REVIEWED Unit SpecificationsTRAiNE® Job Name: GENSCO STOCK Prepared By: Unit Tag: YSC092H3RMA1 X REVIEWED Quantity: 1 BY CITY OF EDMONDS Trane Precedent Gas/Electric Packaged ROOTIOP RECEIVED Aug 18 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Application Unit Size pp y an Z erna imensions (in.) Weight EER IE- External '� DX cooling, 7.5 Ton Dual Airflow Static Height Width Length Minimum Maximum 11.2 EER 13.40 gas heat compressor Pressure 3000 cfm 0.500 in H2O 3.91 ft 4.44 ft 7.39 ft 847.0 lb 1182.0 lb SupplyFan/Drive/ MotorType Multi speed fan Voltage/phase/hertz 208-230/60/3 MCA 43.00 A MOP 50.00 A Controls Unit Controls Microprocessor controls 3ph E111111111111111= NINE,— Entering Dry Bulb 80.00 F Entering Wet Bulb 67.00 F Ambient Temp 95.00 F Leaving Coil Dry Bulb 57.24 F Leaving Coil Wet Bulb 56.76 F Leaving Unit Dry Bulb 58.35 F Leaving Unit Wet Bulb 57.19 F 006. Refrigeration System Options Leaving Dew Point 56.45 F Heating Stages 1 Output Heating Capacity 121.50 MBh Output Heating Capacity with Fan 123.81 MBh Heating EAT 70.00 F Heating LAT 107.80 F Heating Temp Rise 37.80 F Indoor Fan Data Type FC Centrifugal Drive Type Belt Indoor Fan Performance Airflow 3000 cfm Design ESP 0.500 in H2O Component SP 0.000 in H2O Total SP 0.500 in H2O Indoor Motor Operating Power 0.67 bhp Indoor Motor Power 0.50 kW Indoor RPM 1024 rpm ' .door Fan FLA 3.30 A Capacity Gross Total 94.81 MBh Gross Sensible 73.76 MBh Net Total 92.49 MBh Net Sensible 71.44 MBh Fan Motor Heat 2.31 MBh Refrig Charge -circuit 1 3.8 lb Refrig Charge -circuit 2 3.6 lb Outdoor Fan Data Type Propeller Fan Quantity 1 Drive Type Direct Outdoor Fan Performance Outdoor Motor Power 0.67 kW Condenser Fan FLA 3.30 A Exhaust Fan Data Type FC Centrifugal Drive Type Direct Exhaust Fan Performance Exhaust Fan FLA 7.30 A 2018-07-05 19:33:52Z Page 1 of 9 TRAiNE® Job Name: GENSCO STOCK Prepared By: Unit Tag:YSC092H3RMA1X Quantity: 1 Compressor Sect Power 6.67 kW Circuit 1 RLA 14.50 A Circuit 2 RLA 14.00 A 2018-07-05 19:33:52Z Page 2 of 9 TRAINS® Job Name: GENSCO STOCK Prepared By: Unit Tag:YSC092H3RMAlX Quantity: 1 EVAPORATOR SECTION ACCESS PANEL CONDENSATE DRAIN (ALT) 3A"-14 IN PT DIA. HOLE 4 V4'I 27 50" 47 7I8" 1I2" NPT GAS CON NECTION {80M BH & 120M BH ) 3!4"NPT GAS CONNECTION [150MBH,200M5H &250MBH] THROUGH THE BASE CONDENSATE 4118" TOP PANEL CONDENSER FAN ONDENSER COIL UNIT CONTROLWIRE 718"DIA HOLE SERVICE GAUGE PORTACCESS 1 318"DIA HOLE NIT POWER WIRE �CONTROLAND COMPRESSOR ACCESS PANEL PACKAGED GAS / ELECTRICAL ISOMETRIC VIEW —27 518' —1 I I I I I I I I I I I I I I I I 33' I 32 118" IMF I SUPPLY I I I 1 I RETURN 1 4" 1 7 112" 9 718"L17 1f2' �1350" PLAN VIEW UNIT DIMENSION DRAWING RETURN 32114" 2370' SUPPLY L 00 00 4314' 19 114" 9 318" 16 314" 3 7I8' CONDENSATE 8& 518" PACKAGED GAS! ELECTRI! DIMENSION DRAWING NOTES: 1 . TH R U -THE -BASE ELE CTR ICAL IS NOT STAN DARD O N ALL U N ITS. 2. VERIFYALL DIM EN SION S WITH INSTALLER DDCU MENTS BEFORE INSTALLATION. HORIZONTAL A1R FLOW 2018-07-05 19:33:52Z Page 3 of 9 TRAIVE® Job Name: GENSCO STOCK Prepared By: Unit Tag:YSC092H3RMA1X Quantity: 1 ELECTRICAL 1 GENERAL DATA (2X4)(0) GENERAL HEATING PERFORMANCE Model: YSCO2H Oversized M DtDr HEATING -GENERAL DATA Unit Operating Voltage: 187-253 MCA: NIA Unit Primary Voltage: 2r03 MFS: NIA Heating Model: Model:BTU Medium M&diu}0I1i}5,00i} UnitSecondaryVoRage 230 MCB: NIA Heating ]: U nit H ertz: 6l} Heating 0utput(BTU ]: 120,00W84,000 U nit P h ase: 3 N a,,. Burners: 3 N o. Stages 2 EER 11.2 Standard M otor Field Installed Oversized M otcr Gas Inlet Pressure MCA 39.0 MCA NIA NaturaIGas (Min/Mbc): 4.5I14 MFS: 50.0 MFS: NIA LP CM infMax) 11.0114.0 MCB: 50.0 MCB: NIA Gas Pipe Connection Size: 34" INDOOR MOTOR Standard M otor Oversized Motor Field Installed Oversized M otor Number. Number: NIA Number: NIA Horsepower Horsepower. NIA Horsepower: NIA M Dtor Speed (RP M]: M otor Speed CRP M] NIA M otor Speed (RP M k NIA Phase Phase NIA Phase NIA Full Load Amps: Full Load Amps: NIA Full Load Amps: NIA Locked RotorAmps LockedRDtorAmps: NIA LockedRotorAmps: NIA COMPRESSOR Circuit 1,2 OUTDOORMOTOR Number: 1 Number: 1 H Drse pow& r: 3.7I3.1 H DrsepD wer: 0.7 Ph ase: 3 M DtD r Speed (RP M): 1100 Rated Load Amps: 14.5I14.0 Phase: 1 Locked Rotor Am ps: 98.0I83.1 Full Load Amps: 3.3 Locked RotorAmps 12.3 POWER EXHAUST ACCESSORY ta] FILTERS REFRIGERANT t2) (Field Installed Power E)Khaust] Type Phase: NIA Type: Throwaway Horsepower: NIA Furnished: Yes Factory Charge MDtorSpeed (RPM ): NIA Number 4 Circuit#1 3.8113 Full Load Amps: NIA Recommended 2Vx25—xZ" Circuit#2 3.6 to Locked Rotor Am ps: NIA NOTES 1. M aximum (HACR] Circuit Breaker sizing is for installations in the United States only. 2. Refrigerant charge is an approxim atevalue. For a more precisevalue, see unit nameplate and service instructions. 3. Value does not in elude Power Exh aust Accessory. 4. Value includes oversized motor. 5. Value does not in elude Power Exh gust Accessory. 6. EER is rated atAH RI conditions and in accordance with DDE test procedures. 2018-07-05 19:33:52Z Page 4 of 9 TRAINS® Job Name: GENSCO STOCK Prepared By: Unit Tag:YSC092H3RMA1X Quantity: 1 PACKAGED GAS 1 ELECTRICAL CORNER WEIGHT INSTALLED ACCESSORIES NET WEIGHT DATA ACCESSORY WEIGHTS ECONOMIZER MOTORIZED OUTSIDE AIR DAMPER MANUAL OUTSIDE AIR DAM PER BAROMETRIC RELIEF OVERSIZED MOTOR BELT DRIVE MOTOR POWER EXHAUST THROUGHT THE BASE ELECTRICALIGAS (FIDPS) UNIT MOUNTED CIRCUIT BREAKER (FIDPS) UNIT MOUNTED DISCONNECT (FIDPS) POWERED CONVENIENCE OUTLET (FIDPS) HINGED DOORS (FIDPS) HAILGUARD SMOKE DETECTOR, SUPPLYI RETURN NOVAR CONTROL STAINLESS STEELHEAT EXCHANGER REHEAT ROOFCURB BASIC UNIT WEIGHTS CORNER WEIGHTS CENTER OFGRAVITIY SHIPPING NET 265.6Ih ;� 173.OIh (f}LENGHT (F}WIDTH 990.0lb Sd7.01b 249.1}IG 160.01h 46' 21" N OTE: 1. Al weightsare apprDAMate. 2. Weights far Dptionsthat are not list refertD Installation guide. 3. The actual weight are listed Dn the unit nameplate. d. RefertD unit nameplate and installation guide for weights before scheduling transportation and installation ❑funit. 5. The weightshown represents the typical unit Dperating weight forthe configuration selected. Estimated at +1_ 10 % Dfth a nameplate weight. . 6. Verify weight, connection, and all dimension with installer documants hefare installation. 7. Corner weights are given fDrinfDrmatlDn only. 8. N gUShipping weight of optional accessoriesshDuld be addedtD unit weight when Drdering factory Dr field installed accessories PACKAGED GAS I ELECTRICAL RIGGING AND CENTER OF GRAVITY 2018-07-05 19:33:52Z Page 5 of 9 TRAINS® Job Name: GENSCO STOCK Prepared By: Unit Tag:YSC092H3RMAlX Quantity: 1 CLEARANCE 36" QOWNFLOW CLEARANCE36" HORIZONTAL CLEARANCE 18" ROOF OPENING UNITOUTLINE— PACKAGER GAS/ELECTRIC CLEARANCE CLEARANCE FROM TOP OF UNIT72' CLEARANCE48" GLEARANGE36" I 53 114 46" 88 E18" PACKAGED GAS! ELECTRIC DOWN FLOW TYPICAL ROOF OPENING 2018-07-05 19:33:52Z Page 6 of 9 rJaWE. Job Name: GENSCO STOCK Prepared By: Unit Tag: YSC092H3RMA1 X Quantity: 1 General The units shall be convertible airflow. The operating range shall be between 1150F and 0°F in cooling as standard from the factory for units with microprocessor controls. Operating range for units with electromechanical controls shall be between 1150F and 40°F. Cooling performance shall be rated in accordance with ARI testing procedures. All units shall be factory assembled, internally wired, fully charged with R-410A, and 100 percent run tested to check cooling operation, fan and blower rotation, and control sequence before leaving the factory. Wiring internal to the unit shall be colored and numbered for simplified identification. Units shall be cULus listed and labeled, classified in accordance for Central Cooling Air Conditioners. Casing Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces shall be cleaned, phosphatized, and finished with a weather -resistant baked enamel finish. Unit's surface shall be tested 672 hours in a salt spray test in compliance with ASTM 13117. Cabinet construction shall allow for all maintenance on one side of the unit. Service panels shall have lifting handles and be removed and reinstalled by removing two fasteners while providing a water and air tight seal. All exposed vertical panels and top covers in the indoor air section shall be insulated with a cleanable foil - faced, fire -retardant permanent, odorless glass fiber material. The base of the unit shall be insulated with 1/8 inch, foil -faced, closed -cell insulation. All insulation edges shall be either captured or sealed. The unit's base pan shall have no penetrations within the perimeter of the curb other than the raised 1 1/8 inch high downflow supply/return openings to provide an added water integrity precaution, if the condensate drain backs up. The base of the unit shall have provisions for forklift and crane lifting, with forklift capabilities on three sides of the unit. Unit Top The top cover shall be one piece construction or, where seams exist, it shall be double -hemmed and gasket -sealed. The ribbed top adds extra strength and enhances water removal from unit top. Filters Throwaway filters shall be standard on all units. Optional 2-inch MERV 8 and MERV 13 filters shall also be available. Compressors All units shall have direct -drive, hermetic, scroll type compressors with centrifugal type oil pumps. Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus 10 percent of unit nameplate voltage. Internal overloads shall be provided with the scroll compressors. Dual compressors are outstanding for humidity control, light load cooling conditions and system back- up applications. Dual compressors are available on 7'/2-10 ton models and allow for efficient cooling utilizing 3-stages of compressor operation for all high efficiency models. Indoor Fan The following units shall be equipped with a direct drive plenum fan design (T/YSC120F,T/YHC074F, T/YHC092F,T/YHC102F, 120F). Plenum fan design shall include a backward -curved fan wheel along with an external rotor direct drive variable speed indoor motor. All plenum fan designs will have a variable speed adjustment potentiometer located in the control box. 3 to 5 ton units (high efficiency 3-phase with optional motor) are belt driven, FC centrifugal fans with adjustable motor sheaves. 3 to 5 ton units (standard and high efficiency 3-phase) have multispeed, direct drive motors. All 6 to 8'/2 ton units (standard efficiency) shall have belt drive motors with an adjustable idler -arm assembly for quick -adjustment to fan belts and motor sheaves. All motors shall be thermally protected. All 10 tons, 6 ton (074), 7'/2 to 81/2 (high efficiency) units have variable speed direct drive motors. All indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT). 2018-07-05 19:33:52Z Page 7 of 9 ��® Job Name: GENSCO STOCK 0 Prepared By: Unit Tag:YSC092H3RMA1X Quantity: 1 Outdoor Fans The outdoor fan shall be direct -drive, statically and dynamically balanced, draw -through in the vertical discharge position. The fan motor shall be permanently lubricated and shall have built-in thermal overload protection. Multi -Speed Indoor Fan System Multi -speed indoor fan system is designed for use in applications for meeting the minimum requirement of CA Title 24. This system incorporates a multi -speed fan control to change the speed of the fan to 67% of full airflow based off of compressor stages. Evaporator and Condenser Coils Internally finned, 5/16" copper tubes mechanically bonded to a configured aluminum plate fin shall be standard. Evaporator coils are standard for all 3 to 10 ton standard efficiency models. Microchannel condenser coils are standard for all 3 to 10 ton standard efficiency models and 4, 5, 6, 7.5, 8.5 ton high efficiency models. The microchannel type condenser coil is not offered on the 4 and 5 ton dehumidification model. Due to flat streamlined tubes with small ports, and metallurgical tube -to -fin bond, microchannel coil has better heat transfer performance. Microchannel condenser coil can reduce system refrigerant charge by up to 50% because of smaller internal volume, which leads to better compressor reliability. Compact all -aluminum microchannel coils also help to reduce the unit weight. These all aluminum coils are recyclable. Galvanic corrosion is also minimized due to all aluminum construction. Strong aluminum brazed structure provides better fin protection. In addition, flat streamlined tubes also make microchannel coils more dust resistant and easier to clean. Coils shall be leak tested at the factory to ensure the pressure integrity. The evaporator coil and condenser coil shall be leak tested to 600 psig. The assembled unit shall be leak tested to 465 psig. The condenser coil shall have a patent pending 1+1+1 hybrid coil designed with slight gaps for ease of cleaning. A plastic, dual -sloped, removable and reversible condensate drain pan with through -the -base condensate drain is standard. Controls Unit shall be completely factory -wired with necessary controls and contactor pressure lugs or terminal block for power wiring. Unit shall provide an external location for mounting a fused disconnect device. A choice of microprocessor or electromechanical controls shall be available. Microprocessor controls provide for all 24V control functions. The resident control algorithms shall make all heating, cooling, and/or ventilating decisions in response to electronic signals from sensors measuring indoor and outdoor temperatures. The control algorithm maintains accurate temperature control, minimizes drift from set point, and provides better building comfort. A centralized microprocessor shall provide anti - short cycle timing and time delay between compressors to provide a higher level of machine protection. 24-volt electromechanical control circuit shall include control transformer and contactor High Pressure Control All units include High Pressure Cutout as standard. Phase monitor Phase monitor shall provide 100% protection for motors and compressors against problems caused by phase loss, phase imbalance, and phase reversal. Phase monitor is equipped with an LED that provides an ON or FAULT indicator. There are no field adjustments. The module will automatically reset from a fault condition. Refrigerant Circuits Each refrigerant circuit offer thermal expansion valve as standard. Service pressure ports, and refrigerant line filter driers are factory -installed as standard. An area shall be provided for replacement suction line driers. 2018-07-05 19:33:52Z Page 8 of 9 TRANS® Job Name: GENSCO STOCK Prepared By: Unit Tag:YSC092H3RMA1X Quantity: 1 Gas Heating Section The heating section shall have a progressive tubular heat exchanger design using stainless steel burners and corrosion resistant steel throughout. An induced draft combustion blower shall be used to pull the combustion products through the firing tubes. The heater shall use a direct spark ignition (DSI) system. On initial call for heat, the combustion blower shall purge the heat exchanger for 20 seconds before ignition After three unsuccessful ignition attempts, the entire heating system shall be locked out until manually reset at the thermostat/zone sensor. Units shall be suitable for use with natural gas or propane (field -installed kit) and also comply with the California requirement for low NOx emissions (Gas/Electric Only). Human Interface The Human Interface shall have a 5 inch color touchscreen display that conforms to FCC Part 15 Class B with an Ingress Protection Rating of IP24.The display text shall be readable by a person with 20/20 vision at a distance of 3 feet and 60' angle at lighting levels ranging from 100 lux - 25,000 lux. Also, the display shall operate at temperatures of -40' C to 70' C. Firmware and unit configurations shall be able to be restored via a USB storage device. 