APPROVED BLD BLD2021-1583+Plumbing_Plan+11.21.2021_12.01.31_PM+2531702PLUMBING GENERAL ABBREVIATION ABBV FULL NAME ABBV FULL NAME ABBV FULL NAME AAV AIR ADMITTANCE VALVE DN DOWN NTS NOT TO SCALE ABV ABOVE DS DOWNSPOUT OFD OVER FLOW DRAIN AFF ABOVE FINISHED FLOOR DWG DRAWING POC POINT OF CONNECTION AP ACCESS PANEL E EXISTING PRV PRESSURE REDUCING VALVE BEL BELOW ELEV ELEVATION PVC POLYVINYL CHLORIDE BFP BACKFLOW PREVENTER ET EXPANSION TANK RD ROOF DRAIN BOP BOTTOM OF PIPE EWH ELECTRIC WATER HEATER RPBA REDUCED PRESSURE BACKFLOW ASSY BV BALL VALVE F FIRE TOG TOP OF GRATE BWV BACK WATER VALVE FCO FLOOR CLEAN OUT UG UNDER GROUND CB CATCH BASIN FD FLOOR DRAIN LINO UNLESS NOTED OTHERWISE CFF CAP FOR FUTURE FU FIXTURE UNIT VTR VENT THRU ROOF CI CAST IRON GI GREASE INTERCEPTOR W/ WITH CL CENTER LINE GPM GALLONS PER MINUTE WCO WALL CLEAN OUT CO CLEAN OUT GWH GAS WATER HEATER WH WALL HYDRANT CPVC CPVC MATERIAL HB HOSE BIBB WHA WATER HAMMER ARRESTOR DCBP DOUBLE CHECK BACKFLOW PREVENTER HP HIGH PRESSURE WM WATER METER DCVA DOUBLE CHECK VALVE ASSEMBLY IE INVERT ELEVATION YH YARD HYDRANT DEMO DEMOLISH MH MANHOLE DFU DRAINAGE FIXTURE UNIT NIC NOT IN CONTRACT DESCRIPTION BALANCING VALVE GATE VALVE GLOBE VALVE BALL VALVE - FULL PORTED SILENT CHECK VALVE REDUCED PRESS. BACKFLOW PREVENTER BACKFLOW PREVENTER UNION STRAINER PRESSURE RELIEF VALVE PRESSURE REDUCING VALVE PRESSURE / TEMPERATURE PORT PRESSURE GAUGE SOLENOID VALVE PIPE - HEAT TRACE HOSE BIB SUB -METER WATER FLOW WATER HAMMER ARRESTOR FLEX PIPE VENT THROUGH ROOF FLOOR CLEANOUT WALL CLEANOUT FLOOR DRAINS FLOOR SINKS ROOF, OVERFLOW, AND COMBINATION DRAINS PLUMBING SYMBOL LEGEND ABBV SYMBOL DESCRIPTION BALV GAS COCK GV VERTICAL EXPANSION TANK GLV T TEMPERATURE GAUGE BV Q THERMOMETER CV D°4, BALL VALVE W/ 3/4" HOSE ADAPTOR RPBP p CONCENTRIC REDUCER BFP TWO-WAY CONTROL VAVLE UNION THREE-WAY CONTROL VALVE STRN POINT OF CONNECTION PTV PIPE BREAK - PIG TAIL PRV 6• CHWS PIPE - SIZE & ABBREVIATION P/T 6" CHW PIPE - SIZE & ABBREVIATION WITH INSULATION PG ® PUMP CIRCULATION SV ROOF DRAIN (RISER) HB MTR WHA VTR V� OVER -FLOW DRAIN (RISER) FrN 60' OFFSET FOR SUDS 'ITTATT FLTR-1 WC-1 1/2% SLOPE 1%SLOPE 2%SLOPE � EXPANSION THERMAL DOMESTIC PEX MANIFOLD PLUMBING TRAP PLUMBING FIXTURE N.I.C. TAG PLUMBING FIXTURE TAG PLUMBING EQUIPMENT TAG 1/16" PER FOOT PIPE SLOPE 1/8" PER FOOT PIPE SLOPE 1/4" PER FOOT PIPE SLOPE (TYP. UNO) ABBV GC VET TG THERM BV W/ HA CR 2WAY 3WAY P.O.C. RD OD 60° OFST EXP MFLD TRAP PLUMBING SYSTEM LEGEND I= a LINE TYPE FULL NAME ABBR LINE TYPE FULL NAME ABBR DOMESTIC WATER — — — DOMESTIC COLD WATER DCW GD GARAGE