REVIEWED BLD BLD2020-1218+Interior_Lighting_Summary+11.6.2020_11.41.19_AM2015 Washington State Enerqv Code Compliance Forms for Commercial Build inqs including R2, R3, R4 over 3 stories and all R1 Revised Nov 2017
Project Info
Project Title: Sunrise of Edmonds
Date 11/5/2020
Compliance
Applicant Information. Provide contact information for individual mho can
For Building Department Use
forms do not
respond to inquiries about compliance form information provided.
BLD2020-1218
Company Name: ClarklBarnes
require a
password to
RECEIVE[:
Company Address: 1401 West Garfield Street, Seattle, WA 98119
use.
Instructional and
Applicant Name: Johnathon Cave
calculating cells
Nov 12 2020
are mrite-
Applicant Phone: 206-782-8208 ext. 814
protected.
CITY OF EDMONDS
DEVELOPMENT SERVICES
Applicant Email: jcave@clarkbarnes.com
DEPARTMENT
Project Description
0 New Building 0 Addition 0 Alteration 0 No Lighting Scope
Include PROJ-SUM form (included in envelope forms vtorkbook) vuth lighting compliance forms.
Interior Lighting System
All existing lighting fixtures within the areas of work indicated on the permit submittal
Description
drawings are to be replaced with updated fixtures. All existing incandescent fixtures will be
converted to LED. Fixtures will be installed in the same locations, typical.
Full lighting schedule and notes can be found on sheet ID-001 of the permit drawing set.
0 Interior Lighting Plans Included
REVIEWED
BY
CITY OF EDMONDS
Interior Lighting Power
0 Building Area Method 0 Space -by -space Method
Allowance Method
Select method used in project.
Interior Lighting Controls
0 All C405.2.1- C405.2.8 Lighting Controls 0 C405.2 Exception 5 Luminaire Level
Lighting Controls (LLLC)
o Additional Efficiency Package Option
C406.4 Enhanced Digital Lighting
To comply vdth C406.4, no less than 90% of the total installed interior lighting poorer shall comply vdth
required controls per C406.4.
Dwelling Unit Interior
Permanently installed interior lighting fixtures in dvielling units comply vuth: No Dwelling
Lighting
Units
4 C405.2 thru C405.5 Commercial Lighting Controls and LPA
4 C406.3 High Efficacy Lighting
4 R404.1 Residential High Efficacy Lighting. Dmelling unit lighting complies vdth WSECResidential
provisions in lieu of WSEC Commercial provisions.
Exterior Lighting System
N/A
Description
0 Exterior Lighting Plans Included
Building Additions
Compliance Method
Interior lighting
Exterior lighting
Lighting systems in addition area comply with all applicable
provisions as a stand alone new construction project
Refer to Section C502.2.6 for additional
Lighting systems in addition are combined with existing
requirements.
building lighting systems to demonstrate compliance
Addition is combined with existing:
For interior lighting projects, include new + existing -to -remain interior lighting fixture mettage in
Proposed Lighting Wattage table in LTG-INT-BLD or L TG-INT-SPA CE form.
For exterior lighting projects, include new + existing -to -remain exterior lighting fixture wattage in
Proposed Tradable and Proposed Non -Tradable Lighting Wattage tables in LTG-EXT form.
2015 Washington State FnPmv Cnde Cmmnliance Fnrms for Commercial 13uildinas including R2 R3_ R4 nver 3 stnries and all R1 Revised Nnv 2017
Project Title: Sunrise of Edmonds
Date 11/5/2020
Change of Space Use
0 Existing interior lighting systems in areas under -going a change in space use are upgraded to
comply with LPAs for the new space types per Tables C405.4.2(1) or C405.4.2(2).
Identify interior spaces requiring LPD upgrade to the current Code in Proposed Lighting Wattage
table in LTG-INT-BLD or L TG-INT-SPA CE form.