2018-07-05 19:33:52Z Page 9 of 9 Installation, Operation, and Maintenance Packaged Rooftop Air Conditioners Precedent"' —Gas/Electric 5 to 10 Tons-50 Hz Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment. April 2020 RT-SVX38D-EN Introduction Read this manual thoroughly before operating or servicing this unit. Warnings, Cautions, and Notices Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions. The three types of advisories are defined as follows Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices. Indicates a situation that could result in equipment or property -damage only accidents. Important Environmental Concerns Scientific research has shown that certain man-made chemicals can affect the earth's naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants -including industry replacements for CFCs such as HCFCs and HFCs. Important Responsible Refrigerant Practices Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them. Proper Field Wiring and Grounding Required! Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Personal Protective Equipment (PPE) Required! Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below: Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE. • When working with or around hazardous chemicals, ALWAYS refertothe appropriate SDSand OSHA/GHS (Global Harmonized System of Classification and Labeling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions. If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country -specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE. © 2020 RT-SVX38D-EN Introduction Copyright This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revisethis publication at any time, and to make changes to its content without obligation to notify any person of such revision or change. Trademarks All trademarks referenced in this document are the trademarks of their respective owners. Revision History RT-SVX38C-EN (15 March 2015) • General data 6 to 10 ton updates RT-SVX38 D-E N Table of Contents Table of Contents Introduction ............................. 2 Warnings, Cautions, and Notices ........ 2 Copyright ............................. 3 Table of Contents ........................ 4 Model Number Description .............. 5 General Information ..................... 6 Unit Dimensions ........................ 10 Installation ............................. 16 Pre -Installation ....................... 16 Procedure ........................... 16 Foundation .......................... 17 Ductwork ............................ 17 Roof Curb ........................... 18 General Unit Requirements ............ 19 Horizontal Discharge Conversion (5Ton Units) 20 Horizontal Discharge Conversion (6 to 10 Ton Units) ............................... 21 Requirements for Gas Heat ............ 22 Condensate Drain Configuration ........ 22 Filter Installation ...................... 23 Field -Installed Power Wiring ........... 23 Main Unit Power ..................... 23 Space Temperature Averaging (ReliaTeIT"' On- ly) .................................. 25 Pre -Start ............................... 29 Voltage Imbalance .................... 29 Electrical Phasing (Three -Phase Motors) . 29 Test Modes .......................... 31 Unit Start -Up ........................... 32 Verifying Proper Air Flow .............. 32 Economizer Start -Up .................. 32 Compressor Start -Up ................. 33 Final System Setup ................... 33 Maintenance ........................... 34 Fan Belt Adjustment —Belt Drive Units .. 34 Monthly Maintenance ................. 34 Annual Maintenance ...................36 Final Process ..........................37 Troubleshooting .........................38 ReliaTeIT"' Control .....................38 System Status Checkout Procedure ......38 Zone Temperature Sensor (ZTS) Service Indi- cator.................................40 Clogged Filter Switch ..................40 Fan Failure Switch .....................40 Condensate Overflow Switch ...........40 Zone Temperature Sensor (ZTS) Test ....40 Unit Economizer Control (ECA) Troubleshoot- ing..................................41 Resetting Cooling and Ignition Lockouts ..42 Unit Wiring Diagrams Numbers ...........43 Limited Warranty ........................44 Combination Gas Electric Air Conditioner .44 Combination Gas Electric Air Conditioner .44 4 RT-SVX38D-EN Model Number Description Y S C 0 6 1 2 3 4 5 Digit 1—Unit Type T DX cooling Y DX cooling, gas heat W Packaged heat pump Digit 2—Efficiency S Standard Efficiency Digit 3—Airflow C Convertible Digit 4,5,6—Nominal Gross Cooling Capacity (MBh) 060 5 ton (17.6 kW) 072 6 ton (21.1 kW) 090 71/2 ton (26.4 kW) 102 81/2 ton (29.9 kW) 120 10 ton (35.1 kW) Digit 7—Major Design Sequence E R-410A refrigerant Digit 8—Voltage Selection D 380-415/50/3 Digit 9—Unit Controls R ReliaTelTI microprocessor K European Digit 10—Heating Capacity 0 No electric heat? L Low heat$ H High heat$ Digit 11—Minor Design Sequence A First sequence Digit 12,13—Service Sequence ** Factory assigned Digit 14—Fresh Air Selection 0 No Fresh air A Manual outside air damper 0-50%1 B Motorized Outside air damper 0-50% C Economizer, dry bulb 0-100% without barometric relief4 D Economizer, dry bulb 0-100%with barometric relief4 E Economizer, reference enthalpy 0-100% without barometric relief3.4 F Economizer, reference enthalpy 0-100% with barometric relief3,4 G Economizer, comparative enthalpy 0-100%without barometric relief3,4 H Economizer, comparative enthalpy 0-100%with barometric relief3,4 Digit 15—Supply Fan/Drive Type/ Motor 0 Standard drive 1 Oversized motor 0 E 3 R 6 7 8 9 Digit 16—Hinged Service Access/Filters 0 Standard panels/standard filters A Hinged access panels/standard filters B Standard panels/2" MERV 8 filters C Hinged access panels/2" MERV 8 filters D Standard panels/2" MERV 13 filters E Hinged access panels/2" MERV 13 filters Digit 17—Condenser Coil Protection 0 Standard coil 1 Standard coil with hail guard 2 Black epoxy pre -coated condenser coil 3 Black epoxy pre -coated Condenser coil with hail guard 4 CompleteCoatT" condenser coi19 5 CompleteCoatT" condenser coil with hail guard9 Digit 18—Through the Base Provisions 0 No through -the -base provisions Digit 19—Disconnect/Circuit Breaker (three-phase only) 0 No disconnect/no circuit breaker Digit 20—Convenience Outlet 0 No convenience outlet Digit 21—Communications Options 0 No communications interface 1 Trane communications interface 2 LonTalk® communications interface Digit 22—Refrigeration System Option 0 Standard refrigeration systems Digit 23—Refrigeration Controls Note: Applicable to digit 7 = E 0 No refrigeration contro12 1 FrostatT`" 6 Digit 24—Smoke Detector 0 No smoke detector Digit 25—System Monitoring Controls 0 No monitoring control 1 Clogged filter switch 2 Fan failure switch 3 Discharge air sensing tube 4 Clogged filter switch and fan failure switch 5 Clogged filter switch and discharge air sensing tube 6 Fan failure switch and discharge air sensing tube L A 10 11 12 13 7 Clogged filter switch, fan failure switch and discharge air sensing tube A Condensate drain pan overflow switch B Clogged filter switch and condensate drain pan overflow switch C Fan failure switch and condensate drain pan overflow switch D Discharge air sensing and condensate drain pan overflow switch E Clogged filter switch, fan failure switch and condensate drain pan overflow switch F Clogged filter switch, discharge air sensing tube and condensate drain pan overflow switch G Fan failure switch, discharge air sensing tube and condensate drain pan overflow switch H Clogged filter switch, fan failure switch, discharge air sensing and condensate drain pan overflow switch Digit 26—System Monitoring Controls 0 No monitoring controls A Demand control ventilation (CO2)10 Digit 27—Unit Hardware Enhancements 0 No enhancements 1 Stainless steel drain pan Model Number Notes 1. Manual outside air damper will ship factory supplied within the unit, but must be field installed. 2. High pressure control crankcase heaters are standard on all units. 3. Belt drive is standard on all units. 4. Economizer with barometric relief is for downflow configured units only. Order economizer without barometric relief for horizontal configuration. Barometric relief for horizontal configured units must be ordered as field -installed accessory. 5. Standard metering devices are TXVs. 6. Frostat is available as factory -installed option only. 7. Electric heaters are available only for field -installed options. 8. Available only for gas heat models. 9. Not available on heat pumps. 10. Demand control ventilation option includes wiring only. The CO2 sensor is a field -installed only option. RT-SVX38 D-E N 5 General Information Unit Inspection As soon as the unit arrives at the job site • Verifythatthe nameplate data matches the data on the sales order and bill of lading (including electrical data). • Verify that the power supply complies with the unit nameplate specifications. • Visually inspect the exterior of the unit, including the roof, for signs of shipping damage. If the job site inspection of the unit reveals damage or material shortages, file a claim with the carrier immediately. Specify the type and extent of the damage on the "bill of lading" before signing. • Visually inspect the internal components for shipping damage as soon as possible after delivery and before it is stored. Do not walk on the sheet metal base pans. • If concealed damage is discovered, notify the carrier's terminal of damage immediately by phone and by mail. Concealed damage must be reported within 15 days. • Request an immediate joint inspection of the damage by the carrier and the consignee. Do not remove damaged material from the receiving location. Take photos of the damage, if possible. The owner must provide reasonable evidence that the damage did not occur after delivery. • Notify the appropriate sales representative before installing or repairing a damaged unit. Storage Take precautions to prevent condensate from forming inside the unit's electrical compartments and motors in the following situations: • The unit is stored before it is installed. • The unit is set on the roof curb, and temporary heat is provided in the building. Isolate all side panel service entrances and base pan openings (e.g., conduit holes, Supply Air and Return Air openings, and flue openings) from the ambient air until the unit is ready for start-up. Note: Do not use the unit's heater for temporary heat without first completing the start-up procedure detailed under "Unit Start -Up," p. 32. The manufacturer will not assume any responsibility for equipment damage resulting from condensate accumulation on the unit's electrical and/or mechanical components. Unit Nameplate A Mylar unit nameplate is located on the unit's corner support next to the filter access panel. It includes the unit model number, serial number, electrical characteristics, refrigerant charge, as well as other pertinent unit data. Compressor Nameplate The nameplateforthe compressors are located on the side of the compressor. Unit Description Before shipment, each unit is leak tested, dehydrated, charged with refrigerant and compressor oil, and run tested for proper control operation. The condenser coils are either aluminum fin, mechanically bonded to copper tubing or all aluminum microchannel. Direct -drive, vertical discharge condenser fans are provided with built-in thermal overload protection. There are two control systems offered for these units. The electromechanical control option uses a thermostat to perform unit functions. The ReliaTelT"' control module is a microelectronic control system that is referred to as "refrigeration module" (RTRM). The acronym RTRM is used extensively throughout this document when referring to the control system network. These modules through proportional/integral control algorithms perform specific unitfunctions that govern unit operation in response to zone temperature, supply air temperature, and/or humidity conditions depending on the application. The stages of capacity control for these units are achieved by starting and stopping the compressors. The RTRM is mounted in the control panel and is factory wired to the respective internal components. The RTRM receives and interprets information from other unit modules, sensors, remote panels, and customer binary contacts to satisfy the applicable request for cooling. Economizer Control Actuator (Optional) ReliaTel"' Control The ECA monitors the mixed air temperature, return air temperature, minimum position setpoint (local or remote), power exhaust setpoint, CO2 setpoint, CO2, and ambient dry bulb/enthalpy sensor or comparative humidity (return air humidity against ambient humidity) sensors, if selected, to control dampers to an accuracy of +/- 5% of stroke. The actuator is spring returned to the closed position any time that power is lost to the unit. It is capable of delivering up to 25 inch pounds of torque and is powered by 24 VAC. RTCI—ReliaTelT" Trane Communication Interface (Optional) This module is used when the application calls for an ICSTM building management type control system. It allows the control and monitoring of the system through an ICS panel. The module can be ordered from the factory or ordered as a kit to be field installed. Follow the RT-SVX38D-EN installation instruction that ships with each kit when field installation is necessary. RLCI—ReliaTelT°" LonTalk® Communication Interface (Optional) This module is used when the application calls for an ICSTM building management type control system that is LonTalk. It allowsthe control and monitoring of the system through an ICS panel. The module can be ordered from the factory or ordered as a kit to be field installed. Follow the installation instruction that ships with each kit when field installation is necessary. RBCI—ReliaTelT"" BACnetTM Communications Interface (Optional) This module is used when the application calls for an open BACnet protocol. It allows the control and monitoring of the system through an ICS panel. The module can be ordered from the factory or as a kit to be field installed. Followthe installation instructions that ships with each kit when field installation is necessary. RTOM—ReliaTelTM Options Module (Optional) The RTOM monitorsthe supply fan proving, clogged filter, supply air temperature, exhaust fan setpoint, supply air tempering, FrostatTl and smoke detector. Refer to system input devices and functions for operation. System Input Devices and Functions The RTRM must have a zone sensor or thermostat input in order to operate the unit. The flexibility of having several mode capabilities depends upon the type of zone sensor or thermostat selected to interface with the RTRM. The descriptions of the following basic Input Devices used within the RTRM network areto acquaintthe operatorwith their function as they interface with the various modules. Refer to the unit's electrical schematic for the specific module connections. The following controls are available from the factory for field installation. Supply Fan Failure Input (Optional) The Fan Failure Switch can be connected to sense indoor fan operation: FFS (Fan Failure Switch) —If air flow through the unit is not proven by the differential pressure switch connected to the RTOM (factory setpoint 0.07" w.c.) within 40 seconds nominally, the RTRM will shut off all mechanical operations, lock the system out, send a diagnostic to ICS, and the SERVICE outputwill flash. The system will remain locked out until a reset is initiated either manually or through ICS. Clogged Filter Switch (Optional) The unit -mounted clogged filter switch monitors the pressure differential across the return air filters. It is mounted in the filter