FIR2021-0030+Drawings+3.31.2021_9.44.58_AM+2119942Kidde
Fire Systems
FUSIBLE LINKS:
450 DEG F
Approved by Fire
04/20/2021 A ' e
Subject to field inspection
EXISTING
KIDDE WHDR 4 GALLON SYSTEM
TANK #1 USES 10 of 12 FLOW POINTS
City Of Edmonds
Building Department
Work FIRE HOOD SUPRESSION
Address 21110 76TH AVE W
Owner ROMEOS
Approved Date
Building Official
-------------------
Permit Number
FIR2021-0030
RECEIVED
Apr 06 2021
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
91—^ 11
15"x15"
A+
DUCT
CONTROL HEAD
VENT ET
12- ADP
I I
PLUG
I
I
1/2" 0 PIPE
I
ADP
I
�F GRWT R
RT R ADP
27"-45" 24"-48"
20"42" 13"-48"
4 GAL
12 PTS
I
nnn
MAX
15' 12" 12" 36" 24" EXISTING MECHANICAL GAS
FRYER CHAR RANGE RANGE GRIDDLE
BROILER SHUT OFF VALVE -
INSTALLED BY OTHERS
BAFFLE PER NFPA 96
(2017) 12.1.2.5
Tank #1 - 4 Gallon - 12 POINTS MAX
Appliance Noz Qty Noz Type Flow Pts Total Pts
FRYER
1
F
2
2
CHARBROILER
1
GRW
1
1
12" RANGE
1
R
1
1
36" RANGE
2
R
1
2
GRIDDLE
1
ADP
1
1
PLENUM
1
ADP
1
1
DUCT
2
ADP
1
2
Total Flow Points 10
MU CONNECTION TO MAKE UP AIR FAN, SHUT DOWN
UPON ACTIVATION (CONNECTION BY OTHERS)
E
ELECTRIC DISCONNECT, SHUT DOWN UPON
ACTIVATION (CONNECTION BY OTHERS)
z EMT
0
42" - 48"
REMOTE PULL STATION SHALL BE INSTALLED 42" - 48" ABOVE THE
FINISHED FLOOR AND A DISTANCE OF AT LEAST 1 OFT FROM THE
HAZARD BUT NOT MORE THAN 20FT. IT SHALL BE INSTALLED IN THE
PATH OF EXIT AND REQUIRE A MAXIMUM FORCE OF 40 LBS AND A
MAXIMUM MOVEMENT OF 14" FOR ACTUATION
CLASS K WET CHEMICAL EXTINGUISHER
SHALL BE INSTALLED 42" -48" ABOVE THE FINISHED FLOOR
PRE-ENGINEERED SYSTEM SHOP DRAWING ONLY —SCALE: 1/4"=1'-0"