Interior and Exterior
Lighting Power
Interior lighting
Parking garage
Exterior lighting
Lighting Alterations
50% or more of existing are replaced
0
0
0
Select all Lighting Power and Lighting
Control elements that apply to the scope
Less than 50% of existing are replaced
0
0
0
of the retrofit project. If project includes a
Lamp and/or ballast replacement only
—existing total wattage not increased
combination of spaces where less than
50% of the existing fixtures are replaced
in some spaces, and 50% or more of the
fixtures are replaced in others, then
provide separate lighting power
compliance forms for the two retrofit
50% or more replaced - Total lighting power of new + existing -to -remain fixtures shall comply with
total LPA per Sections C405.4.2 and C405.5.2. Include new+ existing -to -remain fixtures in
Proposed Lighting Wattage table in LTG-INT-BLD, L TG-INT-SPA CE or LTG-EXT form.
conditions. Spaces undergoing the same
Less than 50% replaced - Total lighting power of new + existing -to -remain fixtures shall not exceed
type of retrofit may be combined into one
the total lighting power prior to alteration. Include new + existing -to -remain fixtures in the Proposed
lighting power compliance form.
Lighting Wattage table in LTG-INT-BLD, L TG-INT-SPA CE or LTG-EXT form.
50% threshold applies to numberof luminaires for interior spaces and parking garages, and total
Refer to Section C503.6 for additional
installed wattage for exterior luminaires.
requirements.
Lighting Controls
Interior lighting
Parking garage
Exterior lighting
All alteration lighting controls shall be
commissioned perC408.3.
New wiring installed to serve added
fixtures and/or fixtures relocated to
0
0
0
new circuit(s)
New or moved lighting panel
0
0
0
Interior space is reconfigured -
luminaires unchanged or relocated
0
New wiring or circuit - For interior lighting, provide required manual controls per C405.2.3,
occupancy sensor controls per C405.2.1, daylight responsive controls per C405.2.4 and application
13 No changes are being made to
the interior or exterior lighting
systems and existing space
specific lighting controls per C405.2.5. For exterior lighting, provide required controls per C405.2.7.
New or moved panel - Provide all applicable lighting controls as noted for New Wiring and
automatic time switch controls per C405.2.2.
uses and configuration are not
Reconfigured interior space - Provide all required lighting controls that apply to a new interior
changed.
space. Application specific lighting control provisions per C405.2.5 do not apply to reconfigured
over
Project Title:
Sunrise of Edmonds
Date
11/5/2020
Calculation
NOTE9
Area
0 New Construction 0 Addition - o Addition
stand alone + existing
,o Spaces where < 50% of , Spaces where >_ 50% of () Spaces where the Use
luminaires are replaced luminaires are replaced is changing (C505)
For Building Department
Use
LPA
Calculation
Type
10 Standard O Additional Efficiency Package Option
C406.3 Reduced Interior Lighting
To comply with C406.3, the Proposed LPD shall be 25% /omr than the Target LPA.
Refer to C406.3 for additional requirements.