section and is connected to the General Information RTOM. A diagnostic SERVICE signal is sent to the remote panel if the pressure differential acrossthe filters is at least 0.5" w.c. The contacts will automatically open when the pressure differential across the filters decreases to approximately 0.4" w.c. The clogged filter output is energized when the supply fan is operating and the clogged filter switch has been closed for at least 2 minutes. The system will continue to operate regardless of the status of the filter switch. Note: On units equipped with factory installed MERV 13 filters, a clogged filter switch with different pressure settings will be installed. This switch will close when the differential pressure is approximately 0.8' w.c. and open when the differential falls to 0.7" w.c. Condensate Drain Pan Overflow Switch (Optional) ReliaTel Option This input incorporates the Condensate Overflow Switch (COF) mounted on the drain pan and the ReliaTel options module (RTOM). When the condensate level reaches the trip point for 6 continuous seconds, the RTOM will shut down all unit functions until the overflow condition has cleared. The unit will return to normal operation after six continuous seconds with the COF in a non -tripped condition. If the condensate level causes unit shutdown more than two times in a 3-day period, the unit will be locked -out of operation requiring manual reset of diagnostic system through zone sensor or building automation system (BAS). Cycling unit power will also clear the fault. Compressor Disable (CPR1/2) This input incorporates the low pressure control (LPC) of each refrigeration circuit and can be activated by opening a field -supplied contact installed on the LTB. If this circuit is open before the compressor is started, the compressor will not be allowed to operate. Anytime this circuit is opened for 1 continuous second during compressor operation, the compressor for that circuit is immediately turned "Off". The compressor will not be allowed to restart for a minimum of 3 minutes should the contacts close. If four consecutive open conditions occur during the first three minutes of operation, the compressor for that circuit will be locked out, a diagnostic communicated to the remote panel (if installed), and a manual reset will be required to restart the compressor. Low Pressure Control ReliaTel Control When the LPC is opened for 1 continuous second, the compressor for that circuit is turned off immediately. The compressor will not be allowed to restart for a minimum of 3 minutes. RT-SVX38 D-E N General Information If four consecutive open conditions occur during an active call for cooling, the compressor will be locked out, a diagnostic communicated to ICST"", if applicable, and a manual reset required to restart the compressor. On dual compressor units only the affected compressor circuit is locked out. High Pressure Control ReliaTel Control The high pressure controls are wired in series between the compressor outputs on the RTRM and the compressor contactor coils. If the high pressure control switch opens, the RTRM senses a lack of current while calling for cooling and locks the compressor out. If four consecutive open conditions occur during an active call for cooling, the compressor will be locked out, a diagnostic communicated to ICS, if applicable, and a manual reset required to restart the compressor. On dual compressor units only the affected compressor circuit is locked out. Lead/Lag Control (Dual Circuit Only) ReliaTel Control Only Lead/Lag is a selectable input located on the RTRM. The RTRM is configured from the factory with the Lead/Lag control disabled. To activate the Lead/Lag function, simply cut the wire connected to J3-8 at the RTRM. When it is activated, each time the designated lead compressor is shut off due to the load being satisfied, the lead compressor or refrigeration circuit switches. When the RTRM is powered up,e.g., aftera power failure, the control will default to the number one circuit compressor. Zone Sensor Module (ZSM) (BAYSENS106* This electronic sensor features three system switch settings (Heat, Cool, and Off) and two fan settings (On and Auto). It is a manual changeover control with single setpoint. (Cooling Setpoint Only) Zone Sensor Module (ZSM) (BAYSENS108* This electronic sensor features four system switch settings (Heat, Cool, Auto, and Off) and two fan settings (On and Auto). It is a manual or auto changeover control with dual setpoint capability. It can be used with a remote zone temperature sensor BAYSENS077*. Zone Sensor (BAYSENS110*) This electronic sensor features four system switch settings (Heat, Cool, Auto, and Off) and two fan settings (On and Auto) with four system status LEDs. It is a manual or auto changeover control with dual setpoint capability. It can be used with a remote zone temperature sensor BAYSENS077*. Programmable Zone Sensor— (BAYSENS1 19*) This 7-day programmable sensor features 2, 3, or 4 periods for Occupied or Unoccupied programming per day. If the power is interrupted, the program is retained in permanent memory. If power is off for an extended period of time, only the clock and day may have to be reset. The Zone Sensor allows selection of 2, 3, or 4 system modes (Heat, Cool, Auto, and Off), two fan modes (On and Auto). It has dual temperature selection with programmable start time capability. The occupied cooling set point ranges between 45°F and 98°F. The heating set point ranges between 43°F and 96°F. A liquid crystal display (LCD) displays zone temperature, temperature set points, day of the week, time, and operational mode symbols. The Option Menu is used to enable or disable applicable functions, e.g., morning warm-up, economizer minimum position override during unoccupied status, Fahrenheit or Centigrade, supply air tempering, remote zone temperature sensor, 12/24 hour time display, smart fan, and computed recovery. During an occupied period, an auxiliary relay rated for 1.25 amps at 30 volts AC with one set of single pole double throw contacts is activated. Status Inputs (4 Wires Optional) The ZSM can be wired to receive four operating status signals from the RTRM (HEAT, COOL, SYSTEM ON, SERVICE). Four wires from the RTRM should be connected to the appropriate terminals (7, 8, 9, and 10) on the ZSM. Remote Zone Sensor (BAYSENS073*) This electronic sensor features remote zone sensing and timed override with override cancellation. It is used with a Trane Integrated ComfortT`" building management system. Remote Zone Sensor (BAYSENS074*) This electronic sensor features single setpoint capability and timed override with override cancellation. It is used with a Trane Integrated ComfortT" building management system. Remote Zone Sensor (BAYSENS016*) This bullet type temperature sensor can be used for outside air (ambient) sensing, return air temperature sensing, supply air temperature sensing, remote temperature sensing (uncovered). Wiring proceduresvary according to the particular application and equipment involved. Refer to the unit's wiring diagrams for proper connections. Remote Zone Sensor (BAYSENS077*) This electronic sensor can be used with BAYSENS106*, 108*, 110*, 119* remote panels. When this sensor is wired to a BAYSENS119* Remote Panel,wiring must be 18AWG Shielded Twisted Pair (Belden 8760 or equivalent). Referto the specific remote panel for wiring details. RT-SVX38D-EN Wireless Zone Sensor (BAYSENS050) This electronic sensor features five system settings (Auto, Off, Cool, Heat, and Emergency Heat) as well as On and Auto fan settings. It is a manual or auto changeover control with dual setpoint capability. Other features include a timed override function, lockable system settings, and Fahrenheit or Celsius temperature display. Included with the wireless zone sensor is a receiver that is to be mounted inside the unit, a mounting bracket, and a wire harness. High Temperature Sensor (BAYFRST001* This sensor connects to the RTRM emergency stop input on the LTB and provides high limit "shutdown" of the unit. The sensor is used to detect high temperatures due to a high thermal event in the air conditioning or ventilation ducts. The sensor is designed to mount directly to the sheet metal duct. Each kit contains two sensors. The return air duct sensor (X1310004001) is set to open at 135°F. The supply air duct sensor (X1310004002) is set to open at 240°F. The control can be reset after the temperature has been lowered approximately 25°F below the cutout setpoint. Evaporator Frost Control ReliaTelT"" Option This input incorporates the FrostatT11 control (FOS) mounted in the indoor coil circuit and can be activated by closing a field -supplied contact installed in parallel with the FOS. If this circuit is open before the compressor is started, the compressor will not be allowed to operate. Anytime this circuit is opened for 1 continuous second during compressor operation, the compressor for that circuit immediately turns off. The compressorwill not be allowed to restart for a minimum of 3 minutes if the FOS closes. Discharge Line Temp Switch (DLTS) The DLTS is looped in series with HPC and LPC. It prevents compressor from overheating (over 300P dome temp) in case of indoor fan failure (cooling) or outdoor fan failure (heating). Phase Monitor This sensor monitors voltage between the 3 conductors of the 3-phase power supply. Two LED lights are provided: • The green light indicates that a balanced 3-phase supply circuit is properly connected. • The red light indicates that unit operation has been prevented. There are two conditions that will prevent unit operation: • The power supply circuit is not balanced with the proper phase sequence of L1, L2, L3, for the 3 conductors of a 3-phase circuit. General Information • The line to line voltage is not between 180 volts and 633 volts. RT-SVX38 D-E N Unit Dimensions Figure 1 illustrates the minimum operating and service clearances for either a single or multiple unit installation. These clearances are the minimum distances necessary to assure adequate serviceability, cataloged unit capacity, and peak operating efficiency. Providing less than the recommended clearances may result in condenser coil starvation, "short-circuiting" of exhaust and economizer airflows, or recirculation of hot condenser air. Figure 1. Typical installation clearances for single and multiple unit applications NOTE 4 YSC060ED YSC072-120ED 10 RT-SVX38D-EN Figure 2. 5 tons standard efficiency Notes: 1. All dimensions are in inches/millimeters. 2. 1/2 NPT Gas Connection IE@eAPORACSECTION e� ACCESS PANEL ANEL ALTERNATE CONDENSATE DRAIN 3/4 - 94 NPT DIA. HOLE 69 7/8' — 42 1 4" 1749 MM_ 107� MM 1/2 NPT OAS CONNECTION `J L CONTROL AND COMPRESSOR ACCESS PANEL Figure 3. 5 tons standard efficiency —roof curb Note: All dimensions are in inches/millimeters. `\ CC l9`AM�`l CVC ^0*11 36 7/16• �443MM• `r 951 MM 25 3/16' 14 9/16• 640 MM 370 MM 263 MM 336 " V16 42 1 344 • MM S 17 7/S' / 47 (� 6670 / 1MM �F 2. apq�cF 5�8. 51 MM / TOP PANEL 5916" 14 MM 1 5/8" -19'4/ MM 112d MM Unit Dimensions CONDENSER FAN 36 1/4" 921 MM �CONDENSE9 COIL UNIT CONTROL WIRE 7/8' (22M 4) DIA. HOLE SERVICE GAUGE PORT ACCESS 9 a(S' (36MPM) DIA. HOLE UNIT POWER &A IRE 2" (51 MM) DIA. HOLE C� cCF9��,yoe ? . F 18 r91 '1 13/16' �568 MM 65 3,16• 3 MM 1656 MM yo'pi, Al 7/16• /1053 MM RT-SVX38 D-E N 11 Unit Dimensions Figure 4. 5 tons standard efficiency —unit clearance and roof opening Note: All dimensions are in inches/millimeters. CLEARANCE CLEARANCE 36" (914 MM) HORIZONTAL FLOW - 18" (457 MM) DOWNFLOW 36" (914 MM) TYPICAL ROOF OPENING CLEARANCE FROM TOP OF UNIT 72" 1 68 3/16" 40" 37" (1732 MM) (1016 MM) (940 MM) �� \ 441/2 (1130 MM) CLEARANCE 48" (1219 MM) \ CLEARANCE 36" (914 MM) Figure 5. 6, 71/2 tons standard efficiency Note: All dimensions are in inches/millimeters. TOP PANEL ALTERNATE CONDENSATE DRAIN iONNECTION 3/4 - 14 NPT DIA. HOLE 1/2" ® 470 MM 7 275/8' CONDENSER COIL 701 MM UNIT CONTROL WIRE ® 7/8' (22MM) DIA. HOLE 47 7/8" P43 885/8,.1216 MM 95/8 SERVICE GAUGE PORT ACCESS 2251 MM 244 MM 1 3/8" (35MM) DIA. HOLE 5 5/8 143 MM M UNIT POWER WIRE 1 3/8' (35MM) DIA. HOLE M 1/2 NPT GAS CONNECTION / / 353 MM (80 mbh, 120 mbh); 314 NPT GAS CONNECTION (150 mbh, 200 mbh, 250 mbh) CONTROL AND COMPRESSOR ACCESS PANEL 12 RT-SVX38D-EN Figure 6. 6, 71/2 tons standard efficiency —roof curb Note: All dimensions are in inches/millimeters. GL�PRPN/ 46 3/8 51178 MM) g /C873 MM' ' `�\✓ .� � SRN 2' —C (51 MM) C��PRPNGE Figure 7. 6, 71/2 tons standard efficiency —unit clearance and roof opening Note: All dimensions are in inches/millimeters. CLEARANCE 36" (914 MM) \ TYPICAL ROOF OPENING CLEARANCE FROM TOP OF UNIT 72" 68 3/16" 49 37" (1732 MM) (1016 MM) (940 MM) \ 441/2 /130 MM) CLEARANCE 48" (1219 MM) \f CLEARANCE 36" (914 MM) Unit Dimensions CLEARANCE 40, HORIZONTAL FLOW - 18" (457 MM) DOWN FLOW 36" (914 MM) RT-SVX38D-EN 13 Unit Dimensions Figure 8. 81/2 to 10 tons standard efficiency Note: All dimensions are in inches/millimeters. PANEL CONDENSER FAN EVAPORATOR SECTION ACCESS PANEL 46 7/8" 190 MM 4 1/4 108 MM ALTERNATE CONDENSATE DRAIN CONNECTION 3/4 - 14 NPT DIA. HOLE 241/2' ® 622 MM 27 5/8" � CONDENSER COIL 701 MM UNIT CONTROL WIRE 47 7/8" ® 7/8" (22MM) DIA. HOLE 885/81216 MM 95/8 SERVICE GAUGE PORT ACCESS 2251 MM 244 MM 41/4 M 108 MM 1 3/8' (35MM) DIA. HOLE 5 5 143 MM UNIT POWER WIRE 5 5/8 1 3/8' (35MM) DIA. HOLE 43 MM 7 5/8 94 MM 53 1/4" 1/2 NPT GAS CONNECTION 1353 MM (80 mbh, 120 mbh) 3/4 NPT GAS CONNECTION (150 mbh, 200 mbh, 250 mbh) (YC MODELS) CONTROL AND COMPRESSOR ACCESS PANEL Figure 9. 81/2 to 10 tons standard efficiency —roof curb Note: All dimensions are in inches/millimeters. 46 LEPRPNG� 1178 MM) 1 - i4 0 �iM)'6- C wMr�917aM(zs)6(18r 80 1/2• 5(356 MIA) (470 204MM) 83 7/8';MM) (2130 MM) 97j 1b�'7J P ( (25MM) (443 MM) S�Q (B73/8 MM c< (2145/2M) 49 71g (1267 MM) r, (51 MM) 280 MM) c,19 � 36' (512MM) ����R�SCE 14 RT-SVX38D-EN Unit Dimensions Figure 10. 81/2 to 10 tons standard efficiency —unit clearance and roof opening Note: All dimensions are in inches/millimeters. CLEARANCE CLEARANCE 36" (914 MM) HORIZONTAL FLOW - 18" (457 MM) 40, DOWNFLOW 36" (914 MM) TYPICAL ROOF OPENING CLEARANCE FROM TOP OF UNIT 72" 46" (2251 MM) (1168 MM) (1168 MM) \ 531/4� (1352 MM) CLEARANCE 48" (1219 MM) \� CLEARANCE 36" (914 MM) RT-SVX38 D-E N 15 Installation Pre -Installation Fiberglass Wool! Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation. Glass wool fibers may also cause respiratory, skin or eye irritation. Precautionary Measures • Avoid breathing fiberglass dust. • Use a NIOSH approved dust/mist respirator. • Avoid contact with the skin or eyes. Wear long- sleeved, loose -fitting clothing, gloves, and eye protection. • Wash clothes separately from other clothing: rinse washer thoroughly. • Operations such as sawing, blowing, tear -out, and spraying may generate fiber concentrations requiring additional respiratory protection. Use the appropriate NIOSH approved respiration in these situations. First Aid Measures Eye Contact —Flush eyes with water to remove dust. If symptoms persist, seek medical attention. Skin Contact —Wash affected areas gentlywith soap and warm water after handling. Procedure Heavy Objects! Ensure that all the lifting equipment used is properly rated for the weight of the unit being lifted. Each of the cables (chains or slings), hooks, and shackles used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift. Other lifting arrangements could cause equipment or property damage. Failure to follow instructions above or properly lift unit could result in unit dropping and possibly crushing operator/ technician which could result in death or serious injury. Improper Unit Lift! Test lift unit approximately 24 inches to verify proper center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level. Failure to properly lift unit could result in unit dropping and possibly crushing operator/technician which could result in death or serious injury and possible equipment or property -only damage. Figure l 1. Corner weights CENTER OF GRAVITY LENGTH CE Ri; GRAVITY WIDTH D k CENTER OF GRAVITY B C 16 RT-SVX38D-EN Installation Table 1. Maximum unit and corner weights (Ibs/kgs) and center of gravity dimensions (in/mm)—gas/electric models Unit Maximum Model Weights(a) Corner Weights(b) Center of Gravity (in/mm) Tons Model No. Shipping Net A B C D Length Width 5 YSC060E 689/312 584/264 181/82 144/65 122/55 137/62 40/1025 24/600 6 YSC072E 975/443 843/383 296/134 209/95 158/72 180/82 39/980 21/542 71/2 YSC090E 1016/461 884/401 346/157 198/90 159/72 181/82 36/909 20/519 81/2 YSC102E 1125/510 987/447 325/147 278/126 174/79 210/95 41/1031 21/526 10 YSC120E 1149/522 1011/459 344/156 265/120 193/88 209/95 40/1020 21/538 (a) Weights are approximate. (b) Corner weights are given for information only. Figure 12. Rigging and center of gravity ATTA( CABLE Table 2. Factory -installed options (FIOPs)/accessory net weights (lbs)(a)•(b) Accessory YSC060ED Net Weight 5 Ton YSC072E-120ED Net Weight 6 to 10 Ton Barometric Relief 7/3 10/5 Coil Guards 12/5 20/9 Economizer 26/12 36/16 Hinged Doors 10/5 12/5 Manual Outside Air Damper 16/7 26/12 Motorized Outside Air Damper 20/9 30/14 Oversized Motor — 8/4 Roof Curb 61/28 78/35 (a) Weights for options not listed are <5 Ibs. (b) Net weight should be added to unit weight when ordering factory -installed accessories. Foundation Horizontal Units If the unit is installed at ground level, elevate it above the snow line. Provide concrete footings at each support location with a "full perimeter" support structure or a slab foundation for support. Referto Table 1,p. 17fortheunit's operating and point loading weights when constructing a footing foundation. If anchoring is required, anchor the unit to the slab using hold down bolts or isolators. Isolators should be installed to minimize the transmission of vibrations into the building. For rooftop applications, ensure the roof is strong enough to support the combined unit and support structural weight. Refer to Table 1, p. 17 for the unit operating weights. If anchoring is required, anchor the unit to the roof with hold-down bolts or isolators. Check with a roofing contractor for proper waterproofing procedures. Ductwork Figure 13, p. 17, Figure 14, p. 18, Figure 15, p. 18, and Figure 16, p. 18 illustrate the supply and return air openings as viewed from the rear of the unit. Figure 13. 5 ton unit —horizontal supply and return air openings 011111NINNINNIT1111 WTTIIIIIHI II SUPPLY 314A4 NPT DRAIN CONNEC 1ON 23'M4 539MM RETURN 337MM r438.11M 37 MM RT-SVX38 D-E N 17 Installation Figure 14. 6 to 10 tons high units —horizontal supply and return air openings Figure 15, p. 18 and Figure 16, p. 18 illustrate the supply and return air openings in a downflow configuration. To minimize air noise due to turbulence and to reduce static pressure, use elbows with turning vanes or splitters. When attaching the ductwork to the unit, provide a water tight flexible connector at the unit to prevent operating sounds from transmitting through the ductwork. All outdoor ductwork between the unit and the structure should be weather proofed after installation is completed. Figure 15. 5 ton unit —downflow supply and return air openings with through -the -base utilities Figure 16. 6 to 10 tons units—downflow supply and return air openings with through -the -base utilities Roof Curb Downflow The roof curbsforthese units consists of a "full perimeter" enclosure to support the unit just inside of the unit base rail. Before installing any roof curb, verify the following: • It is the correct curb for the unit • It includes the necessary gaskets and hardware • The installation location provides the required clearance for proper operation • The curb is level and square; thetop surface of the curb must be true to assure an adequate curb -to -unit seal Combustible Materials! Maintain proper clearance between the unit heat exchanger, vent surfaces and combustible materials. Refer to unit nameplate and installation instructions for proper clearances. Improper clearances could result in combustible materials catching on fire. Failure to maintain proper clearances could result in death or serious injury or property damage. Verify that appropriate materials were used in the construction of roof and ductwork. Combustible materials should not be used in the construction of ductwork or roof curb that is in close proximity to heater elements or any hot surface. Any combustible material on the inside of the unit base should be removed and replaced with appropriate material. Step-by-step curb assembly and installation instructions ship with each accessory roof curb kit. Follow the instructions carefully to assure proper fit -up when the unit is set into place. Note: To assure proper condensate flow during operation, as well as proper operation of the condensate overflow switch (if equipped), the unit and curb must be level. If the unit is elevated, a field constructed catwalk around the unit is strongly recommended to provide easy access for unit maintenance and service. Recommendations for installing the SupplyAirand Return Air ductworkjoining the roof curb are included in the curb instruction booklet. Curb ductwork must be fabricated and installed by the installing contractor before the unit is set into place. Note: For sound consideration, cut only the holes in the roof deck for the ductwork penetrations. Do not cut out the entire roof deck within the curb perimeter. If Curb Accessory Kit Not Used • The ductwork can be attached directly to the factory -provided flanges around the unit's supply and 18 RT-SVX38D-EN return air openings. Be sure to use flexible duct connections at the unit. • For "built-up" curbs supplied by others, gaskets must be installed around the curb perimeter flange and the supply and return air opening flanges. Rigging Heavy Objects! Ensure that all the lifting equipment used is properly rated for the weight of the unit being lifted. Each of the cables (chains or slings), hooks, and shackles used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift. Other lifting arrangements could cause equipment or property damage. Failure to follow instructions above or properly lift unit could result in unit dropping and possibly crushing operator/ technician which could result in death or serious injury. A rigging illustration and center -of -gravity dimensional data table is shown in Figure 12, p. 17. Refer to the typical unit operating weights table before proceeding. 1. Remove all drill screws fastening wood protection to metal base rail. Remove all screws securing wooden protection to wooden top crate. On 71/2 to 10 ton high efficiency units, remove wire ties from outdoor grill. 2. Remove wooden top crate. 3. Rig the unit as shown in Figure 12, p. 17. Attach adequate strength lifting slings to all four lifting brackets in the unit base rail. Do not use cables, chains, or slings except as shown. 4. Install a lifting bar, as shown in Figure 12, p. 17, to protect the unit and to facilitate a uniform lift. The minimum distance between the lifting hook and the top of the unit should be 7 feet. 5. Test -lift the unit to ensure it is properly rigged and balanced, make any necessary rigging adjustments. 6. Lift the unit enough to allow the removal of base fork pocket protection components as shown in the following figures. Figure 17. Fork pockets Rem( foi bra, Kemove L metal runners and 3 wooden boards Installation 7. Downflow units: align the base rail of the unit with the curb rail while lowering the unit onto the curb. Make sure that the gasket on the curb is not damaged while positioning the unit. General Unit Requirements The following checklist is a summary of the steps required to successfully install a commercial unit. This checklist is intended to acquaint installing personnel with what is required in the installation process. It does not replace detailed instructions in this manual. • Check the unit for shipping damage and material shortage; file a freight claim and notify appropriate sales representative. • Verify correct model, options and voltage from unit nameplate. • Verify that the installation location of the unit will provide the required clearance for proper operation. • Assemble and install the roof curb (if applicable). Refer to the latest edition of the curb installers guide that ships with each curb kit. • Fabricate and install ductwork; secure ductwork to curb. • Install pitch pocket for power supply through building roof. (If applicable) • Rigging the unit. • Set the unit onto the curb; check for levelness. • Ensure unit -to -curb seal is tight and without buckles or cracks. • Install and connect a condensate drain line to the evaporator drain connection. Note: Condensate Overflow Switch (if equipped) will not work if unit is not level properly. Factory -Installed Economizer • Ensure the economizer has been pulled out into the operating position. Refer to the economizer installers guide for proper position and setup. • Install all access panels. Temperature Limit Switch Usage for Gas Heat Units Units are factory shipped in the down flow discharge configuration but can be field converted to a horizontal discharge configuration. Some, but not all, units require a different TC01 limit switch, which is attached to the combustion blower motor if horizontal discharge configuration is used. Note: The following units require a limit switch change out for horizontal discharge. The additional limit switch is shipped attached to the combustion blower housing: YSC060ED*H, YSC072ED*H, YSC090ED*H, YSC102ED*H, YSC120ED*H. RT-SVX38 D-E N 19 Installation If any of the units listed in the previous note are installed in the down flow discharge configuration, remove and discard the additional TC01 limit switch from the combustion blower motor. Table 3. TC01 tripping values Unit Model (Standard Efficiency) TC01 Tripping Values Downflow/ Horizontal YSC060ED*L 170F YSC060ED*H 170F/20OF YSC072ED*L 20OF YSC072E*H 180F/220F YSC090ED*L 20OF YSC090ED*H 180F/22OF YSC102ED*L 20OF YSC102ED*H 190F/260F YSC120ED*L 20OF YSC120ED*H 190F/26OF Horizontal Discharge Conversion (5 Ton Units) Supplies needed by installer for conversion: 3 oz. tube of high temperature RTV sealant. (500°F / 260°C: similar to Dow Corning 736) Important: Failure to use recommended sealant could result in unit performance loss. If a unit is to be converted to a horizontal discharge, the following conversion must be performed: 1. Remove RETURN and SUPPLY duct covers. 2. Locate supply cover. Apply'/4 inch (6mm) continuous bead of 500°F RTV sealant to the flange as shown. Figure 18. Duct cover 3. Position duct cover as shown and rotate 90 degrees to allow entrance into supply opening. 4. Slide duct covers into duct openings until inward edge of duct cover engages with the 2 retaining clips on the duct flanges. Secure the outward edge of each duct cover with 2 screws. 5. Slide RETURN DUCT COVER (insulation side up) into supply opening until inward edge of duct cover engages with the 2 retaining clips on the duct flange. Secure outward edge of the duct cover with two screws. 6. After completing installation of the duct covers for horizontal discharge, proceed to TCO-1 instructions. TC01 Instructions -Unit Model Number YSC060ED*H If the unit being installed is YSC060ED*H, the limit control TC01 must be replaced with the extra limit control shipped in the heater compartment. Replace TC01 using steps 1 through 3 of the following instructions. If the unit being installed is notYSC060ED*H, skip steps 1 through 3and go to the next step in the installation process. Figure 19. TC01 location (YSC060ED*H) Location of TC01 limit for the WS/1-I)C036E, YHC037E. YSC048E, FI ro Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury. 1. Remove the heat section access panel. 2. Remove TC01 from shipping location, attached to the combustion blower. 3. Replace and discard the existing TC01 originally installed at the factory for downflow operation with the TC01, which was shipped attached to the combustion blower for horizontal operation. 4. Replace heat section access panel. 20 RT-SVX38D-EN Horizontal Discharge Conversion (6 to 10 Ton Units) Note: 6 to 10 ton units the supply cover to return opening and return cover to supply opening. Supplies needed by installer for conversion: 3 oz. tube of high temperature RTV sealant (500°F/260°C: Similar to Dow Corning 736). Important: Failure to use recommended sealant could result in unit performance loss. If a unit is to be converted to a horizontal discharge, the following conversion must be performed: 1. Remove RETURN and SUPPLY duct covers. 2. Place SUPPLY DUCT COVER over downflow return opening (insulation side down). 3. Using self -drilling screws (or screws removed from duct cover), screw through dimples to attach DUCT COVER to base. Figure 20. Duct cover Supply Duct Cover Screw into 4 dimples on top edge 4. On original RETURN DUCT COVER, apply'/4" (6mm.) continuous bead of 500°F RTV sealant around flange (opposite insulation side), as shown. Figure 21. Duct cover 5. Slide RETURN DUCT COVER (insulation side up) into supply opening until inward edge of duct cover engages with the 2 retaining clips on the duct flange. Secure outward edge of the duct cover with two screws. Note: If unit is equipped with Return Air Smoke Detector, refer to field conversion instructions for horizontal discharge before installing return air duct. Note: If unit is equipped with Discharge Air Sensing option refer to the following figure for proper tube positioning based on unit tonnage. Installation 6. After completing installation of the duct covers for horizontal discharge, proceed to TCO-1 instructions. Figure 22. Supply and return covers duct cover Insulation side down Insulation side up Return duct cover TC01 Instructions —Unit Model Numbers YSC072ED*H, YSCO90ED*H, YSC102ED*H, YSC120ED*H If the unit being installed is one of these models, the limit control TC01 must be replaced with the extra limit control shipped in the heater compartment. Replace TC01 using steps 1 through 3 in the following instructions. If the unit being installed does not correspond to any of these models, skip steps 1 through 3 and go to the next step in the installation process. Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury. 1. Remove the heat section access panel. 2. Remove TC01 from shipping location, attached to the combustion blower. 3. Replace and discard the existing TC01 originally installed at the factory for downflow operation with the TC01, which was shipped attached to the combustion blower for horizontal operation. 4. Replace heat section access panel. RT-SVX38 D-E N 21 Installation Requirements for Gas Heat Note: The unit gas train and optional through the base gas shut-off valve are rated at 1/2 PSIG maximum. A pressure reducing regulator is recommended to prevent this maximum from being exceeded. These components must be isolated during field gas piping test that exceed 1/2 PSIG. It is recommended that the field piping be capped prior to the unit gas train or optional through the base gas shut-off valve if present. • Gas supply line properly sized and connected to the unit gas train. • All gas piping joints properly sealed. • Gas piping leak checked with a soap solution. If piping connectionsto the unit are complete, do not pressurize piping in excess of 0.50 psig or 14" W.C. to prevent component failure. • Drip leg Installed in the gas piping near the unit. • Minimum gas supply pressure should be 4.5" W.C. • Maximum gas supply pressure must not exceed 14.0" W.C. • Manifold pressure for single stage heaters should be set to 3.3" W.C. • Manifold pressure for two stage heaters should be set to 3.5" W.C. on HIGH FIRE and 1.8" W.C. on LOW FIRE. • Flue Exhaust clear of any obstruction. Condensate Drain Configuration An evaporator condensate drain connection is provided on each unit. Refer to Figure 13, p. 17 and Figure 14, p. 18 for the appropriate drain location. The condensate drain pan is factory installed to drain condensate to the back side of the unit. See Figure 13, p. 17 and Figure 14, p. 18. It can be converted to drain condensate out the front side of the unit or through the base. 4. Slide the condensate drain pan back into the unit, align the drain with the grommeted opening in the rear support panel and push until the coupling is seated in the grommet. 