APPROVED BLD PLN BLD2021-0271+Mechanical_Plan+5.13.2021_4.37.01_PM+2196338rvl Inl I �T DUCT LAYER FIREMASTER FASTWRAP THICK OR EQUIVLANT 3" MIN. OVER LAY. TYP. STEEL BANDING 1/2" WIDE MIN OR PINNING. TYP. TYP. FIRE WRAP OVERLAY DETAIL FireMaster® FastWrap® XL encapsulated blanket product is the basis of a range of systems for up to 2 hour fire protection of ductwork. The blanket is simply attached to the duct using steel banding straps and has the following key features: Non -Combustible product. Tested to meet ISO 6944, ASTM E2336, BS 476 part 24 and EN 1366-1 standards for fire protection of ductwork UL listed Flexible wrap -ideal for circular ducts minimising cutting and fixing Clean, quick and simple installation -encapsulated product Complete encapsulation resists contamination by leaking duct contents (such a grease in kitchen ducts) Zero Clearance to combustibles Provides combined fire, acoustic and thermal insulation NOTE: PENETRATIONS, GUARD RAILS, SERVICE PLATFORMS OR EQUIPMENT SCREEN BY OTHERS IF REQUIRED. Grease Duct Enclosure System Air lfentilation Duct Enclosure System Praduot Data S4 Installation Guide 11. Product Description FireMaster FastWrap L is a fle�cible blanket composed of high temperature fibers classified for applications to 2192°F (1200°C) and fully encapsulated in a durable glass fiber reinforced foil facing for easy handling and installation. FastWrap XL is UL and I.�LC Listed for 1 and 2 hour fire resistive enclosure protection, sera clearance for kitchen exhaust ducts, electrical circuit protection, and as a component in UL firestop designs for fire resistance rated floors, ceilings, and walls. The core fibers in FastVl�rap L are manufactured using Morgan Thermal Ceramics patented SuperwooJ� fiber which is an alkaline -earth silicate wool with low biopersistence and therefore increased safety far installers. FastWrap )CL is under UL's Follow -gyp Service Program to ensure the consistent duality essential to this life -safety application, Approved by Fire 06/01/2021 AFM ��LttCl'e�' Approved, Separate permit for hood suppression system 10' MIN. TO ANY AIR INTAKE AND PROPERTY LINE IN ANY DIRECTION; 10'MIN. FROM SAME OR ADJACENT BUILDING TERMINATION ABOVE THE ROOF PER IMC 506.3.13.3 ONE HR MIN. FIRE WRAP (2 LAYERS ON GREASE DUCT) 6' Kitchen hood New 11' Kitchen hood New N SITE PLAN Kitchen hoods location - 10' MIN. FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT EXHAUST EXHAUST SOURCE. FAN FAN 4'-3" 4'-3" —� 18"MIN. 18"MIN. 22 GA. S.S. WALL 8"MI 18"MIN. FLASHING ON HOOD BACK AND SIDE WALL; 18" MIN. OVER HOOD TOP AND 18"MIN. 18"MIN. 18"MIN. 18"MIN. SIDE. EDGE. TERMINATION ABOVE THE ROOF PER IMC 506.3.13.3 10'MIN. IAUST FANS :ATION ON ROOF: MIN. TO ANY )F EDGE, RMINATION �OVE THE ROOF PER C 506.3.13.3 OJECT TENANT SPACE SIMPLIFIED SITE PLAN —EXHAUST FAN LOCATION ON ROOF SCALE: A/N 10' MIN. TO ANY AIR INTAKE AND PROPERTY LINE IN ANY DIRECTION; 10'MIN. FROM SAME OR ADJACENT BUILDING TENtPE�D MAKE-UP UNIT h���r��ll;�r������a�l��ll;� 12" x 12" OR EQUIVALENT AREA MAKE-UP AIR DUCT. 24 GA. MIN. GALV. METAL, ALL JO SEALED. MAKE-UP AIR PLENUM 18"MIN. i T � SIB .� 18"M I N 6"MIN. Type I kitchen hood required to overhang horizontally beyond the edge of the cooking surface at least 6 inches per I.M.C. 507.4.1 11' LONG WALL CANOPY TYPE I HOOD 116' LONG WALL CANOPY TYPE I HOOD COOKING EQUIPMENT BY OTHERS :��- HOOD FRONT ELEVATION/SECTION DETAIL APPROVED PLANS MUST BE ON JOB SITE —� 6" N. Separate permit required for Fire Suppression systems and structural alterations. 1-1/2" ROXUL RHT 80 FIRE PAD BEHIND SS BACKSPLASH ROXUL RHT 80 IS A MINERAL WOOL BOARD INSULATION.SPECS ATTACHED. Type I kitchen hoods required to overhang horizontally beyond the edge of the cooking surface at least 6 inches per I.M.C. 507.4.1 HOOD TO BE INSTALLED @ 71" MIN - 84" MAX City Of Edmonds Building Department Work MECHANICL FOR T/I Address 515 MAIN ST Owner THE LOFT Approved Date 6-29-2021 Building Official Erie C%a-v�te-+� Permit Number bId2021-0271 EXHAUST FAN ,;, �:�: •'a �.; •':s :..�: •'%s �,�. :..�: • �, �.�: •'% �.;. 4'-3" 1 HOUR MIN. FIRE WRAP (2 LAYER REQIRED ON GREASE DUCT). 12" x 12" OR EQUIVALENT AREA 16GA. GALV. STEEL ALL LIQUID TIGHT WELDED EXHAUST DUCT. 3" INTERNAL STAND❑FF, 1-1/2" ROXUL RHT 80 FIRE PAD BEHIND SS BACKSPLASH ROXUL RHT 80 IS A MINERAL WOOL BOARD INSULATION.SPECS ATTACHED. 22 GA. S.S. WALL FLASHING ON HOOD BACK AND SIDE WALL; 18" MIN. OVER HOOD TOP AND SIDE EDGE. HOOD SIDE ELEVATION/SECTION DETAIL SCALE: 1 /2"=1'-0" APPROVED BY PLANNING �,� ��� Jun 08 2021 PROPERTY DESCRIPTION: PARCEL NUMBER:00434202103000 ADDRESS: 515 MAIN ST PROPERTY OWNER: TAX TABLE PROPERTIES LLC BUILDING CONSTRUCTION TYPE: wooD FRAME LEGAL: 5601000 SW1/4 SEC24 T27N R3E TENANT BUSINESS: THE LOFT N VICINITY MAP SCALE: A/N 11' & 6' TYPE I WALL CANOPY KITCHEN HOODS NOTES: (1) HOODS: One 11'-0" 3650ELPX-2-PSP-F - lift 0" Long Low Proximity Sloped Type I Hood with Front Perforated Supply Plenum with Built-in 3" Back Standoff Type I S.S. Hood, 20 GA. 430 Stainless Steel construction where exposed. 16"tall X 16" stainless steel baffle filters with handles and bottom hanging hook, L55 Series E26 Canopy Light Fixture -High Temp Assembly, Includes Clear Thermal and Shock Resistant Globe (L55 Fixture). One 6'-0" 3650ELPX-2-PSP-F -Eft 0" Long Low Proximity Sloped Type I Hood with Front Perforated Supply Plenum with Built-in 3" Back Standoff Type I S.S. Hood, 20 GA. 430 Stainless Steel construction where exposed. 16"tall X 16" stainless steel baffle filters with handles and bottom hanging hook, L55 Series E26 Canopy Light Fixture -High Temp Assembly, Includes Clear Thermal and Shock Resistant Globe (L55 Fixture). (2) EXHAUST DUCTS: 2) 12" X 12" or equivalent area, 16 GA. Galvanized steel all welded construction. (3) CONTINUOUS ENCLOSURE CONSTRUCTION: FireMaster° FastWrap® Fire Wrap (one hour Min. Fire Rated. UL, ICBO, ASTM tested and listed product) Continuous duct enclosure shall be sealed around the duct at the point of penetration and vented to the exterior through a weather protected opening (roof curb). Duct wrap should be installed at a minimum of 3"below T bar non-combustible ceiling to top of roof curb minimum 18" above the roof and at least 18" away from wood. (4) EXHAUST FANS: (1) EADU85H High Speed Direct Drive Centrifugal Upblast Exhaust Fan, with speed control (speed control included for single phase only), disconnect switch and 15-3/4" wheel Exhaust Fan handles 2200 CFM @-0.750" we ESP, Fan runs at 1408 RPM. Exhaust Exhaust Motor: 0.750 HP, 1 Phase 208 V, 60Hz, 5.2FLA, TEAO-ECM 16.8 SONES. 93 Lbs. (1) EADU85H High Speed Direct Drive Centrifugal Upblast Exhaust Fan, with speed control (speed control included for single phase only), disconnect switch and 15-3/4" wheel Exhaust Fan handles 1200 CFM @ -1.200" we ESP, Fan runs at 1279 RPM. Exhaust Exhaust Motor: 0.750 HP, 1 Phase 208 V, 60Hz, 5.2FLA, TEAO-ECM 11.2 SONES. 93 Lbs. (5) MAKE UP AIR UNIT: EA2-D.250-20D Direct Gas Fired Heated Make Up Air Uni, 3060 CFM @ 0.500" S.P., Fan runs at 1241 RPM, Make up air motor 1.500 HP, 3 phase 208 V, 60Hz, 6.6 FLA, Premium (E-Plus3) Eff. Down discharge, mesh EZ kleen metal mesh filters. Motorized Back Draft Damper 22.75" X 24", Galvanized Construction. Heater supplies 179802 BTUs. 55°F Temperature Rise. Fuel: Natural Gas.RTC Solutions • 40-90°F Discharge Temp Control. Gas Manifold for DF2 GM - BTU 0 - 825001 - 7 in. w.c. - 14 in. w.c. Tempered make up air unit is 668 Lbs. 10.7 Sones. (6) Exhaust fan, Make up air unit, hood lights and any electrical appliances or outlets should be interlocked with the fire suppression system, fire suppression system should also be able to shut down gas flow. (7) Fire Suppression system will conform to UL-300, NFPA 96, all local, state codes and insurance requirements. On separate permit for FD review and trip test. (8) All design and work will confrom to IMC-12, UL-300, NFPA 96, SMC, all local, state codes and insurance requirements. (9) Work performed for this project includes install one Type I 11' wall canopy kitchen hood and one Type I 6' wall canopy kitchen hood , exhaust fan, tempered make up air unit, grease duct work 2 layers of fire wrap, new stainless stee122 Ga finish #4 with fire pad on hoods wall, and new fire suppression system. Fire suppression system on separate permit for FD approval and review. GREASE DUCT LEAKAGE TEST: GREASE DUCT LEAKAGE TEST SHALL BE PERFORMED FOR THE ENTIRE DUCT AND JOINT SYSTEM PER IMC SEC. 506.3.2.5. IMC 506.3.2.5 HOOD EXHAUST &MAKE UP AIR CALCULATIONS HOOD (LF) RATE (CFM/ LF) REQUIRED HOOD CFM DUCT SIZE DUCT AREA FPM EXHAUST (I) 11' 200 2200 12" X 12"' 1.00 2200 EXHAUST (2) 6' 200 1200 12" X 12"' 1.00 1200 HEATED MAKE UP AIR UNIT 3060 12" X 12"' 1.00 3060 i� � � ��' �9 � � 33 °O z °O w oo � �� �3 �� �. {w- --. � � � V � � � Q O i`j O O t� � � 'c� ._ � � � ��� � Q � � � 'W O �c �� Z W V W � O CV � }, � a Q � � ,, +� LL � Q � .