User Note
Maximum Allowed Lighting Wattage
Location (plan #,
room #)
Space Type
Ceiling
Height"OTE2
Gross Interior
Area in ft2
Allowed
Watts per fe
Wafts Allowed
(watts/ft2 x area)
Hair Salon 125
Office: Enclosed
158
0.890
141
Nurse/Well 232
Office: Enclosed
214
0.890
190
Serve/Dining 329
Dining area: all other
1102
0.520
573
Toilet 328
Restroom: all other
50
0.780
39
REM Office 331
Office: Enclosed
148
0.890
132
Activity Rm 333
Office: Enclosed
222
0.890
198
Res Laundry332
Laundry/washing area
100
0.480
48
Living Rm 324
Lounge/breakroom: all other
526
0.580
305
Reflect Rm 335
Office: Enclosed
91
0.890
81
Lv3 Corridor A-C
Corridor: all other
1901
0.530
1008
Total Area 4512
Retail Display Allowance from LTG-INT-DISPLAY
Lobby Art/Exhibit Display Allowance from LTG-INT-DISPLAY NOTE 8� Allowed Wafts
2715
Proposed Lighting Wattage N0TE3
Location (plan #,
room #)
Fixture Description NOTE 4, 5, 6
Number of
Fixtures
Watts/
Fixture NOTE 7
Watts
Proposed
Hair Salon 125
Sconce - lamp type B
2
40
80
Hair Salon 125
Existing CFL downlight - lamp type D/E
6
26
156
Nurse/Well 232
Under cab lighting - 32" length - lamp type LED
5
17
84
Nurse/Well 232
Under cab lighting - 24" length - lamp type LED
2
15
29
Nurse/Well 232
Existing CFL downlight - lamp type D/E
8
26
208
Serve/Dining 329
Recessed retrofit downlight - lamp type LED
23
10
230
Serve/Dining 329
Semi -flush - 21" - lamp type LED
6
48
288
Serve/Dining 329
Pendant - lamp type LED
2
60
120
Serve/Dining 329
Under cab lighting - 8" length - lamp type LED
4
7
26
Serve/Dining 329
Under cab lighting - 24" length - lamp type LED
3
15
44
Serve/Dining 329
Under cab lighting - 32" length - lamp type LED
1
17
17
Toilet 328
Recessed retrofit downlight - lamp type LED
1
10
10
Toilet 328
Flush mount incandescent - lamp type Al
1
60
60
Toilet 328
Sconce incandescent - lamp type All 9 x 3
1
300
300
REM Office 331
Recessed retrofit downlight - lamp type LED
5
10
50
REM Office 331
Under cab lighting - 24" length - lamp type LED
4
15
59
REM Office 331
Under cab lighting - 8" length - lamp type LED
1
7
7
Activity Rm 333
Recessed retrofit downlight - lamp type LED
5
10
50
Activity Rm 333
Under cab lighting - 8" length - lamp type LED
1
7
7
Activity Rm 333
Under cab lighting - 24" length - lamp type LED
1
15
15
Activity Rm 333
Under cab lighting - 32" length - lamp type LED
1
17
17
Activity Rm 333
Semi -flush - 16" - lamp type LED
1
32
32
Res Laundry 332
Recessed retrofit downlight - lamp type LED
5
10
50
Living Rm 324
Sconce - lamp type B
2
40
80
Living Rm 324
Semi -flush - 16" - lamp type LED
3
32
96
Living Rm 324
Recessed retrofit downlight - lamp type LED
10
10
100
Reflect Rm 335
Recessed retrofit downlight - lamp type LED
4
10
40
Lv3 Corridor A C
Recessed retrofit downlight - lamp type LED
37
10
370
Proposed Retail Display Lighting from LTG-INT-DISPLAYI
Total Proposed Watts may not exceed Total Allowed Watts for Interior Lighting Total Proposed Wattsl 2624
Interior Lighting Power Allowance COMPLIES
Note 1 - List all unique space types per Table C405.4.2(2) that occurin the project scope. Select space type category from drop down menu.
Note 2 - Indicate ceiling height for atriums and spaces utilizing the ceiling height adjustment per Table C405.4.2(2), Footnotes d thru f.
Note 3 - List all proposed lighting fixtures including exempt lighting equipment and existing -to -remain fixtures.
Note 4 - For proposed Fixture Description, indicate fixture type, lamp type (e.g. T-8), number of lamps in the fixture, and ballast type (if included).
For
track lighting, list the length of the track (in feet) in addition to the fixture, lamp, and ballast information.
Note 5 - For lighting equipment eligible for exemption per C405.4.1, note exception number and leave Watts/Fixture blank.
Note 6 - Existing -to -remain fixtures shall be included in the Proposed Lighting Wattage table in the same manner as new fixtures. Identify as
existing
in fixture description.
