BLD REV 1 APPROVED PLANSGENERAL NOTES: 1.0 GENERAL THESE STRUCTURAL NOTES SUPPLEMENT THE SPECIFICATIONS, ANY DISCREPANCY FOUND AMONG THE DRAWINGS, SPECIFICATIONS, THESE NOTES, AND THE SITE CONDITIONS SHALL BE REPORTED TO THE OWNER, WHO SHALL CORRECT SUCH DISCREPANCY IN WRITING. ANY WORK DONE BY THE CONTRACTOR AFTER DISCOVERY OF SUCH DISCREPANCY SHALL BE DONE AT THE CONTRACTOR'S RISK. THE CONTRACTOR SHALL VERIFY AND COORDINATE THE DIMENSIONS AMONG ALL DRAWINGS PRIOR TO PROCEEDING WITH ANY WORK OR FABRICATION. THE CONTRACTOR 15 RESPONSIBLE FOR ALL BRACING AND SHORING DURING CONSTRUCTION. 1.1 CODES ALL METHODS, MATERIALS AND WORKMANSHIP SHALL CONFORM TO THE REQUIREMENTS OF THE CITY OF EDMONDS: 2015 INTERNATIONAL RESIDENTIAL CODE (IRC), AS AMENDED AND ADOPTED BY THE CITY OF EDMONDS AND THE STATE OF WABHINGTON± A.G.I. 318, A.I.-S.C. 9TH EDITION, AND A.I.T.C. 3RD EDITION. 1.2 DESIGN CRITERIA A. LIVE LOADS ROOF (SNOW) 25 PSF FLOOR RES 40 PSF FLOOR DECKS (o0 PSF B. LATERAL LOADS: WIND DESIGN CRITERIA: 1. BASIC WIND SPEED 85 mph 2. WIND IMPORTANCE, I W = 1.00 (CATEGORY II) 3. WINDOW EXPOSURE 'B' 4. INTERNAL PRESURE COEFFICIENT N/A (SIMPLIFIED WIND LOAD METHOD - 1609.6) 5. COMPONENTS AND CLADDING ZONE POSITIVE PRESSURE NEGATIVE PRESSURE 1 l l.9 PSF -133 PSF 2 11.9 P5F -152 PSF 2 (OVERHANG) -24.1 PSF 3 11.9 PSF -152 PSF 3 (OVERHANG) -24.1 PSF 4 13.0 PSF -14.1 PSF 5 13.0 PSF -11A PSF TOPOGRAPHIC EFFECT FACTOR K =1.0 Tz SEISMIC DESIGN CRITERIA: 1. SEISMIC IMPORTANCE, le = 1.0 SEISMIC USE GROUP I 2. MAPPED SPECTRAL RESPONSE ACCELARATIONS 8 =1.55% B, = .545, 3. SITE CLA58 : D 4. SITE RESPONSE COEFFICIENTS: 8 cls = 1.03% 8 c1l =.545 5. SEISMIC DESIGN CATEGORY: D 6. BASIC SEISMIC -FORGE -RESTING SYSTEM: BEARING WALL SYSTEM 1. DE51GN BASE SHEAR: 18.8 KPS 8. SEISMIC RE5PON5E COEFFIENTS: Cs =0.14 9. RESPONSE MODIFICATION FACTOR: R=6.5 10. SIMPLIFIED SEISMIC ANALYSIS RPOCEDURE 1.3 SOIL DATA FOR LOCATIONS SEE SOILS REPORT. 501L BEARING g CONT. SPREAD FOOTINGS = 2000 PSF. ALLOW 33-I/3% INCREASE FOR LOADS FROM WIND OR SEISMIC ORIGIN. EQUIVALENT FLUID ACTIVE IORE85URE AND PA551VE IORE85URE ARE 35 PCF AND 300 PCF, RESPECTIVELY. 2.0 SITE WORK 2.1 EXCAVATION EXCAVATE FOR FOOTINGS DOWN TO DEPTH SHOWN ON DRAWINGS OR TO FIRM UNDISTURBED MATERIAL. AREAS OVER -EXCAVATED SHALL BE BACKFILLED WITH LEAN CONCRETE (F'c = 2000 PSI), OR BE STRUCTURALLY FILLED PER SECTION 22 AND SHALL BE AT THE CONTRACTOR'S EXPENSE. 2.2 BACKFILL AND COMPACTION BACKFILL SHALL NOT BE PLACED UNTIL AFTER THE REMOVAL OF ALL FORMS, 5CREED8, OTHER WOOD DEBRIS AND MATERIAL SUBJECT TO ROT OR CORROSION. USE ONLY MATERIALS APPROVED FOR BACKFILL . IN AREAS UNDER SLABS OR FOOTINGS, MATERIAL SHOULD BE GRANULAR IN NATURE, PLACED IN (o-INCH LIFTS AND COMPACTED TO AT LEAST 955ko OF MAXIMUM DRY DENSITY AS DETERMINED BY AASHTO COMPACTION TEST, PROCEDURE T-180. THE FILL SHOULD BE LIMITED TO CLEAN, GRANULAR MATERIAL. 3.0 CONCRETE 5 BACKS OF CONCRETE PER CUBIC YARD 3.1 GENERAL ALL CONCRETE SHALL BE HARD ROCK CONCRETE MEETING REQUIREMENTS FOR "ULTIMATE STRENGTH TYPE CONCRETE", PER ACI 301, "SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDING." PROPORTIONING OF INGREDIENTS FOR EACH CONCRETE MIX SHALL BE BY METHOD 2 OR THE ALTERNATE PROCEDURE GIVEN IN ACI 301. PLACE CONCRETE PER ACI-304 AND CONFORM TO ACI-604(306) WINTER CONCRETING AND ACI-605(305) FOR HOT WEATHER CONCRETING. CONCRETE SHALL BE PLACED TO AVOID SEGREGATION, HONEYCOMBING OR POCKETS. USE INTERIOR MECHANICAL VIBRATORS WITH 1000 RPM MINIMUM FREQUENCY. DO NOT OVER -VIBRATE. CONCRETE SHALL BE POURED MONOLITHICALLY BETWEEN CONSTRUCTION OR CONTROL JOINTS. PROTECT ALL FRESHLY PLACED CONCRETE FROM PREMATURE DRYING AND EXCE551VE HOT OR COLD TEMPERATURES FOR SEVEN DAYS AFTER POURING. PROVIDE ENGINEER WITH PROPOSED CONSTRUCTION OR CONTROL JOINT LOCATIONS FOR HIS APPROVAL, OR USE JOINTS AS SHOWN ON THE DRAWINGS. ALL TIER AND ANCHORS SHALL BE CUT OFF FLUSH WITH THE BUF�FACE± SURFACES WHERE EXPOSED SHALL BE SMOOTH AND FREE FROM IRREGULARITIES. 3.2 STRENGTH TWENTY-EIGHT DAY COMPRESSIVE STRENGTHS SHALL BE: SLABS ON GRADE : 2000 PSI± MAX SLUMP 3" (UNSUPERVISED) FOOTING 4 WALLS: 2000 PSI± MAX SLUMP 4" (UNSUPERVISED) THESE SLUMPS MAY BE INCREASED IF A PROPER ADDITION OF POZZOLITH IS ADDED TO ALLOW HIGHER SLUMP AND GREATER WORKABILITY WITHOUT CHANGING THE WATER CONTENT OF THE ORIGINAL MIX DESIGN. PROPORTION MIX ACCORDING TO IRC 1904. 