REVIEWED BLD2021-0271+Manufacturer_Specifications_and_Installation_Instructions+2.19.2021_12.36.02_PM+2055519unnn TATFnRMATTnAT — .Tnn4JR9dQA9
MAX
EXHAUST
PLENUM
TOTAL
HOOD CONFIG
RISER(S)
HOOD
TAG
MODEL M
NUFACTUR
RLENGTH
COOKING
TYPE
APPLIANCE
DESIGN
TOTAL
SUPPLY
HOOD
END TO
WIDTH
LONG
HEIGHT
DIA
CFM
VEL
SP
NO
TEMP
DUTY
CFM/FT
EXH CFM
CFM
CONSTRUCTION
END
ROW
3650
600
430 SS
1
ECON-AIR
I1' 0'
I
HEAVY
200
2200
10'
21'
4'
2200
1509
-0.503'
0
ALONE
ALONE
ELPX-2
DEG
WHERE EXPOSED
206
300
430 SS
2
ECON-AIR
8' 0'
DEG
I
N/A
0
0
1980
ALONE
ALONE
MISC-PSP
WHERE EXPOSED
unnn TATFnRMATTn AT
PATENT NUMBERS
AC-PSP (UNITED STATES) - US PATENT 7963830 B2.
AC-PSP WALL (CANADA) - CA PATENT 2820509.
AC-PSP ISLAND (CANADA) - CA PATENT 2520330.
FILTERS)
LIGHTS)
UTILITY CABINET(S)
HOOD
TAG
EFFICIENCY @ 7
WIRE
FIRE
SYSTEM
ELECTRICAL
SWITCHES
FIRE
SYSTEM
HOOD
ANGIN
TYPE
SIZE
MODEL #
QUANTITY
NO
TYPE
QTY
HEIGHT
LENGTH
MICRONS
QTY
TYPE
GUARD
LOCATION
SIZE
PIPING
WEIGHT
1
SS BAFFLE WITH
8
16'
16'
30%
3
RECESSED
NO
NO
320
HANDLES
LBS
2
0
NO
99
LBS
FTnnn nPTTON.4
HOOD
TAG
OPTION
NO
RIGHT QUARTER END PANEL 26' TOP WIDTH, 0' BOTTOM WIDTH, 26' HIGH 43isss.
1
LEFT QUARTER END PANEL 26' TOP WIDTH, 0' BOTTOM WIDTH, 26' HIGH 430
PFRFORATF.n .41TPPT.Y PT.FATTTM/.4)
HOOD
NO
TAG
POS
LENGTH
WIDTH
HEIGHT
TYPE
RISERS)
WIDTH
I LENG
DIA
CFM
I SP
2
Front
96'
20'
6'
MUA
12'
24'
660
0.194'
MUA
12'
24'
660
0.194'
MUA
12'
24'
660
0.194'
f V FIELD CUT
10' X 21'
EXHAUST
RISER,
36'
U.L, LISTED RECESSED ALLANSON
ROUND LED FIXTURE AND LED LIGHT.
11' O'NOM./11' 0.00'OD.
PLAN VIEW - HOOD #1
11' 0.00" LONG 3650ELPX-2
G7 ITI
��30 3 30
8' O'NOM✓8' 0,00'OD.
PLAN VIEW - HOOD #2
8' 0.00" LONG 206MISC-PSP
HOOD CORNER
1/2' - 13 TPI HANGING ANGLE
GRADE 5 NINIMUND � (HARDWARE BY INSTALLER)
STEEL HEX NUTS
12' GRADE 5
(HINIMU() STEEL
FLAT WASHER
1/2' - 13 TPI
GRADE 5 OtIMMU )
STEEL ALL-THREAR
1/2' - I3 TPI
OR DE 5 OtINMU )
STEEL HEX MIT.
HmD CORNER
HANGING ANGLE
(VEIGHT BEARING
ANCHOR POINT
FOR MOD).
Le MADE 5
(MINIMUM) STEEL
1/2' - I3 TPI
GRADE 5 (MDRDIUN)
STEEL !EX NUTS.
ASSEMBLY INSTRUCTIONS
HANGING ANGLE MUST BE SUPPORTED WITH 1/2' - 13 TPI
GRADE 5 (MINIMUM) ALL -THREAD. SANDWICH HANGING
ANGLES AND CEILING ANCHOR POINTS WITH 1/2' GRADE 5
(MINIMUM) STEEL FLAT WASHERS AND 1/2' - 13 TPI
GRADE 5 (MINIMUM) HEX NUTS AS SHOWN. MUST USE
DOUBLED HEX NUT CONFIGURATION BENEATH HOOD HANGING
ANGLES AND ABOVE CEILING ANCHORS. MAINTAIN 1/4' OF
EXPOSED THREADS BENEATH BOTTOM HEX NUT, TORQUE
ALL HEX NUTS TO 57 FT-LBS.