DRAIN GD — PDCW — DOMESTIC COLD WATER - HIGH PRESS DCW-HP GD GARAGE DRAIN (UNDERGROUND) GD — DFw — DOMESTIC FILTERED WATER DFW GW GREASE WASTE GW - - DOMESTIC HOT WATER DHW — — GwuG — — GREASE WASTE (UNDERGROUND) GW — — — NPTW — — DOMESTIC HOT WATER 140 DHW 140 iW INDIRECT WASTE IW — — NPCw — — DOMESTIC HOT WATER 160 DHW 160 — PSS — — PUMPED SANITARY SEWER PSS — — DHW — — DOMESTIC HOT WATER - HIGH PRESSURE HW-HP PW PUMPED WASTE PW — — — — — — — — — — — — — DOMESTIC HOT WATER CIRC DHWC — — — — — — — — — — — — — — — VENT V — — — — — NPTWC — — — — — DOMESTIC HOT WATER CIRC 140 DHWC 140 WASTE W — — — — — SPC — — — — — DOMESTIC HOT WATER CIRC 160 DHWC 160 — SS — SANITARY SEWER SS — — — — — DHWC — — — — — DOMESTIC HOT WATER CIRC - HIGH PRESS DHWC-HP ow- — — DTW — — DOMESTIC TEMPERED WATER DTW — — FTDR — — FOOTING DRAIN FTDR — — — — — DTWC — — — — — DOMESTIC TEMPERED WATER CIRC DTWC ORL OVERFLOW RAIN LEADER ORL MEDICAL & LAB GASSES RL RAIN LEADER RL AR ARGON AR PSD PUMPED STORM DRAIN PSD CO2 CARBON DIOXIDE CO2 — — — SD — — — STORM DRAIN SD HE HELIUM HE /A INSTRUMENT AIR IA IA -IN INSTRUMENT AIR INTAKE IA -IN LA LAB AIR LA MA MEDICAL AIR MA MVAC MEDICAL VACUUM MVAC MVAC-E MEDICAL VACUUM EXHAUST MVAC-E N2 NITROGEN N2 N20 NITROUS OXIDE N20 02 OXYGEN 02 VW VACUUM VAC WAGD WASTE ANESTHETIC GAS DISPOSAL WAGD WAGD-E WASTE ANESTHETIC GAS DISPOSAL EXH WAGD-E MEDICAL EQUIPMENT SCHEDULE NO. EQUIPMENT DESCRIPTION 0-1 OXYGEN WALL OUTLET - CHEMETRON - PATTONS MEDICAL 01 SERIES 01-CHWAL-OXY-N, SAFETY KEYED OUTLET FOR CHEMETRON TYPE CONNECTION, US COLOR CODED FOR OXYGEN, 1/21, OD (QTY 2) CONNECTION CLEANED FOR OXYGEN SERVICE, W/ CYCOLOY TYPE FACE PLATE SEPARATE FROM THE PRIMARY VALVE WITH GAS CHECK. (VERIFY CONNECTION TYPE BEFORE ORDERING.) N-1 N20 WALL OUTLET - CHEMETRON - PATTONS MEDICAL 01 SERIES 01-CHWAL-N20-N, SAFETY KEYED OUTLET FOR CHEMETRON TYPE CONNECTION, US COLOR CODED FOR NITROUS OXIDE, 1/2" OD (QTY 1) CONNECTION CLEANED FOR OXYGEN SERVICE, W/ CYCOLOY TYPE FACE PLATE SEPARATE FROM THE PRIMARY VALVE WITH GAS CHECK. (VERIFY CONNECTION TYPE BEFORE ORDERING.) W-1 WAGD WALL OUTLET - CHEMETRON - PATTONS MEDICAL 01 SERIES 01-CHWAL-WAG-N, SAFETY KEYED OUTLET FOR CHEMETRON TYPE CONNECTION, US COLOR CODED FOR WAGD, 112" OD (QTY 1) CONNECTION CLEANED FOR OXYGEN SERVICE, W/ CYCOLOY TYPE FACE PLATE SEPARATE FROM THE PRIMARY VALVE WITH GAS CHECK. (VERIFY CONNECTION TYPE BEFORE ORDERING.) V-1 VACUUM WALL OUTLET - CHEMETRON - PATTONS MEDICAL 01 SERIES 01-CHWAL-VAC-N, SAFETY KEYED OUTLET FOR CHEMETRON TYPE CONNECTION, US COLOR CODED FOR VACUUM, 1/2" OD (QTY 5) CONNECTION, W/ CYCOLOY