT12 clips with the 3/8" lag screws installed through the 3" car decking and into beams below at 16" on center, also noted that SDWH screws from the bottom plate to decking below were installed. The contractor requested this inspection for today as the roofers were on site and were going to be covering this hardware, found per structural detail 4 on S6.1. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Michael Mattox Reported to: WG Clark Construction Company Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Department Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000t, 10-16-13, Rev.lo Page 1 of 1 Distribution Page Report Number: M7191427.0034 Service Date: 03/09/20 Report Date: 03/16/20 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 POST -INSTALLED ANCHORS REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0035 Service Date: 03/11/20 Report Date: 03/17/20 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds. WA 98020 Permit No.: BLD2018-1658 Samples: N/A On site for the following inspections: 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmonds, WA Project No. Weather: M7191427 Inside 1) Post -installed anchors at grid lines 1 to 2/A.8 to B.2 and south wall. The anchors were installed per RFI 113 and detail 17/S3.2. Holes were drilled to depth and cleaned. Simpson SET-XP was placed and bars inserted. Epoxy expiration date is 09/2021. Approximately (110) bars were installed. Contractor installed slab reinforcing, per RFI 113, prior to inspector departing site. 2) Post -installed anchors at the shear walls on Level 1, per RFI 068. Holes were drilled to depth and cleaned. Hilti HIT-HY 200-R epoxy was placed and all -thread anchor inserted. Epoxy expiration date is 12/2020. Anchors were spaced per detail 20/S6.3 for 5/8" diameter anchors. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: David Bernier Reported to: WG Clark Construction Co. Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Department Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000t, 10-16-13, Rev.lo Page 1 of 1 Distribution Page Report Number: M7191427.0035 Service Date: 03/11 /20 Report Date: 03/17/20 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 CONCRETE COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0039A Service Date: 03/19/20 Report Date: 03/27/20 Task: Client Project - M7191427 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Airf«-con CO"A" Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmonds, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Mix ID: 3344 Supplier: CalPortland Batch Time: 0909 Plant: 260 Truck No.: 1759 Ticket No.: 2307079 Field Test Data Test Slump (in): Air Content (%): Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Laboratory Test Data Set Specimen Avg Diam. No. ID (in) 1 1 3.99 1 2 1 3 1 4 Initial Cure: Cure Box Result Specification 5 3/4 71 45 Sample Date: Sampled By: Weather Conditions: Accumulative Yards: Placement Method: Water Added Before (gal): Water Added After (gal): Sample Location: Placement Location: Age at Maximum Area Date Date Test Load (sq in) Received Tested (days) (lbs) 12.5 03/20/20 03/26/20 7 47,070 03/20/20 04/16/20 28 03/20/20 04/16/20 28 03/20/20 04/16/20 28 Final Cure: Moist Room Comments: Not tested for plastic unit weight. Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Michael Mattox Reported To: Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. 03/19/20 Sample Time: 0943 Michael Mattox Sunny 10 Batch Size (cy): 10 Pump 10 0 South Sidewalk Compressive Strength Fracture Tested (psi) Type By 3,760 2 MRS Reviewed By: _ Heath Defo Senior Project Field Manager Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cR000t, 11-16-12, Rev.6 Page 1 of 1 Distribution Page Report Number: M7191427.0039A Service Date: 03/19/20 Report Date: 03/27/20 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 CONCRETE COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0039A Service Date: 03/19/20 Report Date: 04/17/20 Revision 1 - 28-day results Task: Client Project - M7191427 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Airf«-con CO"A" Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmonds, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Sample Date: 03/19/20 Sample Time: 0943 Sampled By: Michael Mattox Mix ID: 3344 Weather Conditions: Sunny Supplier: CalPortland Accumulative Yards: 10 