April 20, 2020
City of Edmonds
Building Division
Subject: Plan Review Comments
Plan Check: BLD2020-0224
Project Address: 1143 6`' Ave S.
Madden Roof and Deck Addition
This is a letter in response to items 1 and 2 of the Plan Review Comments
dated 3/31/20 .
1. Existing smoke and carbon monoxide detectors are shown on sheets
A2 and A3. The detectors are for both smoke and carbon monoxide.
The new fixture location is shown at the existing Bedroom 2. All of
the existing detectors, and the new one are inter connected. One goes
off they all go off.
2. The new roofs will be vented at the new eaves with a continuous
1" air space to the new continuous ridge vents above.
See sheet A4.
There are no crawl space areas.
Total new roof vented area: 404sf at 1/150 = 2.7sf
Please let me know if you have additional questions
Sincerely
Michael A. George Architect
mikeaiakyahoo.com
425-330-5505
4474 REGISTERED
RCHITECT
rA E OF �W114iaTOt7
WST
COAST
S TRUCTURALLY/
ENGINEERING, INC.
9540 Semiahmoo Parkway #137
Blaine, WA 98230
April 16, 2020
City of Edmonds
Building Division
Subject: Plan Review Comments
Plan Check: BLD2020-0224
Project Address: 1143 61 Ave S.
Madden Roof Addition and Deck
WCSE Project No: W4468
This letter is in response to items 3-6 of the Plan Review Comments dated 3/31/20 for the above
referenced subject.
3. A prefabricated metal railing will be used. The loading requirements have been added to the
plans.
4. The size and material are now indicated on the plans.
5. Holdowns are now shown on the framing plan and detail.
6. A post to beam connection detail has been added.
If there are any questions regarding the above or if we may be of further assistance, please contact this
office.
rSinandless PE, SE
West Coast Structural Engineering Inc.
4-16-20