5. Replace the front support panel by aligning the panel with tabs in the raceway. Align the condensate drain pan support in the grommeted hole as the panel is put in place. 6. Replace evaporator access panel and supply air access panels. To Convert Drain Condensate through the Base of Unit 1. Remove evaporator access panel and supply air access panels. 2. Remove the support panel that the condensate drain pan exits through. 3. Slide the condensate drain pan out of the unit. 4. Place on a level surface in the position it was removed from the unit. 5. Remove the plug knockout in the bottom of the drain pan to convert it to through the base drainage. 6. Plug the original condensate drain opening with a field -supplied 3/4" NPT plug. 7. Slide the condensate drain pan back into the unit, align the drain support with the grommeted opening in the rear support panel and push until the support is seated in the grommet. 8. Replace the front support panel by aligning the panel with tabs in the raceway. Align the plugged condensate drain pan coupling in the grommeted hole as the panel is put in place. 9. Replace evaporator access panel and supply air access panels. A condensate trap must be installed at the unit due to the drain connection being on the "negative pressure" side of the fan. Install the P-Trap using the guidelines in Figure 23, p. 23. Before drain pan removal, switch wire must be A condensate drain line must be connected to the P-Trap. disconnected from wire tie on panel and any tape before Pitch the drain lines at least 1/2 inch for every 10 feet of drain pan can be removed. horizontal run to assure proper condensate flow. Do not Care must be taken wire does not catch on bottom of allow the horizontal run to sag causing a possible double - Indoor coil or any protrusions when drain pan is removed. trap condition which could result in condensate backup To Convert Drain Condensate through Front of due to "air lock". Unit 1. Remove evaporator access panel and supplyairaccess panels. 2. Remove the support panel that the condensate drain pan exits through. 3. Slide the condensate drain pan out of the unit and rotate 180°. 22 RT-SVX38D-EN Installation • Verify that the power supply available is compatible Figure 23. Condensate trap installation with the unit's nameplate ratings. Panel Enclosure • ppThe available supplypower must be within 10% of the .75 inch NPT rated voltage stamped on the nameplate. Female Connector • Use only copper conductors to connect the power supply to the unit. 1.5l inch • 381 mm Use Copper Conductors Only! Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors could result in equipment damage. IU Cleanout Plug Drain Pan Removal (Units with Condensate Overflow Switch Option) Before drain pan removal, the switch wire must be disconnected from wire tie on panel and/or any tape before drain pan can be removed. Care must be taken so the wire does not catch on the bottom of indoor coil or any protrusion. Note: When reversing the drain pan, on some units, the condensate overflow switch will need to be moved to the second hole in its bracket to avoid contact with headers or indoor coil. Filter Installation The quantity of filters is determined by unit size. Access to the filters is obtained by removing the filter access panel. Refer to the unit Service Facts (shipped with each unit) for filter requirements. Note: Do not operate the unit without filters. Field -Installed Power Wiring Proper Field Wiring and Grounding Required! All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury. An overall dimensional layout for the field -installed wiring entrance into the unit is illustrated in "Unit Dimensions," p. 10. To ensure that the unit's supply power wiring is properly sized and installed, use the following guidelines. Note: If the unit is not equipped with an optional factory installed non -fused disconnect switch or circuit breaker, afield -supplied disconnect switch must be installed at or near the unit in accordance with the National Electrical Code (NEC latest edition). Main Unit Power Proper Field Wiring and Grounding Required! All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury. Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury. Standard Wiring 1. Location of the applicable electrical service entrance is illustrated in "Unit Dimensions," p. 10. Complete the unit's power wiring connections at Compressor Contactor # 1 (CC1) inside the unit control panel. Refer to the customer connection diagram that is shipped with the unit for specific termination points 2. Provide proper grounding for the unit in accordance with local and national codes. RT-SVX38 D-E N 23 Installation Figure 24. All units Seal between wiring and conduit ; with weatherproof sea ler to prevent; air leakage Field -powered Control wiring ,' convenience outlet conduit conduit�i Power wiring conduit Black gasket 1 Field -Installed Control Wiring Note: All field wiring must conform to NEC guidelines as well as state and local codes. Control Power Transformer The 24-voltcontrol power transformers areto be used only with the accessories called out in this manual. Transformers rated greater than 50 VA are equipped with internal circuit breakers. If circuit breaker trips, turn off all power to the unit before attempting to reset it. Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury The transformer is located in the control panel. The circuit breaker is located on the left side of the transformer; reset it by pressing the black reset button. Controls Using 24 VAC Before installing any connecting wiring, refer to "Unit Dimensions," p. 10 for the electrical access locations provided on the unit, Table 4, p. 24for AC conductor sizing guidelines, and the following guidelines: • Use copper conductors unless otherwise specified. • EnsurethattheAC control wiring between the controls and the unit's termination point does not exceed 3 ohms/conductor for the length of the run. Note: Resistance in excess of 3 ohms per conductor may cause component failure due to insufficient AC voltage supply. Note: Be sure to check all loads and conductors for grounds, shorts, and mis-wiring. • Do not run the AC low voltage wiring in the same conduit with the high voltage power wiring. • Route low voltage wiring per Figure 27, p. 25. Table 4. Electromechanical thermostat 24V AC conductors with ReliaTelT°° Distance from Unit to Control Recommended Wire Size 000 to 460 feet 18 gauge 000 to 140 m .75 mm2 461 to 732 feet 16 gauge 141to223m 1.3mm2 733 to 1000 feet 14 gauge 224 to 305 m 2.0 mm2 Controls using DC Analog Input/Outputs (Standard Low Voltage Multi -Conductor Wire) Before installing any connecting wiring between the unit and components using a DC analog input\output signal, refer to "Unit Dimensions," p. 10 for the electrical access locations provided on the unit. • Table 5, p. 24 lists the conductor sizing guidelines that must be followed when interconnecting the DC binary output devices and the system components using a DC analog input/output signal to the unit. Note: Resistance in excess of 2.5 ohms per conductor can cause deviations in the accuracy of the controls. Note: Ensure that the wiring between controls and the unit's termination point does not exceed 2.5 ohms per conductor for the length of the run. • Do not run the electrical wires transporting DC signals in or around conduit housing high voltage wires. • Route low voltage wiring per Figure 27, p. 25. DC Conductors Table 5. Zone sensor module wiring Distance from Unit to Control Recommended Wire Size 0 to 150 feet 22 gauge 0 to 45.7 m .33 mm2 151 to 240 feet 20 gauge 46 to 73.1 m .50 mm2 241 to 385 feet 18 gauge 73.5 to 117.3 m .75 mm2 386 to 610 feet 16 gauge 117.7 to185.9 m 1.3 mm2 611 to 970 feet 14 gauge 186.2 - 295.7 m 2.0 mm2 24 RT-SVX38D-EN Figure 25. ReliaTelT°° conventional thermostat field wiring diagrams RTRM THERMOSTAT I RC J7-1 12a vnci HEAT HEAT 1 W1 J7-3 1O0F HEAT 2 Wz J7-5 COOL -z° - ON OL - J7-4 AUTO FAN ;� -OFF HEAT RH �V� � J7-9 COOL COOL1 F COOL2 0 I HEAT Figure 26. ReliaTel options module J7-2 J7-6 Je --m-msx vXrss J4 J9 J10 ill XFA e>r 00 J12 M cops FMI SPO El r A O -0 O pENMp 0 0 8 �o N 'o--o--o--o--o' O J6 OOOOOO J7 Installation Figure 27. ReliaTel control customer low voltage routing Refrigeration Communication Module Interface 4_.... ReliaTel Conventional Wiring Route field wiring as shown and secure with 2 wire ties. Space Temperature Averaging (ReliaTelT"' Only) Space temperature averaging is accomplished by wiring a number of remote sensors in a series/parallel circuit. Using the BAYSENS016* or BAYSENS077*, at least four sensors are required to accomplish space temperature averaging. See Figure 28, p. 26. • Example #1 illustrates two series circuits with two sensors in each circuit wired in parallel. The square of any number of remote sensors is required. • Example #2 illustrates three sensors squared in a series/parallel circuit. Using BAYSENS077*, two sensors are required to accomplish space temperature averaging. • Example #3 illustrates the circuit required for this sensor. Table 6, p. 28 lists the temperature versus resistance coefficient for all sensors. RT-SVX38 D-E N 25 Installation Figure 28. Examples EXAMPLE #1 ZSM REMOTE SENSORS #1 #2 #3 #4 o ---- ----� l r__I -- 2 O 2 0 0 0 O 0---.t7------- J-------- 2 EXAMPLE #2 Z S M REMOTE SENSORS #1 L OL1 2 L 2 o Y� #4 #5 #s II II II �I #7 #8 #9 II II ILL LL _-_ _j 2 EXAMPLE #3 Z S M REMOTE SENSORS #1 #2 0.. .. 1 C� I 2 Remote Sensor #1 Remote Sensor #2 VVVV VVVV Remote Sensor #3 Remote Sensor #4 VVVV VVVV ZSM ZSM TERMINAL # I TERMINAL # 2 Remote Sensor #1 Remote Sensor #2 Remote Sensor #3 VVVV\1�VVVV\1�VVVV Remote Sensor #4 Remote Sensor #5 Remote Sensor #8 VVVVp ;VVVV\1�VVVV Remote Sensor #7 Remote Sensor #8 Remote Sensor #9 VVVV\l�VVVVv-----YVVVV ZSM TERMINAL # 1 Remote Sensor #1 Remote Sensor #2 VVVVVVVV VVVV VVVV ZSM TERMINAL # 1 ZSM TERMINAL # 2 ZSM TERMINAL # 2 26 RT-SVX38D-EN Installation Figure 29. Typical field wiring diagrams for optional controls (ReliaTelTI only) RTRM RTRM RTRM 1 2 1 1 5 6 7 8 9 10 II 12 11 2 3 1 5 6 7 8 9 10 II @ 4 1 2 D 1 5 6 7 8 9 10 II 12 W y 0 4 0 0 0 0 0 0 0 0 0 0 0 A 09 99 Q 0 0 0 0 0 0 0 0 A0 0 0 0 00 0 0 0 0 0 0 0 1 L- I I , I I I I I I I `L-, ``_______ I L_________ - 1 1 I BAYSENS075' I u l l L-------- 1 i 1 1 1 OOO DOO TBI ASYSTAT669A L, I i I OPTION REMOTE 2 D SENSOR _ T81 BAYSENS075* ASYSTAT669AOPT OpE ©O 6 ©®O SENSOR T81 BAYSEN5106* ZONE SENSOR �^ BAYSENS108* ® 2�, ZONE SENSOR BAYSENS110* ® e ZONE SENSOR CUT WIRE JUMPER R11 ADJACENT TO TEMPERATURE SLIDES ON ZONE SENSOR CUT WIRE JUMPER R11 ADJACENT TO WHEN OPTIONAL REMOTE SENSOR TEMPERATURE SLIDES ON ZONE SENSOR IS USED. WHEN OPTIONAL REMOTE SENSOR IS USED. RTRM RTRM RTRM 1 2 D 1 56 7 8 9 10 11 1211 1 2 71 5 6 7 8 9 1011 12 IA 1 2 3 A 5 6 7 0 9 10 II 124 b O O O O O O O O O O O O J6 0 0 0 0 0 0 0 00 0 0 As 0 0 0 0 0 0 0 0 0 90 001 I LI I I IL ------- L._____-- 1 L------1 I I 2 1 1 1 ob© BAYSENS119*IIII ( 1^ — 1 ASYSTAT666A------ ZONE SENSOR I I 11 BAYSEN5073* ZONE SENSOR BAYSEN5074* ZONE SENSOR IIIII I I I I I envsErvso7s* 1 I ASYSTAT669A I I ICS WITH OVERRIDE AND ICS WITH SETPOINT,OVERRIDE OPTIONAL REMOTE 5EN50R I I I I I ' CANCELLATION BUTTON AND CANCELLATION BUTTON PnA. LLkmw, sw . . ddA 9dyy BAYFR57003A ECA L----'I -IJ.10i IF ED N PR--------- 7 E ) 1I ,I PM, 1OO,Ir SOPR[Al.. rA�RR0YDD UpRx R L SuOdY atl / IGgu Lmt tenlrtl R.I\ Duel X1310ON001 xlgn L'mD Cmlyd 1I 1 I I,IFl mum P99RIDn POIMIfynOte+ 1 I W D0 I x13100W002 Red------ Iph BAYSTA1013A RT-SVX38D-EN 27 Installation Table 6. Temperature vs. resistance Table 8. Iron pipe size (S1) millimeters Temperature Iron Pipe Size (SI) Millimeters Degrees F° Degrees CO Nominal Resistance Length of Pipe 15 mm 20 mm 25 mm 32 mm 40 mm -200 -28.90 170.1 K - Ohms (Meters) Pipe Pipe Pipe Pipe Pipe -150 -26.10 143.5 K - Ohms 4.6 2.15 4.98 9.76 21.23 34.54 -100 -23.30 121.4 K - Ohms 9.1 1.47 3.39 6.82 15.14 24.06 -50 -20.60 103.0 K - Ohms 13.7 1.21 2.80 5.63 12.31 19.82 00 -17.80 87.56 K - Ohms 18.3 1.07 2.43 4.89 10.76 17.27 50 -15.00 74.65 K - Ohms 22.9 - 2.18 4.38 9.76 15.40 100 -12.20 63.80 K - Ohms Note: Capacity of pipe of different diameters and lengths in cu. meter per 150 -9.40 54.66 K - Ohms hr. with pressure drop of 74.6 pa and specific gravity of 0.60. 200 -6.70 46.94 K - Ohms 250 -3.80 40.40 K - Ohms Figure 30. Schematic diagram for field gas piping to unit 300 -1.10 34.85 K - Ohms 350 1.70 30.18 K - Ohms 400 4.40 26.22 K - Ohms 'A" NPT Test Plug Field -supplied Ground 6" min. Union - 45° 7.20 22.85 K - Ohms To Gas Train 500 10.00 19.96 K -Ohms / / Gas Supply Line / 550 12.80 17.47 K - Ohms Gas Shutoff Unit Access Hole (field supplied outside unit cabinet) \ 600 15.60 15.33 K - Ohms Drip Leg 650 18.30 13.49 K - Ohms 700 21.10 11.89 K - Ohms 750 23.90 10.50 K - Ohms 800 26.70 9.297 K - Ohms 850 29.40 8.247 K - Ohms 900 32.20 7.330 K - Ohms 95° 35.01 6.528 K - Ohms Table 7. Sizing natural gas pipe mains and branches Iron Pipe Size (IPS) Inches 1/2" 3/4" 1„ 11/4" 11/2 Length of Pipe (ft) Pipe Pipe Pipe Pipe Pipe 15 76 176 345 750 1220 30 52 120 241 535 850 45 43 99 199 435 700 60 38 86 173 380 610 75 77 155 345 545 Note: Capacity of pipe of different diameters and lengths in cu. ft. per hr. with pressure drop of 0.3" and specific gravity of 0.60 28 RT-SVX38D-EN Pre -Start Use the following checklist \in conjunction with the "General Unit Requirements" checklist to ensure that the unit is properly installed and ready for operation. Hazardous Voltage w/Capacitors! Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN • Verifythatthe condenser airflowwill be unobstructed. Rotating Components! During installation, testing, servicing and troubleshooting of this product it may be necessary to work with live and exposed rotating components. Have a qualified or licensed service individual who has been properly trained in handling exposed rotating components, perform these tasks. Failure to follow all safety precautions could result in rotating components cutting and slashing technician which could result in death or serious injury. • Verify that the condenser fan and indoor blower turn freely without rubbing and are properly tightened on the shafts. • Check the supply fan belts for proper tension and the fan bearings for sufficient lubrication. If the belts require adjustment, or if the bearings need lubricating, refer to the maintenance section of this manual for instructions. • Verifythatacondensatetrapisinstalled and the piping is properly sized and pitched. • Verify that the correct size and number of filters are in place. • Inspect the interior of the unit for tools and debris and install all panels in preparation for starting the unit. Voltage Imbalance Three phase electrical power to the unit must meet stringent requirements for the unit to operate properly. Measure each leg (phase -to -phase) of the power supply. Each reading must fall within the utilization range stamped on the unit nameplate. If any of the readings do not fall within the proper tolerances, notify the power company to correct this situation before operating the unit. Excessivethree phase voltage imbalance between phases will cause motors to overheat and eventually fail. The maximum allowable voltage imbalance is 2%. Measure and record the voltage between phases 1, 2, and 3 and calculate the amount of imbalance as follows: Voltage Imbalance= 100 x AVA - VD where: AV (Average Voltage)= Volt 1 + Volt 2 + Volt 3 V1, V2, V3 = Line voltage readings VD = Line voltage reading that deviates the farthest from the average voltage. Example: If the voltage readings of the supply power measured 221, 230, and 227, the average volts would be: 221 + 230 + 227 = 226 Avg. 3 VD (reading farthest from average) = 221 The percentage of imbalance equals: 100 x 226 - 227 — 2.2% 226 The 2.2% imbalance in this example exceeds the maximum allowable imbalance of 2.0%. This much imbalance between phases can equal as much as a 20% current imbalance with a resulting increase in motor winding temperatures that will decrease motor life. If the voltage imbalance is over 2%, notify the proper agencies to correct the voltage problem before operating this equipment. Electrical Phasing (Three -Phase Motors) The compressor motor(s) and the supply fan motor are internally connected for the proper rotation when the incoming power supply is phased as A, B, C. Before starting the unit, quickly determine and correct proper electrical supply phasing by using an instrument such as an Associated Research Model 45 Phase Sequence Indicator and the following steps: • Turn the field -supplied disconnect switch that provides power to the main power terminal block or to the "Line" side of the optional factory -mounted disconnect switch to the OFF position. • Connect the phase sequence indicator leads to the terminal block or to the "Line" side of the optional factory -mounted disconnect switch as follows: Black (phase A) to L1 Red (phase B) to L2 Yellow (phase C) to L3 RT-SVX38 D-E N 29 Pre -Start • Close the field -supplied main power disconnect switch or circuit protector switch that provides the supply power to the unit. Note: Upon closing main power disconnect and the unit -mounted disconnect switch or circuit breaker, the phase monitorwill verify proper phasing. If LED on face of the monitor is red, correct supply power fault. Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. To prevent injury or death from electrocution, it is the responsibility of the technician to recognize this hazard and use extreme care when performing service procedures with the electrical power energized. • Observe the ABC and CBA phase indicator lights on the face of the sequencer. The ABC indicator light will glow if the phase is ABC. If the CBA indicator light glows, open the disconnect switch or circuit protection switch and reverse any two power wires. • Restore the main electrical power and recheck the phasing. If the phasing is correct, open the disconnect switch or circuit protection switch and remove the phase sequence indicator. Compressor Crankcase Heaters (Optional) Each compressor can be equipped with a crankcase heater (on some unitsthe crankcase heater comes standard). The proper operation of the crankcase heater is important to maintain an elevated compressor oil temperature during the OFF cycle to reduce oil foaming during compressor starts. Oil foaming occurs when refrigerant condenses in the compressor and mixes with the oil. In lower ambient conditions, refrigerant migration to the compressor could increase. When the compressor starts, the sudden reduction in crankcase pressure causes the liquid refrigerant to boil rapidly causing the oil to foam. This condition could damage compressor bearings due to reduced lubrication and could cause compressor mechanical failures. Before starting the unit in the "Cooling" mode, set the system switch to the OFF position and turn the main power disconnect to the ON position and allow the crankcase heater to operate a minimum of 8 hours. Before closing the main power disconnect switch, ensure that the "System" selection switch is in the OFF position and the "Fan" selection switch is in the "Auto" position. Close the main power disconnect switch and the unit -mounted disconnect switch, if applicable. Note: Upon closing main power disconnect and the unit -mounted disconnect switch or circuit breaker, the phase monitorwill verify proper phasing. If LED on face of the monitor is red, correct supply power fault. Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. To prevent injury or death from electrocution, it is the responsibility of the technician to recognize this hazard and use extreme care when performing service procedures with the electrical power energized. ReliaTel` Controls Upon power initialization, the RTRM performs self -diagnostic checks to ensure that all internal controls are functional. It also checks the configuration parameters against the components connected to the system. The Liteport LED located on the RTRM module turns on within one second of power -up if internal operation is okay. Use one of the following "Test" procedures to bypass sometime delays and to startthe unit at the control panel. Each step of unit operation can be activated individually by temporarily shorting across the "Test" terminals for two to three seconds. The Liteport LED located on the RTRM module will blink when the test mode has been initiated. The unit can be left in any "Test" step for up to one hour before it will automatically terminate, or it can be terminated by opening the main power disconnect switch. Once the test mode has been terminated, the Liteport LED will glow continuously and the unit will revert to the "System" control. 30 RT-SVX38D-EN Pre -Start Table 9. Service test guide for component operation Test PWM Multi -Speed Fan Step Mode Fan Econ (a) Comp i Comp 2 Heat 1 Heat 2 Resistance Output(b) Output Minimum Fan On Position Off Off Off Off 1 Setpoint 0% 2.21<0 50% low Minimum On Selectable Off Off Off Off Ventilation 2 Economizer On Open Off Off Off Off 3.31<0 50%(c) low Test Open 3 Cool On Minimum On (d) Off Off Off 4.71<0 82% low Stage 1 Position 4(e) Cool On Minimum On(d) On(d) Off Off 6.8KQ 100% High (2-step cooling) Stage 2 Position Low (3-step cooling) 5(e) Cool On Minimum On(d) On(d) Off Off 8.21<0 100% High Stage 3 Position 6(e) Reheat On Minimum On On Off Off 33KQ 1000/0 High 7(e) Heat On Minimum Off Off On Off 10KQ 100% High Stage 1 8(e) Heat On Minimum Off Off On On 15KO 100% High Stage 2 (a) The exhaust fan will turn on anytime the economizer damper position is equal to or greater than the exhaust fan setpoint. (b)The PWM Output is in reference to the user selected maximum unit fan speed. (c) Regardless of the Economizer Mode configuration, the unit will run the Supply Fan at the minimum speed during the Economizer step of the Service Test. (d)The condenser fans will operate any time a compressor is on, providing the outdoor air temperatures are within the operating values. (e) Steps for optional accessories and non -applicable modes in unit will be skipped. (f) Units with Enhanced Dehumidification only will not perform this step during Service Test. Test Modes There are three methods in which the "Test" mode can be cycled at LTB-Test 1 and LTB-Test 2. 1. Step Test Mode —This method initiates the different components of the unit, one at a time, by temporarily shorting across the two test terminals for two to three seconds. For the initial start-up of the unit, this method allows the technician to cycle a component "On" and have up to one hour to complete the check. 2. Resistance Test Mode —This method can be used for start-up providing a decade box forvariable resistance outputs is available. This method initiates the different components of the unit, one at a time, when a specific resistance value is placed across the two test terminals. The unitwill remain in the specifictest mode for approximately one hour even though the resistance is left on the test terminals. 3. Auto Test Mode —This method is not recommended for start-up due to the short timing between individual component steps. This method initiates the different components of the unit, one at a time, when a jumper is installed across the testterminals. The unit will start the first test step and change to the next step every 30 seconds. At the end of the test mode, control of the unit will automatically revert to the applied "System" control method. For unit test steps, test modes, and step resistance values to cycle the various components, refer to Table 9, p. 31. ReliaTelT"' Controls Upon power initialization, the Gas Ignition Module (IGN) performs self -diagnostic checks to ensure that all internal controls are functional. It also checks the configuration parameters against the components connected to the system. The System LED located on the IGN module is turned on within one second of power -up if internal operation is okay. RT-SVX38 D-E N 31 Unit Start -Up Verifying Proper Air Flow Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. Units with Belt Drive Indoor Fan Much of the systems performance and reliability is closely associated with, and dependent upon, having the proper airflow supplied both to the space that is being conditioned and across the evaporator coil. The indoorfan speed is changed by opening or closing the adjustable motor sheave. Before starting the SERVICE TEST, set the minimum position setpointforthe economizerto 0 percent using the setpoint potentiometer located on the Economizer Control (ECA), if applicable. ReliaTelT" Control: Using the Service Test Guide in Table 9, p. 31, momentarily jump across the Test 1 and Test 2 terminals on LTB1 one time to start the Minimum Ventilation Test. With the fan operating properly, determine the total system airflow (CFM) by: 1. Measuring the actual RPM, 2. Measurethe amperage atthe supplyfan contactorand compare itwith the full load amp (FLA) rating stamped on the motor nameplate. a. Calculate the theoretical BHP using (Actual Motor Amps/ Motor Nameplate Amps) X Motor HP. b. Using the fan performance tables in the unit Service Facts, plot the actual RPM (step 1) and the BHP (step 2a) to obtain the operating CFM. 3. If the required CFM is too low, (external static pressure is high causing motor HP output to be below table value), a. Relieve supply and/or return duct static. b. Change indoor fan speed and repeat steps 1 and 2. • To increase fan rpm: Loosen the pulley adjustment set screw and turn sheave clockwise. • To decrease fan rpm: Loosen the pulley adjustment set screw and turn sheave counterclockwise. • If the required CFM is too high, (external static pressure is low, causing motor HP output to be above table value), change indoorfan speed and repeat steps 1 and 2. • To stop the SERVICE TEST, turn the main power disconnect switch to the OFF position or proceed to the next component start-up procedure. Economizer Start -Up ReliaTel Control: Using the Service Test Guide in Table 9, p. 31, momentarily jump across the Test 1 and Test 2 terminals on LTB1 one time to start the Minimum Ventilation Test. 1. Setthe minimum position setpointforthe economizer to the required percentage of minimum ventilation using the setpoint potentiometer located on the Economizer Control (ECA). The economizer will drive to its minimum position setpoint, exhaust fans (if applicable) may start at random, and the supply fan will start when the SERVICE TEST is initiated. Rotating Components! During installation, testing, servicing and troubleshooting of this product it may be necessary to measure the speed of rotating components. Have a qualified or licensed service individual who has been properly trained in handling exposed rotating components, perform these tasks. Failure to follow all safety precautions when exposed to rotating components could result in death or serious injury. The exhaust fan will start anytime the economizer damper position is equal to or greaterthan the exhaust fan setpoint. 2. Verify that the dampers stroked to the minimum position. ReliaTel Control: Momentarily jump across the Test 1 and Test 2 terminals on LTB1 one additional time if continuing from previous component start-up or until the desired start-up component Test is started. 3. Verify that the dampers stroked to the full open position. 4. To stop the SERVICE TEST, turn the main power disconnect switch to the OFF position or proceed to the next component start-up procedure. Remove electro mechanical test mode connections (if applicable). 32 RT-SVX38D-EN Compressor Start -Up 1. Attach a set of service gauges onto the suction and discharge gauge ports for each circuit. Refer to the refrigerant circuit illustration in the Service Facts. ReliaTell" Control: Momentarily jump across the Test 1 and Test 2 terminals on LT131 one additional time if continuing from previous component start-up or until the desired start-up component Test is started. Scroll Compressors a. Once each compressor has started, verify that the rotation is correct. If a scroll compressor is rotating backwards, it will not pump and a loud rattling sound can be observed. b. If the electrical phasing is correct, before condemning a compressor, interchange any two leads (at the compressor terminal block) to check the internal phasing. If the compressor runs backward for an extended period (15to 30 minutes), the motor winding can overheat and cause the motor winding thermostat to open. 2. After the compressor and condenser fan have started and operated for approximately 30 minutes, observe the operating pressures. Compare the operating pressures to the operating pressure curve in the Service Facts. 3. Check system superheat. Follow the instruction listed on the superheat charging curve in the Service Facts. Superheatshould be within ±5°Fofthe superheat chart value. 4. Repeat steps 1 through 4 for each refrigerant circuit. 5. To stop the SERVICE TEST, turn the main power disconnect switch to the OFF position or proceed to the next component start-up procedure. Remove electro mechanical test mode connections (if applicable). Gas Heat Units Open the main disconnect switch to shut the unit off and to reset the RTRM. ReliaTel Control: Follow the Test Guide in Table 9, p. 31 to start the unit in the heating mode. Momentarily jump across the Test 1 and Test 2 terminals on LT131 one additional time if continuing from previous component start-up or until the desired start-up component Test is started. When starting the unit for the first time or servicing the heaters, it is a good practice to start the heater with the main gas supply turned off. Once the ignition system and components have been checked, open the main power disconnect switch to reset the unit. Unit Start -Up Final System Setup After completing all of the pre -start and start-up procedures outlined in the previous sections (i.e., operating the unit in each of its Modes through all available stages of cooling and heating), perform these final checks before leaving the unit: • Program the Night Setback (NSB) panel (if applicable) for proper unoccupied operation. Refer to the programming instructions for the specific panel. • Verify that the Remote panel "System" selection switch, "Fan" selection switch, and "Zone Temperature" settings for automatic operation are correct. • Inspect the unit for misplaced tools, hardware, and debris. • Verify that all exterior panels including the control panel doors and condenser grilles are secured in place. • Close the main disconnect switch or circuit protector switch that provides the supply power to the unit's terminal block or the unit -mounted disconnect switch. Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. Make sure all personnel are standing clear of the unit before proceeding. The system components will start when the power is applied. RT-SVX38 D-E N 33 Maintenance Fan Belt Adjustment —Belt Drive Units Rotating Components! During installation, testing, servicing and troubleshooting of this product it may be necessary to measure the speed of rotating components. Have a qualified or licensed service individual who has been properly trained in handling exposed rotating components, perform these tasks. Failure to follow all safety precautions when exposed to rotating components could result in death or serious injury. The fan belts must be inspected periodically to assure proper unit operation. Replacement is necessary if the belts appear frayed or worn. Units with dual belts require a matched set of belts to ensure equal belt length. When removing or installing the new belts, do not stretch them over the sheaves. Loosen the belts using the belt tension adjustment bolts on the motor mounting base. Once the new belts are installed, using a Browning or Gates tension gauge (or equivalent) illustrated in Figure 31; adjust the belt tension as follows: 1. To determine the appropriate belt deflection: a. Measure the center -to -center shaft distance (in inches) between the fan and motor sheaves. 7. Recheck the belt tension at least twice during the first 2 to 3 days of operation. Belt tension may decrease until the new belts are "run in". Figure 31. Belt tension gauge Deflection = Belt Span (in) 64 Deflection = Belt Span (mm) 1S7 Small Force Scale O-Ring — Large Span Scale O-Ring— Table 10. Belt tension measurement and deflection Belts Cross- Section Small p,D. Range Deflection Force (Lbs) Super Gripbelts Gripnotch Steel Cable Gripbelts Min. Max. Min. Max. Min. Max 3.0-3.6 3 4 112 3 7/8 5 1/2 3 1/4 4 A 3.8-4.8 3 1/2 5 4 112 6 1/4 3 3/4 4 3/4 5.0-7.0 4 5 1/2 5 6 7/8 4 1/4 5 1/4 3.4-4.2 4 5 1/2 5 3/4 8 4 1/2 5 1/2 B 4.4-5.6 5 1/8 7 1/8 6 1/2 9 1/8 5 3/4 7 1/4 5.8-8.8 6 3/8 8 3/4 7 3/8 10 1/8 7 8 3/4 b. Divide the distance measured in Step la by 64; the resulting value represents the amount of belt Monthly Maintenance deflection that corresponds to the proper belt tension. 2. Set the large 0-ring on the belt tension gauge at the deflection value determined in Step 1b. 3. Set the small O-ring at zero on the force scale of the gauge plunger. 4. Placethe large end of the gauge atthe center of the belt span; then depress the gauge plunger until the large O-ring is even with the top of the next belt or even with a straightedge placed across the fan and motor sheaves. Refer to Figure 9. 5. Remove the belt tension gauge. The small O-ring now indicates a number other than zero on the plunger's force scale. This number represents the force (in pounds) required to give the needed deflection. 6. Compare the "force" scale reading (Step 5) with the appropriate "force" value listed in Table 10. If the "force" reading is outside the range, readjust the belt tension. Note: Actual belt deflection "force" must not exceed the maximum "force" value shown in Table 10. Rotating Components! During installation, testing, servicing and troubleshooting of this product it may be necessary to measure the speed of rotating components. Have a qualified or licensed service individual who has been properly trained in handling exposed rotating components, perform these tasks. Failure to follow all safety precautions when exposed to rotating components could result in death or serious injury. Before completing the following checks, turn the unit OFF and lock the main power disconnect switch open. Filters Inspect the return air filters. Clean or replace them if necessary. Refer to the unit Service Facts for filter information. 34 RT-SVX38D-EN Condensate Overflow Switch During maintenance, the switch float (black ring) must be checked to ensure free movement up and down. Cooling Season • Check the unit's drain pans and condensate piping to ensure that there are no blockages. • Inspect the evaporator and condenser coils for dirt, bent fins, etc. If the coils appear dirty, clean them according to the instructions described in "Coil Cleaning" later in this section. • Manually rotate the condenser fan(s) to ensure free movement and check motor bearings for wear. Verify that all of the fan mounting hardware is tight. • Inspect the F/A-R/A damper hinges and pins to ensure that all moving parts are securely mounted. Keep the blades clean as necessary. • Verify that all damper linkages move freely; lubricate with white grease, if necessary. • Check supply fan motor bearings; repair or replace the motor as necessary. • Check the fan shaft bearings for wear. Replace the bearings as necessary. • Check the supply fan belt. If the belt is frayed or worn, replace it. Refer to the "Fan Belt Adjustment" section for belt replacement and adjustments. • Verify that all wire terminal connections are tight. • Remove anycorrosion presenton the exterior surfaces of the unit and repaint these areas. • Generally inspect the unit for unusual conditions (e.g., loose access panels, leaking piping connections, etc.) • Make sure that all retaining screws are reinstalled in the unit access panels once these checks are complete. • With the unit running, check and record the ambient temperature, compressor suction and discharge pressures (each circuit), and superheat (each circuit). • Record this data on an "operator's maintenance log" like the one shown in Table 11, p. 37. If the operating pressures indicate a refrigerant shortage, measurethe system superheat. For guidelines, refer to the "Compressor Start -Up" section. Note: Do not release refrigerant to the atmosphere! If adding or removing refrigerant is required, the service technician must comply with all federal, state and local laws. Heating Season • Inspect the unit's air filters. If necessary, clean or replace them. • Check supply fan motor bearings; repair or replace the motor as necessary. Maintenance • Inspect both the main unit control panel and heat section control box for loose electrical components and terminal connections, as well as damaged wire insulation. Make any necessary repairs. • Clean burner area; verify gas heat system operates properly. Coil Cleaning Regular coil maintenance, including annual cleaning, enhances the unit's operating efficiency by minimizing: • Compressor head pressure and amperage draw • Evaporator water carryover • Fan brake horsepower, due to increased static pressure losses • Airflow reduction At least once each year, or more often if the unit is located in a "dirty" environment, clean the evaporator and condenser coils using the instructions outlined below. Be sure to follow these instructions as closely as possible to avoid damaging the coils. Note: For units equipped with hail guards follow removal procedure listed below. Hail Guard Removal • Unlatch hail guard. • Pull the top ofthe hail guard outward until the fastener studs are free of the retaining nuts. • Liftthe hail guard from the lower retaining bracket and set aside. To clean refrigerant coils, use a soft brush and a sprayer (either a garden pump -up type or a high-pressure sprayer). A high -quality detergent is also required; suggested brands include SPREX A.C., OAKITE 161, OAKITE 166, and COILO. If the detergent selected is strongly alkaline (ph value exceeds 8.5), add an inhibitor. Hazardous Chemicals! Coil cleaning agents can be either acidic or highly alkaline. Handle chemical carefully. Proper handling should include goggles or face shield, chemical resistant gloves, boots, apron or suit as required. For personal safety refer to the cleaning agent manufacturer's Materials Safety Data Sheet and follow all recommended safe handling practices. Failure to follow all safety instructions could result in death or serious injury. 1. Remove enough panels from the unit to gain access to the coil. 2. Protect all electrical devices such as motors and controllers from any over spray. 3. Straighten any bent coil fins with a fin comb. RT-SVX38 D-E N 35 Maintenance 4. Mix the detergent with water according to the manufacturer's instructions. If desired, heat the solution BUT DO NOT EXCEED 150°F maximum to improve its cleansing capability. Hazardous Pressures! Coils contain refrigerant under pressure. When cleaning coils, maintain coil cleaning solution temperature under 150°F to avoid excessive pressure in the coil. Failure to follow these safety precautions could result in coil bursting, which could result in death or serious injury. 5. Pour the cleaning solution into the sprayer. If a high-pressure sprayer is used: a. Do not allow sprayer pressure to exceed 600 psi. b. The minimum nozzle spray angle is 15 degrees. c. Maintain a minimum clearance of 6" between the sprayer nozzle and the coil. d. Spray the solution perpendicular (at 90 degrees) to the coil face. 6. Spray the leaving -airflow side of the coil first; then spray the opposite side of the coil. Allow the cleaning solution to stand on the coil for 5 minutes. 7. Rinse both sides of the coil with cool, clean water. 8. Inspect both sides of the coil; if it still appears to be dirty, repeat Steps 6 and 7. 9. Reinstall all of the components and panels removed in Step 1 and any protective covers installed in Step 2. Note: For units equipped with hail guards follow reinstallation procedure listed below. Hail Guard Reinstallation 1. To reinstall the hail guard, locate the bottom of the hail guard in the lower bracket and secure it to the upper unit bracket with the attached fasteners. Note: Secure hail guard latches. Figure 32. Slide latch Detail A ch Pull down to disengage guard 2. Restore the unit to its operational status and check system operation. Annual Maintenance • Clean and repaint any corroded surface. 36 RT-SVX38D-EN Final Process For future reference, you may find it helpful to record the unit data requested in the blanks provided. Complete Model Number Unit Serial Number Wiring Diagram Numbers (from unit control panel) Table 11. Sample maintenance log Schematics Connections Maintenance Refrigerant Circuit #1 Refrigerant Circuit #2 Suct. Disch. Liquid Disch. Liquid Current Press. Press. Press. Super Sub- Compr. Suct. Press. Press. Super- Sub - Ambient Compr. Psig/ Psig/ Psig/ -heat cool. Oil Press. Psig/ Psig/ heat cool. Date Temp. F/C Oil Level kPa kPa kPa F/C F/C Level Psig/kPa kPa kPa F/C F/C -ok -ok - low - low - ok - ok - low - low - ok - ok - low - low - ok - ok - low - low - ok - ok - low - low - ok - ok - low - low - ok - ok - low - low - ok - ok - low - low - ok - ok - low - low - ok - ok - low - low - ok - ok low - low Note: Check and record the data requested above each month during the cooling season with the unit running. RT-SVX38D-EN 37 Troubleshooting ReliaTelTM Control The RTRM has the ability to provide the service personnel with some unit diagnostics and system status information. Before turning off the main power disconnect switch, use the following steps to check the ReliaTel Refrigeration Module (RTRM). All diagnostics and system status information stored in the RTRM will be lost when the main power is turned off. Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. To prevent injury or death from electrocution, it is the responsibility of the technician to recognize this hazard and use extreme care when performing service procedures with the electrical power energized. 1. Verify that the Liteport LED on the RTRM is burning continuously. If the LED is lit, go to Step 3. 2. If the LED is not lit, verify that 24 VAC is present between J1-1 and J1-2. If 24 VAC is present, proceed to Step 3. If 24 VAC is not present, check the unit main power supply and check the transformer (TNS1). Proceed to Step 3 if necessary. 3. Using "Method 1" or "Method 2" in the "System Status Diagnostic" section, check the following: System status Heating status Cooling status If a System failure is indicated, proceed to Step 4. If no failures are indicated, proceed to Step 5. 4. If a System failure is indicated, recheck Steps 1 and 2. If the LED is not lit in Step 1, and 24 VAC is present in Step 2, the RTRM has failed. Replace the RTRM. 5. If no failures are indicated, use one of the TEST mode procedures described in the "Unit Start -Up" section to start the unit. This procedure allows you to check all of the RTRM outputs and all of the external controls (relays, contactors, etc.) that the RTRM outputs energize, for each respective mode. Proceed to Step 6. 6. Step the system through all of the available modes, and verify operation of all outputs, controls, and modes. If a problem in operation is noted in any mode, you may leave the system in that mode for up to one hour while troubleshooting. Refer to the sequence of operations for each mode, to assist in verifying proper operation. Make the necessary repairs and proceed to Steps 7 and 8. 7. If no abnormal operating conditions appear in the test mode, exit the test mode by turning the power to OFF at the main power disconnect switch. 8. Refer to the individual component test procedures if other microelectronic components are suspect. System Status Checkout Procedure Check system status by using one of the following two methods: Method 1 If the Zone Sensor Module (ZSM) is equipped with a remote panel with LED status indication, you can checkthe unit within the space. If the ZSM does not have LEDs, use Method 2. BAYSENS110*, BAYSENS109*, BAYSENS119*, BAYSENS023A all have the remote panel indication feature. The LED descriptions are listed below. LED 1 (System) On During normal operation Off If a system failure occurs or LED fails Flashing Indicates test mode LED 2 (Heat) On When the heat cycle is operating Off When the heat cycle terminates or LED fails Flashing Indicates a heating failure LED 3 (Cool) On When the cooling cycle is operating Off When the cooling cycle terminates or LED fails Flashing Indicates a cooling failure LED 4 (Service) On Indicates a clogged filter Off During normal operation Flashing Indicates an evaporator fan failure or condensate overflow switch failure The following sections contain a complete listing of failure indication causes. System failure Check the voltage between terminals 6 and 9 on J6; it should read approximately 32 VDC. If no voltage is present, a system failure has occurred. Refer to Step 4 in 38 RT-SVX38D-EN the previous section for the recommended troubleshooting procedure. Heating Failure Verify heat failure by ignition module (IGN) LED indicator: Off No power or power failure On Normal Slow flash Normal, heat call Fast flash 1 flash Communication failure 2 flashes System lockout 3 flashes Pressure switch fail 4 flashes TC01 or TCO2 open 5 flashes Flame without gas valve 6 flashes Flame rollout open Cooling Failure • Cooling and heating set point (slide pot) on the zone sensor has failed. Refer to the "Zone Sensor Test Procedure" section. • Zone temperature thermistor ZTEMP on ZTS failed. Refer to the "Zone Sensor Test Procedure" section. • CC1 or CC2 24 VAC control circuit has opened —check CC1 and CC2 coils and any of the controls below that apply to the unit (HPC1, HPC2). • LPC1 has opened during the 3-minute minimum "on time" during 4 consecutive compressor starts —check LPC1 or LPC2 by testing voltage between the J1-1 and J3-2 terminals on the RTRM and ground. If 24 VAC is present, the LPCs has not tripped. If no voltage is present, LPCs has tripped. Service Failure • If the supplyfanproving switch has closed , the unitwill not operate (when connected to RTOM)—check the fan motor, belts, and proving switch. • Clogged filter switch has closed —check the filters. • If the condensate overflow switch is closed, the unit will not operate —check the float position is not in a tripped condition and verify an "open" between wires