� � w J 0 � o W O = 0 � � H 2 �n Lu REVISIONS: RESUB May 14 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT SHEET TITLE: -- GENERAL NOTE AND INFORMATION -- SITE PLAN (REFLECT ROOF UNIT LOCATION) -- A: HOOD FRONT ELEVATION/SECTION -- B: HOOD SIDE ELEVATION/SECTION -- OTHER DETAILS DATE � � 2 /23/ 2020 SHEET: GAS PIPING INSTALLATION G-1 Steel Pipe - Schedule 40 Capacity of Pipe (MBH z CFH) Pipe Size (in) Pipe Length (ft) Nominal Inside diameter 10 20 40 80 150 300 1/2 0.622 120 85 60 42 31 22 3/4 0.824 272 192 136 96 70 50 1 1.049 547 387 273 193 141 100 11/4 1.380 1200 849 600 424 310 219 11/2 1.610 1860 1316 930 658 480 340 2 2.067 3759 2658 1880 1330 971 686 21/2 2.469 6169 4362 3084 2189 1593 1126 3 3.068 11225 7938 5613 3969 2898 2049 100000 112" 314" T' 1 V4" I 40' of 1 1/2" Black steel pipe schedule 10000 —1 V2^ 40, total pipe run 40'. of 1-1/2" of pipe —2" table shows 40' max 930 MBH-CFH = to —2 V2" 1,023,800 BTU's, max BTU's for this g -4„ application 636,000 BTU's 1000 6 6" C3 100 10 engineeringtoolbox.com III 10 100 Pipe Length (feet) Appliances: 1.- 6 burner range 2.- 6 burner range 3.- Broiler 4.- Griddle 5.- Fryer 6.- Fryer Total BTU's 1000 Main gas V`J Gas meter model AC-630. 693,000 BTU's to be used for this project to be provided by PSE 180,000 BTU's Gas meter location by the back alley. W dM LO v M N Individual manual gas valve per gas appliance Fire suppression system automatic shut off gas valve 180,000 BTU's 48,000 BTU's 48,000 BTU's 90,000 BTU's Fire Suppression Systems(Service & Installation) 90,000 BTU's • Kitchen Hood Installations 636,000 BTU's Fire Extinguishers Complete Food Truck Builds 14611 Ambaum Blvd SW Burien, WA 98166 206-617-4951 unnn TATFnRMATTnAT — Jnn4JR9dQ.@2 MAX EXHAUST PLENUM TOTAL HOOD CONFIG RISER(S) HOOD TAG MODEL M NUFACTUR RLENGTH COOKING TYPE APPLIANCE DESIGN TOTAL SUPPLY HOOD END TO WIDTH LENG HEIGHT DIA CFM VEL SP NO TEMP DUTY CFM/FT EXH CFM CFM CONSTRUCTION END ROW 3650 600 430 SS 1 ECON-AIR I1' 0' I HEAVY 200 2200 10' 21' 4' 2200 1509 -0.503' 0 ALONE ALONE ELPX-2 DEG WHERE EXPOSED 206 300 430 SS 2 ECON-AIR 11' 0' DEG I N/A 0 0 1980 ALONE ALONE MISC-PSP WHERE EXPOSED unnn TATFnRMATTn TT PATENT NUMBERS AC-PSP (UNITED STATES) - US PATENT 7963830 B2. AC-PSP WALL (CANADA) - CA PATENT 2820509. AC-PSP ISLAND (CANADA) - CA PATENT 2520330. FILTERS) LIGHTS) UTILITY CABINET(S) HOOD TAG EFFICIENCY @ 7 WIRE FIRE SYSTEM ELECTRICAL SWITCHES FIRE SYSTEM HOOD ANGIN TYPE SIZE MODEL # QUANTITY NO TYPE QTY HEIGHT LENGTH MICRONS QTY TYPE GUARD LOCATION SIZE PIPING WEIGHT 1 SS BAFFLE WITH 8 16' 16' 30% 3 RECESSED NO NO 320 HANDLES LBS 2 0 NO 99 LBS FTnnn nPTTON.4 HOOD NO TAG OPTION RIGHT QUARTER END PANEL 26' TOP WIDTH, 0' BOTTOM WIDTH, 26' HIGH 430 SS. 1 LEFT QUARTER END PANEL 26' TOP WIDTH, 0' BOTTOM WIDTH, 26' HIGH 430 SS. PFRFnRATF.n .41TPPT.Y PT.FATTTM/.4) HOOD NO TAG POS LENGTH WIDTH HEIGHT TYPE RISERS) WIDTH I LENG DIA CFM I SP 2 Front ill 20' 6' MUA 12' 24' 660 0.194' MUA 12' 24' 660 0.194' MUA 12' 24' 660 0.194' 36' FIELD CUT X 21' EXHAUST RISER, U.L, LISTED RECESSED ALLANSON ROUND LED FIXTURE AND LED LIGHT. 11' O'NOM./11' 0.00'OD. PLAN VIEW - HOOD #1 11' 0.00" LONG 3650ELPX-2 ter% ter% ter% 11' O'NOM./11' 0.00'OD. PLAN VIEW - HOOD #2 11' 0.00" LONG 206MISC-PSP HOOD CORNER SUPPLY PLENUM 1/2' - 13 TPI HANGING ANGLE I/2' - 13 TPI HANGING ANGLE GRADE s OONMUN) STEEL HEX NUTS. (HARDWARE BY INSTALLER) STEEL NMADE IX NUINI TS ) (HARDWARE BY INSTALLER) 12' GRADE 5 (MUN NIN) STEEL 1/2' GRADE 5 (MINIMUM) STEEL FLAT VASXER. FLAT WASHER 1/2' - 13 TPI 1/2' - 13 TPI GRADE 5 (MINIMUM) GRADE 5 PNIINMUN) STEEL ALL -THREAD, STEEL ALL -THREAD. 1/2' - 13 TPI 1/2' - 13 TPI GRADE 5 ONIMMUN) STEEL HEX MIT. GRR➢E 5 (MINIMUM) STEEL HEX NUT. SUPPLY PLENUM 1/2' GRADE 5 HOID COINER HANGING ANGLE (HININU) STEEL FLAT WASHER HANGING ANGLE (WEIGHT BEARING ANCHON POINT 1/2' GRADE 5 (HINMIM) STEEL FLAT WASHER, (WEIGHT BEARING ANCHOR POINT FIR SUPPLY FOR MOD). PLENUM). 1/2' GRADE 5 1/2' MAD5 (MINIMUM) STEEL FLAT WASHER. (MINIM.) STEEL FLAT WASHER 1/2' - 13 TPI 1/Y - l3 TPI GRADE 5 GRADE 5 X MT. N) STEEL HIX MIT. X NUTS. STEEL !E% NUTS. ASSEMBLY INSTRUCTIONS ASSEMBLY INSTRUCTIONS HANGING ANGLE MUST BE SUPPORTED WITH 1/2' - 13 TPI GRADE 5 (MINIMUM) ALL -THREAD. SANDWICH HANGING ANGLES AND CEILING ANCHOR POINTS WITH 1/2' GRADE 5 (MINIMUM) STEEL FLAT WASHERS AND 1/2' - 13 TPI GRADE 5 (MINIMUM) HEX NUTS AS SHOWN. MUST USE DOUBLED HEX NUT CONFIGURATION BENEATH HOOD HANGING ANGLES AND ABOVE CEILING ANCHORS. MAINTAIN 1/4' OF EXPOSED THREADS BENEATH BOTTOM HEX NUT, TORQUE ALL HEX NUTS TO 57 FT-LBS. HANGING ANGLE MUST BE SUPPORTED WITH 1/2' - 13 TPI GRADE 5 (MINIMUM) ALL -THREAD. SANDWICH HANGING ANGLES AND CEILING ANCHOR POINTS WITH 1/2' GRADE 5 (MINIMUM) STEEL FLAT WASHERS AND 1/2' - 13 TPI GRADE 5 (MINIMUM) HEX NUTS AS SHOWN. MUST USE DOUBLED HEX NUT CONFIGURATION ABOVE CEILING ANCHORS. SINGLE HEX NUT BENEATH HANGING ANGLE IS ACCEPTABLE FOR PSP HANGING ANGLES. MAINTAIN 1/4' OF EXPOSED THREADS BENEATH BOTTOM HEX NUT. TORQUE ALL HEX NUTS TO 57 FT-LBS, FIELD CUT EXHAUST RISER. 16' SS BAFFLE WITH HANDLES AND HOOK. 3' INTERNAL STANDOFF IT IS THE RESPONSIBILITY OF THE ARCHITECT/OWNER TO ENSURE THAT THE HOOD CLEARANCE FROM LIMITED -COMBUSTIBLE AND COMBUSTIBLE MATERIALS IS IN COMPLIANCE WITH LOCAL CODE REQUIREMENTS. GREASE DRAIN WITH REMOVABLE CUP. FIELD INSTALLED QUARTER END PANELS. ISON ROUND LED FIXTURE AND I K WARM OUTPUT. SECTION VIEW MODEL 3650ELPX2 HOOD - #9 14' NOM. rig FOR QUESTIONS, CALL THE PATENT NUMBERS Seattle ❑ffice AC-PSP (UNITED STATES) - US PATENT 7963830 32. Hlnanshu Waldya AC-PSP WALL (CANADA) - CA PATENT 2820509. PHONE- (425) 212-5996 AC-PSP ISLAND (CANADA) - CA PATENT 2520330. EMAIL, reg85@econalr.con HOOD INFORMATION - JOB 4842682 HOOD INFORMATION HOOD OPTIONS 3' FIELD CUT PERFORATED SUPPLY PLENUM S 10' X 11' EXHAUST 36' RISER. U.L. LISTED L55 SERIES E26 CAN PY LIGHT FIXTURE - HIGH TEMP ASS MBLY. Q 6' O'NOM./6' 0.00'OD. PLAN VIEW — HOOD #1 (New Hood) 6' 0.00" LONG 3650ELPX-2 16' 12' - -- - - I '4 2" 19 1/4' 33 1/2" 6' O'NOM./G' 0.00'OD. NSF OPLAN VIEW — HOOD #New Hood PSP) 6' 0.00" LONG 166MISC—PSP JOB Loft - Fans and Controls - R2 Vent® k o �'� ecomairLOCATION SEA021 WA, DATE 4/14/2021 JOB # 4842682 .0mev� ✓, DWG # 1 DRAWN BY REV SCALE 3/8' = 1'-0' MAX EXHAUST PLENUM TOTAL HOOD CONFIG RISER(S) HOOD TAG MODEL M NUFACTUR RLENGTH COOKING TYPE APPLIANCE DESIGN TOTAL SUPPLY HOOD END T❑ WIDTH LENG HEIGHT DIA CFM VEL SP NO TEMP DUTY CFM/FT EXH CFM CFM CONSTRUCTION END ROW 3650 600 430 SS 1 New Hood ECON-AIR 6' 0' DEG I HEAVY 200 1200 10' 11' 4' 1200 1571 -0.794' 0 ALONE ALONE ELPX-2 WHERE EXPOSED New Hood 166 300 430 SS 2 PSP ECON-AIR 6' 0' DEG I N/A 0 0 1080 ALONE ALONE MISC-PSP WHERE EXPOSED FILTER(S) LIGHT(S) UTILITY CABINET(S) HOOD TAG EFFICIENCY @ 7 WIRE FIRE SYSTEM ELECTRICAL SWITCHES FIRE SYSTEM HOOD ANGIN TYPE SIZE MODEL # QUANTITY NO TYPE QTY HEIGHT LENGTH MICRONS pTY TYPE GUARD LOCATION SIZE PIPING