3.3 MATERIAL: MATERIAL: CEMENT, WATER 4 AGGREGATES PER ACI 301 A. CEMENT MUST CONFORM TO ABTM 150, TYPE I OR TYPE II. ENGINEER'S APPROVAL 18 REQUIRED FOR USE OF TYPE III CEMENT. B. WATER TO BE CLEAN AND POTABLE. G. COARSE AND FINE AGGREGATES TO CONFORM TO ASTM-G33. 3.4 MATERIALS A. WATER REDUCING ADMIXTURES: MUST CONFORM TO A5TM-C494, POZZOLITH 344N, POZZOLITH IOOXR, OR POZOLITH 122HE. POZZOLITH SHALL BE INCORPORATED INTO ALL CONCRETE IN EXACT ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS "SYNERGIZED PERFORMANCE SYSTEMS" CONCRETE U51NG POZZOLITH ADMIXTURES TO PRODUCE FLOWABLE CONCRETE MAY BE USED WITH THE ENGINEER'S APPROVAL. ADMIXTURES AND DOSAGES WILL VARY DEPENDING ON CLIMATIC CONDITIONS AND THE CONTRACTOR'S J055ITE REQUIREMENTS. MAXIMUM SLUMP FOR "SYNERGIZED PERFORMANCE SYSTEMS" CONCRETE SHALL NOT EXCEED 8" USE IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. B. AIR ENTRAINMENT: CONFORM TO ASTM-C260 AND A5TM-C494, MB-AE-10 BY MASTER BUILDER ENTRAIN 5% +/- 1% AIR BY VOLUME IN ALL EXPOSED CONCRETE. C. OTHER ADMIXTURE: NO OTHER ADMIXTURES PERMITTED UNLESS PRIOR APPROVAL IS GIVEN BY THE ENGINEER 3.5 REINFORCING STEEL DETAIL, FABRICATE AND PLACE PER ACI-315 AND ACI-318. SUPPORT REINFORCEMENT WITH APPROVED CHAIRS, SPACERS, OR TIES. A. STEEL REINFORCEMENT SHALL BE NEW, DEFORMED BILLET STEEL, MEETING ASTM A615, GRADE 60 FOR 05 AND LARGER BARS, EXCEPT AS NOTED± GRADE 40 FOR 04 AND SMALLER BARS. SHOP DRAWINGS SHALL BE MARKED ACCORDINGLY AND SUBMITTED TO THE ENGINEER FOR REVIEW PRIOR TO FABRICATION. GRADE 60 REBARS SHALL NOT BE BENT IN FIELD AFTER PLACING. B. REINFORCEMENT IN ALL WALLS, SLABS, AND FOOTINGS SHALL BE CONTINUOUS AROUND CORNERS OR CORNER BARS PROVIDED, BOTH VERTICAL AND HORIZONTAL. C. LAPS: ALL TENSION SPLICES ARE ACCORDING TO ACI 310-09, CLASS B AND ALL COMPRESSION SPLICES ARE 30 DIAMETERS, UNLESS NOTED OTHERWISE. D. TRIM REINFORCING: AROUND ALL OPENINGS SHALL BE A MINIMUM 1-*5 TOP AND BOTTOM, EXTENDING 2'-6" BEYOND OPENING AT EACH CORNER SEE TYPICAL DETAILS. E. WELDING: TACK WELDING OF REBAR IS NOT PERMITTED UNLESS CALLED F. MINIMUM REINFORCING: WHERE REINFORCEMENT IS NOT SHOWN ON DRAWINGS, THE "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE" (ACI 318-89) SHALL BE REFERRED TO FOR PROPER REINFORCEMENT. G. REBAR COVER: PROVIDE CONCRETE PROTECTION FOR REINFORCEMENT AS FOLLOWS: 3" CONCRETE DEPOSITED AGAINST EARTH 2" CONCRETE DEPOSITED AGAINST FORMS BUT EXPOSED TO EARTH 1-1/2" TO TIES IN COLUMNS, AND TIED REBAR IN WALLS 1-1/2" FOR BARS IN SLABS ON GROUND 3/4" INTERIOR FACE OF WALLS H. WELDED WIRE FABRIC: ASTM-AI85 AND A5TM-A82 J. MINIMUM STEEL REQUIREMENTS FOR CONCRETE WALL USING 04 REBAR HEIGHT VERTICAL HORIZONTAL 014118" O.C. 18" O.G. 6'-9' 1(o" O.C. 10" O.G. 3.6 FOUNDATION ANCHOR BOLTS 5/8" STEEL BOLTS, WITH 1" MIN. EMBEDMENT INTO CONCRETE. PROVIDE A MIN. OF (2) BOLTS PER SILL PLATE. ANCHOR BOLTS SHALL BE PLACED AT 12" O.G. FOR ONE STORY, 48" O.G. FOR TWO STORY RESIDENCES AND REFER TO LATERAL ENGINEERING FOR THREE STORY RESIDENCES. ADDITIONALLY, ONE BOLT MUST BE NO LESS THAN 1" FROM EACH END OF EACH INDIVIDUAL SILL PLATE. ANCHOR BOLT WASHERS MUST BE A MINUMUM OF 3"x3" (SQUARE) x 3/16" (THICKNESS) 4.0 CARPENTRY 4.1 ROUGH CARPENTRY ALL 2x FRAMING LUMBER SHALL BE STUD GRADE DOUG-FIR FOR STUDS AND STANDARD OR BETTER FOR PLATES OR AS SHOWN ON THE DRAWINGS OR BELOW. ALL 2" LUMBER SHALL BE KILN DRIED (KD) OR SURFACE DRIED (81D). EACH PIECE OF LUMBER SHALL BEAR THE STAMP OF THE WEST COAST LUMBER INSPECTION BUREAU SHOWING GRADE MARK OR APPROVED EQUAL. OTHER MATERIALS AS SHOWN BELOW 2x 4 3x STUDS - STUD GRADE DOUG-FIR 2x JOISTS - 01 DOUG-FIR 4 x 4 4 4 x 6 COLUMNS - *1 DOUGLAS FIR 6x HEADERS - *1 DOUGLAS FIR 4x HEADERS - *2 DOUGLAS FIR ALL EXPOSED MATERIALS OR MATERIAL IN CONTACT WITH CONCRETE SHALL BE PRESSURE TREATED. 4.3 CARPENTRY HARDWARE A. BOLTS SHALL BE ABTM A-301. B. WASHERS SHALL BE MALLEABLE IRON WASHERS(MIN). C. NAILS SHALL BE COMMON, AMERICAN OR CANADIAN MANUFACTURER ONLY. D. LAG SCREWS, SHEAR PLATES - SEE NATIONAL DESIGN SPECIFICATION. E. ANCHORS AND CONNECTORS SHALL BE 51MP50N, TECO, BOWMAN OR OTHER ICBO APPROVED. F. PROTECTION HARDWARE EXPOSED TO WEATHER OR TO VIEW OR IN UNHEATED PORTION OF BUILDING SHALL BE GALVANIZED. 