Note 7 - For proposed Watts/Fixture enter the luminaire wattage for installed lamp and ballast using manufacturer or other approved source. For
luminaires with screw -in lamps, enter the manufacturer's listed maximum input wattage of the fixture (not the lamp wattage). For low
voltage
lighting, enter the wattage of the transformer. For line voltage track/buswey systems, enter the larger of the attached luminaire wattage or
50
wattsAineal foot, or enter the wattage limit of permanent current limiting device.
Note 8 - Lobby Art/Exhibit Display Allowance is independent of the Maximum Allowed Lighting Wattage. Enter all proposed lobby art/exhibit display
fixtures in LTG-INT-DISPLAYform only.
Note 9 - Calculation Area Details:
a. Lighting fixtures in a building addition may comply as a stand alone project, or they may be combined with the overall existing building
lighting systems to demonstrate compliance. Refer to C502.1.
b. For alterations and building additions, provide Space Types and gross interior areas in the Maximum Allowed Lighting Wattage table. If
building addition will comply as combined with the overall existing building lighting systems, include all applicable existing Space Types
and arncs intarinr araac_
Lighting, Motor, and Electrical Permit Checklist, Pg. 1 LTG-CHK
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 R3 R4 over 3 stories and all R1 Revised Nov 2017
Project Title: Sunrise of Edmonds Date 11/5/2020
The following information is necessary to check a permit application for compliance with the lighting, motor, and electrical requirements in the
Applicability
Location in
w ding DepartmenT
(yes,no,na)
Code Section
Component
Compliance information required in permit documents
Documents
Notes
LIGHTING
CONTROLS
Sheet ID-001. (E)
Yes
C405.2
Lighting controls,
For all lighting fixtures, indicate lighting control method on plans
locations, typ.
general
for spaces and lighting zone(s) served, or exception taken
Same controls
Luminaire level
Indicate on plans all fixtures provided with LLLC in lieu of
NA
C405.2
lighting controls
C405.2 lighting controls; provide description of control
LLLC
capabilities and performance parameters
For permanently installed lighting fixtures in dwelling units,
Lighting in dwelling
indicate lighting control method on plans for spaces and
NA
C405.1
units
lighting zone(s) served, or demonstrate compliance with high
efficacy exce tior
C405.2.3
Indicate on plans the method of manual lighting control (whether
C405.2.1.1
combined with occupancy sensor, automatic light reduction,
Sheet ID-001. (E)
Yes
C405.2.2.2
Manual controls
daylight responsive or specific application controls), location of
locations, typ.
C405.2.4
manual control device and area or specific application it serves
Same controls
C405.2.2.1
Indicate on plans which method of manual 50% lighting load
NA
C405.2.2.2
Manual interior light
reduction is provided, or whether lighting load is reduced via
C405.2.3
reduction controls
occupancy sensors or daylight responsive controls
Indicate on plans the method of automatic shut-off control durin
unoccupied periods (occupancy sensor, time switch or digital
Method of automatic
timer switch) for all lighting zones;
NA
C405.2.2
shut-off control
Indicate locations where automatic shutoff is provided by other
methods (occupancy sensor or digital timer switch) or which
time switch control exception applies
Indicate on plans the spaces served by occupancy sensors
Indicate whether occupancy sensor controls are configured to
C405.2.1
Occupancy sensor
NA
C405.2.1.1
controls
be manual -on, automatic 50%-on, or serve a space eligible for
automatic 100%-on per exce tior
Occupancy sensor
Indicate aisleways and open areas in warehouse spaces
NA
C405.2.1.2
controls -
provided with occupancy sensor controls that reduce lighting
warehouses
Power by 50%
Automatic time
Indicate locations of override switches on plans and the lighting
NA
C405.2.2.1
switch controls
zones served include areas . ft
Indicate digital timer switch control includes: manual on/off, time
NA
C405.2.6
Digital timer switch
delay, audible and visual indication of impending time-out
Indicate primary and secondary sidelight daylight zone areas on
plans, include sq. ft.;
Indicate toplight daylight zone areas on plans, include sq. ft.
