FIR2021-0030+Drawings+3.31.2021_9.44.58_AM+2119942Kidde Fire Systems FUSIBLE LINKS: 450 DEG F Approved by Fire 04/20/2021 A ' e Subject to field inspection EXISTING KIDDE WHDR 4 GALLON SYSTEM TANK #1 USES 10 of 12 FLOW POINTS City Of Edmonds Building Department Work FIRE HOOD SUPRESSION Address 21110 76TH AVE W Owner ROMEOS Approved Date Building Official ------------------- Permit Number FIR2021-0030 RECEIVED Apr 06 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT 91—^ 11 15"x15" A+ DUCT CONTROL HEAD VENT ET 12- ADP I I PLUG I I 1/2" 0 PIPE I ADP I �F GRWT R RT R ADP 27"-45" 24"-48" 20"42" 13"-48" 4 GAL 12 PTS I nnn MAX 15' 12" 12" 36" 24" EXISTING MECHANICAL GAS FRYER CHAR RANGE RANGE GRIDDLE BROILER SHUT OFF VALVE - INSTALLED BY OTHERS BAFFLE PER NFPA 96 (2017) 12.1.2.5 Tank #1 - 4 Gallon - 12 POINTS MAX Appliance Noz Qty Noz Type Flow Pts Total Pts FRYER 1 F 2 2 CHARBROILER 1 GRW 1 1 12" RANGE 1 R 1 1 36" RANGE 2 R 1 2 GRIDDLE 1 ADP 1 1 PLENUM 1 ADP 1 1 DUCT 2 ADP 1 2 Total Flow Points 10 MU CONNECTION TO MAKE UP AIR FAN, SHUT DOWN UPON ACTIVATION (CONNECTION BY OTHERS) E ELECTRIC DISCONNECT, SHUT DOWN UPON ACTIVATION (CONNECTION BY OTHERS) z EMT 0 42" - 48" REMOTE PULL STATION SHALL BE INSTALLED 42" - 48" ABOVE THE FINISHED FLOOR AND A DISTANCE OF AT LEAST 1 OFT FROM THE HAZARD BUT NOT MORE THAN 20FT. IT SHALL BE INSTALLED IN THE PATH OF EXIT AND REQUIRE A MAXIMUM FORCE OF 40 LBS AND A MAXIMUM MOVEMENT OF 14" FOR ACTUATION CLASS K WET CHEMICAL EXTINGUISHER SHALL BE INSTALLED 42" -48" ABOVE THE FINISHED FLOOR PRE-ENGINEERED SYSTEM SHOP DRAWING ONLY —SCALE: 1/4"=1'-0"