4.4 MINIMUM NAILING - PER 2015 IRC 4.5 GLUE -LAMINATED TIMBER ALL STRUCTURAL GLUE -LAMINATED TIMBER, MATERIALS, MANUFACTURE AND QUALITY CONTROL SHALL BE IN CONFORMANCE WITH VOLUNTARY PRODUCT STANDARD 10.6.56 "STRUCTURAL GLUED LAMINATED TIMBER", AND ALL MEMBERS SHALL BE MARKED WITH A QUALITY MARK THEREOF. ALL PLIES SHALL BE DOUGLAS FIR COAST REGION. CAMBERS ARE AS SHOWN ON THE DRAWINGS. ALL MEMBERS SHALL BE EITHER COMBINATION 24F-V4 (SIMPLE SPAN) OR 24F-V8 (CANTILEVERED OR CONTINUOUS SPAN) AS APPLICABLE. ALL MEMBERS SHALL BE INDUSTRIAL APPEARANCE AND SHALL BE GLUED WITH WATERPROOF ADHESIVE PER P.S. 56. ARCHES SHALL BE COMBINATION 24F-VS AND HAVE EXTERIOR GLUE, ARCHITECTURAL GRADE. 5.0 MISCELLANEOUS VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO PROCEEDING. PROVIDE ERECTION BRACING AS NECESSARY UNTIL PERMANENT SUPPORT AND STIFFNESS ARE INSTALLED. REFER TO ARCHITECTURAL PLANS FOR WALL OPENING, ARCHITECTURAL TREATMENT AND DIMENSIONS NOT SHOWN. REFER TO MECHANICAL AND ELECTRICAL PLANS FOR SIZE AND LOCATION OF ALL OPENINGS FOR DUCTS, PIPES, CONDUITS, ETC., NOT SHOWN. 6.0 TABLE OF AREAS LIVING AREA 4543 SQUARE FEET EXISTING LIVING AREA 211 SQUARE FEET PROPOSED LIVING AREA 4814 SQUARE FEET TOTAL NEW GARAGE 250 SQUARE FEET NEW DECK 1008 SQUARE FEET 7.0 ENERGY WINDOWS 30 'U' VALUE DOORS 20 V VALUE 2015 WASHINGTON STATE ENERGY CODE CREDIT:5a: ALL SHOWER HEADS AND KITCHEN FAUCETS SHALL BE RATED AT 1.15 GPM OR LESS, AND ALL OTHER FAUCETS SHALL BE RATED AT 1.0 GPM OR LESS. EXISTING MEDIUM GAS FURNACE 15K BTUH FILTER FABRIC SECURED TO 2" X 2" 14 GA. WIRE FABRIC EQUAL CD 8"- 12" 8" PLACE 3/4"-1,5" WASHED GRAVEL IN THE TRENCH AND ON BOTH SIDES OF FILTER FABRIC FENCE ON THE SURFACE, 0 i ICONTRACTOR/DEVELOPER SHALL MAINTAIN AND REPLACE STRAW BALES TO INSURE PROPER ER❑SI❑N CONTROL, 'C190-199v NO OVERHANG MORE THAN 18" INTO THE - SETBACK FILTER FABRIC MATERIAL IN C❑NTIN❑US ROLLS. USE STAPLES OR WIRE RINGS TO ATTACH FABRIC TO WIRE. I I I I II II II WIRE MESH SUPPORT FENCE TO SUPPORT FILTER FABRIC, II II II II I�Illll�lillllll111lll���llllllllllllll�l���illl�,�� I „III„i���lll�llll� I I __ ________ BURY BOTTOM OF FILTER MATERIAL 8" TO 12" II II I I 6' MAX. I u 2" X 2" WOOD POSTS OR EQUIVALENT CITY INSPECTI❑N REQUIRED ON ALL ER❑SI❑N CONTROL METHODS BEFORE OTHER WORK CAN BEGIN. C ITY OF EDMONDS APPROVED HYV I S I U N ATE STANDARD DETAIL FILTER FABRIC FENCE FlLTRATION SYSTEMS DATE 7/24/01 SCALE NTS DWG No. E1.1 FILTER FENCE PER CITY / / INC G.O. STANDARD DETAIL ER-1300 C-11- / --- E'kISTINC _ / j NOTE: ALL DISTURBED AREAS TO NEW / TUB / / I EXISTING/ / / NOS IB / I / E 'n BE COMPOST AMENDED PER 2014 SWMMWW BMP r.5.13. DEGI� �Ss / I I I� arag A Hi� T48" INT I I I \ SETE4,Ac: / y EXIs�N DEC / L_ -I- - - - FIRE \ rb 252.24' ---------- POWER - - - _ - - NO GARAGE ADDITION EXISTING PAVED DRIVEWAY 0� / I PIr � Exiting \ \\ I --------------- WAT1=1z--------� - - - - - - ry TEMP. STOCK _ _ - - - - - - u,, _ _-------- PILE,COV�R/ I` � I IV�I,ISe I - ---GONGXIST( ETE----------SEWER------- � � NOTE: W/I 24 Hi�S. I J WALKWAY NO STORM / /EW I I En, bse - I / IN STREET PE IOUs I EX t / / EXIST NG / / COVE�ED / 68" HIGH I I Cj �r�l l � I PORCH REM I VE I eck8 \\ \ / / EXIS�ING I / - DEC _ - / T- G------- -6-- - - - -c/ I Cover-ae Calc„ EXISTING BUILDING FOOTPR*G` 3,805 SQ.F . NEW FOOTPRINT 113 SQFT. EXISTING DECK TO BE REMOVED -80 SQ.FT. OT t5UILDING5 F PRINT 3,898 SQFT. LOT AREA 28,634 SQFT. PERCENTAGE 0.136 Impervious Calc,; XIS IDENCE 3,341 SQ EXISTI G COVERED PORCH 110 SQFT. EXISTING HOT TUB 25 SQ.FT. I N RIVEW 4,635 SQFT. TOTAL IMPERVIOUS 8,111 SQFT. LOT AREA 28,634 SQFT. PERCENTAGE 0.283 Tax Account Number; 21032400212400 Zoning; RS-12 ite Pan SCALE: 111=10'-0" 02 269.93' Height Calc,; A: 106' B: 106' C: 109' D: 109' TOTAL = 430.00' AVERAGE GRADE = 101.50 ACTUAL HEIGHT: 131.83 (EXISTING) ALLOWED HEIGHT: 132.50' REVISED PLAN APPROVED CITY OF EDMONDS BUILDING DIVISION Eri,ce C4wfer BUILDING OFFICIAL Mar 11 2021 APPROVED DATE REVISION Mar 08 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ■IIIIIIIIIII ■L�IIIIIIIII ■ IIIIIIIIIII ■■ IIIIIIIIIIII Q LU W LLJ j 5 J C� LU L-L] `n (� III D Li > �zQ�- Q � N 00 W - � -ow�LO Z U o0 _ N z O 8 m CO Lyj 0 N Z 0 0 00 0) Q Z ® 0 0 W Z Z WQCO a0Q Fn l Q® Z �v0 W L1J GENERAL NOTES, SITE PLAN W120311$111111111Na DESIGN DGW DRAWN DGW ISSUE DATE :05/03/20 LATEST REV. : 03/03/21 z O N . 