Swedish Edmonds Campus-OR #6-3412-12.21.21Medical Gas Services 918 S Horton St, Suite 917 Seattle, WA 98134 medgasservices.io (425) 894 5918 Medical Gas Line Verification Report Date: December 215t,2021 Job Number: 3412 Contractor: MacDonald -Miller Facility Solutions Date(s) / Time(s) of Testing: December 215t, 2021- 0100 hrs. Facility: Swedish Edmonds Campus 2160176th Ave W Edmonds, WA. 98026 Scope of Work: Installation of new medical oxygen, vacuum, nitrous oxide and WAGD inlets/outlets downline of existing zone valves Our firm certifies that the verifier named in the report is properly trained and certified to perform the activities required. All testing and measurement equipment are properly calibrated and maintained. As a representative of Medical Gas Services, LLC, the verifier named in this report has conducted testing and verification of medical gas piping systems and related equipment to certify the following on the above date. General Findings: A. Medical gases and vacuum are in compliance with NFPA 99 (2012ed): Category 1 B. No crossed lines were found in medical gas or vacuum systems in the tested areas on the day of testing. C. Medical gases meet minimum concentration. D. Medical gases meet minimum flow and are at normal pressure. E. Medical vacuum meets minimum flow and is at normal vacuum pressure. F. Medical gas system components in the area tested are in compliance with NFPA 99 (2012ed). G. Medical Gas Line Purity Test: PASS H. Initial Line Pressure Test: PASS (150# for 24 hrs.) I. Permit #: BLD-2021-1583 / City of Edmonds J. Attachments: Worksheet Note: Existing Equipment and Systems NFPA 99(2012ed)115114 - An existing system that is not in strict compliance with the provisions of this standard shall be permitted to be continued in use as long as the authority havingiurisdiction has determined that such use does not constitute a distinct hazard to life. 3412-12.21.21-VR Pg.1 of 3 Medical Gas Services 918 S Horton St, Suite 917 Seattle, WA 98134 medgasservices.io (425) 894 5918 II. Medical Gases: A. Oxygen: 1. Static Line Pressure: 54.5 psi 2. Dynamic Outlet Free Flow: >3.5 scfm 3. Dynamic Outlet Free Flow: >6.0 scfm (for 3 seconds in 'Critical Care Area') 4. Oxygen Concentration: 98.6% 5. Delta Flow: PASS B. Nitrous Oxide: 1. Static Line Pressure: 55.1 psi 2. Dynamic Outlet Free Flow: >3.5 scfm 3. Nitrous Oxide Concentration: >99.0% 4. Delta Flow: PASS III. Vacuum: A. Medical - Surgical Vacuum 1. Static Line Vacuum: 21.14" HqV 2. Dynamic Inlet Free Flow: >3.0 scfm 3. Delta Flow: PASS B. WAGD (Waste Anesthesia Gas Disposal) (Not A Separate System) 1. Static Line Vacuum: 21.14" HqV 2. Dynamic Inlet Free Flow: >3.0 scfm 3. Delta Flow: PASS IV. Particulate Test: PASS V. Odor: None VI. Outlets / Inlets: A. Brand: Patton's Medical B. Quick Connect Style: Chemetron VII. Zone Valves: A. Brand: Chemetron B. Down line gauges: Some C. Labeled for Area Controlled: Yes VIII. Alarms: A. Area Alarms: 1. Brand: Could not locate 2. Labeled for Area Monitored: Could not locate 3412-12.21.21-VR Pg. 2 of 3 Medical Gas Services 918 S Horton St, Suite 917 Seattle, WA 98134 medgasservices.io (425) 894 5918 IX. Brazier: Garrett T. Swearingen A. Brazier Number: SWEARGT872D2 B. Contractor: MacDonald -Miller Facility Solutions X. Comments: A. Oxygen zone valve does not have a downline pressure gauge B. Nitrous oxide zone valve does not have a downline pressure gauge C. Could not locate area alarm for operating rooms XI. Recommendations: A. Install zone valve with downline pressure gauge B. Install zone valve with downline pressure gauge C. Confirm and locate operating room area alarm Reviewed By: Matthew Waacchhsmuth - ASSE 6030 Verifier 3412-12.21.21-VR Pg. 3 of 3 Medical Gas Services 918 S Horton St, Suite 917 Seattle. WA 98134 medsasservices.io (425) 894 5918 Surgical Outlet Ei Zone Valve Evaluation Worksheet Facility: Swedish Edmonds Campus Job #: 3412 Date: 12.21.21 Area Tested: Operating Room 6 Verifier: MW ?one Valve - r-1 New 171 Existing Labeled As: OR 6 1ZV Brand: Chemetron Gas 3 Part Valve DL Gauge a. pal Act PSI Comments: OX ® Yes ❑ No ❑ Yes ® No -- 54.5 MA ❑ Yes ❑ No ❑ Yes ❑ No N20 ® Yes ❑ No ❑ Yes ® No -- 55.1 VAC ® Yes ❑ No ® Yes ❑ No 24 21.14 WAGD ❑ Yes ❑ No ❑ Yes ❑ No -- 21.14 Same System N2 ❑ Yes ❑ No ❑ Yes ❑ No I_�f7�:1_�ICTi''n■�►•C7T�■�►C.�i�7�Z�.'l�f�:�■�►C��►1�4:i�i ■ • Labeled As: Could Not Locate Brand: Gas PSI Set HI Set LO Sensor Comments: OX Could not find area alarm MA N20 VAC WAG D N2 Uutlets & Inlets - M New I I Existino Outlet / Inlets Brand: Patton's Medical Location: Wall I Quick Connect: Chemetron Area Room Door Gas Flow SCFM Delta Flow Conc. % Part. Comments: OR # 6 OX >8 <5 98.6 .000 OX >8 <5 98.6 .000 VAC 5 >12 -- -- VAC 5 >12 -- -- VAC 5 >12 -- -- VAC 5 >12 -- -- VAC 5 >12 -- -- WAGD 5 >12 -- -- N20 >8 <5 >99 .000 3412-12.21.21 PS.1 of 1