WEIGHT 1 New Hood SS BAFFLE WITH 4 16' 16' 30% 2 L55 SERIES E26 N❑ NO 213 HANDLES LBS 2 New Hood 0 NO 66 PSP LBS HUUD TAG OPTION NO RIGHT QUARTER END PANEL 26' TOP WIDTH, 0' BOTTOM WIDTH, 26' HIGH 430 SS. 1 New Hood LEFT QUARTER END PANEL 26' TOP WIDTH, 0' BOTTOM WIDTH, 26' HIGH 430 SS. HOOD NO TAG POS LENGTH WIDTH HEIGHT TYPE RISER(S) WIDTH LENG DIA CFM SP 2 New Hood PSP Front 72' 16' 6' MUA 12' 20' S40 0,159' MUA 12' 20' S40 0,159' HUU➢ CURNER FULL LENGTH SUPPLY PLENUM GRAD - l3 TPI HANGING ANGLE G/2' - 13 TPI HANGING ANGLE Ile - 13 TPI HANGING ANGLE GRADE s X NUTSN) STEEL HEX NUTS. (HARDWARE BY INSTALLER) STEEL HEX M GRADE 5 IIDVJMNI BY INSTALLER) GRADE 5 (MINIMUM) STEEL HEX MITS (HARDWARE BY INSTALLER) I/2' MADE 5 1/2' GRADE 5 1/2' WADE 5 (MINIMIM) STEEL (MMIMIM) STEEL FLAT WASHER. (MINMUN) ST RAT WASHER FLAT WASHER. t/2' - l3 TPI 1/2' - 13 TP 1/2' - 13 TPI GRADE 5 (MINIMIM) GRADE 5 HDUMN) STEEL ALL -THREAD. WADE 3 NIN STEEL ALL-T STEEL ALL -THREAD. I/2' - l3 TPI I/2' - 13 TPI GRADE 5 0HDUMN) 1/2' - l3 TP GRADE 5 (MINIMIM) STEEL HEX NUT. FaOD CORNER GRADE 5 X N STEEL HE% NLENGTH STEEL HE% MST. SUPPLY PLEMM HANGING ANGLE t/2' WADE 5 (MWIM) STEEL HANGING ANGLE GRAD GRADE 5IWT GING ANGLE 1/2' WADE 5 (WEIGHT BEARING FLAT WASHER. (WEIGHT DEARING PNINMUN) STANCHOR HEARING P➢DVT (MDiIMIM) STEEL FLAT WASHER. ANCH➢R PDINT POINT FIR Hm FLAT WASHERHW MOD). FOR SU'PLY PLENUM). I/2' GRADE 5 t/2' GRADE 5 NINMUN) STEEL NMINIMUN) STEEL FLAT VASHER. RAT VASHER. 1/2'(NM WADE 5 (NMISTEEL - 13 TPI M - 13 TPI GRADE 5 FLAT WASHER. GRAD - 13 TPI GRADE STEEL HEX MIT. STEEL 5 X NUT. X NUTS. STEEL HEX NUTS. GRADE 5 UT IX N.N STEEL XNUT. ASSEMBLY INSTRUCTIONS ASSEMBLY INSTRUCTIONS ASSEMBLY INSTRUCTIONS HANGING ANGLE MUST BE SUPPORTED WITH 1/2' — 13 TPI GRADE 5 (MINIMUM) ALL —THREAD, SANDWICH HANGING ANGLES AND CEILING ANCHOR POINTS WITH 1/2' GRADE 5 (MINIMUM) STEEL FLAT WASHERS AND 1/2' — 13 TPI GRADE 5 (MINIMUM) HEX NUTS AS SHOWN. MUST USE DOUBLED HEX NUT CONFIGURATION BENEATH HOOD HANGING ANGLES AND ABOVE CEILING ANCHORS. MAINTAIN 1/4' OF EXPOSED THREADS BENEATH BOTTOM HEX NUT. TORQUE ALL HEX NUTS TO 57 FT—LBS. HANGING ANGLE MUST BE SUPPORTED WITH 1/2' — 13 TPI GRADE 5 (MINIMUM) ALL —THREAD. SANDWICH HANGING ANGLES AND CEILING ANCHOR POINTS WITH 1/2' GRADE 5 (MINIMUM) STEEL FLAT WASHERS AND 1/2' — 13 TPI GRADE 5 (MINIMUM) HEX NUTS AS SHOWN. MUST USE DOUBLED HEX NUT CONFIGURATION ABOVE CEILING ANCHORS. SINGLE HEX NUT BENEATH HANGING ANGLE IS ACCEPTABLE FOR FULL LENGTH HANGING ANGLES. MAINTAIN 1/4' OF EXPOSED THREADS BENEATH BOTTOM HEX NUT. TORQUE ALL HEX NUTS TO 57 FT—LBS. HANGING ANGLE MUST BE SUPPORTED WITH 1/2' — 13 GRADE 5 (MINIMUM) ALL —THREAD. SANDWICH HANGING ANGLES AND CEILING ANCHOR POINTS WITH 1/2' GRADI (MINIMUM) STEEL FLAT WASHERS AND 1/2' — 13 TPI GRADE 5 (MINIMUM) HEX NUTS AS SHOWN, MUST USE DOUBLED HEX NUT CONFIGURATION ABOVE CEILING ANCHORS. SINGLE HEX NUT BENEATH HANGING ANGLE I: ACCEPTABLE FOR PSP HANGING ANGLES. MAINTAIN 1/4' EXPOSED THREADS BENEATH BOTTOM HEX NUT. TORQUE ALL HEX NUTS TO 57 FT—LBS. TPI OF 36' L55 SERIES E26 CANOPY LIGHT FIXTURE - FIELD CUT EXHAUST RISER. � HIGH TEMP ASSEMBLY, INCLUDES CLEAR THERMAL \4/ AND SHOCK RESISTANT GLOBE (L55 FIXTURE). 16' CAPTRATE SOLD FILTER WITH HOOK, HOOD ❑M. 3' INTERNAL STANDOFF, IT IS THE RESPONSIBILITY OF THE ARCHITECT/OWNER TO ENSURE THAT THE HOOD CLEARANCE FROM LIMITED -COMBUSTIBLE AND COMBUSTIBLE MATERIALS IS IN COMPLIANCE WITH LOCAL CODE REQUIREMENTS. GREASE DRAIN WITH REMOVABLE CUP. FIELD INSTALLED QUARTER END PANELS, EQUIPMENT BY OTHERS. I + 71' SECTION VIEW MODEL 3650ELPX2 HOOD — #> (New Hood) L'VLTATTCT L'AAT TATL'n D1LATTn AT — Tnr) 14DA9-2D9 FAN UNIT TAG QTY FAN UNIT MODEL # MANUFACTURER CFM ESP RPM MOTOR HP BHP PHASE VOLT FLA DISCHARGE WEIGHT SONES NO ENCL VELOCITY (LBS) 1 EF-LOFT 1 DU85HFA CAPTIVEAIRE 2200 0.750 1408 TEAO-ECM 0.750 0.5060 1 208 5.2 696 FPM 93 15.1 2 EXH NEW 1 DU85HFA CAPTIVEAIRE 1200 1.200 1271) TEAO-ECM 0.750 0.3790 1 208 1 5.2 380 FPM 93 11.2 ,LTTTA FART TATFn R,LTATTn AT — .Tn P4dPd.9RR9 FAN MIN DESIGN MOTOR WEIGHT UNIT TAG QTY FAN UNIT MODEL # BLOWER HOUSING CFM CFM ESP RPM ENCL HP VOLT FLA MCA MOCP (LBS) SONES NO WIBHPPHASE 3 MAU COMMON I EA2-D.250-20D 20MF-2-MOD A2-D.250 2000 3060 0.500 1241 ODP,PREMIUM 1.500 3 208 6.6 8.3A 15A 668 10.7 /'AO L'TDL'n 11AVLl—TrD ATD TTATTm/QI FAN INPUT OUTPUT REQUIRED INPUT GAS BURNER UNIT TAG BTUs BTUs TEMP RISE PRESSURE GAS TYPE EFFICIENCY(%) NO 3 MAU COMMON 195437 179802 1 55•F 7 IN. W.C. - 14 IN. W.C. NATURAL 92 k'AAT nDTTn ATC' FAN UNIT NO TAG QTY DESCRIPTION 1 GREASE BOX. I FAN BASE CERAMIC SEAL - INSTALLED AT PLANT - FOR GREASE DUCTS. 1 EF-LOFT 1 ECM WIRING PACKAGE - EXHAUST - MODBUS CONTROL -MSC- (TELCO), CCW ROTATION. 1 2 YEAR PARTS WARRANTY. I GREASE BOX. 1 FAN BASE CERAMIC SEAL - INSTALLED AT PLANT - FOR GREASE DUCTS. 2 EXH NEW 1 ECM WIRING PACKAGE - EXHAUST - MODBUS CONTROL -MSC- (TELCO), CCW ROTATION. 1 2 YEAR PARTS WARRANTY. 1 MOTORIZED BACKDRAFT DAMPER FOR A2-D HOUSING. MEETS AMCA CLASS 1A RATING. 1 INLET PRESSURE GAUGE, 0-35'. 1 MANIFOLD PRESSURE GAUGE, -5 TO 15' WC. I LOW FIRE START. 3 MAU COMMON 1 AC INTERLOCK RELAY - 24VAC COIL. I SEPARATE 120V WIRING PACKAGE (REQUIRED AND USED ONLY FOR DCV OR PREWIRE WITH VFD) - THREE PHASE ONLY. I SIZE 2 DIRECT FIRED HEATER LOW CFM PROFILE PACKAGE. USED ON HEATERS UNDER 2500 CFM. 1 12 YEAR PARTS WARRANTY. VAAT A000VC'n DTWV FAN UNIT NO TAG EXHAUST SUPPLY GREASE CUP GRAVITY DAMPER WALL MOUNT SIDE DISCHARGE GRAVITY DAMPER MOTORIZED DAMPER WALL MOUNT 1 EF-LOFT YES 2 EXH NEW YES 3 MAU COMMON YES FANS #1 (EF-LOFT). #2 (EXH NEW) - DU85HFA EXHAUST FAN 3( I I 22 1/2 NN 2aDUCT KR SERWONN HOOD AND FAN (BY OTHERS). TOP VIEW 31 7/8 24 3/4 FEATURES, - DIRECT DRIVE CONSTRUCTION (NO BELTS/PULLEYS). - ROOF MOUNTED FANS. - RESTAURANT MODEL. - UL705 AND UL762 AND ULC-S645 - VARIABLE SPEED CONTROL. - INTERNAL WIRING. - THERMAL OVERLOAD PROTECTION (SINGLE PHASE). - HIGH HEAT OPERATION 300'F (149•C). - GREASE CLASSIFICATION TESTING. - NEMA 3R SAFETY DISCONNECT SWITCH. NORMAL TEMPERATURE TEST EXHAUST FAN MUST OPERATE CONTINUOUSLY WHILE EXHAUSTING AIR AT 300•F (149'0 UNTIL ALL FAN PARTS HAVE REACHED THERMAL EQUILIBRIUM, AND WITHOUT ANY DETERIORATING EFFECTS TO THE FAN WHICH WOULD CAUSE UNSAFE OPERATION. ABNORMAL FLARE-UP TEST EXHAUST FAN MUST OPERATE CONTINUOUSLY WHILE EXHAUSTING BURNING GREASE VAPORS AT 600'F (316'0 FOR A PERIOD OF 15 MINUTES WITHOUT THE FAN BECOMING DAMAGED TO ANY EXTENT THAT COULD CAUSE AN UNSAFE CONDITION. 11281111011 GREASE BOX. FAN BASE CERAMIC SEAL - INSTALLED AT PLANT - FOR GREASE DUCTS. ECM WIRING PACKAGE - EXHAUST - MODBUS CONTROL -MSC- (TELCO), CCW ROTATION. 2 YEAR PARTS WARRANTY. FAN #3 EA2-D.250-20D - HEATER (MAU COMMON) 1. DIRECT GAS FIRED HEATED MAKE UP AIR UNIT WITH 20' MIXED FLOW DIRECT DRIVE FAN. 2. INTAKE HOOD WITH EZ FILTERS. 3. DOWN ➢ISCHARGE - AIR FLOW RIGHT -) LEFT. 4. MOTORIZED BACK DRAFT DAMPER 22.75' X 24' FOR SIZE 2 STANDARD 6 MODULAR HEATER UNITS W/EXTENDED SHAFT, STANDARD GALVANIZE➢ CONSTRUCTION, 3/4' REAR FLANGE, LOW LEAKAGE, LF120S ACTUATOR INCLUDED. 5. GAS PRESSURE GAUGE, 0-35', 2.5' DIAMETER, 1/4' THREAD SIZE. 6. GAS PRESSURE GAUGE, -5 TO +15 INCHES WC., 2.5' DIAMETER, 1/4' THREAD SIZE. 7. LOW FIRE START. ALLOWS THE BURNER CIRCUIT TO ENERGIZE WHEN THE MODULATION CONTROL IS IN A LOW FIRE POSITION. S. COOLING INTERLOCK RELAY. 24VAC COIL. 120V CONTACTS. LOCKS OUT BURNER CIRCUIT WHEN AC IS ENERGIZED. 9. SEPARATE 120VAC WIRING PACKAGE FOR MAKE-UP AIR UNITS. OPTION MUST BE SELECTED WHEN MOUNTING VFD IN PREWIRE PANEL OR WITH DCV PACKAGE. PROVIDES SEPARATE 120VAC INPUT TO SUPPLY FAN. THIS 120V SIGNAL MUST BE RUN BY ELECTRICIAN FROM DCV TO MUA SWITCH. 10. PROFILE PLATE CONFIGURATION FOR SIZE 2 DIRECT FIRED UNIT FOR LOW CFM APPLICATIONS. 11. HINGED DOUBLE WALL INSULATED DOOR ASSEMBLY (BURNER/BLOWER SECTION). 12. 