C405.2.4.2
Daylight zones -
For small vertical fenestration assemblies (rough opening less
NA
C405.2.4.3
Sidelight and toplight
than 10 percent of primary daylight zone) where daylight
responsive controls are not required, provide fenestration area
to da li ht zone calculation(s)
Indicate on plans lighting zone(s) served by daylight responsive
controls;
Identify sidelight and toplight daylight zones that are not
provided with daylight sensing controls and the exception(s) tha
NA
C405.2.4
Daylight responsive
apply;
Indicate on plans the lighting load reduction method -
controls
continuous dimming, or stepped dimming that provides at least
two even steps between 0%-100% of rated power
Indicate that daylight sensing controls are configured to
completely shut off all controlled lights in the lighting zone
Additional controls -
Identify spaces and lighting fixtures on plans that require
NA
C405.2.5
Specific application
specific application lighting controls per this section
licjhtinci controls
Indicate on plans that display and accent lighting, and display
C405.2.5 -
Display and accent
case lighting are controlled independently from both general
NA
Items 1&2
lighting
area lighting and other lighting applications within the same
space:
Indicate manual and automatic lighting control method
Lighting, Motor, and Electrical Permit Checklist, Pg. 2 LTG-CHK
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 R3 R4 over 3 stories and all R1 Revised Nov 2017
Project Title: Sunrise of Edmonds Date 11/5/2020
The following information is necessary to check a permit application for compliance with the lighting, motor, and electrical requirements in the
Applicability
Location in
building Department
(yes,no,na)
Code Section
Component
Compliance information required in permit documents
Documents
Notes
C405.2.5 -
Hotel/motel guest
Indicate method of automatic control - vacancy or captive key
NA
Item 3
control of all installed luminaires and switched receptacles in
rooms
guest room
C405.2.5 -
Supplemental task
Indicate method and location of automatic shut-off vacancy
Under cab lights
Yes
Item 4
lighting
control for supplemental task lighting, including under -shelf or
to be hardwired
under -cabinet lighting
er (E) bldci strd
Indicate on plans eligible non -visual lighting applications,
include sq. ft. area of each lightinq control zone
Indicate on plans that non -visual lighting are controlled
C405.2.5 -
Lighting for non-
NA
Item 5
visual applications
independently from both general area lighting and other lighting
applications within the same space;
Indicate method of manual lighting control and applicable
automatic lighting control
Indicate on plans that lighting equipment for sale or
Lighting equipment
demonstration are controlled independently from both general
NA
C405.2.5 -
for sale or
area lighting and other lighting applications within the same
Item 6
demonstration
space:
Indicate method of manual lighting control and applicable
automatic lighting control
Identify on plans egress fixtures that function as both normal
and emergency means of egress illumination
Provide calculation of lighting power density of total egress
C405.2.5 -
Means of egress
lighting;
NA
Item 7
lighting
total egress ig mg power ensi y is greater an sq.