SUPPLY PLENUM
I/2' - 13 TPI HANGING ANGLE
MADE 5 (MINIM)
STEEL HEX NUTS. (HARDWARE BY INSTALLER)
1/2' GRADE 5
(HDOMUM) STEEL
FLAT VASHER.
1/2' - 13 TPI
GRADE 5 (MMIMIM)
STEEL ALL -THREAD.
1/2' - 13 TPI
GRADE 5 (MINIMUM)
STEEL HEX NUT.
1/2' GRADE 5
(HIND M) STEEL
FLAT VASHER.
SUPPLY PLENUM
HANGING ANGLE
(WEIGHT BEARING
ANCHOR POINT
FOR SUPPLY
PLENUM).
I/2' GRADE 5
_IMIM) STEEL -
FLAT WAVER
I/2' - 13 TPI
GRADE 5 (MINIMU )
STEEL HEX NUT.
ASSEMBLY INSTRUCTIONS
HANGING ANGLE MUST BE SUPPORTED WITH 1/2' - 13 TPI
GRADE 5 (MINIMUM) ALL -THREAD. SANDWICH HANGING
ANGLES AND CEILING ANCHOR POINTS WITH 1/2' GRADE 5
(MINIMUM) STEEL FLAT WASHERS AND 1/2' - 13 TPI
GRADE 5 (MINIMUM) HEX NUTS AS SHOWN. MUST USE
DOUBLED HEX NUT CONFIGURATION ABOVE CEILING
ANCHORS. SINGLE HEX NUT BENEATH HANGING ANGLE IS
ACCEPTABLE FOR PSP HANGING ANGLES. MAINTAIN 1/4' OF
EXPOSED THREADS BENEATH BOTTOM HEX NUT. TORQUE
ALL HEX NUTS TO 57 FT-LBS,
.,.,.,.,.,.,.,.,...............................
REVIEWED
BY
CITY OF EDMONDS
BUILDING DEPARTMENT
BLD2021-0271
RECEIVED
Feb 19 2021
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
FIELD CUT EXHAUST RISER.
16' SS BAFFLE WITH
HANDLES AND HOOK.
3' INTERNAL STANDOFF.
IT IS THE RESPONSIBILITY
OF THE ARCHITECT/OWNER TO
ENSURE THAT THE HOOD CLEARANCE
FROM LIMITED -COMBUSTIBLE
AND COMBUSTIBLE MATERIALS
IS IN COMPLIANCE WITH
LOCAL CODE REQUIREMENTS.
GREASE DRAIN
WITH REMOVABLE CUP.
FIELD INSTALLED
QUARTER END PANELS.
ISON ROUND LED FIXTURE AND
I K WARM OUTPUT.
SECTION VIEW MODEL 3650ELPX2
HOOD - #9
14' NOM.
VAIN
RECEIVED
Feb 19 2021
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
L`VLTATTQT VAAT TATL`/IDILATT/)AT - T/)r) I4p RA009
FAN
UNIT
TAG
QTY
FAN UNIT MODEL #
MANUFACTURER
CFM
ESP
RPM
MOTOR
HP
BHP
0
VOLT
FLA
DISCHARGE
WEIGHT
SONES
NO
ENCL
VELOCITY
(LBS)
1
1
EADU85H
ECON-AIR
2200
0.750
1408
TEAO-ECM
0.750
OS060
1
208
1 5.2
1 696 FPM
88
16.8
NTTTA FAN TNFnPMATTTIAT - .TnR.94RR49.R2
FAN
MIN
DESIGN
MOTOR
WEIGHT
UNIT
TAG
QTY
FAN UNIT MODEL #
BLOWER
HOUSING
CFM
CFM
ESP
RPM
ENCL
HP
BHP
0
VOLT
FLA
MCA
MOCP
CLBS)
SEINES
NO
2
1
EA-AI-G10
GIOD
Al
0
1980
0.500
922
TEAO-ECM
1.000
0.6230
1
115
11.6
15.6A
25A
230
20
WHAT /)DTT!)ATQ
FAN
UNIT
TAG
QTY
DESCRIPTION
NO
I
GREASE BOX.
1
ECM WIRING PACKAGE - EXHAUST - MANUAL OR 0-IOVDC REFERENCE SPEED CONTROL -MSC-
1
(TELCO), CCW ROTATION.
I
ECM WIRING PACKAGE - DD SUPPLY - MANUAL OR 0-10VDC REFERENCE SPEED CONTROL -MSC-
2
(TELCO).
I
MOTORIZED BACKDRAFT DAMPER FOR SIZE 1 HOUSING. MEETS AMCA CLASS IA RATING.
RAM
EXHAUST
SUPPLY
FAN
UNIT
NO
TAG
GREASE
GRAVITY
WALL
SIDE
GRAVITY
MOTORIZED
WALL
CUP
DAMPER
MOUNT
DISCHARGE
DAMPER
DAMPER
MOUNT
1
YES
2
YES
FAN #1 EADU85H - EXHAUST FAN
3(
I JII
22 1/2
24 r
/\EUSTRISER ONDUCTWORK
AND FAN (BY OTHERS),
FEATURES,
DIRECT DRIVE CONSTRUCTION (NO BELTS/PULLEYS).