4 �3 LLI 4 Q LLU LL KITCHEN JENNAIRE C-203 82 Imm 1.5 LAUNDR`I' NUTONE QT-100 62 Imm 1.5 M. BATH NUTONE QT-50 62 Sm 1.5 POWDER NUTONE QT-50 62 Sm 1.5 SOURCE SPECIFIC FAN SCHEDULE NO SCALE BORED HOLES -MAXIMUM SIZE IN HOLE00% OF WIDTH 2x4-2.1" (2-1/6") DIA. HOLE 2x6-3.3" C3-5/16") DIA. HOLE NOTCHES -MAXIMUM DEPTH, 409- OF WIDTH. 2x4-1.4" (1-3/16") DEEP NOTCH 2x6-22" (2-3/16") DEEP NOTCH 5/6" MIN. EDGE DISTANCE STUD PORTION OF STUD REMAINING AT NOTCHES OR HOLES SHALL BE SOUND WOOD WITHOUT EXCESSIVE STRENGTH -REDUCING PROPERTIES SUCH AS KNOTS, SPLITS, EXCESSIVE SLOPE OF GRAIN, ETC. INTERIOR NONBEARING WALLS STUD PENETRATION NO SCALE BORED HOLES -MAXIMUM SIZE HOLE, OF WIDTH 2x4-1.4" C1-3/8") DIA. HOLE 2x6-22" (2-3/161) DIA. HOLE BORED HOLES IN DOUBLE STUDS -MA SIZE IN HOLE IN DOUBLE STUDS 60% WIDTH. NO MORE THAN TWO ADJOININC DOUBLE STUDS TO BE BORED. 2x4-1.4" C1-3/8") DIA. HOLE 2x6-22" (2-3/16") DIA. HOLE NOTCHES -MAXIMUM DEPTH, 25% OF WI 2x4-.8-1" (1/6") DEEP NOTCH 2x6-1.3-1" (1-3/8") DEEP NOTCH WIDTH 5/8" MIN. EDGE DISTANCE STUD EXTERIOR WALLS AND BEARING WALLS STUD PENETRATION NO SCALE 0 2x SOLID BLOCKING (EXCEPT Lu WHERE ENDS OF JOISTS ARE NAILED TO A HEADER. BAND OR RIM JOIST OR TO AN ADJOINING = U STUD OR 5 f OTHER APPROVED MEANS) z OT 0-1 _4 O NOTCHES NOT Ll Fl PERMITTED WITHIN NOTCHES WITHIN THIRD OF SPAN, BUT BORED HOLES ARE BORED HOLES 1/3 SPAN EACH END PERMITTED ALSO PERMITTED STANDARD JOIST PENETRATION 00 1 ast Elevation SCALE: 1/4" =1' -m" Elevation REVISED PLAN APPROVED CITY OF EDMONDS BUILDING DIVISION Erica Carfer BUILDING OFFICIAL Mar 11 2021 APPROVED DATE AND REVISION Mar 08 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ■IIIIIIIIIII ■LIIIIIIIII LIIIIIIIII ■IIIIIIIIIII ■■IIIIIIIIIIII it n,- Q W W LLw W LLJ U) 0 z > �z�� Q Q N r� N 00 W — 0) — 0 w LO °° Z _ N z 0 �m(L� 0 N Z 0 0 00 z ® 0 0 W Z Z WQCl) 00Fn cr W ♦)°` cr >- Q Z �v0 V) 2 CM o Im 00 W EXTERIOR ELEVATIONS PROJECT NO. DESIGN : DGW DRAWN : DGW ISSUE DATE :05/03/20 LATEST REV. : 03/03/21 A2 17' Cl H. DEV� 1 ROOF VIA i1601Lc A 0011 11"1 At park. Sv o-,,.t" ( r--lo4�: b1 o[,wr►9 �av� �2, �ac.�• S i ZP �a- b e ae rv� W' v r A Ir � ' ,N1"-3T D,15 �rorn W0CA, rn� hif-a M r0.c*-'' fln (-6 wrav d beo m xi- 51,N1i l a-r tvh d ►-; ovl� ovf Sl ry,e, ktwlf �, sk 1 � a h d a*- -er d s r ocif (,ro 1a60s) 3�12xCI GL15 24-p—V r$ MTS '>Iy&f u� .each s z de a� beaw. — l4eY\51 h b � ckl Sf-u-n cc, to kir,d�r — van ► n - van �.�) IOj -C Ole hails iv kcaLdcv' . Exce 55 stra p t-e.vk gVf" 60� b-e a.V,ouVX A b o*m. 0E c bz4sn . •— �5 �I a bCa►'+'� 4-� v 64t Le) j . l-�e crier h o �� ow � t V ; e,w - fYow" i +� s i d e — Ina.►-d kA)&y)e , c,a.v\ 1,)4e. i r\-7i-zd Ie d c h e citide.) MSTcA-S cr-> -b 'j kov44' ,vvZf' 4 I•.a1 f t -tom of bean studs y I.TP4 -�o m sFvr,OS C4� LT P4 fynm StvdS to add. � S��a c cht" W.U/I rot t 2 STRAP DETA 6,4 v V-� e s� On eX� eri vr� Vs� - NI S-rw 4-v w i 44x Z-vV�o-X LoO�'�'►d 1344 l4e"2, toil Amu lte, ot L1A-) Ll l 'CfAV,&S OZ66 m 0-etw'e-e t) sF ; A ors ► 'xi II C,ub C Sto�i/ sty &-�S -� vy\ o-�-� w t d+t-, o-f %cct►yn oc�tv-- M'5TA 4-h'aP i�tcu- �w�► 6 I S C Le C�) (0j" uk�.ls 4 4e,-e,� bzct m r,-Aj )m9 vy- 0 v I de, -�L l I V1-61 I�J- S` d �a,� �� � Siya- 3 B E A M D E T A wv-ewi beam s ;Li-ktj h SMALL ME AWNING W KNEE -BR/ oc i 0C oc 0C N : 1orth ' Elevation 26909 k� �AL SSIONALE�G 3/5/2021 - D'efails 1-3 ONLY Z w 0 CD Q N z — J Q O 00 00 rn I W ~ — �w�o z-0 Q N F- � Z p I) mD W —0 Y � 0 N z 0 0 00 C) 0 Q U W z U z C) z W Q u� O Q u� LL 1 Q m U z O v — V-) 0 m 00 W EXTERIOR ELEVATIONS PROJECT NO. DESIGN DGW DRAWN : DGW ISSUE DATE : 05/03/2, LATEST REV. : 03/03/2' AJ BUILDING OFFICIAL Mar 11 2021 APPROVED DATE 36" RAIL COMPOSITION ROOFING OVER 3OL5: ROOFING FELT (INTERWOVEN) OVER 1/2" APA RATED SHEATHING OVER 2x4 RAFTERS AND CEILING JOISTS AT 24"O.C. WITH R-49 INSULATION WIND BAFFLE (P GLR. MIN.) VENTED BLOCKING MATCH EXISTING METAL GUTTER WITH 1x8 FASCIA DOUBLE 2x6 TOP PLATE 5/8" GYPSUM WALL BOARD MATCH EXISTING SIDING PER ELEVATIONS OVER 15L5. BUILDING PAPER OVER -1/16" APA RATED SHEATHING OVER 2x6 STUDS AT Iro"O.C. WITH R-21 INSULATION AND 1/2" GYPSUM WALL BOARD 2x6 SOLE PLATE 2xI0 RIM JOIST DOUBLE 2x4 TOP PLATE 3/4" T/G APA RATED FLOORING - OVER 2xI0 HF NO.2 FLOOR JOISTS AT fro"O.C. WITH 5/8" G.W.B. 2x4 STUDS AT 16 "O.G. 4" CONCRETE SLAB ON BLACK 6 MIL VAPOR BARRIER ON 4" OF CLEAN SAND OR GRAVEL 2x4 PRESSURE TREATED MUD SILL WITH 5/8" A.B. AT 