ft., indicate on plans egress fixtures requiring automatic shut-off
during unoccupied periods;
Indicate method of automatic shut-off contro
Indicate on exterior lighting plans and fixture schedules the
automatic lighting control method, control sequence, and
locations served;
For building facade and landscape lighting, indicate automatic
Exterior lighting
controls shut off lighting as a function of dawn/dusk and fixed
NA
C405.2.7
controls
opening/closing time;
For all other exterior lighting, indicate automatic controls shut ofi
lighting as a function of available daylight; include control
sequence that also reduces lighting power by at least 30%
between 12am-6am, or from 1 hour after closing to 1 hour
before open'na, or based upon motion sensoi
Exterior building
For building grounds fixtures greater than 100 watts, indicate on
NA
C405.5.1
grounds lighting
plans whether fixtures have efficacy greater than 80 lumens or;
controls
are controlled by motion sensor, or are exempt lighting per
C405.5.2
Area controls -
Indicate location(s) of master control switch(es) intended to
C405.2.5
Master control
control multiple independent switches; circuit breaker may not
NA
(listed after
switches and circuit
be used as a master control switch
C405.2.7)
Verify that no 20 amp circuit controlled by a single switch or
power limit
automatic control is loaded beyond 80°k
ADDITIONAL
EFFICIENCY
PACKAGE OPTION - ENHANCED DIGITAL LIGHTING CONTROLS
To comply with additional efficiency package option, indicate on
plans all interior lighting fixtures that are individually addressed
Enhanced digital
and provided with continuous dimming, or exception taken;
NA
C406.4
lighting controls
Include calculation of percent total installed interior lighting
power that is configured with required enhanced lighting control
functions (min 90% to comply with additional efficiency package
option)
Lighting, Motor, and Electrical Permit Checklist, Pg. 3 LTG-CHK
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 R3 R4 over 3 stories and all R1 Revised Nov 2017
Project Title: Sunrise of Edmonds Date 11/5/2020
The following information is necessary to check a permit application for compliance with the lighting, motor, and electrical requirements in the
pp ica i i y
Location in
w ding Department
(yes
Code Section
Component
Compliance information required in permit documents
Documents
Notes
INTERIOR
LIGHTING
POWER & EFFICACY
Include all luminaires in lighting fixture schedule; indicate fixture
types, lamps, ballasts, and manufacturer's rated watts per
Sheet ID-001
fixture;
Identify spaces eligible for lighting power exemption on plans
Total connected
Yes
C405.4.1
interior lighting
and in compliance forms; indicate the exception applied;
Identify lighting equipment eligible for lighting power exemption
C405.4.2
power
in fixture schedule and in compliance forms; indicate the
exception applied;
Indicate that exempt lighting equipment is in addition to general
area lighting and is controlled independently
NA
C405.3
Exit signs
Indicate location of exit signs on plans and rated watts per
fixture in li tin fixture schedule maximum 5 watts per side'
If high efficacy exception is applied to permanently installed
Lighting in dwelling
lighting fixtures in dwelling units, indicate in lighting fixture
NA
C405.1
units -lamp efficacy
schedule if lamps in fixtures are high efficacy per R404.1.
Calculate percentage of fixtures with high efficacy lamps in
prooect (min 0 to comply with exception)
Interior Li ina Power Calculation - Indicate com liance path taken
Building Area
Complete required compliance forms — proposed wattage per
NA
C405.4.2.1
Method
building area does not exceed maximum allowed wattage per
building area: identify locations of building areas on plans
Complete required compliance forms — total proposed wattage
Yes
C405.4.2.2
Space -By -Space
does not exceed maximum allowed wattage; identify locations o
Sheet ID-001
Method
space types on plans, including retail display areas, lobby art &
exhibit display areas and ceilina hei hts as applicable
ADDITIONAL
EFFICIENCY
PACKAGE OPTION - REDUCED INTERIOR LIGHTING POWER DENSITY
To comply with additional efficiency package option,
Reduced lighting
demonstrate in compliance forms that total connected interior
NA
C406.3
power density
lighting wattage is 25% less than the total maximum allowed
lighting wattage via Building Area Method or Space -By -Space
Method
Reduced lighting
For project with dwelling units, to comply with additional
power density -
efficiency package option indicate in lighting fixture schedule if
NA
C406.3