2 YEAR PARTS WARRANTY. -NOTE' SUPPLY DUCT MUST BE INSTALLED TO MEET SMACNA STANDARDS. A MINIMUM STRAIGHT DUCT LENGTH MUST BE MAINTAINED DOWNSTREAM OF UNIT ➢ISCHARGE AS OUTLINED IN AMCA PUHLICATIGN 201. WHEN USING RECTANGULAR DUCTWORK, ELBOWS MUST BE RADIUS THROAT, RADIUS BACK WITH TURNING VANES, FLEXIBLE DUCTWORK AND SQUARE THROAT/SQUARE BACK ELBOWS SHOULD NOT BE USED. ANY TRANSITION AND/OR TURNS IN THE DUCTWORK WILL CAUSE SYSTEM EFFECT. SYSTEM EFFECT WILL ➢RASTICALLY INCREASE STATIC PRESSURE AND REDUCE AIRFLOW. DO NOT RELY ON UNIT TO SUPPORT DUCT IN ANY WAY. FAILURE TO PROPERLY SIZE DUCTWORK MAY CAUSE SYSTEM EFFECTS AND REDUCE PERFORMANCE OF THE EQUIPMENT. SUGGESTED STRAIGHT DUCT SIZE IS 20' x 20'. a 18 SUPPLY SIDE HEATER INFORMATION' WINTER TEMPERATURE = 20'F. TEMP. RISE = 55'F. BTUs CALCULATED OFF ACTUAL AIR DENSITY. OUTPUT BTUs AT ALTITUDE OF 0.0 FT. = 179802. INPUT BTUs AT ALTITU➢E OF 0.0 FT. = 195437. 10' AIRFLOW. 3/4' 4— 1—T evz 1 5/8' •_'a"'�'T I 16' . x. v. uTrs xc rcsicrcv ra vvvm ram .an.Tm mw xm'm..n, FLE% CONDUIT "'F wsO4iII v vn aT owwc Cgl rc wW xm xm m�e x md°� OR FIELD WIRING. 135 7/8' 40 1/8' 42 1/8' FRVI� NECT36 3/4'ITCH.Q. ' FIRED MODULE. 39 9/16' AlFRaov. NPT. e MINIMUM 7 13/16' STRAIGHT DUCT PER AMCA- L--J I --I- MIN. 20' ® GREASE DUCT & CHIMNEY SPECIFICATI❑NS PR❑VIDE GREASE DUCT EQUAL TO EC❑N-AIR MODEL "EDW" ROUND 20 GAUGE 430 STAINLESS STEEL DUCTWORK, MODEL "EDW" IS LISTED TO UL-1978 AND IS INSTALLED USING "V" CLAMP L❑CKING C❑NNECTI❑NS SEALED WITH 3M FIRE BARRIER 2000 PLUS. MODEL "EDW" DOES NOT REQUIRE WELDING PR❑VIDING IT HAS BEEN INSTALLED PER THE MANUFACTURES INSTALLATI❑N GUIDE, PR❑VIDE RATED ACCESS DOORS AT EVERY CHANGE IN DIRECTI❑N AND EVERY 12' ON CENTER, PER MANUFACTURES LISTING MODEL "EDW" H❑RIZ❑NTAL RUNS LESS THAN 75 FT. CAN BE SLOPED 1/16" PER 12", H❑RIZ❑NTAL RUNS MORE THAN 75 FT. CAN BE SLOPED 3/16" PER 12". DUCT SHOULD BE SLOPED AS MUCH AS P❑SSIBLE TO REDUCE THE CHANCE OF GREASE ACCUMULATI❑N IN H❑RIZ❑NTAL RUNS, IF THE DUCT OR CHIMNEY IS WITHIN 18 INCHES OF C❑MBUSTIBLE MATERIAL, PR❑VIDE UL-2221 OR UL-103 HT LISTED DOUBLE WALL GREASE DUCT OR DOUBLE WALL CHIMNEY EQUAL TO EC❑N-AIR MODEL "EDW- 2R, 2R TYPE HT, 3R, OR 3Z" ROUND 20 GAUGE 430 STAINLESS INNER DUCT INSULATED WITH A 24 GAUGE 430 STAINLESS OUTER SHELL, CUSTOMER APPROVAL TO MANUFACTURE: APPROVED AS NOTED ❑ APPROVED WITH NO EXCEPTION TAKEN ❑ REVISE AND RESUBMIT ❑ SIGNATURE YOUR TITLE DATE FAN. HIGH TEMP GASKET TD SEAL THE FAN TRANSITION PLATE. =R DUCT IS FULLY WELDED TRANSITION PLATE, ALL RE DYE TESTED. VENTED CURB ROOF TERMINATION, TO THE OTHER. LISTEI Installation Wiring JOB 4842682 - Loft DRAWING NUMBER RP4842682-3 SHIP DATE 411412021 MODEL EA2-D.250-20D Installed Options 120 V 1 PH. 240 V 1 PH. 208/460/600 V 3 PH. Disconnect Disconnect Disconnect Switch Switch Switch Gal -flex Gal -flex Gal -flex conduit conduit 9- conduit (in unit) (in unit) (in unit) 9- 9- DCV Connections Factory Factory Factory wiring wiring wiring Field Wired Switch ® ® ® ® ® ® ® ® ® ® ® Customer Customer Customer )BK (WHrupplied BK RD GR supplied BK BK B R WH GR supplied wiring wiring wiring POWER FROM DEDICATED BREAKER Power Connection See above details, D3 IN HEATER TO IL1A IN DCV D7 IN HEATER TO IL1B IN DCV WIRE TO®\ o DCV �\ J16-5 & J16-6 ON MUA FIELD WIRED CONTACTS SFOI E BL-- WHEN USED WITH PREWIRE sFc1-U WIRE TO SFC1/SFO1 NOTES WIRE COLOR BK - BLACK YW - YELLOW BL - BLUE GR - GREEN BR - BROWN GY - GRAY OR - ORANGE PR - PURPLE RD - RED PK - PTNK WH - WHITE ELECTRICAL PACKAGE — JORJl4842682 SWITCHES FANS CONTROLLED NO TAG PACKAGE # LOCATION OPTION LOCATION QUANTITY FAN TAG I TYPE I 0 I HP VOLT1 FLA I LIGHT EF-Loft EXHAUST 1 0.750 208 5.2 1 ECP Common DCV-2111 WALL MOUNT IN SS BOX 05 - SS WALL SMART CONTROLS DCV EXH New EXHAUST 1 0.750 208 5.2 MOUNT BOX MAU Common SUPPLY 3 1.500 208 6.6 1 FAN DEMAND CONTROL VENTILATION HOOD CONTROL PANEL SPECIFICATIONS1 - CONTROLS SHALL BE LISTED BY ETL (UL 508A) AND SHALL COMPLY WITH DEMAND VENTILATION SYSTEM TURNDOWN REQUIREMENTS ❑UTLINED IN IECC 403.2.8 (2015). - THE CONTROL ENCLOSURE SHALL BE NEMA 1 RATED AND LISTED FOR INSTALLATION INSIDE OF THE EXHAUST HOOD UTILITY CABINET. THE CONTROL ENCLOSURE MAY BE CONSTRUCTED OF STAINLESS STEEL OR PAINTED STEEL. - TEMPERATURE PROBE(S) LOCATED IN THE EXHAUST DUCT RISER(S) SHALL BE CONSTRUCTED OF STAINLESS STEEL. - A DIGITAL CONTROLLER SHALL BE PROVIDED TO ACTIVATE THE HOOD EXHAUST FANS DYNAMICALLY BASED ON A FIXED DIFFERENTIAL BETWEEN THE AMBIENT AND DUCT TEMPERATURES SENSORS. THIS FUNCTION SHALL MEET THE REQUIREMENTS OF IMC 507.1.1. - A DIGITAL CONTROLLER SHALL PROVIDE ADJUSTABLE HYSTERESIS SETTINGS TO PREVENT CYCLING OF THE FANS AFTER THE COOKING APPLIANCES HAVE BEEN TURNED OFF AND/OR THE HEAT IN THE EXHAUST SYSTEM IS REDUCED. - A DIGITAL CONTROLLER SHALL PROVIDE AN ADJUSTABLE MINIMUM FAN RUN-TIME SETTING TO PREVENT FAN CYCLING. - VARIABLE FREQUENCY DRIVES (VFDS) SHALL BE PROVIDED FOR FANS AS REQUIRED. THE DIGITAL CONTROLLER SHALL MODULATE THE VFDS BETWEEN A MINIMUM SETPOINT AND A MAXIMUM SETPOINT ON DEMAND. THE DUCT TEMPERATURE SENSOR INPUTS) TO THE DIGITAL CONTROLLER SHALL BE USED TO CALCULATE THE SPEED REFERENCE SIGNAL. - THE VFD SPEED RANGE OF ❑PERATION SHALL BE FROM 0% TO 100% FOR THE SYSTEM, WITH THE ACTUAL MINIMUM SPEED SET AS REQUIRED TO MEET MINIMUM VENTILATION REQUIREMENTS. - AN INTERNAL ALGORITHM TO THE DIGITAL CONTROLLER SHALL MODULATE SUPPLY FAN VFD SPEED PROPORTIONAL TO ALL EXHAUST FANS THAT ARE LOCATED IN THE SAME FAN GROUP AS THE SUPPLY FAN. - THE SYSTEM SHALL OPERATE IN PREP MODE DURING LIGHT COOKING LOAD OR COOL DOWN MODE WHEN SUFFICIENT HEAT REMAINS UNDERNEATH THE HOOD SYSTEM AFTER COOKING ❑PERATIONS HAVE COMPLETED. OPERATION DURING EITHER OF THESE PERIODS WILL DISABLE THE SUPPLY FANS AND PROVIDE AN EXHAUST FAN SPEED THAT IS EQUAL TO THE MINIMUM VENTILATION REQUIREMENT, - A DIGITAL CONTROLLER SHALL DISABLE THE SUPPLY FAN(S), ACTIVATE THE EXHAUST FAN(S), ACTIVATE THE APPLIANCE SHUNT TRIP, AND DISABLE AN ELECTRIC GAS VALVE AUTOMATICALLY WHEN FIRE CONDITION IS DETECTED ON A COVERED HOOD. A DIGITAL CONTROLLER SHALL ALLOW FOR EXTERNAL BMS FAN CONTROL VIA DRY CONTACT (EXTERNAL CONTROL SHALL NOT OVERRIDE FAN ❑PERATION LOGIC AS REQUIRED BY CODE). - AN LCD INTERFACE SHALL BE PROVIDED WITH THE FOLLOWING FEATURES A. ON/OFF PUSH BUTTON FAN & LIGHT SWITCH ACTIVATION. B. INTEGRATED GAS VALVE RESET FOR ELECTRONIC GAS VALVES (N❑ RESET RELAY REQUIRED), C. VFD FAULT DISPLAY WITH AUDIBLE & VISUAL ALARM NOTIFICATION. D. DUCT TEMPERATURE SENSOR FAILURE DETECTION WITH AUDIBLE & VISUAL ALARM NOTIFICATION. E. MIS -WIRED DUCT TEMPERATURE SENSOR DETECTION WITH AUDIBLE & VISUAL ALARM NOTIFICATION. F. A SINGLE LOW VOLTAGE CAT-5 RJ45 WIRING CONNECTION. G. AN ENERGY SAVINGS INDICATOR THAT UTILIZES MEASURED KWH FROM THE VFDS, DUCT ROOM TEMPERATU SENSOR. TYPICAL HOOD CONTROL PANEL INSTALLATION SEQUENCE OF ❑PERATIONS1 THE HOOD CONTROL PANEL IS CAPABLE OF OPERATING IN ONE OR MORE OF THE FOLLOWING STATES AT ANY GIVEN TIME: - AUTOMATIC: THE SYSTEM OPERATES BASED ON THE DIFFERENTIAL BETWEEN ROOM TEMPERATURE AND THE TEMPERATURE AT THE HOOD CAVITY OR EXHAUST DUCT COLLAR. FANS ACTIVATE AT A CONFIGURABLE TEMPERATURE DIFFERENTIAL THRESHOLD. DEPENDING ON THE JOB CONFIGURATION EACH FAN ZONE CAN BE CONFIGURED AS STATIC OR DYNAMIC, THESE TERMS REFER To WHETHER A VARIABLE MOTOR (SUCH AS EC MOTORS OR VFD DRIVEN MOTORS) MODULATE WITH TEMPERATURE. IF THE PANEL IS EQUIPPED WITH VARIABLE SPEED FANS AND THE ZONE IS DEFINED AS 'DYNAMIC', THESE WILL MODULATE WITHIN A USER -DEFINED RANGE BASED ON THE TEMPERATURE DIFFERENTIAL. PANELS EQUIPPED WITH VARIABLE SPEED FANS AND A FAN ZONE DEFINED AS 'STATIC', FANS WILL RUN AT A SET SPEED CALCULATED FOR THE DRIVE. DEMAND CONTROL VENTILATION SYSTEMS ARE CAPABLE OF MODULATING EXHAUST AND MAKE UP AIR FAN SPEEDS PER THE REQUIREMENTS OUTLINED IN IECC 403.2.8. - MANUAL; THE SYSTEM OPERATES BASED ON HUMAN INPUT FROM AN HMI. - SCHEDULE:A WEEKLY SCHEDULE CAN BE SET TO RUN FANS FOR A SPECIFIED PERIOD THROUGHOUT THE DAY. THERE ARE THREE OCCUPIED TIMES PER DAY TO ALLOW