Batch Size (cy): 10 Batch Time: 0909 Plant: 260 Placement Method: Pump Truck No.: 1759 Ticket No.: 2307079 Water Added Before (gal): 10 Water Added After (gal): 0 Field Test Data Sample Location: Test Result Specification Placement Location: South sidewalk Slump (in): 5 3/4 Air Content (%): Concrete Temp. (F): 71 Ambient Temp. (F): 45 Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Laboratory Test Data Age at Maximum Compressive Set Specimen Avg Diam. Area Date Date Test Load Strength Fracture Tested No. ID (in) (sq in) Received Tested (days) (lbs) (psi) Type By 1 1 3.99 12.5 03/20/20 03/26/20 7 47,070 3,760 2 MRS 1 2 3.99 12.5 03/20/20 04/16/20 28 62,280 4,980 2 HRB 1 3 3.99 12.5 03/20/20 04/16/20 28 62,450 4,990 2 HRB 1 4 3.99 12.5 03/20/20 04/16/20 28 61,250 4,900 2 HRB Average (28 days) 4,960 Initial Cure: Cure Box Final Cure: Moist Room Comments: Average compressive strength of 28 day cylinders complies with the specified strength. Not tested for plastic unit weight. Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Michael Mattox Reported To: Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Senior Project Field Manager Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cR000t, 11-16-12, Rev.6 Page 1 of 1 Distribution Page MAYES TESTING ENGINEERS Report Number: M7191427.0039A nlrerracon COMPANY Service Date: 03/19/20 20225 Cedar Valley Rd Ste 110 Report Date: 04/17/20 Revision 1 - 28-day results Lynnwood, WA 98036-6365 Task: 425-742-9360 Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe WOOD FRAME OBSERVATIONS REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0040 Service Date: 03/20/20 Report Date: 03/26/20 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds. WA 98020 Permit No.: BLD2018-1658 Samples: N/A 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmonds, WA Project No. Weather: M7191427 Sunny Continued with lateral wood framing inspections per schedule S6.3 and RFI 42 for wall sheathing, panel edge and field nailing, framing at adjacent panel edges, (2) 2X framing nailing, bottom plate nailing, alternate bottom plate connection to framing, top plate connection at the following shear wall locations: Level 1 at SW2 grid lines 12/B to C; SW4's at NW corner; 2SW3 and 2SW2 at grid lines A/9 to 10 and 10/A to A.5; 2SW2 at grid lines B/5 to 6, 2.5 to 4 and 8 to 9; 2SW2 at grid lines C/11 to 12; 2SW2 at grid lines 10.5/C to D; 2SW2 at grid lines 6.7/C to D; and 2SW4 at grid lines C.25/2 to 3. Installations meet contract documents. Note: Hold-downs and anchor bolt inspections were previously inspected; the second side sheathing inspection will be performed later after MEP final inspection by the City of Edmonds. Continued with lateral wood framing inspections per schedule S6.3 and RFI 42 for wall sheathing, panel edge and field nailing, framing at adjacent panel edges, (2) 2X framing nailing, bottom plate nailing, alternate bottom plate connection to framing, top plate connection at the following shear wall locations: Level 2 at 2SW4 grid lines 2.2/13.25 to B.75; 2SW4 at grid lines 2.7/13.25 to B.75; 2SW4 at grid lines B.7/2.2 to 2.7; 2SW4 at grid lines 2.7/A.8 to B; SW2 at grid lines 13/2.75 to 3.75, 5.5 to 6.75 and 6.75 to 7.5; 2SW4 at grid lines C/10.5 to 11.75; SW2 at grid lines 12C.25 to C.5; SW4 at grid lines D/10.5 to 11.25; 2SW4 at grid lines C.1/4.5 to 6; 2SW4 at grid lines B.75/C to D. Note: Hold-downs and anchor bolt inspections were previously inspected; the second side sheathing inspection will be performed later after MEP final inspection by the City of Edmonds. Verified GLB bolted connections at roof plan S2.4 and pertinent details to be completed. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Todd Wirtz Reported to: WG Clark Construction Company Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Department Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000t, 10-16-13, Rev.lo Page 1 of 1 Distribution Page Report Number: M7191427.0040 Service Date: 03/20/20 Report Date: 03/26/20 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 WOOD FRAME OBSERVATIONS REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0041 Service Date: 03/26/20 Report Date: 03/30/20 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds. WA 98020 Permit No.: BLD2018-1658 Samples: N/A 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmonds, WA Project No. Weather: M7191427 Cloudy Reviewed detail 4 on S6.1 for the parapet wall straps on the exterior of the building at 1-line from B.3 to C, south elevation. Found LSTA21 straps were nailed over the sheathing at the studs, and the wall in this area was also nailed per the shear wall schedule. Inspected (1) sheet of sheathing that was missing on a previous inspection for shear wall nailing as follows: grid lines A 3 to 4 and A 9 to 10. Noted that the contractor used nail spacing 2/12 for the scheduled SW3 and found work to be per plans. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Michael Mattox Reported to: WG Clark Construction Co. Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Department Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000t, 10-16-13, Rev.lo Page 1 of 1 Distribution Page Report Number: M7191427.0041 Service Date: 03/26/20 Report Date: 03/30/20 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS A Irerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 SAMPLE PICK-UP REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0043 Service Date: 03/25/20 20225 Cedar Valley Rd Ste 110 Report Date: 05/11/20 Revision 1 - Transferred from M7191337.0005 Lynnwood, WA 98036-6365 425-742-9360 Client Project Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmonds, WA PO Box 717 Edmonds, WA 98020 Project No.: M7191427 Permit No.: BLD2018-1658 Weather: Overcast, high 40's Samples: (1) sample of 5/8" crushed rock (Proctor) Took a sample of imported 5/8" crushed rock material from the on -site stockpile and transported to Mayes Testing Engineers Lynnwood, WA laboratory for optimum moisture -density determination testing (Proctor). Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Karl Pauly Reported to: WG Clark Construction Company Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Department Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000t, 10-16-13, Rev.lo Page 1 of 1 Distribution Page MAYES TESTING ENGINEERS Report Number: M7191427.0043 nlrerracon COMPANY Service Date: 03/25/20 20225 Cedar Valley Rd Ste 110 Report Date: 05/11/20 Revision 1 - Transferred from M7191337.0005 Lynnwood, WA 98036-6365 Task: 425-742-9360 Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe EARTHWORK OBSERVATION REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0044 Service Date: 03/26/20 Report Date: 05/11/20 Revision 1 - Transferred from M7191337.0007 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds. WA 98020 Permit No.: BLD2018-1658 Samples: N/A 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmonds, WA Project No. Weather: M7191427 Overcast On site to perform field density testing on waterline trench (12'x15'x4' deep) imported backfill subgrade. May Valley Excavation performed the earthwork. Soil Fill Placement Observation At the time of arrival, noticed the material to be used as fill at the area were import materials visually classified as 5/8" crushed rock. Material was observed to be adequately moisture -conditioned and placed in lifts approximately 1' thick. Compaction efforts were applied utilizing a HoPac. The fill placed was observed to be firm and stable after the compaction efforts. Field density tests were conducted utilizing a nuclear density gauge. The test results met the minimum specified compaction requirement of 95%. Refer to the attached Field Density Test Report for individual test data. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Babatunde Soyinka Reported to: WG Clark Construction Company Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Department Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000t, 10-16-13, Rev.lo Page 1 of 1 MAYES TESTING ENGINEERS .Wrommw s,,, - 20225 Cedar }Val lay Road Suite 110 Ph 425.742.9360 L}-nnwood. WA 98036 Fax 425 745 1737 SOIL FIELD DENSITY TEST REPORT Page 1 of 1 Project No.: M7191427 Date: 03/27/20 Project: Edmonds Sr. Center Activity Center Inspector: Babatunde O. (Jimi) Soyinka Test No. Location Depth or Elevation (feet) Probe Depth (inches) Moisture (%) Dry Density (lb/cu.ft.) Compaction (%) Compaction Requirement Minimum (%) Pass Fail Type of Material and Use Optimum Optimum Corrected Field Test Maximum Corrected Field Test 1 Waterline utility trench 2 10 6.1 6.1 5.8 133.4 133.4 126.8 95% 95 X 5/8" crushed gravel 2 Waterline utility trench 1 12 6.1 6.1 5.4 133.4 133.4 