connecting to RTOM J6-1, J6-2 (ReliaTellm controls). Simultaneous Heat and Cool Failure • Emergency stop is activated Method 2 The second method for determining system status is done by checking voltage readings at the RTRM (J6). The following sections list system indication descriptions and the approximate voltages. System Failure • Measure the voltage between terminals J6-9 and J6-6. • Normal operation = approximately 32 VDC Troubleshooting • System failure = less than 1 VDC, approximately 0.75 VDC • Test mode = voltage alternates between 32 VDC and 0.75 VDC Heat Failure • Measure the voltage between terminals J6-7 and J6-6. • Heat operating = approximately 32 VDC • Heat off = less than 1 VDC, approximately 0.75 VDC • Heating failure = voltage alternates between 32 VDC and 0.75 VDC Cool Failure • Measure the voltage between terminals J6-8 and J6-6. • Cool Operating = approximately 32 VDC • Cool Off = less than 1 VDC, approximately 0.75 VDC • Cooling Failure = voltage alternates between 32 VDC and 0.75 VDC Service Failure • Measure the voltage between terminals J6-10 and J6-6. • Clogged filter = approximately 32 VDC. • Normal = less than 1 VDC, approximately 0.75 VDC Fan Failure = voltage alternates between 32 VDC and 0.75 VDC. To use LEDs for quick status information at the unit, purchase a BAYSENS110* ZSM and connect wires with alligator clamps to terminals 6 through 10. Connect each respective terminal wire (6 through 10) from the Zone Sensor to the unit J6 terminals 6 through 10. Note: If the system is equipped with a programmable zone sensor, (BAYSENS119*, or BAYSENS023A), the LED indicators will not function while the BAYSENS110* is connected. Resetting Cooling and Ignition Lockouts Cooling failures and heating lockouts are reset in an identical manner. Method 1 explains resetting the system from the space; Method 2 explains resetting the system at the unit. Note: Before resetting Cooling Failures and Ignition Lockouts check the Failure Status Diagnostics by the methods previously explained. Diagnosticswill be lost when the power to the unit is disconnected. Resetting Lockouts —Method 1 To reset the system from the space, turn the "Mode" selection switch at the zone sensor to the OFF position. After approximately 30 seconds, turn the "Mode" selection switch to the desired mode, e.g., Heat, Cool, or Auto. RT-SVX38 D-E N 39 Troubleshooting Resetting Lockouts —Method 2 To reset the system at the unit, cycle the unit power by turning the disconnect switch to OFF and then to ON. Lockouts can be cleared through the building management system. Refer to the building management system instructions for more information. Zone Temperature Sensor (ZTS) Service Indicator The ZSM SERVICE LED is a generic indicator that will signal the closing of a Normally Open switch at any time, providing the Indoor Motor (IDM) is operating. This indicator is usually used to indicate a clogged filter or an air side fan failure. The RTRM will ignore the closing of this Normally Open switch for 2 (±1) minutes. This helps prevent nuisance SERVICE LED indications. The exception is the LED will flash 40 seconds after the fan is turned to ON if the Fan Proving Switch is not made. Clogged Filter Switch This LED will remain lit the entire time that the Normally Open switch is closed. The LED will be turned off immediately after resetting the switch (to the Normally Open position), or any time that the IDM is turned to OFF. If the switch remains closed, and the IDM is turned to ON, the SERVICE LEDwill beturned to ON again afterthe 2 (±1) minute ignore delay. This LED being turned to ON will have no other affect on unit operation. It is an indicator only. Fan Failure Switch When the "Fan Failure" switch is wired to the RTOM, the LED will remain flashing the entire time the fan proving switch is closed, indicating a fan failure, and it will shut down the unit operations. Condensate Overflow Switch When the "Condensate Overflow Switch" is closed, a drain pan overflow condition is indicated, and it will shut unit operations down. Zone Temperature Sensor (ZTS) Test Note: These procedures are not for programmable or digital models and are conducted with the Zone Sensor Module electrically removed from the system. Test 1—Zone Temperature Thermistor (ZTEMP) This component is tested by measuring the resistance between terminals 1 and 2 on the Zone Temperature Sensor. Below are some typical indoor temperatures, and corresponding resistive values. Test 2—Cooling Set Point (CSP) and Heating Set Point (HSP) Table 12. Cooling setpoint and heating setpoint Zone Temperature Nominal ZTEMP Resistance 50oF 10.0 Co 19.9 K-Ohms 55 Fo 12.8 Co 17.47 K-Ohms 60 Fo 15.6 Co 15.3 K-Ohms 65 Fo 18.3 Co 13.49 K-Ohms 70 Fo 21.1 Co 11.9 K-Ohms 75 Fo 23.9 Co 10.50 K-Ohms 80 Fo 26.7 Co 9.3 K-Ohms 85 Fo 29.4 Co 8.25 K-Ohms 90 Fo 32.2 Co 7.3 K-Ohms The resistance of these potentiometers are measured between the following ZSM terminals. Refer to the chart above for approximate resistances at the given setpoints. Cool SP = Terminals 2 and 3 Range = 100 to 900 Ohms approximate Heat SP = Terminals 2 and 5 Range = 100 to 900 Ohms approximate Test 3—System Mode and Fan Selection The combined resistance of the Mode selection switch and the Fan selection switch can be measured between terminals 2 and 4 on the Zone Sensor. The possible switch combinations are listed below with their corresponding resistance values. Test 4— LED Indicator Test, (SYS ON, HEAT, COOL, and SERVICE) Method 1 Testing the LED using a meter with diode test function. Test both forward and reverse bias. Forward bias should measure a voltage drop of 1.5 to 2.5 volts, depending on your meter. Reverse bias will show an Over Load, or open circuit indication if LED is functional. Method 2 Testing the LED with an analog Ohmmeter. Connect Ohmmeter across LED in one direction; then reverse the leads for the opposite direction. The LED should have at least 100 times more resistance in reverse direction, as compared with the forward direction. If high resistance in both directions, LED is open. If low in both directions, LED is shorted. 40 RT-SVX38D-EN Method 3 To test LEDs with ZSM connected to unit, test voltages at LED terminals on ZSM. A measurement of 32 VDC, across an unlit LED, means the LED has failed. Programmable and Digital Zone Sensor Test Testing serial communication voltage 1. Verify 24 VAC is present between terminals J6-14 and J6-1 1. 2. Disconnect wires from J6-11 and J6-12. Measure the voltage between J6-11 and J6-12; it should be about 32 VDC. 3. Reconnect wires to terminals J6-11 and J6-12. Measure voltage again between J6-11 and J6-12; voltage should flash high and low every 0.5 seconds. The voltage on the low end will measure about 19 VDC, while the voltage on the high end will measure from approximately 24 to 38 VDC. 4. Verify all modes of operation, by running the unit through all of the steps in the "Test Modes" section discussed in "Unit Start -Up". 5. After verifying proper unit operation, exit the test mode. Turn on the fan continuously at the ZSM, by pressing the button with the fan symbol. If the fan comes on and runs continuously, the ZSM is good. If you are not able to turn on the fan, the ZSM is defective. ReliaTelTr' Refrigeration Module (RTRM) Default Chart If the RTCI loses input from the building management system, the RTRM will control in the default mode after approximately 15 minutes. If the RTRM loses the Heating and Cooling setpoint input, the RTRM will control in the default mode instantaneously. The temperature sensing thermistor in the Zone Sensor Module is the only component required for the "Default Mode" to operate. Unit Operation without a Zone Sensor This procedure is for temporary operation only. The economizer and condenser fan cycling functions are disabled. Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury 1. Open and lock the unit disconnect switch. 2. Remove the Outside Air Sensor (OAS) from the condenser section of unit. Troubleshooting 3. Use 2 wire nuts to individually cap the wires. 4. Locate the RTRM (J6). Connect 2 wires to terminals J6-1 and 2. 5. Connect the sensor (OAS) using two wire nuts to the 2 field -supplied wires that were connected to terminals 1 and 2 on J6. Unit Economizer Control (ECA) Troubleshooting ReliaTel Control Verify economizer status by economizer actuator (ECA) LED indicator: Off No power or power failure On Normal, OK to economize Slow flash Normal, not OK to economize Fast flash 1/2 sec on/2 sec off Communications failure Pulse flash 2 sec onP/2 sec off 1 flash Actuator fault 2 flashes CO2 sensor 3 flashes RA humidity sensor 4 flashes RA temp sensor 5 flashes OA quality sensor 6 flashes OA humidity sensor 7 flashes OA temp sensor 8 flashes MA temp sensor 9 flashes RAM fault 10 flashes ROM fault 11 flashes EEPROM fault Heating Failure Verify heat failure by ignition module (IGN) LED indicator: Off No power or power failure On Normal Slow flash Normal, heat call Fast flash 1 flash No communication 2 flashes System lockout 3 flashes Pressure switch fail 4 flashes TC01 or TCO2 open 5 flashes Flame w/o gas valve 6 flashes Flame rollout open Cooling Failure • Cooling and heating set point (slide pot) on the thermostat has failed. • CC1 or CC2 24 VAC control circuit has opened, check CC1 and CC2 coils, and any of the controls below that apply to the unit (HPC1, HPC2, LPC1, LPC2, FrostatT"" ) RT-SVX38 D-E N 41 Troubleshooting Resetting Cooling and Ignition Lockouts Cooling failures and ignition lockouts are reset in an identical manner. Method 1 explains resetting the system from the space; Method 2 explains resetting the system at the unit. Resetting Lockouts —Method 1 To reset the system from the space, turn the "Mode" selection switch at the thermostat to the OFF position. After approximately 30 seconds, turn the "Mode" selection switch to the desired mode,e.g., Heat, Cool, or Auto. Resetting Lockouts —Method 2 To reset the system at the unit, cycle the unit power by turning the disconnect switch to OFF and then to ON. 42 RT-SVX38D-EN Unit Wiring Diagrams Numbers Note: Wiring diagrams can be accessed using e-Library by entering the diagram number in the literature Table 13. Unit wiring diagram numbers order number search field or by contacting technical support. Schematic Type Description Control Power Connection Diagram 4366-1012-0110 4366-1005-0104 4366-1543-0110 060EDR 4366-1015-0104 4366-1005-0104 4366-1540-0110 072EDR 4366-1015-0104 4366-1005-0104 4366-1540-0110 090EDR 4366-1042-0110 4366-1034-0110 4366-1532-0110 102EDR 4366-1042-0110 4366-1034-0110 4366-1532-0110 120EDR 4366-2231-0110 4366-2230-0110 4366-2236-0110 060EDK 4366-2231-0110 4366-2230-0110 4366-2236-0110 072EDK 4366-2231-0110 4366-2230-0110 4366-2236-0110 090EDK 4366-2231-0110 4366-2230-0110 4366-2236-0110 102EDK 4366-2231-0110 4366-2230-0110 4366-2236-0110 120EDK RT-SVX38D-EN 43 Limited Warranty Combination Gas Electric Air Conditioner YCC, YCD, YCH, YCP, YSC and YHC (Parts Only) Models Less Than 20 Tons for Residential Use* This limited warranty is extended by Trane to the original purchaser and to any succeeding owner of the real property to which the Combination Gas Electric Air Conditioner is originally affixed, and applies to products purchased and retained for use within the U.S.A. and Canada. If any part of your Combination Gas Electric Air Conditioner fails because of manufacturing defectwithin five years from the date of the original purchase, Warrantor will furnish without charge the required replacement part. Any local transportation, related service labor, diagnosis calls, air filters, refrigerant and related items are not included. If the sealed motor -compressor fails because of a manufacturing defect within five years from the date of original purchase, Warrantor will furnish without charge the required replacement compressor. Any local transportation, related service labor, diagnosis calls, refrigerant and related items are not included. In addition, if the optional, factory installed, stainless steel heat exchanger fails because of a manufacturing defect within ten years from the date of start-up, Warrantor will furnish without charge a replacement heat exchanger. Any local transportation, related service labor and diagnosis calls are not included. This limited warranty does not cover failure of your combination gas electric air conditioner if it is damaged while in your possession, failure attributable or caused by unreasonable use of the combination gas electric air conditioner and/or failure to properly maintain the combination gas electric air conditioner as set forth in the Use and Care manual. This limited warranty applies to product installed on or after 10/1/2001 where product is manufactured after 1/1/2000. This limited warranty is not retroactive to any installations prior to 10/1/2001 or on product produced prior to 2000. USE, AND IN NO EVENT SHALL WARRANTOR BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES. Some states do not allow limitations on how long an implied limited warranty lasts or do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not applyto you. This limited warranty gives you specific legal rights, and you may also have other rights which varyfrom state to state. Parts will be provided by our factory organization through an authorized service organization in your area listed in the yellow pages. If you wish further help or information concerning this limited warranty, contact: Trane 2701 Wilma Rudolph Blvd. Clarksville, TN 37040-1008 Attention: Manager, Product Service G W-618-4001 Combination Gas Electric Air Conditioner YCZ, YCY, YCX, YCC, YCD, YCH, YCP, YHC and YSC (Parts Only) Models Less Than 20 Tons for Commercial Use* This warranty is extended by Trane to the original purchaser and to any succeeding owner of the real property to which the Combination Gas Electric Air Conditioner is originally affixed, and applies to products purchased and retained for use within the U.S.A. and Canada. There is no warranty against corrosion, erosion or deterioration. If any part of your Combination Gas Electric Air Conditioner fails because of a manufacturing defectwithin one year from the date of the original purchase, Warrantor will furnish without charge the required replacement part. In addition, if the sealed motor -compressor fails because of a manufacturing defect within the second through fifth year from the date of original purchase, Warrantor will furnish without charge the required replacement compressor. In addition, if the optional, factory installed, stainless steel THE LIMITED WARRANTY AND LIABILITY SET FORTH heat exchanger fails because of a manufacturing defect HEREIN ARE IN LIEU OF ALL OTHER WARRANTIES AND within ten years from the date of start-up, Warrantor will LIABILITIES, WHETHER IN CONTRACT OR IN furnish without charge a replacement heat exchanger. NEGLIGENCE, EXPRESS OR IMPLIED, IN LAW OR IN Any local transportation, related service labor and FACT, INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR PARTICULAR diagnosis calls are not included. *This limited warranty is for residential usage of this equipment and not applicable when this equipment is used for a commercial application. A commercial use is any application where the end purchaser uses the product for other than personal, family or household purposes. 44 RT-SVX38D-EN Trane and American Standard create comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or americanstandardair.com. Trane and American Standard have a policy of continuous product and product data improvement and reserve the right to change design and specifications without notice. We are committed to using environmentally conscious print practices. RT-SVX38D-EN 02 Apr 2020 Supersedes RT-SVX38C-EN (Mar 2015) ©2020