FOR THE USER TO SET UP A TIME THAT IS SUITABLE TO THEIR NEEDS. ANY TIME THAT IS WITHIN THE DEFINED OCCUPIED TIME, THE SYSTEM WILL RUN AT MODULATION MODE AND FOLLOW THE FAN PROCEDURE ALGORITHM BASED ON TEMPERATURE DURING THIS TIME. DURING UNOCCUPIED TIME, THE SYSTEM WILL HAVE AN EXTRA OFFSET TO PREVENT UNINTENDED ACTIVATION OF THE SYSTEM DURING A TIME WHERE THE SYSTEM IS NOT BEING ❑CCUPIED, - OTHER, THE SYSTEM OPERATES BASED ON THE INPUT FROM AN EXTERNAL SOURCE (DDC, BMS OR HARD -WIRED INTERLOCK). - FIRE; UPON ACTIVATION OF THE HOOD FIRE SUPPRESSION SYSTEM, THE EXHAUST FAN WILL COME ON OR CONTINUE TO TO RUN, THE HOOD MAKEUP AIR WILL SHUTDOWN, AND A SIGNAL WILL BE SENT FOR ACTIVATING THE SHUNT TRIP BREAKER PROVIDED BY THE ELECTRICIAN. FUEL GAS WILL SHUT OFF VIA A MECHANICAL/ELECTRICAL GAS VALVE ACTUATED BY THE HOOD FIRE SUPPRESSION SYSTEM. JOB NO (MODEL NUMBER `' errand (DRAWN BY (SCHEMATIC TYPE DESCRIPTION OF OPERATION' 4842682 JOB NAME DC V -2111 INSTALL ➢ DATE DWG NO moControl Ventilation, w/ control for 2 Exhaust Fans, 1 Supply Fan, Exhaust on In Fire, Lights out In Fire, Fan dulate based on duct temperature. INVERTER DUTY 3 PHASE MOTOR REQUIRED FOR USE WITH VFD. Room temperature nsor shipped loose for Field Installatlon.VerIfy distance between VFD and Motors additional cost could apply IF Loft - Fans and Controls - R2 4/14/2021 ECP #1-1 distance ex.peeds sD feet. I 2 BREAKER PANEL TO PRIMARY CONTROL PANEL Responsibilityi Electrician 3 BREAKER SIZE SHOWN IS THE MAXIMUM ALLOWED _ BREAKER PANEL PRIMARY CONTROL 4 Hot —_� BREAKER IPH _Neu{rnl 120 V _ _ —Gro—I — GND 5 15 A CONTROL POWER. DO NOT WIRE TO GFCI OR SHUNT TRIP - BREAKER. 6 1ST HOOD LIGHT BREAKER SHARED W/ CONTROL POWER. SWITCH #1 _ 7 BREAKER 3PH LINE _ —LINE — 208 V LINE MCA- 8.2 A — — — — — — — — — Goounntl _ GND 6 MOCP, 15 A MAUCommon SM-1 WIRE TO VFD QUICK CONNECTOR 9 10 BREAKER PANEL TO FANS Responsibility, Electrician 11 BREAKER PANEL FANS ----------------LINE —_ — 12 BREAKER IPH ________ _----LINE --POWER TO 208V -------------------- Ground ECM FANS MCA- 6.5A EF-Loft 13 MOCP, 15A LINE 14 BREAKER IPH -------------------- LINE POWER TO 208V ---------- Ground ---------- ECM FANS _ MCA, 6.5A EXH New 15 MOCP, 15A 16 17 CONTROL PANEL TO FANS Responsibility, Electrician 18 PRIMARY PANEL FAN, 03 19 Load Wiring Ul _—LOAn �Er=l-- _ ® BLACM SM-1 V1 — Lon LEG 2-- — ® BLACM WIRE TO _ LOAD LEG 3— _ ® BLACM 20 VFD QUICK -- 1120VNOT-- _ ® REI CONNECTOR N1 —120V NEUTRAL-- — ® WHIT E GAIT GR --—OUND -- — ® MEE! 41 IF VFD MOUNTED IN 2ND PANEL, MUST HAVE ITS OWN CONDUIT WIRE SF SIGNAL DO NOT SHARE CONDUITI FROM PANEL WITH 22 ECPM03. 1 II 23 1 1124 REMOVE JUMPER MAKE UP AIR ON PCB MUA ZONE 1 DAMPER D3 PROVING ------------ INTERLOCK LOW VOLTAGE CONNECTION FOR TERMINAL NAMES DAMPER INTERLOCK, WIRE DO NOT APPLY MULTIPLE SUPPLY ON THE SAME IF MUA BY OTHERS ZONE IN SERIES. SHOULD HAVE CONTINUITY WHEN DAMPER IS PROVEN OPEN. NOT REQUIRED FOR ALL UNITS. SEE MAKE-UP AIR SCHEMATIC. CONTROL PANEL TO ACCESSORY ITEMS Responsibilityi Electrician MICROSWITCH 1 :ONTROL PANEL TO — — — — — — — — — — — — — — '�. 94,NO Epp IGY 1NC FIRE SYSTEM AR1 -------------- ----J MICROSWITCH WIRE Cl TO COMMON Cl). WIRE AR1 TO NORMALLY CLOSED (2). Cl TO AR1 SHOULD HAVE MS-1 *NO CAP CONTINUITY WHEN ARMED, I,NC 1 - - - - IF MORE THAN ONE FIRE SYSTEM, WIREIF__ IN SERIES AS SHOWN r - MS-2 4,N0 oFF n01 L— — — — — — — — — — — — — — — — — — — J :ONTROL PANEL J 4 ALL SWITCHES FACTORY WIRED TO CAT-5 CONNECTION SWITCHES HOOD LIGHTS 1 :ONTROL PANEL — — — — — — — — — — — BLACK _ TO Lvi ___________ WHITE --- HOOD LIGHTS GND— — — — — — — — — — — GREEN_ ----J 1400 W MAX WIRE TO J-BOX ON TOP OF HOOD :ONTROL PANEL T1A- - - - - - - - - - - - - - --- E;� TO 11B WIRE TO CONTROL BOARD. INSTALL — J 'ITCH TO TEMP ROOM TEMP SENSOR IN ROOM AWAY FROM HEAT SENSOR SOURCES. DO NOT INSTALL SENSOR ON THE CEILING GRID, SEE MANUAL. T 208 V �DUCTCONTROL � SENSOR 6.6 TOT2B SENSOROMOUNTEDLIN OEXHAUST DUCT RIS�ER1 :ONTROL PANEL �7 TO ---- — J WIRE TO CONTROL BOARD. SHIP LOOSE DUCT SENSOR SENSOR MOUNTED IN EXHAUST DUCT DUCT STAT -ONTROL PANEL T4A TO WIRE TO CONTROL BOARD. SHIP LOOSE DUCT SENSOR ISENSOR MOUNTED IN EXHAUST DUCT DUCT STAT ONTROL PANEL JS J7 r J8 IF MORE THAN ONE MSC IS PRESENT TO WIRE IN SERIES BY MEANS OF r — MSC J7 AND J8 CAT-5 JACKS. DO NOT MS EXCEED 5 MSC BOARDS ON ONE J7 J8 ECPM03 JACK. THE FOLLOWING CONNECTIONS MAY OR MAY NOT BE REQUIRED BASED ON JOBSITE SPECIFICATIONS _ _ _ _ _ HOT TO SHUNT COIL SHUN COIL SIGNAL FOR N1 ONTROL PANEL ST NEUTRAL FROM SHUNT COIL - - 7 SIGN - - - - - - EXTERNAL ST TERMINAL IS ENERGIZED SHUNT TRIP IN FIRE CONDITION. C ONTROL PANEL K$ - - - HOT ONTAR_COIL HOT -TO -CONTACTOR -COIL - SIGNAL FOR N1 _ NEUTRAL TO CONTACTOR COIL — — — — — EXTERNAL KS TERMINAL IS DE -ENERGIZED ONTACTOR COIL IN FIRE CONDITION. ONTROL PANEL C2 Cy_ _ _ _ _ _ _ _ _ _ COMMON — SPARE FIRE A _PARE _ _ CON_ T_ ACT_S _ WILNO_RML _MAKE C2 TOALLY OPEN S— _ SYSTEM DRY AR2 WHEN SYSTEM IS ARMED. THEY CONTACT ARE USED_TO DISABLE EQUIPMENT ILINI KUL YAINLL Jt LI-------------- -- DRY CONTACT - - - - - - - NORMALLY OPEN ON/OFF WITH SFu - - - - - - - - - - - COMMON - SUPPLY FAN _ _ _ _ _ _ NORMALLY OPEN GROUP 1 SPARE CONTACTS WILL MAKE COMMON TO NORMALLY OPEN WHEN SUPPLY FAN IS ON. DCV SPEED + + -------------- -TO EMS ON P 7-I0V OUTPUT WIRE TO ECPM03 TERMINALS ON PCB CONFIGURABLE OUTPUT. (TOTAL) SEE ECPM03 OWNERS MANUAL. VFD ANALOG - - - - - - - - - - - - - - + - TO EMS 7-IOV OUTPUT 2- - - - - - - - - - - - - - - IN VFD WIRE TO VFD TERMINAL STRIP. PROPORTIONAL TO FREQUENCY. (EACH VFD) SEE VFD OWNERS MANUAL. EMS SWITCH ,ONTROL PANEL H1- - - - - - - - — — — — — — —co-CNO TO I01- - - - - - - - - - - - - - ----J EXTERNAL SIGNAL SWITCH THROUGH EMS WILL ACTIVATE ZONE1 FANS AND SWITCH LIGHTS UNLESS SPECIFIED OTHERWISE, ALL FACTORY AC WIRING 16 AWG. ALL FACTORY DC WIRING 18 AWG. 1 J9 120V 1 WH z -- CONTROL INPUT 120V BK _ H1=LINE, N1=NEUTRAL, 15A BREAKER. DO NOT 3 CONNECT TO SHUNT TRIP = ® BREAKER. SEE s + 2 KS aK — — INSTALLATION 24V SCHEMATIC -- FOR ADDITIONAL REQ, PS-ol DC TERMINAL GAS USED FOR 1 N L AC BK 120V POWERED GAS - — — VALVES ONLY PANEL LID Ii G�-- zz= 3 w J7 120V FTni 1 BK BK 14AWG R -b _ BK -Hl BK �NI 5 EFl 3 BK HOOD GHTS�-r���JUMPER 4 BK ❑V1 6 DC+ BL g RD ROl 7 MAKE UP AIR INTERLOCK. JUMP R 8 �J10 J10 ECPM03 ECPM03 9 24 ARI SF1 EFI EF1 BK F N WH SECONDARY PANEL COOLING IF NEC NOTE- All items on ECPM03 J3 line to be daisy chained from one component to the next, with EOL120A at end of line. Pace PN, EOL120A in empty RJ45 port. ECPM03/DAISY CHAIN mm ,o�x 1 moor �oart 11 MSC-01 MSC-02 1 M-1 J7 0 ICI — J J8 — J J8 MOTOR POWER CIRCUIT NOTE- IF VFD HAS 1PH 240V INPUT, USE L1 & L2 ONLY IF VFD HAS 1PH 120V INPUT, USE L1 & N ONLY. MTR:MAUCommon 14 AWG FLA:6.6 3 PH BK O BK U/TI HPi1.500 208 V BK BK V/T2 P100: 01 PIOIiN/A 15 A BK GR W/T3 P102:0.0 GR P10301.8 GND BK BK L1 P107100 BK BK L2 P108:94 P131-N/A BK BK L3/N P150:01 O P167- 71.8 VFD- ESV152NO2YXB57V94, 225 410 21 DRY CONTACTS (SHOWN DE -ENERGIZED) 14 AWG RA-1-1 ON/OFF - — WITH FD3E C YW 14 AWG RA-2-1 ON/OFF _ — NO° WITH C YW SUP 14 AWG RA-2-2 — �O C YW 81 11Morgan CAdvanced Materials Datasheet Code US: 714-236 © 2014 Thermal Ceramics is a business of Morgan Advanced Materials UL QDL 'J VALIDATED ✓ FIREMASTER FASTW RAP XL IS A LOW VOC EMITTING MATERIAL PER CA SECTION 01350 ✓ FIREMASTER FASTWRAP XL IS MOLD RESISTANT PER ASTM C1338-01 Commonly referred to test method CA Section 01350 is CDPH Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers Version 1. 