48" O.G. AND WITHIN 12" OF ENDS, MIN. 7" EMBED. (USE 3"xV'A/4" WASHERS) EXISTING AND FINISHED GRADE �4 (1) NO.4 BAR TOP AND (2) NOA BARS BOTTOM CONTINUOUS AND NO.4 VERTICAL AT 16"O.C. I` (ALTER HOOKS) FOOTINGS TO REST ON FIRM UNDISTURBED SOIL WALL SECT. SCALE = 1/2" = 1'-011 EXISTING ROOF STRUCTURE DOUBLE 2x6 TOP PLATE - WITH HI CLIP, EACH TRUSS �7 Z N X w Z 0 O ff Z w 4 dJ O 0- d III 61I 311 @ GARAGE SIDING PER ELEVATIONS OVER 15 LB. BUILDING PAPER OVER -1/1ro" APA RATED SHEATHING OVER 2x6 STUDS AT 16" O.G. WITH R-21 GATT INSULATION AND 1/2" GYPSUM WALL BOARD AT X THE INTERIOR Z N 3/4" T/G APA RATED FLOORING X (GLUED AND NAILED) OVER III II I w MATCH EXIST. TJI FLOOR JOISTS AT 16" O.C. WITH R-30 GATT INSULATION 2x6 SOLE PLATE MATCH EXISTING RIM JOIST L 2x6 PRESSURE TREATED MEF-50 WITH 1/2" RND. x 10" ANCHOTS AT 48" O.G. AND WITHIN 12" ENDS, MINIMUM -P EMBEDMENT (USE 3"x3"A/4" WASHERS) (1) NO.4 BAR TOP AND (2) NOA BARS EXISTING AND - Z BOTTOM CONT. AND " FINISHED GRADE VERTS. AT 4 O.C.NOA O.C. N `� m BLACK 6 MIL VAPOR - BARRIER-sicO sic Z Z 4" PERFERATED DRAIN PIPE, �, CONNECT TO STORM SEWER 77-7 WALL SECT. DIN NG SCALE: 3/4" = 1'-m" 161I op 3'-10 3/4" 0 FF REMOVE EXISTING DECK 114 U OW811 ' z TI ITH , MP. ENCLOS. 50 ® N - existing g 8 bath 2- KING10114 i ain SCALE: 1/4"=1'-mll C{i deck 120x6 TEMP. FIREPLACE REMAINS den 14.75x13 I \ - - - - - - - - - - - - - 1'1=IT- 26 closet 13.5x8 POLE/SHELF NOTE: VERIFY SMOKE DETECTORS IN EACH BEDROOM AND IN EACH HALLWAY, TYPICAL EACH LEVEL, INSTALL HARDWIRED UNITS IF NEEDED existing master bedroom 10 X 5� EGRESS bevel N UP m Cn �'-211 4'-0 L balcony deck 11'-mll GAS OVERHANG EDGE FIRE PIT 19'-5 1/2" 12'-0 1/2" 0 9'-8 3/4" 16 xgp� TEMP. 0 BUILT- INS e-din i�ag seating area N 17x11 •5 13x12.75 _ gteat room REMOVE EXISTING WALLS (TYPICAL) 15x19 GAS FIREPLACE INSTALL 10'-0" PER MFG. SPECIFICATIONS 0 42" HIGH T 7 /I o o EATING BAR ° ° I I C� kitchen BUILT-INS 0 19 X9 tt 4'-3 1/2" GAS RA E WITH 15'-I 1/4" 100 CFM AN V.T.O. - �H NDR. INK - < 0 48" FRIG. UP 05 0000 POLE�5HE existing W WC PANTRY en tr y COATS x3 �4\ 26 2- 26 F_I; � 36x6 WITH \ `r TEMP. GLASS DOWN ADD BRICK VENEER TO THESE AREAS oor an EXISTING: 2,598 SQUARE FEET NEW: 211 SQUARE FEET TOTAL: 2,869 SQUARE FEET F III _j existing III, J covered laundryy hall 10x14.5 m D porch 3 I 0 \ m VENT DRYER OUT V THE NORTH WALL OR J 28 28 �❑ THE ROOF L lmm GFM FAN, WHOLE HOUSE �� EXHAUST ELEV OR 01 (BY ERS), �4 SIoK W SHE DRYER IFY LL D ENSIO ) 10'-0 3/4" d4'- I :0 /All 14'-11 1/211 garage 12x20.75 roY-3 3/4" office 10x16 NG MASONRY IST(E LACE 11 V LT SMOKE DETECTOR -CONNECTED WITH UINI TERY BACK UP - TYP. 26 26 closet 12.5x3.5 x N IRV mechanical N REMOVE EXISTING DOOR, FRAME IN in NOTE: 5/8" TYPE 'X' G.W.B. ALL GARAGE AREA, WALLS, CEILING, POSTS AND BEAMS 1 3/8" SOLID -CORE DOOR WITH SELF -CLOSING HINGES El garage 23x26-31 0 0 ELIMINATED GARAGE EXTENSION REVISED PLAN APPROVED CITY OF EDMONDS BUILDING DIVISION Erica Garfer BUILDING OFFICIAL Mar 11 2021 APPROVED DATE it aX REVISION Mar 08 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ■ II IIIII (III ■��IIIIIIIII ■ II IIIII (III ■■ (III (III (III Q W W w j z 5 JoCn W LLJ U) oLILJ LILJ > � Q N N 0 00 00 W z — < °' Z 0 w < LO °° _ N z 0 LLJ �1 Z O 0 00 0) ® O 0 w Z Z WQ� o0a Fn I w>- cc Q® Z �v0 � 0) 00 W MAIN LEVEL FLOOR PLAN 91015104111111,11161 DESIGN DGW DRAWN DGW ISSUE DATE :05/03/20 LATEST REV. : 03/03/21 3/4" T/G APA RATED SUBFLOOR 2x SOLID BLOCKING FLOOR JOISTS (PER PLAN) - BEAM PER LPCZ4 Z d POST PER PLAN fl- SIMPSON P5644 OR P5666 w SEE PLAN FOR POST SIZE 0 a a PER PLAN ISOLATED FOOTING SCALE = 1" =1'-O" P.T. POST PER PLAN P5544 (ZMAX) NO.4 BARS, EACH WAY (PER PLAN) EXISTING AND FINISHED GRADE L-J PER PLAN aDECK POST FOOTING 2 SCALE = P =1' 1-1/2" ROUND MIN. CONT. HANDRAIL BALUSTERS TO CONFORM TO IRC R312 LJ 2x12 P.T. TREAD - 2x4 P.T. THRUST BLOCK WITH 1/2" ROUND C INCH ANCHORS AT 24" O.G. EDGE OF DECK, OR HOUSE CONCRETE PATIO WITH 8" THICK- ENED EDGE AT-] BEARING (3) 2x12 P.T. STRINGERS TYPICAL EXTERIOR STAIR NO SCALE NOTE: USE LAMINATED GLASS WHERE SKYLIGHTS ARE MORE THAN 16S.F. IN AREA OR MORE THAN 12 FEET ABOVE A WALKING SURFACE OR ACCESSIBLE AREA (OTHERWISE SAFETY GLAZING IS ADEQUATE) 2x RAFTERS OR TRUSSES AT 24" O.G. (SEE PLAN) DOUBLE HEADERS AT q� SPANS GREATER THAN ,Qc 4'-0" O O� 2x4 LIGHT WELL (R 4 REQUIREDO.C. Ur)r)er