127.5 96% 95 X 5/8" crushed gravel 3 Waterline utility trench SG 12 6.1 6.1 5.7 133.4 133.4 127.4 96% 95 X 5/8" crushed gravel Compaction Standard Used WSDOT T606 WSDOT FOP for AASHTO T180 F ASTM D698 ASTM D 1557 X Compaction Test Method Used WSDOT FOP for AASHTO T310 ASTM D6938 X Comments: MTE Nuclear Gauge No.: 38115 Density Std. Count: 2356 Moisture Std. Count: 657 MTE 1400-2C, Rev 4,11.01.17 Distribution Page MAYES TESTING ENGINEERS Report Number: M7191427.0044 nlrerracon COMPANY Service Date: 03/26/20 20225 Cedar Valley Rd Ste 110 Report Date: 05/11/20 Revision 1 - Transferred from M7191337.0007 Lynnwood, WA 98036-6365 Task: 425-742-9360 Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe STRUCTURAL STEEL OBSERVATIONS REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0045 Service Date: 05/07/20 Report Date: 05/11/20 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds. WA 98020 Permit No.: BLDG2018-1658 Samples: N/A 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmonds, WA Project No. Weather: M7191427 Clear, 50s Inspected the field welding of the Level 2 East and North canopy C-channel and HSS connections. The welding was inspected per plan pages S2.3 and S5.1, and RFI's 54 and 73. The North canopy is on grid line 12 from B to 13.5. The East canopies are on grid line D from 5.5 to 6.7, and grid line D from 8.5 to 11.5. Inspected the C- channel to framing connections, the HSS to framing and to C-channel connections. The field welds conformed to the project documents and were visually acceptable per AWS D1.1. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Carl Harrington Reported to: WG Clark Construction Co. Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Heath Defoor, PE Department Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000t, 10-16-13, Rev.lo Page 1 of 1 Distribution Page Report Number: M7191427.0045 Service Date: 05/07/20 Report Date: 05/11/20 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Nekia Williams -Wolfe MAYES TESTING ENGINEERS Alrerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 GENERAL OBSERVATION REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0047 Service Date: 05/21/20 Report Date: 05/27/20 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds. WA 98020 Permit No.: BLD2018-1658 Samples: (4) 4x8" cylinders 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmonds, WA Project No. Weather: M7191427 Rainy Inspected reinforcing steel and observed the placement of approximately (8.5) cubic yards of CalPortland mix 61818 concrete at the grease inceptor vault slab. The concrete was placed by bucket and mechanically consolidated. Cast (1) set of (4) 4x8" lab -cure cylinders for compressive strength testing. The reinforcing steel appears to be as shown on detail 6/CB3.3. The scheduled epoxy -grouted anchors inspection was canceled. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: John Chebul Reported to: WG Clark Construction Co. Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. — Reviewed By: -- Heath Defoor, PE Department Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusiveiy for fhe use of fhe client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000t, 10-16-13, Rev.lo Page 1 of 1 Distribution Page Report Number: M7191427.0047 Service Date: 05/21 /20 Report Date: 05/27/20 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Matthew Raskasky MAYES TESTING ENGINEERS Alrerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 CONCRETE COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0047A Service Date: 05/21/20 Report Date: 06/01/20 Task: Client Project - M7191427 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Airf«-con CO"A" Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmonds, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Specified Strength: 5,000 psi @ 28 days Mix ID: 61818 Supplier: CalPortland Batch Time: Plant: Truck No.: 7670 Ticket No.: 2332653 Field Test Data Test Slump (in): Air Content (%): Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Laboratory Test Data Result Specification 4 70 57 Set Specimen Avg Diam. No. ID (in) _ 1 a 3.99 1 b 1 c 1 d Initial Cure: Outside Plastic Lids Sample Date: Sampled By: Weather Conditions: Accumulative Yards: Placement Method: Water Added Before (gal): Water Added After (gal): Sample Location: Placement Location: Age at Maximum Area Date Date Test Load (sq in) Received Tested (days) (lbs) 12.5 05/22/20 05/28/20 7 66,560 05/22/20 06/18/20 28 05/22/20 06/18/20 28 05/22/20 06/18/20 28 Final Cure: Moist Room Comments: Not tested for plastic unit weight. Loader bucket. Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: John Chebul Reported To: Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. 05/21/20 Sample Time: John Chebul Rain 4.5 of 8.5 Batch Size (cy): Other (Please see Comments) 0 Grease interceptor vault slab. 4.5 Compressive Strength Fracture Tested (psi) Type By 5,320 2 HRB Reviewed By: 4-4- th Defoor, PE Senior Project Field Manager Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cR000t, 11-16-12, Rev.6 Page 1 of 1 Distribution Page Report Number: M7191427.0047A Service Date: 05/21 /20 Report Date: 06/01 /20 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Matthew Raskasky MAYES TESTING ENGINEERS Alrerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 CONCRETE COMPRESSIVE STRENGTH TEST REPORT MAYES TESTING ENGINEERS Report Number: M7191427.0047A Service Date: 05/21/20 Report Date: 06/19/20 Revision 1 - 28-day results Task: Client Project - M7191427 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Airf«-con CO"A" Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmonds, WA PO Box 717 Edmonds, WA 98020 Permit No.: BLD2018-1658 Material Information Sample Information Specified Strength: 5,000 psi @ 28 days Sample Date: 05/21/20 Sample Time: Sampled By: John Chebul Mix ID: 61818 Weather Conditions: Rain Supplier: CalPortland Accumulative Yards: 4.5 of 8.5 Batch Size (cy): 4.5 Batch Time: Plant: Placement Method: Other (Please see Comments) Truck No.: 7670 Ticket No.: 2332653 Water Added Before (gal): 0 Field Test Data Water Added After (gal): Sample Location: Test Result Specification Placement Location: Grease interceptor vault slab. Slump (in): 4 Air Content (%): Concrete Temp. (F): 70 Ambient Temp. (F): 57 Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Laboratory Test Data Age at Maximum Compressive Set Specimen Avg Diam. Area Date Date Test Load Strength Fracture Tested No. ID (in) (sq in) Received Tested (days) (lbs) (psi) Type By 1 a 3.99 12.5 05/22/20 05/28/20 7 66,560 5,320 2 HRB 1 b 3.99 12.5 05/22/20 06/18/20 28 93,690 7,490 2 HRB 1 c 3.98 12.44 05/22/20 06/18/20 28 89,100 7,160 5 HRB 1 d 3.99 12.5 05/22/20 06/18/20 28 86,020 6,880 2 HRB Average (28 days) 7,180 Initial Cure: Outside Plastic Lids Final Cure: Moist Room Comments: Average compressive strength of 28 day cylinders complies with the specified strength. Not tested for plastic unit weight. Loader bucket Samples Made By: Mayes/Terracon Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: John Chebul Reported To: Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. Reviewed By: Thomas Cain Senior Project Field Manager Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cR000t, 11-16-12, Rev.6 Page 1 of 1 Distribution Page Report Number: M7191427.0047A Service Date: 05/21 /20 Report Date: 06/19/20 Revision 1 - 28-day results Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Matthew Raskasky MAYES TESTING ENGINEERS Alrerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 EARTHWORK OBSERVATION REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0048 Service Date: 06/10/20 Report Date: 06/12/20 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds. WA 98020 Permit No.: BLDG2018-1658 Samples: N/A 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmonds, WA Project No.: M7191427 Weather: Partly cloudy, 60's Picked up a density moisture gauge at the Mayes Testing Engineers (MTE) Lynnwood Lab and transported it to the project site. Inspected the compaction of the backfill placed at the new grease interceptor structure on the east side of the building. The fill material is Type 17 gray sand with gravel, with a Proctor density of 131.9 per cubic foot at 5.9% optimal moisture content (MTE Lab Number 4663). The material was placed by excavator in approximately 1' lifts and compacted with a hoe -pack. Per the email from Sean Gertz, Landau Associates, dated 06/10/20, the minimum compaction specification is 90%. The material was placed from 7' below the top of the structure to 4' below the top of the structure. The material placed today met the 90% minimum compaction specification. See the attached Soil Field Density Test Report for locations and results. Returned the density moisture gauge to the MTE Lynnwood Lab. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Carl Harrington Reported to: WG Clark Construction Co. Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. C n Reviewed By: Thomas Cain Senior Project Field Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000t, 10-16-13, Rev.lo Page 1 of 1 MAYES TESTING ENGINEERS • JHJ2LLII144W W 20225 Cedar Val lay Road. Sute 110 Ph 426.742.9360 Lynnwood. WA 98036 Fax 425 74!5 1737 SOIL FIELD DENSITY TEST REPORT Project No.: Project: Inspector: Page 1 of 1 M7171427 Date: 06/10/20 Edmonds Senior Center Activity Center Carl Harrinqton Test No. Location Depth or Elevation (feet) Probe Depth (inches) Moisture (%) Dry Density (ib/cu.ft.) Compaction (%) Compaction Requirement Minimum (%) Pass Fail Type of Material and Use Optimum Optimum Corrected Field Test Maximum Corrected Field Test 1 Grease Interceptor TOS -6' 12 5.9 5.9 4.8 131.9 131.9 126.5 96% 90 X Type 17 2 Grease Interceptor TOS -5' 12 5.9 5.9 3.9 131.9 131.9 129.1 98% 90 X Type 17 3 Grease Interceptor TOS 4 12 5.9 5.9 3.2 131.9 131.9 127.9 97% 90 X Type 17 Compaction Standard Used WSDOT T606 WSDOT FOP for AASHTO T180 ASTM D698 ASTM D 1557 X Compaction Test Method Used WSDOT FOP for AASHTO T310 1 1 ASTM D6938 X Comments: Backfill at grease interceptor structure, east side of building. MTE Nuclear Gauge No.: ToD of Structure=TOS 24 Density Std. Count: 2027 Moisture Std. Count: 673 MTE 1400-2C, Rev 4, 11.01.17 Distribution Page Report Number: M7191427.0048 Service Date: 06/10/20 Report Date: 06/12/20 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Matthew Raskasky MAYES TESTING ENGINEERS Alrerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 WOOD FRAME OBSERVATIONS REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0049 Service Date: 06/10/20 Report Date: 06/12/20 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds. WA 98020 Permit No.: BLD2018-1658 Samples: N/A 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmonds, WA Project No. Weather: M7191427 Indoors Verified sheathing and nailing of the second side of shear walls designated Type 2SW2 and Type 2SW4 on the Second Level at grid lines 10/A-A.2 and 2.7/13.3-13.6. The sheathing and nailing were per the schedule in detail 20/S6.3. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: David Bernier Reported to: WG Clark Construction Co. Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. C n Reviewed By: Thomas Cain Senior Project Field Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000t, 10-16-13, Rev.lo Page 1 of 1 Distribution Page Report Number: M7191427.0049 Service Date: 06/10/20 Report Date: 06/12/20 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Matthew Raskasky MAYES TESTING ENGINEERS Alrerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 WOOD FRAME OBSERVATIONS REPORT Report Number: M7191427.0050 Service Date: 06/11/20 Report Date: 06/15/20 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds. WA 98020 Permit No.: BLD2018-1658 Samples: N/A MAYES TESTING ENGINEERS nlrerracan cmernxv 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmonds, WA Project No. Weather: M7191427 Cloudy On Level 2 at shear wall type 2SW4 (second side) along grids 2.6/A-B (reference S2.3 and S6.3 shear wall schedule), the sheathing, panel edge and field nailing were verified per the shear wall schedule. Top plate clips that were installed prior to second side sheathing per photo below: ''� The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000t, 10-16-13, Rev.10 Page 1 of 2 WOOD FRAME OBSERVATIONS REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0050 Service Date: 06/11/20 Report Date: 06/15/20 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Client Project Edmonds Senior Center Edmonds Senior Center Activity Center Attn: Daniel Johnson 220 Railroad Ave 220 Railroad Ave Edmonds, WA PO Box 717 Edmonds. WA 98020 Proiect No.: M7191427 To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Todd Wirtz Reported to: WG Clark Construction Co. Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. C n Reviewed By: Thomas Cain Senior Project Field Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000t, 10-16-13, Rev.lo Page 2 of 2 Distribution Page Report Number: M7191427.0050 Service Date: 06/11 /20 Report Date: 06/15/20 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Matthew Raskasky MAYES TESTING ENGINEERS Alrerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 GENERAL OBSERVATION REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0051 Service Date: 06/29/20 Report Date: 07/07/20 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds. WA 98020 Permit No.: BLD2018-1658 Samples: N/A 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmonds, WA Project No. Weather: M7191427 Cloudy Inspected second side diaphragm nailing of 2SW4 shear walls from Level 2 to roof at grids B-C/2-3, C/4-6, C/10.5-12 and C-D/6.6 for nail size, nail spacing, sheathing size and sheathing grade, per detail 20/S6.3. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Harold Edmonds Reported to: WG Clark Construction Co. Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. C n Reviewed By: Thomas Cain Senior Project Field Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000t, 10-16-13, Rev.lo Page 1 of 1 Distribution Page Report Number: M7191427.0051 Service Date: 06/29/20 Report Date: 07/07/20 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Robert Drucker (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Matthew Raskasky MAYES TESTING ENGINEERS Alrerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 GENERAL OBSERVATION REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0053 Service Date: 07/17/20 Report Date: 07/20/20 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds. WA 98020 Permit No.: BLD2018-1658 Samples: N/A 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmonds, WA Project No. Weather: M7191427 Inside Inspection of second side of double sided shear walls. Shear nailing was installed per schedule. Location: L1 shear walls at grid lines B.3 to D from 1 to 12. Observed installation of 3/4" all -thread epoxy anchor bolts. Holes were drilled to 8-1/2" of embedment, per detail 5/S5.1. and cleaned per specification. The epoxy used was Hilti HIT HY 20OR (lot # 175927L2, expiration 02/2021). Location: anchor bolts for north stair. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Barry Tuttle Reported to: WG Clark Construction Company Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. C n Reviewed By: Thomas Cain Senior Project Field Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000t, 10-16-13, Rev.lo Page 1 of 1 Distribution Page Report Number: M7191427.0053 Service Date: 07/17/20 Report Date: 07/20/20 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Robert Drucker (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Matthew Raskasky MAYES TESTING ENGINEERS Alrerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 WOOD FRAME OBSERVATIONS REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0054 Service Date: 07/31/20 Report Date: 08/05/20 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds. WA 98020 Permit No.: BLD2018-1658 Samples: N/A 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmonds, WA Project No. Weather: M7191427 Clear Inspected the second side of the Level 1 double -sided shear walls at grids 2.5-10/A-13. Shear nailing was installed per schedule on detail 20/S6.3. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Barry Tuttle Reported to: WG Clark Construction Company Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. C n Reviewed By: Thomas Cain Senior Project Field Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000t, 10-16-13, Rev.lo Page 1 of 1 Distribution Page Report Number: M7191427.0054 Service Date: 07/31 /20 Report Date: 08/05/20 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Robert Drucker (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Matthew Raskasky MAYES TESTING ENGINEERS Alrerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 EARTHWORK OBSERVATION REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0055 Service Date: 07/01/20 Report Date: 08/06/20 Revision 1 - Transferred from M7191337.0023 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds. WA 98020 Permit No.: BLD2018-1658 Samples: N/A 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmonds, WA Project No. Weather: M7191427 Overcast On site to perform field density testing on frontage sewage line using imported backfill up to subgrade, close to Railroad Avenue. WG Clark Construction Company performed the earthwork activities. Soil Fill Placement Observation At the time of arrival, noticed the material to be used as fill at the area was import material visually classified as recycled concrete. Material was observed to be adequately moisture -conditioned and placed in lifts approximately 1' thick. Compacting efforts were applied utilizing a HoPac and hand plate compactor. The fill placed was observed to be firm and stable after the compaction efforts. Field density tests were conducted utilizing a nuclear density gauge. The test results met the minimum specified compaction requirement of 95%. Refer to the attached Field Density Test Report for individual test data. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Babatunde Soyinka Reported to: WG Clark Construction Company Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. C n Reviewed By: Thomas Cain Senior Project Field Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000t, 10-16-13, Rev.lo Page 1 of 1 MAYES TESTING ENGINEERS .lfnraccn ca— 20225 Cedar Valley: Road Suple 110 Ph 425.742.9360 Lynnwood. WA 98036 Fax 425 745 1737 SOIL FIELD DENSITY TEST REPORT Page 1 of 1 Project No.: M7191427 Date: 7/1/2020 Project: Edmonds Senior Center Activity Center Inspector: Jimi Soyinka Test No. Location Depth or Elevation (feet) Probe Depth (inches) Moisture (%) Dry Density (Ib/cu.ft.) Compaction (%) Compaction Requirement Minimum (%) Pass Fail Type of Material and Use Optimum Optimum Corrected Field Test Maximum Corrected Field Test 1 Sewage/Railroad Ave. SG 10 5.9 5.9 5.1 131.9 131.9 124.8 95% 95 Recycled conc. 2 Sewage/Railroad Ave. SG 10 5.9 5.9 4.6 131.9 131.9 125 95% 95 Recycled conc. Compaction Standard Used WSDOT T606 WSDOT FOP for AASHTO T180 ASTM D698 ASTM D 1557 X Compaction Test Method Used WSDOT FOP for AASHTO T310 ASTM D6938 X Comments: MTE Nuclear Gauge No.: 20939 Density Std. Count: 1578 Moisture Std. Count: 543 MTE 1400-2C, Rev 4, 11.01.17 Distribution Page Report Number: M7191427.0055 Service Date: 07/01 /20 Report Date: 08/06/20 Revision 1 - Transferred from M7191337.0023 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Robert Drucker (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Matthew Raskasky MAYES TESTING ENGINEERS Alrerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 MASONRY OBSERVATIONS REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7191427.0056 Service Date: 08/31/20 Report Date: 09/16/20 Client Edmonds Senior Center Attn: Daniel Johnson 220 Railroad Ave PO Box 717 Edmonds. WA 98020 Permit No.: BLD2018-1658 Samples: N/A 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project Edmonds Senior Center Activity Center 220 Railroad Ave Edmonds, WA Project No. Weather: M7191427 Observed placement of, and verified special inspection requirements for, the exterior stone cladding/veneer of the building. The contractor was installing materials using industry standard practices and manufacturer instructions, as well as following project specifications. Per the project plan sheet S0.5 "Inspection Schedule", notes 1 and 2 under "Nonstructural Components" state that no special inspection is required for exterior cladding/veneer less than 30' in total height. The building surface receiving cladding/veneer is 253-3/8" in height; and therefore, no special inspection is required. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Phil Dupont Reported to: WG Clark Construction Company Contractor: WG Clark Construction Co. Report Distribution: See attached distribution list. C n Reviewed By: Thomas Cain Senior Project Field Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cr000t, 10-16-13, Rev.lo Page 1 of 1 Distribution Page Report Number: M7191427.0056 Service Date: 08/31 /20 Report Date: 09/16/20 Task: Distribution List (1) Edmonds Senior Center, Daniel Johnson (1) City of Edmonds WA, Leif Bjorback (1) City of Edmonds WA, Milton Thompson (1) Environmental Works, Inc., Alise Kuwahara Day (1) Environmental Works, Inc., Robert Drucker (1) Environmental Works, Inc., Sally Knodell (1) Mayes Testing Engineers, Inc, Donna Pollard (1) Mayes Testing Engineers, Inc, Todd Wirtz (1) Reid Middleton, Katy Brawner (1) Reid Middleton, Paul Crocker (1) WG Clark Construction Co, Jim Bray (1) WG Clark Construction Co, Matthew Raskasky MAYES TESTING ENGINEERS Alrerracon COMPANY 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360