1, Feb 2010 Grease Duct Enclosure System Air Ventilation Duct Enclosure System Product Data & Installation Guide 1. Product Description Thermal Ceramics FireMaster° FastWrap XL is a flexible blanket composed of high temperature fibers classified for applications to 2192°F (1200°C) and fully encapsulated in a durable glass fiber reinforced foil facing for easy handling and installation. Thermal Ceramics FastWrap XL is UL and ULC Listed for 1 and 2 hour fire resistive enclosure protection, zero clearance for kitchen exhaust ducts, electrical circuit protection, and as a component in UL firestop designs for fire resistance rated floors, ceilings, and walls. The core fibers in FastWrap XL are manufactured using Thermal Ceramics patented SuperwoW fiber which is an alkaline -earth silicate wool with low biopersistence and therefore increased safety for installers. FastWrap XL is under UL's Follow -Up Service Program to ensure the consistent quality essential to this life -safety application. f/R"SIER Product Features • Thin and Lightweight at 1-1/2" (38mm) thick, 6 pcf (96 kg/m3) density • Contours easily to complex duct designs • Grease duct installation UL and ULC Listed with butt joints at all seams on both layers • Fully foil encapsulated for fast and clean installation • Contains 2192°F (1200°C) rated fibers • Microbial Resistance validated by UL Environment • Good sound absorption • Compliant to IMC, NFPA 96, UMC, CMC, CNBC 2. Applications • 2 hour enclosure and firestop system for kitchen exhaus duct • Zero clearance to combustibles • 1, 2 and 3 hour enclosure and firestop system for hazardous exhaust ducts, pressurization ducts, clothes dryer exhaust ducts, trash and linen chutes, and other fire rated HVAC ducts • 1 hour electrical circuit integrity protection • Engineered and tested solutions for fire protection of structural steel and storage vessels per ASTM E119, ISO 834, and UL1709 3. Specifications - Division 23 07 00 (or 15080) CSI Spec and AutoCAD available online, www.arcat.com/sd/clients/thermcer.html. Thermal Ceramics FireMaster FastWrap XL is a flexible high temperature insulation rated to 2192°F (1200°C) that is fully encapsulated in FSP facing. The duct enclosure system shall be listed by UL and /or ULC per ASTM E 2336, CAN/ULC S144 and ISO 6944 for 1-, 2- and 3-hour rating and zero clearance to combustibles, and tested per ASTM E84 for a flame/ smoke rating less than 25/50. Insulation shall have a nominal thickness of 1-1/2 inches (38 mm) and density of 6 Ibs/ft3 (96 kg/m3). Insulation shall have a R-Value of 7.3 at 75°F. Installation shall be in strict accordance to manufacturers published installation instructions, UL or ULC Listings, and shop drawings. FastDoorTM XL shall be used for duct access where specified or as required by code. FOR REFERENCE ONL Y www.morganthermalceramics.com 12:2014 Page 1 of 8 11Morgan CAdvanced Materials 4. Physical Characteristics Units/ Wt./ Product Unit Size Ctn. Ctn. FastWrap XL Roll 1-1/2" x 24" x 25' 1 37.5 lbs. FastWrap XL Roll 1-1/2" x 48" x 25' 1 75 lbs. 5. Performance Specifications Reference Standard Standard No. Performance Grease Duct Enclosure ASTM E2336 Pass System Section 16.1 - ASTM E136 Pass Non -Combustibility Section 16.2-Fire Resistance ASTM E119 Pass (wall) Section 16.3 - Durability Test ASTM C518 Pass Section 16.4 - Internal Fire ASTM E2336 Pass Test Section 16.5 - Fire Engulfment ASTM E814/ Pass (duct) E 119 ULC Grease Duct Test Pass Protocol Standard Methods of Fire CAN/ULC Resistance Tests - Grease Pass S144 Duct Assemblies Grease Duct Clearances UL 1978 Pass Air Ventilation Duct Enclosure ISO 6944 Pass Surface Burning ASTM E84 <25/50 Characteristics Thermal Resistance ASTM C518 7.3 per layer (R-value @ 75°F) Mold Growth ASTM C1338 ULE Validated CA Standard Low VOCs 101350 ULE Validated FOR REFERENCE ONLY] 6. Listings/Building Code Reports Listed Uses Agency Listing Layers Grease Duct Enclosure per UL G18 ASTM E2336 and AC101 (2006, 2 2009, 2012 IMC, NFPA 96, ICC-ES ESR 2213 UMC, CMC) ULC Grease Duct Test Protocol ULC FRD 4, 7* 2 and CAN/ULC S144' Grease Duct Insulation OPL TC/BI 120-01 1 (2003 IMC) Through Penetration FireStop UL System per ASTM E814, See Figure 2 1 or 2 UL 1479 ULC UL HNLJ.V1, 1- or 2-hour Ventilation Duct 19,29 1 FRD 3, 5, Enclosure per ISO 6944-1985 ULC 6, 18 3-hour Ventilation Duct UL HNLJ.V2 2 Enclosure per ISO 6944-1985 Electrical Circuit Protective UL FFHIT.5 2 System 7. Storage Thermal Ceramics FastWrap XL must be stored in a dry warehouse environment on pallets. Pallets should not be stacked. 8. Installation Thermal Ceramics FastWrap XL shall be installed by a qualified contractor in accordance with manufacturer's instructions and laboratory design listings. Materials and Equipment • Thermal Ceramics FastWrap XL blanket • Aluminum foil tape • Glass filament reinforced tape (optional) • Carbon steel or stainless steel banding material, minimum 1/2" (13mm) wide, minimum 0.015" (0.4mm) thick, with steel banding clips • Hand banding tensioner and crimping tool • Minimum 12 gage (3mm) steel insulation pins; steel speed clips, minimum 1-1/2" (38mm) square or 1-1/2" (38mm) diameter, or equivalent sized cup -head pins; • Capacitor discharge stud gun • Thermal Ceramics FastDoorTM XL • An approved firestop sealant www.morganthermalceramics.com 12:2014 Page 2 of 8 11Morgan CAdvanced Materials General Cut edges of the blanket shall be taped with aluminum foil tape to prevent exposed edges of the insulation absorbing grease and moisture in the event of a compromised grease duct joint or condensation. Overlaps and/or tightly butted joints are used to block heat transfer in the event of duct deformation resulting from thermal expansion. Filament tape is suggested to hold the blanket in place until steel banding or pinning is installed to permanently secure the blanket. A. Installation on Grease Duct per ASTM E2336 and CAN/ULC S144 (Figure 1) System requires two layers of insulation applied directly to the duct with tight butt joints at all seams on both layers. The first layer of insulation is cut to a length sufficient to wrap around the duct and provide a tight butt joint where the blanket ends meet. Adjacent blankets on the first layer are butted tightly together with longitudinal seams offset minimum 6" (150mm). The second layer of insulation is installed in the same method as the first layer, with seams between layers offset a minimum of 6" (150mm). Banding and/or pinning per Section D is used to permanently secure the insulation to the duct. B. Installation on HVAC Duct per ISO 6944 (Figure 1) System requires one layer of insulation applied directly to the duct with 3" (75mm) overlaps at all seams. The insulation is cut to a length sufficient to wrap around the duct and provide a 3" (75mm) overlap where the blanket ends meet. Adjacent blankets are installed to provide a minimum overlap of 3" (75mm). Banding and/or pinning per Section D is used to permanently secure the insulation to the duct. C. 2 & 3 Sided Wrap Installation (Figure 4) When space does not allow for a complete wrap applied to the duct on all four sides, the FastWrap XL is approved for 2 or 3 sided installations with mechanical attachment to a rated concrete or CMU assembly. (See Figure 4 for installation details.) D. Mechanical Attachment Methods 1) Banding (Figure 1) - Minimum 1/2" (13mm) wide carbon steel or stainless steel banding, 0.015" (0.4mm) thick, is placed around the entire perimeter of the insulated duct on maximum 10-1/2" (270mm) centers and 1-1/2" (38mm) from each blanket edge or 1-1/2" (38mm) from each collar edge when using the butt joint FIFA#411701rp and collar method. The banding is placed around the blanket and tightened to firmly hold the FastWrap XL in place against the duct, but not cause any cutting or damage to the blanket. 2) Pinning - Pinning on all sides of the duct may be used as an alternative to banding. For ducts wider than 24" (610mm) pinning is required on the bottom of horizontal runs, or on one side of vertical runs (in addition to steel banding). When applicable, 12 Gage (0.4mm) steel pins are installed on 12" (305mm) centers along the width of the duct and 10-1/2" (270mm) centers along the length of the duct. Pins that extend beyond the outer blanket layer shall be turned down or the excessive length cut off to prevent sharp edges. Shoot through pins (cup head pins) may be used in conjunction with steel banding to prevent blanket sag. E. Access Doors 1) FastDoor TM XL (Figure 3) - FastDoor XL is a UL Listed, liquid tight duct cover panel supplied complete with a single layer insulation cover per UL Listing HNKT G18. The FastDoor XL is installed per included installation instructions. No field welding is required. 