SCALE: 1/4" =1' -m" 2x CEILING JOISTS C TRUSSES AT 24" O.C. (IF REQUIRED) -4SKYLIGHT/LIGHT WELL NO SCALE bevel Floor Ex— REVISED PLAN APPROVED CITY OF EDMONDS BUILDING DIVISION Eri -1 Geer BUILDING OFFICIAL Mar 11 2021 APPROVED DATE REVISION Mar 08 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ■IIIIIIIIIII ■LIIIIIIIII LIIIIIIIII ■ IIIIIIIIIII ■■ IIIIIIIIIIII it cj:� Q W W w W (� Ld D z w CD Q oo N N rq DD .J — 0 w Lo °° Z _ N z 0 �m LyLl C-\-"- 0 N Z 0 0 00 Z ® 0 0 W Z Z WQCl) 00Q c® cr W >- ♦♦ ), Q Z �v0 0) CM Im 00 W UPPER LEVEL FLOOR PLAN PROJECT NO. DESIGN : DGW DRAWN : DGW ISSUE DATE :05/03/20 LATEST REV. : 03/03/21 A5 EXISTING BUILDING PAPER ON 7/16" APA RATED 5HEATHIN6 ON 2x6 STUDS AT 16" O.G. P AIR SPACE ADDED BRICK VENEER WITH 22 GA. x P ANCHOR TIES AT 24" O.C. VERT., 12" O.G. HORIZ. 3/8" WEEP AT 32: O.G. CON. MTL FLASHING _ FINISHED GRADE ADDED BRICK VENEER SCALE = P=1'-O" VARI (2) 2x TOP PLATE (S E P WINDOW HEADER (IF APPLICABLE) (SEE FRAMING PLAN FOR SIZE) NAIL SHEATHING TO HEADER AT 6" O.G. BOTH WAYS (OR PER SHEAR WALL TABLE) (2) 2x STUDS, NAIL SHEATHING TO EACH STUD Sd NAILS AT 6" O.C. (OR PER SHEAR WALL TABLE), AT ALL PLATES, HEADERS, AND STUDS SHEATHING (PER WALL SECTION) STHD14RJ TIE ANCHOR (NAIL TO BOARD FORM. BEND UP AFTER CONCRETE CURES.) USE (30) 16d SINKERS EACH (MINIMUM 1 1/2" EDGE DISTANCE) 2x P.T. PLATE, NAIL SHEATHING 70 RIM JOIST AND BOTTOM PLATE ANCHOR BOLTS PER SHEAR WALL TABLE OR WALL SECTION WITH MINIMUM -1" EMBEDMENT (USE- 3"x3"x.1/4" PLATE WASHERS) FLOOR JOISTS (REFER TO PLAN FOR JOIST 51ZE AND DIRECTION) LATERAL SHEAR :2) WALL DETAIL NO SC FLOOR JOISTS (PARALLEL OR PERPENDICULAR, SEE - FRAMING PLANS) 16d PLATE TO PLATE RIM JOIST TYPICAL NAILING SIMPSON LTP5 (OR A35'S ABOVE) 16d PLATE 70 PLATE FOR SHEAR WALL COMPONENTS SEE FRAMING PLANS uo SIMPSON A35 (OR LTP5'S BELOW) Iiiii")SHEAR WALL NAILING SCALE = V=1'-O" FIELD NAILING PER SHEAR WALL SCHEDULE 2x6 STUD PANEL EDGE NAILING PER SHEAR WALL SCHEDULE LAP SHEATHING CONTINUOUS ACROSS END STUD OF PERPINDICULAR STUD PANEL EDGE NAILING PER SHEAR WALL SCHEDULE FIELD NAILING PER SHEAR WALL SCHEDULE EXTERIOR WALL SHEATHING PER SHEAR WALL SCHEDULE SHEARWALL .4 zm SCALE: 1" = I'-m" is NEW 4xI0 HF NO-2--1 rr-� L— J L J L J I L I_ '-8" _ '-11 NEW 4xI0 L _AF NO L - j NEW 44 P O� F_I I F_ I� L1/2 X I I� gyp• x lit I- —1J J L----J L L JL--7. L I J L _j I — — — — — I r\DTT2Z AT EACH �d END OF 1/2" ATR -18"x18"x12" CONCRETE PAD WITH (5) 8DS 1/4 A 1/2 SCREWS WITH (2) NO.A BARS, EACH WAY TO ADJACENT JOIST (USE LPCZ4, P5844) (SEE DETAIL 1/A0) F L J F_ -1 F_ -1 F F L -1 L L J L 6'-0 f;pEM0vE EXISTING � DECK 0 � I I -m" � � L� �L � L J L L J L El J L El J F— I Foundation SCALE: 1/4" =1'-m" Plan NEW 4xI0 HF NO2 LL 7 fiT L J L J P.T. 2x8 DE K J IS7 AT 16" O.C. (TYPICA ) I I I I ISI � 8" PONPRETE W,I4LL ION 16"�c8" TONGRE7IE FOOTING DRILL, IN, AND EPDXY— (3) NOA 5A� S I1 TO EXISTING F�OUNDJAT1 F_ 13 -1 F_ L � 4x4 HF NO2 POSTS WITH PBS44 ZINC, PC44 ZINC (TYP) 9 -m" 10' 1' 2 1/2' 11'-0" n 6, Q 24"x24"x12" CO CR TE ADS I r WITH 3) N .4 AR , E CH WAY 18"xl "A2" C NCRIETE PA T PI AL HIS BE LI qE WITH (2) IqO.4 BARS, EA GH WA ( SE PG 4, 54 ) TYP GA THI BE M INE (US LP Z4, BS 4) _ E Axle NF�I I I I F_I I .. 0 J L J LI Kee k J I L J 3'- 1/2401 I I 0 I I I I I I I I I I I I I I I I I�RIL P111, AND E OXIY �C ) N0.4 AR INT XISTING FOU DA ION EXISTING CONCRETE FOUNDATION TO REMAIN - a" CONCRETE WALL ON 16 "x8" CONCRETE FOOTING 7 L J L 1- NOTE: FIELD LOCATE (3) 16"x8" I I SCREENED FOUNDATION VENTS NOTE: BLACK 6 MIL VAPOR JL JL BARRIER THROUGH- OUT CRAWL SPACE L —1 L 1 L J L EXISTING BEAMS, P0575 AND PADS 70 REMAIN (TYPICAL) L-1 L J L J L J ® L J 6x6 HF NO.] POST WITH NEW UNDER WALL r - ABOVE �x5141F NO2 r - , r - - 6x HF NO.I P05T WITH PB566 70 36 "x36 "AO" I = _ _ � _ _ _ _ _ _- I PB 66 70 30"x30"AO" PAD WITH (4) NO.A BARS, L J PA WITH (4) N0.4 BARS, EACH WAY L - J _ _ 4x4 HF NO.1 POST WITH L - J E CH WAY P5544 70 24"x24"x8" PADS WITH (3) NO.A BARS, r - EACH WAY L 7 F_ 7 I I L 7 LJ —L I I L__1 L--J 8" CONCRETE WALL ON — �4 16"x8" CONCRETE FOOTING m L— J Ll L \ i 4" CONCRETE WALL ON ELEVATOR 16"x8" CONCRETE FOOTING / \ ---------- \ ---6--7T77- - CUT EXISTING SLAB AND MAKE NEW SLA PER DETAIL BELOW J BEARING WALL NOTE: VERIFY REQUIRED AREA AND DEPTH WITH ELEVATOR INSTALLER PRIOR TO POURINCs FOUNDATION B N 0L1 16" L -1 L