TYPE FACE PLATE SEPARATE FROM THE PRIMARY VALVE WITH GAS CHECK. (VERIFY CONNECTION TYPE BEFORE ORDERING.) VS-1 VACUUM WALL SLIDE - CHEMETRON - PATTONS MEDICAL 01 SERIES 01-WALSLIDE-N, SLIDE BRACKET FOR CHEMETRON VACUUM OUTLET, W/ ALUMINUM SLIDE, AND CYCOLOY COVER PLATE. (QTY 5) MED GAS PIPING MATERIAL SCHEDULE PIPING MATERIAL SCHEDULE: LOCATION PIPING SIZE MATERIAL (FOOTNOTE) JOINT MEDICAL OXYGEN GAS, CARBON DIOXIDE GAS, ALL ASTM B 819 COPPER TYPE L FOOTNOTE (a) NITROUS OXIDE GAS ABOVE GROUND MEDICAL VACUUM ALL ASTM B 819 COPPER TYPE L FOOTNOTE (a) WASTE ANESTHETIC GAS DISPOSAL (WAGD) ALL ASTM B 819 COPPER TYPE L FOOTNOTE (a) FOOTNOTES: (a) MEDICAL GAS PIPING, FITTINGS, AND VALVES SHALL BE CLEANED, PROTECTED AND LISTED FOR OXYGEN SERVICE. ALL JOINTS SHALL BE BRAZED USING ANSI/AWS A5.8 COPPER -PHOSPHORUS OR COPPER -PHOSPHORUS -SILVER BRAZING FILLER METAL WITHOUT FLUX. JOINTS SHALL BE PURGED WITH OIL -FREE DRY NITROGEN NF DURING BRAZING AND TESTING IN ACCORDANCE WITH NFPA 99. MED GAS PIPING GENERAL NOTES 1. THESE PLANS ARE SCHEMATIC AND DO NOT SHOW EXACT ROUTING OR EVERY OFFSET WHICH MAY BE REQUIRED. COORDINATE WITH OTHER TRADES AND CONFIRM ALL CLEARANCES BEFORE COMMENCING WORK. 2. MATERIALS, METHODS, AND INSTALLATION SHALL COMPLY WITH THE PROVISIONS OF THE 2012 EDITION OF NFPA 99 HEALTH CARE FACILITIES CODE AND 2018 EDITION OF THE UNIFORM PLUMBING CODE AS AMENDED BY THE STATE OF WASHINGTON. 3. ALL PIPE SIZES NOTED ON DRAWINGS ARE MINIMUMS. 4. HANGERS AND SUPPORTS FOR PIPING SHALL BE IN ACCORDANCE WITH THE 2012 EDITION OF THE NFPA 99, 5.1.10.11.4 & TABLE 5.1.10.11.4.5 5. PIPING PENETRATIONS OF FIRE RATED WALLS OR FLOORS SHALL BE SLEEVED AND FIRE STOPPED WITH LISTED MATERIALS SO AS TO MAINTAIN THE INTEGRITY AND RATING OF THE FLOOR OR WALL. 6. PROVIDE EARTHQUAKE RESTRAINT FOR PLUMBING PIPING AND EQUIPMENT IN ACCORDANCE WITH SECTION 1613 OF THE 2018 IBC AND ASCE 7. MED GAS SCOPE OF WORK DEMO CEILING MOUNTED 02 (2), VAC (1) AND N20 (1) OUTLETS AND ASSOCIATED PIPING. INSTALL NEW WALL MOUNTED 02 (2), VAC (5), N20 (1) AND WAGD (1) OUTLETS AND ASSOCIATED PIPING PROVIDE MEDICAL GAS/VACUUM SYSTEM TESTING & CERTIFICATION IN ACCORDANCE WITH NFPA 99. LEGAL DESCRIPTION PARCEL NUMBER: 00580700002500 LEGAL DESCRIPTION: SOLNERS 5 ACRE TRACTS BLK 000 D-00 - N 1/2 OF TRS 27 & 28 & S 1/2 OF TRS 25 & 26 TGW TH PTN OF VAC 10TH ST SE (FORMERLY 216TH ST SW ADJ THRTO) & TGW TH PTN OF TR 29 SD PLAT LY WILY OF FDL - COM AT NWCOR SD TR 29 TH ELY ALG N BDY 42.12FT TO BEG OF LN HEREIN DESC TH SLY TAP 35.44FT FIR SW CR OF SD TR 29 AS MEAS ALG S BDY SD TR & TERM OF LN HEREIN DESC (PER CITY