ROOF MOUNTED FANS.
RESTAURANT MODEL.
UL705 AND UL762 AND ULC-S645
VARIABLE SPEED CONTROL.
INTERNAL WIRING.
THERMAL OVERLOAD PROTECTION (SINGLE PHASE).
HIGH HEAT OPERATION 300•F (149•C).
GREASE CLASSIFICATION TESTING.
NEMA 3R SAFETY DISCONNECT SWITCH.
EXHAUST FAN MUST OPERATE CONTINUOUSLY
WHILE EXHAUSTING AIR AT 300'F (149'C)
UNTIL ALL FAN PARTS HAVE REACHED
THERMAL EQUILIBRIUM, AND WITHOUT ANY
DETERIORATING EFFECTS TO THE FAN WHICH
WOULD CAUSE UNSAFE OPERATION.
ABNORMAL FLARE-UP TEST
EXHAUST FAN MUST OPERATE CONTINUOUSLY
WHILE EXHAUSTING BURNING GREASE VAPORS
AT 600'F (316'C) FOR A PERIOD OF
15 MINUTES WITHOUT THE FAN BECOMING
DAMAGED TO ANY EXTENT THAT COULD CAUSE
AN UNSAFE CONDITION.
OPTIONS
GREASE BOX.
ECM WIRING PACKAGE - EXHAUST
- MANUAL OR 0-10VDC
REFERENCE SPEED CONTROL
-MSC- (TELCO), CCW ROTATION.
RECEIVED
Feb 19 2021
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
FAN #2 EA-Al-G10D - SUPPLY FAN
1. DIRECT DRIVE UNTEMPERED SUPPLY UNIT WITH 10' BLOWER IN SIZE #1 HOUSING WITH SPEED CONTROL, DISCONNECT SWITCH.
2. INTAKE HOOD WITH EZ FILTERS.
3. DOWN DISCHARGE - AIR FLOW RIGHT -> LEFT.
4. ECM WIRING PACKAGE AND MANUAL OR 0-10VDC CONTROL FOR SUPPLY EC MOTORS. MSC CONTROLLER. xwD❑ NOT ORDER UNDER
WARRANTY, SEE PART NUMBER 'CAS MSC)K)K,
5. MOTORIZED BACK DRAFT DAMPER 16' X 18' FOR SIZE 1 UNTEMPERED UNITS W/EXTENDED SHAFT, STANDARD GALVANIZED
CONSTRUCTION, 3/4' REAR FLANGE, LOW LEAKAGE, TFB120S ACTUATOR INCLUDED.
6. HINGED DOUBLE WALL INSULATED DOOR ASSEMBLY (BURNER/BLOWER SECTION).
xNOTE: SUPPLY DUCT MUST BE INSTALLED TO MEET SMACNA STANDARDS, A MINIMUM STRAIGHT DUCT LENGTH MUST BE MAINTAINED
DOWNSTREAM OF UNIT DISCHARGE AS ❑UTLINED IN AMCA PUBLICATION 201. WHEN USING RECTANGULAR DUCTWORK, ELBOWS MUST
BE RADIUS THROAT, RADIUS BACK WITH TURNING VANES. FLEXIBLE DUCTWORK AND SQUARE THROAT/SQUARE BACK ELBOWS SHOULD
NOT BE USED. ANY TRANSITION AND/OR TURNS IN THE DUCTWORK WILL CAUSE SYSTEM EFFECT, SYSTEM EFFECT WILL
DRASTICALLY INCREASE STATIC PRESSURE AND REDUCE AIRFLOW. D❑ NOT RELY ON UNIT TO SUPPORT DUCT IN ANY WAY. FAILURE
TO PROPERLY SIZE DUCTWORK MAY CAUSE SYSTEM EFFECTS AND REDUCE PERFORMANCE OF THE EQUIPMENT.
SUGGESTED STRAIGHT DUCT SIZE IS 14' x 14'.
BLOWER DISCHARGE.
HASE RAIL
INNER DIMENSION.
7 1/4" ---1
— — —°
00
13 1/4'
L-
0
6 3/8'
FLEX CONDUIT
FOR FIELD
WIRING.
76 1/2'
27 3/8'
32 1/8'
LIFTING LUG.
AIRFLOW.
SERVICE AIRFLOW.
DISCONNECT �
29 3/4' SWITCH.
BLOWER/MOTOR
ACCESS DOOR
00 24' SERVICE
CLEARANCE REQ.
3 3/4'
MINIMUM I RECEIVED
ECEIVED
DUCT PER AMCA)K Feb 19 2021
L _ J CITY OF EDMONDS
DEVELOPMENT SERVICES
MIN. 14" DEPARTMENT
JOB Loft
� � Vet® k o �'� econoairLOCATION SEAT020 WA,
"��DATE 12/22/2020 JOB # 4664932
�� � ✓, DWG # 4 DRAWN BYA_CASH 85
REV SCALE 3/8' = V-0'