dwelling unit lamp
lamps in interior fixtures have efficacy rating of 60 lumens per
efficacy
watt or more. Calculate percentage of fixtures with lamps that
have this efficacv ratina (min 95 /o to comDly with option'
EXTERIOR
LIGHTING POWER & EFFICACY
Include all luminaires in lighting fixture schedule; indicate fixture
types, lamps, ballasts, and manufacturer's rated watts per
fixture;
Identify exterior applications eligible for lighting power
Total connected
NA
C405.5.2
exterior lighting
exemption on plans and in compliance forms; indicate exception
applied;
power
Indicate that exempt exterior lighting is controlled independently
from non-exempt exterior lighting; include exception claimed for
each fixture or group of fixtures under exception category
NA
Table
Exterior lighting zone
Indicate building exterior lighting zone as defined by the AHJ
C405.5.2(1)
Exterior building
For building grounds fixtures rated at greater than 100 watts tha
NA
C405.5.1
grounds lighting
are complying based on efficacy, indicate rated lamp efficacy (in
lumens per watt) in fixture schedule
Exterior lighting
Complete required compliance form — proposed wattage for
NA
C405.5.2
power calculations
exterior lighting plus base site allowed does not exceed
maximum allowed
Lighting, Motor, and Electrical Permit Checklist, Pg. 4 LTG-CHK
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 R3 R4 over 3 stories and all R1 Revised Nov 2017
Sunrise of Edmonds Date 11/5/2020
The following information is necessary to check a permit application for compliance with the lighting, motor, and electrical requirements in the
Applicability
I
Location in
Building Department
(yes,no,na)
I Code Section
Component
Compliance information required in permit documents
Documents
Notes
LIGHTING
ALTERATIONS
Where Z o of existing luminaires in interior spaces or
parking garage are replaced; indicate compliance path (building
area or space -by -space method); include all new and existing -to
Sheet ID-001
remain luminaires in compliance form (LTG-INT-BLD or LTG -
Interior and parking
INT-SPACE); indicate proposed lighting wattage does not
Yes
C503.6
garage lighting
exceed maximum allowed Der compliance Datt
Where < 50 0 of existing luminaires in interior spaces or
fixture alterations
parking garage are replaced; indicate total existing lighting
wattage in each space prior to alteration; include all new and
NA
existing -to -remain luminaires in LTG-INT-SPACE form; indicate
proposed total lighting wattage in alteration area does not
Where Z 50% of existing exterior lighting wattage is replaced;
include all new and existing -to -remain luminaires in LTG-EXT
form; indicate proposed total exterior lighting wattage does not
Exterior lighting
exceed maximum allowec
/o Where < 50 of existing exterior lighting wattage is replaced;
NA
C503.6
fixture alterations
indicate total existing lighting wattage prior to alteration; include
all new and existing -to -remain luminaires in LTG-EXT form;
indicate proposed total exterior lighting wattage does not excee
Where new wiring is installed to serve new interior luminaires
Interior lighting wiring
and /or luminaires are relocated to a new circuit; indicate lightin
NA
C503.6
alterations
controls are provided (as applicable) - manual (C405.2.3);
occupancy sensor (C405.2.1); daylight responsive (C405.2.4);
Exterior lighting
Where new wiring is installed to serve new exterior luminaires
NA
C503.6
wiring alterations
and /or luminaires are relocated to new circuit; indicate exterior
liahtina controls are provided C405.2.7
Where a new lighting panel is installed or an existing panel is
Lighting panel
moved (all new raceway and conductor wiring); indicate lighting
NA
C503.6
alterations
controls are provided (as applicable) - same provisions as
wiring alterations; time switch controls and manual light
reduction controls (C405.2.2)
Where interior space(s) is reconfigured (permanently installed
Yes
C503.6
Interior space
walls or ceiling -height partitions); indicate lighting controls are
Sheet A1.3; demo
reconfiguration
provided (as applicable) - same provisions as lighting panel
keynote 7
alterations
Identify existing luminaires being upgraded with bulb and / or
Sheet ID-001. LED
Yes
C504.2
Lighting repairs
ballast replacement; indicate fixture alteration does not increase
retrofits noted
existing fixture wattacie
Identify spaces on plans where the building area type or space
use type is being changed from one type to another per Tables
C405.4.20) or (2)
Indicate compliance path (building area or space -by -space
NA
C505.1
Change of space use