J (2) NO.A, CONTINUOUS NO.4 AT 10" O.C., ALTERNATE SIDES- EPDXY 4" INTO SLAB T-EX16TING CONCRETE SLAB ON GRADE I ELIMINATED GARAGE EXTENSION REVISED PLAN APPROVED CITY OF EDMONDS BUILDING Ii SON REVISION Mar 08 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT H. DELI O4 WASpr, Sw `W �1p 26909 � w� CO) AL �SSIONAL e 3/5/2021 - Structural ONLY ■ II IIIII IIII ■ L�IIIIIIIII Q w Lw j 5 W U� LJ U) 0 LJ LJ z LLJ > �zCD Q Q� N N r� 00 W — - °' 0 w ( < LO °° Z _ N z (s 0 N Z 0 O 00 0) z ® O w Z 0 Z waCO Q O Q Fn f w ♦� im Q Z �v0 0) ma 00 00 w FOUNDATION PLAN PROJECT NO. DESIGN :DGW DRAWN : DGW ISSUE DATE :05/03/20 LATEST REV. : 03/03/21 A6 CORNER BUILDING OFFICIAL Mar 11 2021 APPROVED DATE Ir C`I H. DEVj� LABEL APA RATED SHEATHING NAIL SIZE AND SPACING STUD AND BLOCKING SIZE RIM JOIST OR BLOCK 2x BOTTOM PLATE (1), (2), (4), (12), (13) AT EDGES (4),(5) AT ADJOINING EDGES (3), CONNECTION TO TOP ATTACHMENT (ro), (14) PLATE (1), (0) NAILING TO WOOD BELOW (9) w6 15/32" ONE SIDE 0.1314 1/2" AT roll O.C. 2x CLIP AT 22" O.G. 0.148x3 1/4" AT 8" O.C. 2x HF NAILER PER PLAN - 1`0/4" STIFFENER 3/lro" WELD 3 SIDES. STIFFENER MAY BE REPLACED WITH BEAM CONNECTION PLATE f21/4" 3/1ro" MIN FILLET WELD ALL AROUND (3) 3/4" DIA. A325N BOLTS SSLT HOLES STEEL BEAM STEEL BEAM (COPED AS SHOWN) STL. BEAM TO STL. BEAM FLOOR SHEATHING 2x (RIPPED TO FIT) WITH 5/8" DIAM. BOLTS AT Iro" O.G. (STAGER EACH SIDE) 2x's 2x's RIPPED RIPPED TO FIT TO FIT - 5/8" DIAM. BOLTS AT tl, 24" O.G. STEEL gr- Am��1 I I (STAGGERED P OFF CENTER) -7 TJI FLOOR JOISTS AT Iro" O.C. NOTE: IF FLOOR JOISTS ARE PARALLEL TO BEAM, PROVIDE BLOCKING AT 48" O.C. FOR (3) JOIST SPACES. HANG BLOCKING FROM JOISTS. 2QLSTEEL BEAM (FLUSH) CALE: 1/2" = 1'-m" Framing Notes. 1.) ALL NEW ROOF FRAMING TO BE PRE-ENGINEERED ROOF TRUSSES AT 24" O.G., UNLESS OTHERWISE NOTED. 2.) ALL EXTERIOR OPENINGS SHALL HAVE 4x8 HF NO.2 HEADERS, UNLESS OTHERWISE NOTED. 3.) ALL FLOOR JOISTS TO BE 2xI0 HF NO2 AT Iro" O.C., UNLESS OTHERWISE NOTED. 4.) ALL SHADED AREAS SHALL BE 2x4 HF NO.2 BACKFRAMING AT 24" O.G. ROOF DIAPHRAGM: FLOOR DIAPHRAGM: 15/32" EXPOSURE 1 APA RATED SHEATHING, 3/4" EXPOSURE 1 APA RATED UNBLOCKED, WITH 8d NAILS AT roll O.G. AT SHEATHING, UNBLOCKED, WITH SUPPORTED PANEL EDGES AND 8d NAILS 10d NAILS AT ro" O.G. AT SUP - AT 12" O.G. AT FIELD. PORTED PANEL EDGES AND lmd NAILS AT 10" O.G. AT FIELD. REQUIRED NOTES EXISTING &xIo DF F-� EXISTING NIP JACKS III w 0 Qy zll X w EXIST roxro HF NO.] � I w m wZ w-i ;u Z Ldw ,QOQ � N n wF- -1 4 QU-w �20 LU ®?-Iw RIDGE �\_ N d) w d) p LU 3 1/2"x5 1/2" PSL POST 0- 0 X L 4U 4 Q <<�k (2) 2x TRIMMEF PLUS KING STL ER TRUSS k�R=1` roxI0 HF NO.2 HEADER z 0 72x BLOCKING Z AIL BELOW) ~ MMERSXG STUD w 5 1/8"x 1/2" GLB (24F-V Lower Roof/ Framin SCALE: 1/4" =1'-O" 9 2 Ro 1.) INSTALL PANELS EITHER HORIZONTALLY OR VERTICALLY. 2.) WHERE SHEATHING IS APPLIED ON BOTH SIDES OF WALL, PANEL EDGE JOINTS ON 2x FRAMING SHALL BE STAGGERED SO THAT JOINTS ON THE OPPOSITE SIDES ARE NOT LOCATED ON THE SAME TUDS. 3.) BLOCKING IS REQUIRED AT ALL PANEL EDGES. 4.) PROVIDE SHEAR WALL SHEATHING AND NAILING FOR THE ENTIRE LENGTH OF THE WALLS INDICATED ON THE PLANS. ENDS OF FULL HEIGHT WALLS ARE DESIGNATED BY EXTERIOR OF THE BUILDING, CORRIDORS, WINDOWS, OR DOORWAYS OR AS DESIGNATED ON PLANS. SEE PLANS FOR HOLDOWN REQUIREMENTS. 5.) SHEATHING EDGE NAILING IS REQUIRED AT ALL HOLDOWN POSTS. EDGE NAILING ALSO REQUIRED TO EACH STUD USED IN BUILT-UP HOLDOWN POSTS. (0.) INTERMEDIATE FRAMING TO BE WITH 2x MINIMUM MEMBERS. FIELD NAILING AT 12" O.C_ 1.) BASED ON 0.131A 1/2" LONG NAILS USED TO ATTACH FRAMING CLIPS DIRECTLY TO FRAMING. USE 0.131x2 1/2" LONG NAILS WHERE INSTALLED OVER SHEATHING. 8.) FRAMING CLIPS: A35 OR LTP5 OR APPROVED EQUIVALENT. 9.) WHERE PLATE ATTACHMENT SPECIFIES (2) ROWS OF NAILS, PROVIDE DOUBLE JOIST, RIM OR EQUAL. ATTACH PER DETAILS. 10.) ANCHOR BOLTS SHALL BE PROVIDED WITH STEEL PLATE WASHERS .229"x3"x3". EMBED ANCHOR BOLTS -1" MINIMUM INTO THE CONCRETE. 11.) PRESSURE TREATED MATERIAL CAN CAUSE EXCESSIVE CORROSION IN THE FASTENERS. PROVIDE HOT -DIPPED ZINC -COATED GALVANIZED (ELECTRO-PLATING IS NOT ACCEPTABLE) OR STAINLES STEEL NAILS AND CONNECTOR PLATES (FRAMING ANGLES, ETC.) FOR ALL CONNECTORS IN CONTACT WITH PRESSURE TREATED FRAMING MEMBERS. 