EDM BLA REC AF NO 199909155005) CONTACT LIST TITLE NAME COMPANY PHONE NUMBER EMAIL PROJECT ENGINEER KIM LARSEN MACDONALD MILLER 206-768-4116 KIM.LARSEN@MACMILLER.COM PROJECT ENGINEER JORDAN CROWE MACDONALD MILLER 206-768-3836 JORDAN.CROWE@MACMILLER.COM PROJECT MANAGER JAKE BURSTEIN MACDONALD MILLER 206-255-6723 JAKE.BURSTEIN@MACMILLER.COM I PLUMBING FOREMAN FRANK TINNIN MACDONALD MILLER 206-571-9813 FRANK.TINNIN@MACMILLER.COM APPROVED PLANS MUST BE ON JOB SITE ALL WORK SUBJECT TO FIELD INSPECTION FOR CODE COMPLIANCE Approved by Fire 11/30/2021 AFM /CFtttere►- I— - — - — - — - — - — - — - — - — - — - — - — - — - — - — - — - — - — - — - — - — - — - — - — - — - — - — - — - — - — Provide Med Gas testing reports to the I City Inspector at the time of inspection. ------------------------------------------------------------ I i I i City Of Edmonds Building Department Work PLUMBING- MED GAS Address 21601 76TH AVE W Owner SWEDISH HOSP- SURGICL CENTER ------------------------------- Approved Date ; 12/07/2021 Building Official Eri,& Cv fe r Permit Number BLD2021-1583 215th St SW SITE < o= 216th St SW 216th St SW 218th S SW a Iv r r- 220th St SW o(y) � U) �, z a� � � _ O MM W 6 04 E U) o LL co U^) _ L 0J O C) 0 U) U)0Q o E� 0 > U ' °o U_ J Q � N j LI � o 11 /19/2021 z O U) W I" RECEIVED Nov 21 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT U) (Q V 0 U-1 G U) Oz cf) U)O 0 2 z 0 C) Ow N w 2i� J C) 0 >Q Q = L1J w U I-_ r_z = > U �r� V! _� vJ CV LULU vJ 0000 ENGINEER: LAST REVISED: K LARSEN 11-19-21 CHECKED BY: DATE PLOTTED: D JACQUES 11-19-21 CAD: ISSUE DATE: F MAMERTO DRAWING NUMBER: D-3579-77212273-00 SHEET NUMBER: TPO.01 z O U U) z O U Of O LL 0 LU 7) W C) O z a E a� 0 z T LL VICINITY MAP N NO SCALE 7 8 \ 2" C.W %" HW. 2" W UP H.W.C. 4" DN 2" V. UP 2"WUP �v GAS TRACK (2) 02 & VAC (1) N20 1%" W. OF 1%" V. UP 14 2" V L 2"W4"H& CW UP CLG. OUTLETS (2) 02 & VAC (1) N20 CLG. OUTLETS (2) 02 & VAC (1) N20 ME VAC 1%" V. DN ')2"VUP VAC O O VAC " W QPF— %4" HW. & 1" C.W. 08 2" V WASHER O 0 STERILIZER O %" CW 2" FUN O DR & 4" STM __V 0 s4"H&CW 1%" FFD ROUGH IN & CONN. SONIC CLEANER rl - r — I —STERILIZER- PROVIDE — 1%" FUN. DR%" CW %4' STM SUPPLY & RET. I(E) 1 1/4"MVAC Y4" H & C.W. & lY2" W. 2" V. DN IN /EY R AFT �/2" V DN F-2 //—STERILI; PROVIDI DRAIN, i I I I I I I I I I I 9 10 3" FLUSHING F L R, DR, SEE NOTE 1. FLUSH VALVE SEE NOTE 2. ACCESS PANEL 2" V. UP I I 1' C.W. &1" R.W. UP I I I 2 1 I I I I AREA OF WORK I I I I I I J rVl/7 � O Il- OD EoD 7 Q I� C:) O O00L TT VJ +� C'4 E U) D cp N O O U) LL J N Q c O i .gC) U) o cu E� ' o Q��Z Q ' U O O U N J Q LL �o 11 /19/2021 