2) Field Fabricated Access Doors - Each access door assembly has four threaded rods 1/4 inch (6mm) in diameter and 5" (127mm) in length, with one welded to each corner of the door opening. Hollow steel tubes, 4-1/2" (114mm) long are installed outside the access cover plate and over the threaded rods. Four 12 gage (3mm) and 4-1/2" (114mm) long steel insulation pins are welded to the access cover plate to allow for installation of the three layers of FastWrap XL. One layer of FastWrap XL is cut to approximately the same size as the access panel, and impaled over the insulation pins on the panel. A second layer of FastWrap XL is cut so as to overlap the first layer a minimum of 1-1/2" (38mm). It is essential that the first and second layer fit tightly against the surrounding wrap with no through openings. The third and outside layer should be cut to overlap the second insulation layer by a minimum of 1-1/2" (38mm). Minimum 1-1/2" (38mm) round or square insulation clips are installed on the insulation pins to secure the three layers of insulation to the access cover plate. All cut edges of the insulation shall be taped with minimum 3" (75mm) wide aluminum foil tape. Wing nuts and washers are installed on the four threaded rods, and tightened against the hollow steel tubes to seal the FOR REFERENCE ONLY www.morganthermalceramics.com I ] 12:2014 Page 3 of 8 11Morgan CAdvanced Materials access cover plate to the duct. F. Through Penetration Firestop System (Figure 2) - When the duct penetrates a fire rated assembly an approved fire stop system must be employed. Figure 2 provides a complete list of UL / ULC firestop design listings which can be found in the Certifications Directory at www.ul.com for US systems and www.ulc.ca for Canadian systems. Prior to installing any firestop system the surfaces of all openings and penetrating items must be clean and dry. The FastWrap XL core blanket (or mineral wool where allowed by the firestop design listing) must be compressed into the annular space. The packing material must be recessed a minimum depth from the surface of the concrete or gypsum assembly. The recessed opening must be filled with a minimum thickness of an approved firestop sealant. The packing material type and compression, minimum recess (typically 1/4" (6mm)), and approved firestop sealant and thickness (typically 1/4" (6mm)) shall be as specified in an approved UL / ULC firestop design listing. When there is not sufficient annular space around the duct to run the FastWrap XL enclosure system continuous through the fire rated assembly, the enclosure may terminate above and below the floor/ceiling assembly or on either side of a wall assembly as shown in Figure 2. When this method is used, the FastWrap XL must be mechanically attached on either side of the fire rated assembly using one of the attachment methods described in Section D, spaced a maximum of 1-1/2" (38mm) from the fire rated assembly. G. Support Hanger Systems 1) Grease ducts: Trapeze support hangers shall be spaced on maximum 60 in. (1500 mm) centers. Hanger rods or straps shall be anchored with steel drop in or wedge expansion type masonry anchors. No additional protection is required for hangers and supports meeting the requirements of the Table below. Hanger Cross Maximum Trapeze Support (or Section Perimeter, in (mm) equivalent Yield Strength), in mm 3,8 in (10 mm) threaded rod 148 (3759) 2 (51) x 2 (51) x 1,8 (3) in angle 2) HVAC ducts: Trapeze support hangers shall be spaced on maximum 60 in. (1500 mm) centers. Hanger rods or straps shall be anchored with steel drop in or wedge expansion type masonry anchors. No additional FIFA#41170rp protection is required for hangers and supports meeting the requirements of the Table below. Max. Perimeter, Trapeze Support (or Hanger Cross Section in (mm) equivalent Yield Strength), in (mm) 1 in x 16 gage strap 100 (2540) (25 mm x 1.5 gage strap) 14 in (6 mm) threaded rod 50 (1270) 1Yz (38) x V (38) x 316 (5)angle 36 in (10 mm) threaded 150 (3810) 1 % (38) x V (38) x 316 (5) rod le angle 12 in (12.7 mm) threaded 218 (5540) 2 (51) x 2 (51) x 1/4 (6) angle rod 9. Maintenance and Repair No maintenance is required when installed in accordance with Thermal Ceramics (TC) installation instructions. If damage is limited to the foil facing, aluminum foil tape can be used to repair the foil facing. If an area of blanket is found to be damaged the following procedure must be in- corporated. If the damaged area is larger than 8" (203mm) x 8" (203mm) the entire wrap section must be removed and replaced according to TC installation instructions. If the damaged area is small (less than 8" (203mm) x 8" (203mm)), the damaged area must be cut away and replaced with a new section 1" (25mm) larger in length and width than the cut out, such that the new section can be compressed tightly into the cut out area. All cut edges of the new section must be taped and sealed with aluminum foil tape. The new section must be held in place with either pinning or banding per TC installation i nstructions. 10. Limitations Thermal Ceramics FireMaster FastWrap XL shall be installed in accordance with these installation instructions and appropriate laboratory design listings. The integrity of FastWrap XL systems is limited to the quality of the installation. For personal protective equipment recommendations, please see SIDS. Thermal Ceramics, FireMaster, and FastWrap are trademarks of Morgan Advanced Materials. FireMaster products are manufactured by Thermal Ceramics and are distributed by authorized distributors. FOR REFERENCE ONL Y www.morganthermalceramics.com 12:2014 Page 4 of 8 11Morgan CAdvanced Materials f/IPf�gSIER mom Grease and HVAC Duct Enclosure System 1 or 2 Hour Shaft Alternative / Zero Clearance to Combustibles z 71/2' 38 3 Butt Joint / Butt Joint Typical s TWO LAYER INSTALLATION (Grease Duct DerASTM E2336 and CAN/ULC S144) Telescope Wrap Option Butt Joint Option Checkerboard Wrap Option SINGLE LAYER INSTALLATION OPTIONS (2-Hour rated HVAC Duct per UL HNLJ V-19) LEGEND 1 Two Layers of XL Insulation for ASTM E2336 and CAN/ULC S144 Grease Duct Enclosures One Layer of XL Insulation for 2-Hour Air Ventilation Duct Enclosures 2 Steel banding minimum 1/2" 13 wide by 0.015" 0.4 thick. 3 Tight butt joints no overlap) at perimeter and longitudinal joints, both layers for grease ducts 4 Min. 3" 75 overlap on perimeter and between adjacent blankets 5 Optional 6" XL collar 6 Hangers - size dependent weight of assembly see datasheet Section G 7 ez Tra e Suorts - size dependent on weight of assembly see datasheet Section G 8 1 Steel Rectangular or Round Duct size, gage and construction dependent per Listed Design) The integrity of Thermal Ceramics duct systems is limited to the quality of the installation. XL001-10 FOR REFERENCE ONL Y www.morganthermalceramics.com 12:2014 Page 5 of 8 11Morgan CAdvanced Materials FIRF, gM FireMaster° FastWrap° ) Commercial Kitchen Grease Duct Enclosure System Air Ventilation Duct Enclosure System Through Penetration Firestop Systems XL Insulation continuous through rated wall assembly XL insulation terminated on both sides of the rated wall assembly XL Insulation continuous through rated floor/ceiling assembly Packing XL insulation terminated at the top and boftorr surface of the floor/ceiling assembly Firestop Designs perASTM E814 / UL 1479 -Consult UL / ULC Directories for System Details UL Listing F- & T-Ratio 1 Floor/Wall 2 Penetrant 3 Enclosure Per 4 Termination 5 Firestop Sealant Details C-AJ-7012 