12) 1/16" APA RATED SHEATHING (OSB) MAY BE USED IN PLACE OF 15/32" SHEATHING PROVIDED THAT ALL STUDS ARE SPACED AT Iro" O.C.. 13.) WHERE WOOD SHEATHING (W) IS APPLIED OVER GYPSUM SHEATHING (G), CONTACT THE ENGINEER OF RECORD FOR ALTERNATE NAILING REQUIREMENTS. 14.) AT ADJOINING PANEL EDGES, (2) 2x STUDS NAILED TOGETHER MAY BE USED IN PLACE OF A SINGLE 3x STUD. DOUBLE 2x STUDS MAY BE CONNECTED TOGETHER BY NAILING THE STUDS TOGETHER WITH 3" LONG NAILS OF THE SAME SPACING AND DIAMETER AS THE PLATE NAILING. 15.) CONTACT THE ENGINEER OF RECORD FOR ADHESIVE OR EXPANSION BOLT ALTERNATIVES TO CAST -IN -PLACE ANCHOR BOLTS. (SPECIAL INSPECTION MAY BE REQUIRED). er Floor KING STUD CONTINUOUS L6TA9 WITH (8) FROM BOTTOM TO TOP 0.1484 1/2 NAILS (CENTER PLATES, EACH SIDE OF AT EDGE OF OPENING), HEADER OPENING (TYPICAL) (TYPICAL) (PER PLAN) PANEL NAILIN NE IGN SHEAR WALL (PER BLOC YPICA 1 DGE (FULL AN) WINDOWLGN)ST O,Pe1NIClG HOLD DOWN HOLD DOWN (PER PLAN) (PER PLAN) iear a aDe, SW AROUND OPENING SCALE: 1/2" = 1'-0" PLF CAPACITY SILL PLATE ATTACHMENT ANCHOR BOLT TO SILL PLATE SIZE CONCRETE BELOW (10), (15) AT FOUNDATION (11) 5/8" AT 48" O.C. I 2x NOTE: SEE DETAILS ON A3 FOR STR FFING r r , r 4xro DF NO.1 , r 3 1/8"x9" GLB (24F-VS) (TYPICAL) rr07 3) 2xro 5 1/8"x12" G B (24F-V8) 5 I IFY IQUfTH-M1=Cx L CIS TW12x2 WIDE (FLUS FR 242o cown I aDe, 10 DDT1Z WITH (ro) 0.145A 1/2" NAILS TO (2) 2x STUDS, USE 3/0" DIAM. ATR (EMBED MIN. 4" INTO SET-XP EPDXY), (ALSO INSTALL ABOVE AND BELOW FLOOR FRAMING) U I SEE ETAIL 11 A75 ,I •• . 1 df E T. 2x10 JST. x i ca AT Iro" O.C. 4 w _ - > - _Iz �I I o-1 LUil I wir 3: <1 L I i � I DEMO EMI IV�I zN LU 1 III EXISTI � I I �IL� &x10 � EAM�� I Z 4 N H - ----- XI I I ,�Lwd) ' X� I � I I pg�0 =wol XI I I ��u QD d) x I I I -I W z N I I n I � I I �� EXIST. 2xI0 JST. PEMOVE E ESN UJ LL J �I I AT 12" O.G. �I 'I X II I >L I I n (roxro NO. IS ACC i TABLE HERE NEW BEARING ALL I I BASED O CHAN TO LENGTH OF �F__ I I STEEL BEAM. SEE F REVIOUS �? I I REVISION CALCUL TIONS) roxro HF Nd.l 0 6 IIII - O II 2xI0 HF NO.2 (FLUSH FgM) F2 N � U N 6 X 4 (2) 1 3/4"x9 1/4" 2.0E LVL ' BEARING WALL (FLUSH FRAME) EL�O2 BYO /HER (VE I ALL DIMENSIONS) W6 1 �Q O C BEARING WALL �< N X O f d) EXISTING u; rox14 DF NO.1 BEAM EXISTING r, EXISTING EXISTING rox12 DF NO.1 rox12 DF NO.I rox12 DF NO.1 6 4 N N O N N STING 4x1 NO.2 EXI G 4x12 DF .2 X EXISTING DF N0,2-' ELIMINATED GARAGE EXTENTION REVISED PLAN APPROVED CITY OF EDMONDS BUILDING DIVISION Eric Comer Mar 11 2021 I APPROVED DATE REVISION Mar 08 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT SSjONALE�� 3/5/2021 - Structural ONLY IIIIIIIIIII■��IIIIIIIIII Q W W w JoCn W LLJ U) (� LiJ D ■ Z Lli > � Q < N N r� o00 LU z o 0 w Lo °° Z _ N z 0 Lij 0 N Z 0 0 00 z ® 0 0 W Z Z WQ� Q 0 Q Q Z �00 V! 2 W W LOWER ROOF/ UPPER FLOOR FRAMING PLAN PROJECT NO. DESIGN DGW DRAWN DGW ISSUE DATE :05/03/20 LATEST REV. : 03/03/21 A7 FURR OR NOTCH STUDS TO RECEIVE LINING NAILING TO BE A MINIMUM OF P ABOVE FINISHED DAM OR THRESHOLD TILE FLOORING OVER APPROVED LINING OVER SOLIDLY FORMED SUB -BASE with A MIN. 29. SLOPE (1/4" PER 12") \ APPROVED FLANGED DRAIN F- SHOWER PAN DETAIL SCALE: P = 1'-0" 1/4" PLATE STIFFENER, EACH SIDE, CENTER ON POST BELOW 3/l�0 STEEL TYP. BE 3/Uo iF- 2 "x&"xI/4' 6x6 COL. 3/4" RND A30-1 BOLT STEEL BEAM TO POST 2SCALE: 1/2" = 1'-0" 2x5 CAP RAIL Ix2 STOPS TEMPERED GLASS IN VINYL FRAME 6 x6 PO5T 2x6 BOTTOM RAIL 2x4 SPACED CEDAR DECKING 2x RIM JOIST 2x CEDAR BAND 2x DECK JOISTS AT 16" O.C.- BEAM (PER PLAN) 1/2" RND. BOLTS WIl 2" RND WASHERS UNDER BOLT HEAD AND NUT DECK RAILING DETAIL SCALE: 3/4' = 1'-0" TYPICAL WALL A65EM5L 2x SOLE PLATE 5/4x& CEDAR DECKING 1/2" THROUGH BOLTS AT 16" O.C. (GALV.) (2) ROWS OF 16d AT 4"O.C. PRESSURE TREATED JOISTS PER PLAN W/ SIMPSON HANGERS 2x LEDGER (PRESSURE TREATED) P.T. 2x MUD SILL PLATE CONCRETE '--) LEDGER DETAIL 4 SCALE: I"=1'-O" JOIST REVISED PLAN APPROVED CITY OF EDMONDS BUILDING DIVISION Erica Ca-t?.,r BUILDING OFFICIAL Mar 11 2021 APPROVED DATE REVISION Mar 08 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT AL SSIONAL��� 3/5/2021 - ructural ONLY ■IIIIIIIIIII ■LIIIIIIIII LIIIIIIIII ■ IIIIIIIIIII ■■ IIIIIIIIIIII jr cr Q W W w .z5 J C� cn W LL ] cn 0D ■ Z w � Q N N rq o00 z < o —o� w � < °° Z _ w y 0 N Z 0 0 00 z ® 0 0 W Z Z WQCl) 00Q Fn cr W >- ♦♦ ), cr cr a Z �v0 V) 2 cr CM o Im 00 W UPPER ROOF FRAMING PLAN PROJECT NO. DESIGN : DGW DRAWN : DGW ISSUE DATE :05/03/20 LATEST REV. : 03/03/21