I I I I I I I I LLI a 0 0 z O Lu I I I I I I I I w a 0 z O Ln Lu RECEIVED Nov 21 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT z Cn J Z Q 0- O CD O M 75 U W W D 0 C� J z Q O O z I— C/) U U)O 0 02 Q� O z0 D r LL Ow N o y 00cy) Z w O�;Q W� �. LJ c� U ti Z (n 2 Q� O C� U) N_lulJ m dg:t— Z ENGINEER: LAST REVISED: K LARSEN 11-19-21 CHECKED BY: DATE PLOTTED: D JACQUES 11-19-21 CAD: ISSUE DATE: F MAMERTO DRAWING NUMBER: D-3579-77212273-00 SHEET NUMBER: DP1 .01 z 1 /4" = 1'-0" m 3 a 0 a N N r n W 0 0 w U U) a E a w U y c+� n N D1 N n n 7 8 9 2" W UP � H.W.C. 4" DN 2" V. UP 2"WUP �v GAS TRACK (2) 02 & VAC (1) N20 12" W. OF 12" V. UP 14 2" V L 2"W4"H& CW UP CLG. OUTLETS (2) 02 & VAC (1) N20 CLG. OUTLETS (2) 02 & VAC (1) N20 ME VAC 12" V. DN )2"VUP VAC O O VAC " W QPF— %a" HW. & 1" C.W. 13 08 2" V O WASHER OSTERILIZER O 2" CW 2" FUN O DR & 4" STM �EK s4"H&CW 12" FFD ROUGH IN & CONN. SONIC CLEANER - r r - I -STERILIZER- PROVIDE — 12" FUN. DR2" CW %4' STM SUPPLY & RET. I(E) 1 1/4"MVAC s4"H&C.W.&lY2"W 2" V. DN IN /EY R AFT �/2" V DN F-2 �STERILI; PROVIDI DRAIN, i I I I I I I I I I I U > VAC 2" V DN. 4" H& CW DN. 10 U z VV ur I 07 2 DN. t 2" V UP I I I REFER TO ARCHITECTURAL ELEVATIONS FORE ACT FIRE HOSE I VAC PLACEMENT OF MEDICAL CAB' 2 V GAS WALL INLETS/OUTLETS I I N 1 I 1/2"N20 DROP 1" H & CW DN I VS 1 V 1 3/4"VAC 12" V. DN I 2 V. DN 1 1 /2"DROP02 4" H& CW 0 VAC I I _ DROP 12" V. DN� - D VAC U > MVAC WALL OUTLET VAC LO POC TO (E) (E) 1 1/4"MVAC z I I 1 1 /4"MVAC I O I z ., I I I I (E) 1 1/4"MVAC I (E) MVAC I ZVB I I 02 & N20 C I ZVB C P-15 12" V. DN. I I I 1" H&CW DN. + 12" I r-14 I I � I I O I I . I I HORIZ. VENT & WATER IN WALL I i I I I I I I I i I I I /E I j I � I I � I I I I I I 02 4 I I I I � I I 4„ � I O.R. I I i I I � I V. DN. 2" V. DN. P-14 I X---------------------- -- — + 2Y I 2 I P-14 I -,T 14"� 3" FLUSHING F L R, DR, SEE NOTE 1. FLUSH VALVE SEE NOTE 2. ACCESS PANEL 2" V. UP I I 1' C.W. &1" R.W. UP I I I 2 1 I I I I AREA OF WORK I __Lm I I I I I L_J rVl/7 � O I� - 7 L Q I� C:) O O 00 � (fl VJ TT +� C'4 E U) D N O O N (� O i � o cu E� ' o Q'01z ' U O O U N J Q o LL c: �c 11 /19/2021 I I I I I I I I LLI Q 0 z O L > Lu I I I I I I I I w I — a 0 z O T > Lu RECEIVED Nov 21 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT v J z rQ O V M z U W Q � J O Oz �� U U)0 C) Q � O zo D r U- Ow co o G =ern z w Q;Q W C) W �_� U) co ui U�.. J co � tiz V _�� QRZ O C� U)N� m Z ENGINEER: LAST REVISED: K LARSEN 11-19-21 CHECKED BY: DATE PLOTTED: D JACQUES 11-19-21 CAD: ISSUE DATE: F MAMERTO DRAWING NUMBER: D-3579-77212273-00 SHEET NUMBER: TP1.01 z 1 /4" = V-0"