2-hour Concrete/CMU 84x24; 26 Ga Duct V19; FRD3; 5; 18 wrap through 1/2 in; STI; Tremco C-AJ-7014 3-hour Concrete/CMU 84x24; 26 Ga Duct V2; wrap through 1/2 in; STI; Tremco C-AJ-7019 1 or 2-hour Concrete/CMU 84x24; 26 Ga Duct V19; FRD3, 5, 18 terminate at 1/4 in; STI; Tremco C-AJ-7021 2-hour Concrete/CMU 49x24; 16 Ga Duct G18; FRD4; 7 terminate at 1/4 in; STI; Tremco C-AJ-7095 2-hour Concrete/CMU 39x39; 22 Ga Duct V19; FRD3, 5, 18 wrap through 1/4 in; STI Hilti; Rectorseal; Tremco C-AJ-7098 2-hour Concrete/CMU 49x24; 16 Ga Duct G18; FRD4; 7 wrap through 1/4 in; STI; Hilti; Rectorseal; Tremco F-C-7036 1 or 2-hour Wood/Gyp Floor 24x12; 16 Ga Duct G18; FRD4; 7 wrap through 1/4 in; STI; Hilti; Rectorseal; Tremco F-C-7055 1-hour Wood/Gyp Floor 4 Dia; 30 Ga Duct V29; FRD28 wrap through 1/4 in; STI W-J-7086 2-hour Concrete/CMU Wall 100x100; 26 Ga Duct V19; FRD3;5; 18 terminate at 1/4 in; STI W-L-7121 1 or 2-hour Gyp Wall 30x30; 16 Ga Duct G18; FRD4; 7 wrap through 1/4 in; STI; Hilti; Rectorseal; Tremco W-L-7145 1 or 2-hour Gyp Wall 100x100; 26 Ga Duct V19; FRD3; 5; 18 terminate at 5/8 in; STI The integrity of Thermal Ceramics duct systems is limited to the quality of the installation. XL003-5 FOR REFERENCE ONL Y www.morganthermalceramics.com 12:2014 Page 6 of 8 11Morgan CAdvanced Materials 4 %f ref r� �f ref ref ref ref ref r ref ref f ASTM E 2336 Compliant Enclosure and Door System FIGURE 3 1 UL listed FastDoor XL access panel 2 All Thread Rods and wing nuts 3 Retainer Clips with threaded nut and wing bolts 4 Insulation layers as required by UL or ITS Listings 5 FastDoor XL; 1-1/2 inch thick single layer insulation f/IP"STER FastDoor XL1 Access Doors Sizes Available Opening Sizes Ordering Code 10" x 4" Door Opening '434-6970-033-99X1 10" x 6" Door Opening 434-6970-034-99X1 12" x 8" Door Opening 434-6970-035-99X1 12" x 12" Door Opening 434-6970-036-99X1 16" x 12" Door Opening 434-6970-037-99X1 20" x 20" Door Opening 434-6970-038-99X1 —*Special Order; Curved and SS Available FOR REFERENCE ONL V www.morganthermalceramics.com 12:2014 Page 7 of 8 11Morgan CAdvanced Materials f/R"47ER Im Commercial Kitchen Grease Duct Enclosure System Air Ventilation Duct Enclosure System 1 Or 2 Or 3 Hour Shaft Alternative / Zero Clearance to Combustibles 2 and 3 Sided Wrap Detail for Attaching to Walls and/or Ceilings Note: Ducts must be independently supported per code LEGEND 1 Rated Concrete floor/ceiling, or wall - with rating equal or greater than enclosure rating 2 Two layers of XL Insulation for Grease Duct Enclosures (install per UL G18)) One layer of XL Insulation for Air Ventilation Duct Enclosures (install per UL V19) Two layers of XL Insulation for 3-hr Air Ventilation Duct Enclosure (install per UL V2) 3 Concrete fastener system 4 3/16" (5) thick x 2" (50) -3" (75) wide bar stock perforated 12" (305) o.c. 5 8" (203) maximum Air Gap 6 Duct 7 Steel banding min. 1/2" (13) wide by 0.015" (0.4) thick. 8 Banding clip The integrity of Morgan Thermal Ceramics duct systems is limited to the quality of the installation. XL005-4 FOR REFERENCE ONL Y www.morganthermalceramics.com 12:2014 Page 8 of 8 ROXUL The Better Insulation General Product Information: ROXUL® products are mineral wool fibre insulations made from basalt rock and slag. This combination results in a non- combustible product with a melting point of approximately 2150°F (1177°C), which gives it excellent fire resistance properties. ROXUL mineral wool is a water repellent yet vapour permeable material. Product OXUL BOARD INSULATION INS PROCESS EQUIPMENTT INSULATION 40 42 23** ��� � MINERAL BOARD INSULATION 07 21 13** Description & Common Applications: The RHT® 80 product is a non-combustible, rigid mineral wool insulation board that is water repellent and designed for high temperature applications where durability and compressive resistance are required. Common application areas for the RHT series of board insulation include storage tank insulations, drying/oven equipment, petro-chemical and power generating equipment protection where high temperature, fire resistance, and moisture resistance are concerns. Compliance and Performance: ASTM C 612 Mineral Fiber Block and Board Thermal Insulation MEA Approval New York City Approval City Of Los Angeles Approval Fire Performance: ASTM E 136 Behaviour of Materials at 750°C (13827) CAN4 S114 Test for Non -Combustibility ASTM E 84(UL 723) Surface Burning Characteristics CAN/ULC S102 Surface Burning Characteristics Maximum Service Temperature: ASTM C 411 Hot Surface Performance Dimensional Stability: ASTM C 356 Linear Shrinkage Moisture Resistance: ASTM C 1104 Moisture Sorption Thermal Resistance: ASTM C 518 (C 177) R-value/inch @ 75°F RSI value/25.4 mm @ 24°C Corrosive Resistance: Type IVB, Complies 332-97-M RR 25444 Non -Combustible Non -Combustible Flame Spread = 0 Smoke Developed = 0 Flame Spread = 0 Smoke Developed = 0 In Compliance with ASTM C612 @ 1200°F(650°C) < 1 % @ 1200°F(650°C) 0.04% 4.2 hr. ft2.F/Btu* 0.74 m2M ASTM C 665 Corrosiveness to Steel Pass ASTM C 795 Stainless Steel Stress Corrosion Specification as per Test Conforms Methods C871 and C692: U.S. Nuclear Regulatory Commission, Reg. Guide #1.36: U.S. Military Specifications MIL-1-24244 (all versions including B and C) Acoustical Performance ASTM C 423 CO-EFFICIENTS AT FREQUENCIES Thickness 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz NRC 1.5" 0.17 0.58 1.06 1.07 1.00 0.99 0.95 2.0" 0.39 0.84 1.08 1.01 1.02 1.01 1.00 3.0" 0.68 0.92 1.08 1.03 1.03 1.03 1.00 4.0" 1.00 0.95 1.06 1.04 1.06 1.08 1.05 *MASTER FORMAT 1995 EDITION **MASTER FORMAT 2004 EDITION *** at the time of manufacturing ROXUL b HHT 80 Thermal Conductivity: 0.13 0.11 0.09 � U � E 3 0.07 F 0.05 0.03 0 100 200 300 400 Mean Tempe rat re (C) Compressive Strength: ASTM C 165 at 10%: 167 psf (8 kPa) at 25%: 334 psf (16 kPa) Density: ASTM C 612-93 - Nominal 8.0 lb s/ft3 128 kg/m3 ASTM C 612-00 - Actual >_ 1.5" thickness 5.8 Ibs/ft3 93 ka/m3 Dimensions: 24" (width) x 48" (length) 610 mm (width) x 1219 mm (length) Thickness: Product thickness is available in 1" through 5" in 1/2" increments Dimensions: 36" (width) x 48" (length) 914 mm (width) x 1219 mm (length) Thickness: Product thickness is available in 1.5", 2" and 3" For additional sizes, please contact our customer service representatives. Facing: This product can be faced with reinforced foil. Please note that the facing will influence the product's service temperature range. **** "Provisions for lot testing may be required, consult manufacturer." 0.90 0.80 0.70 c x 0.60 v 0.50 € o? 0.40 0.30 0.20 100 200 300 400 500 600 700 Mean Temperature (F) Key Application Qualifiers: • Easy to install • Service temperature 1200°F (650°C) • Non-combustible • Lightweight • Can be fabricated/laminated • Excellent thermal resistance • Low moisture sorption • Good compressive resistance • Non -corrosive • Chemically inert • CFC and HCFC free product and process • Made from natural & recycled materials Other ROXUL Products: Please consult ROXUL for all your insulation needs. We have an extensive range of products for all applications from pipe insulation to commercial products to residential batts. ROXUL invites all inquiries and will act promptly to service all of your requirements. Note: As ROXUL Inc. has no control over installation design and workmanship, accessory materials or application conditions, ROXUL Inc. does not warranty the performance or results of any installation containing ROXUL Inc's. products. ROXUL Inc's. overall liability and the remedies available are limited by the general terms and conditions of sale. This warranty is in lieu of all other warranties and conditions expressed or implied, including the warranties of merchantability and fitness for a particular purpose. ROXUL INC. Milton, Ontario Tel: 905-878-8474 Fax: 905-878-8077 www.roxul.com Tel:1-800-265-6878 Fax:1-800-991-0110 Revised: March 30, 2010 Supersedes: March 10, 2009