FIR2021-0153+Fire_Alarm_Voltage_Calculations+12.27.2021_11.48.31_AM+2592480RECEIVED Dec 27 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT F I R2021-0153 REVIEWED BY CITY OF EDMONDS -•::::: COSCO Fire Protection EOL Voltage Drop Calculation Starting Voltage 20.4 Volts Minimum Voltage @ EOL 16 Volts Voltage Drop Warning % 10.00% Current Draw Wire Type Resistance Length Actual Resistance Voltage @ EOL Percent Drop Circuit Name Amps AWG Ohms/1000ft. Feet (One Way) Ohms Volts Percent NAC 1 0.605 1#14 Solid 3.07 200 1.23 19.66 3.64 NAC 2 0.000 #14 Solid 3.07 0 0.00 20.40 0.00 NAC 3 0.000 1#14 Solid 1 3.07 0 0.00 20.40 0.00 NAC 4 0.000 1#14 Solid 1 3.07 0 0.00 20.40 0.00 Resistance Table Wire Type Resitance AWG Ohms/1000ft. #10 Solid 1.21 #10 Stranded 1.24 #12 Solid 1.93 #12 Stranded 1.98 #14 Solid 3.07 #14 Stranded 3.14 #16 Solid 4.89 #16 Stranded 4.99 #18 Solid 7.77 #18 Stranded 7.95 Note: All Resistance values are taken from Table 8 Conductor Properties of the NFPA 70 National Electrical Code. All values are for Direct Current Resistance at 75°C (1670F).