method); include all new and existing -to -remain luminaires in
compliance form (LTG-INT-BLD or LTG-INT-SPACE); indicate
proposed lighting wattage does not exceed maximum allowed
per compliance path
RECEPTACLES
Identify all controlled and uncontrolled receptacles on electrical
plans in each space in which they are required; include
Controlled
receptacle configuration such as spacing between controlled
NA
C405.10
receptacles
and uncontrolled, duplex devices. etc:
Indicate on plans whether the method of automatic control foi
each controlled receptacle zone is by occupant sensor or
Programmable time-of-dav contro
Lighting, Motor, and Electrical Permit Checklist, Pg. 5 LTG-CHK
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 R3 R4 over 3 stories and all R1 Revised Nov 2017
Sunrise of Edmonds Date 11/5/2020
The following information is necessary to check a permit application for compliance with the lighting, motor, and electrical requirements in the
pp ica i i y
I
Location in
Building Department
(yes,no,na)
I Code Section
Component
Compliance information required in permit documents
Documents
Notes
MOTORS, TRANSFORMERS, ELECTRIC METERS, INTERIOR TRANSPORTATION
NA
C405.6
Electrical
Include electrical transformer schedule on electrical plans;
transformers
indicate transformer size efficiency, or exception takes
Dwelling unit
Indicate on electrical plans that each dwelling unit in Group R-2
NA
C405.7
electrical energy
has a separate electrical energy meter
consumption
Electric motor
Include all motors, including fractional hp motors, in electric
NA
C405.8
efficiency
motor schedule on electrical plans; indicate hp, rpm, rated
efficiency, or exception appliec
For luminaires in each elevator cab, provide calculated average
efficacy of combined fixtures that indicates efficacy is not less
than 35lumens per watt;
Indicate rated watts per cfm for elevator cab ventilation fans do
NA
C405.9.1
Elevator cabs
not exceed 0.33 watts per cfm
Indicate automatic controls that de -energize lighting and
ventilation fans when elevator is stopped and unoccupied for a
period of 15 minutes or more
Escalators and
Indicate escalators comply with ASME A17.1/CSA B44;
NA
C405.9.2
moving walks
automatic controls are configured to reduce operational speed t
the minimum permitted when not in use
NA
C405.9.3
Regenerative drive
Indicate all one-way down or reversible escalators are provided
with a variable frequency regenerative drive
DOCUMENTATION
AND SYSTEM REQUIREMENTS TO SUPPORT COMMISSIONING (Cx)
Indicate that all electrical systems (receptacles, transformers,
motors, vertical and horizontal transportation) for which the
WSEC requires control functions and / or configuration to
Scope of electrical
Derform specific functions are required to be commissioned
power and lighting
Where total building lighting load is > 20 kW, or where total
NA
C408.3
systems
lighting load of luminaires requiring daylight sensing and / or
commissioning
occupancy control > 10 kW, indicate that all automatic lighting
control systems are required to be commissioned; or provide
building lighting power calculation demonstrating eligibility for
Indicate Cx requirements in plans and specifications for all
applicable electrical and lighting control systems per C408;
Include general summary with at minimum Items 1 thru 4 of the
C405.13
Commissioning
Cx plan per C408.1.2 including: narrative description of
C408.1.1
requirements in
activities, responsibilities of the Cx team, schedule of activities
NA
C408.1.2
construction
including verification of project close out documentation per
C408.1.4.2
documents
C103.6. and conflict of interest plan (if reauired):
Include in general summary that a Cx project report or
C103.6
Compliance Checklist (Figure C408.1.4.2) shall be completed
by the Certified Cx Professional and provided to the owner prior
Ito the final electrical ins ectior
Functional
Identify in plans and specifications the intended operation of all
NA
C408.3.1
performance testing
equipment and controls during all modes of operation, including
criteria
interfacing between new and existing -to -remain systems
PROJECT CLOSE OUT
DOCUMENTATION
Indicate in plans that project close out documentation is
Project close out
required including WSEC lighting compliance forms and
Sheet A1.3
Yes
C103.6.3
documentation
calculations that document all interior and exterior lighting area
General note 13
requirements
and / or surface types, lighting power allowances and installed
densities
11 11U 10 i UMULCU lU1 ally 4U=0L11J11, IJIUVIUW CAF/IQIIQLIVII.
End of Lighting, Motor & Transformer Permit Documents Checklist