Loading...
FIR2020-0108+Fire_Alarm_Battery_Calculations+12.3.2020_4.02.38_PMBattery Calculations for Panel: P1 Part No:AFC-50 - AFC-50, FACP, 50 POINT, 2 NACs Part No. Qty. Description Standby Total Standby Alarm Total Alarm Panel Equipment AFC-50 MB 1 AFC-50 MB 130.000OmA 130.000OmA 200.000OmA 200.000OmA Total Panel Stby 130.000OmA Total Panel Alarm 200.000OmA Peripheral Devices 976090 1 End of line resistors, Pkg of 10 (EOL) 0.000OmA 0.000OmA 0.000OmA 0.000OmA PC2RL 1 L-SERIES 2-WIRE, HORN STROBE, RED, CEILING (Notification) 75CD 89dB 0.000OmA 0.000OmA 143.000OmA 143.000OmA PAD100-PD 1 PHOTO SMOKE SENSOR (Signaling line) 0.5000mA 0.5000mA 0.5000mA 0.5000mA PAD100-SIM 1 SINGLE INPUT MODULE (Signaling line) 0.2400mA 0.2400mA 0.2400mA 0.2400mA Total Peripheral Stby 0.7400mA Total Periph Alarm 143.7400mA Total Standby Amps 130.7400mA Total Alarm Amps 343.7400mA RECEIVED Standby time: 24 Hrs 3.138Ah Dec 04 2020 FIR2020-0108 Alarm time: 5 Min 0.029Ah CITY OF EDMONDS DEVELOPMENT SERVICES Battery requirement: 3.166Ah DEPARTMENT Compensation Factors - Standby: 1.2 Alarm: 1.2 Requirement with compensation: 3.8Ah