REVIEWED BLD RESUB1 BLD2021-1190+Interior_Lighting_Summary+9.28.2021_10.33.25_AM+24323092018e Energy Code Compliance Forms for Commercial Buildinqs including R2, R3, R4 over 3 stories and all R1 Revised Auq 2021 rev. 3
Project Info
Project Title: LifeStance Health
Date 9/24/2021
Compliance
forms do not
Applicant Information. Provide contact information for individual who can
respond to inquiries about compliance form information provided.
For SDCI L se g LD2021-1190
require a
password to
R E j u
Company Name: BlueStreak Consulting
Company Address: 25001 Emery Road, Suite 410
use.
Instructional and
calculating cells
are write-
protected.
Sep 28 2021
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
Applicant Name: Cassie George
Applicant Phone: 216-233-3286
Applicant Email: cgeorge@bluestreak-consulting.com
Project Description
❑ New Building ❑ Addition ❑ Alteration ❑ No Lighting Scope
Include PROJ-SUM form (included in envelope forms workbook) with lighting compliance forms.
Interior Lighting System
All fixtures are LED type. Automatic time -clock within the nLight system controls
Description
the automatic off capabilities of Corridor, Waiting and Reception. All other spaces
that require automatic off controls are provided with wall mounted, occupancy
sensor wall switches. Rooms that are exempt to have automatic controls per
Washington Energy Code are provided with a low voltage on/off switch that is
❑� Interior Lighting Plans Included
programmed to turn the lights 100% on when activated.
Interior Lighting Power
0 Building Area Method ❑ Space -by -space Method
Allowance Method
Select method used in project.
Interior Lighting Controls
0 All C405.2, Item 1 Lighting Controls ❑ Control405. (Item 2 Luminaire Level Lighting
❑ Additional Efficiency Package Option
C406.4 Enhanced Digital Lighting Controls
To comply with C406.4, no less than 90% of the total installed interior
lighting power shall comply with the required controls per C406.4.
Sleeping/ Dwelling Unit
Area of multifamily dwelling units complying with C405.1.1 and C405.7 N/A
Interior Lighting
Area of all other dwelling and sleeping units complying with C405.1.1 and C405.2.5 N/A
Area of all other dwelling and sleeping units complying with C405.5 and C405.2.5 N/A
Exterior Lighting System
Not Applicable
Description
❑ Exterior Lighting Plans Included
Building Additions
Compliance Method
Interior lighting
Exterior lighting
Lighting systems in addition area comply with all applicable
provisions as a stand alone new construction project
❑
❑
Refer to Section C502.2.6 for additional
requirements.
Lighting systems in addition are combined with existing
building lighting systems to demonstrate compliance
❑
❑
Addition is combined with existing:
For interior lighting projects, include new + existing -to -remain interior lighting fixture wattage in
Proposed Lighting Wattage table in LTG-INT-BLD or LTG-INT-SPACE form.
For exterior lighting projects, include new + existing -to -remain exterior lighting fixture wattage in
Proposed Tradable and Proposed Non -Tradable Lighting Wattage tables in LTG-EXT form.
2018 Seattle Enerqv Code Compliance Forms for Commercial Buildinqs includinq R2, R3, R4 over 3 stories and all R1 Revised Auq 2021 rev. 3
Project Title: LifeStance Health
Date 9/24/2021
Change of Space Use
❑ Existing interior lighting systems in areas under -going a change in space use are upgraded to
comply with LPAs for the new space types per Tables C405.4.2(1) or C405.4.2(2).
Identify interior spaces requiring LPD upgrade to the current Code in Proposed Lighting Wattage table in
LTG-INT-BLD or LTG-INT-SPACE form.
Interior and Exterior
Lighting Power
Interior lighting
Parking garage
Exterior lighting
Lighting Alterations
Spaces with more lighting than threshold
added, altered or replaced
❑�
❑
❑
(20% int., 20% garage, 20% ext.)
Spaces with less lighting than threshold
Select all Lighting Power and Lighting
Control elements that apply to the scope
added, altered, or replaced
❑
❑
❑
of the retrofit project. If project includes
(20% int., 20% garage, 20% ext.)
multiple spaces (rooms separated by
Lamp and/or ballast replacement only —
ceiling height partitions), each space
existing total wattage not increased
❑
❑
❑
where less than 20% of the existing
More lighting than threshold replaced - Total lighting power of new + existing -to -remain fixtures shall
fixtures are added, altered or replaced can
be combined on a single LTG-INT-SPACE
comply with total LPA per Sections C405.4.2 and C405.5.3. Include new + existing -to -remain fixtures in
form. Spaces where 20% or more of the
Proposed Lighting Wattage table in LTG-INT-BLD, LTG-INT-SPACE or LTG-EXT form.
fixtures are added, altered or replaced
Less lighting than threshold replaced - Total lighting power of new + existing -to -remain fixtures shall
and additions may be combined onto one
not exceed the total lighting power prior to alteration. Include new + existing -to -remain fixtures in the
lighting power compliance form. Parking
Proposed Lighting Wattage table in LTG-INT-BLD, LTG-INT-SPACE or LTG-EXT form.
garages and exterior lighting also have
20% thresholds.
The threshold for interior lighting is 20% of the luminaires within an enclosed space, for parking garages
the threshold is 20% of the luminaires within the garage, and for exterior spaces the threshold is 20% of
Refer to Section C503.6 for additional
the total installed lighting power for the exterior luminaires.
requirements.
Lighting Controls
Interior lighting
Parking garage
Exterior lighting
New wiring installed to serve added
All alteration lighting controls shall be
commissioned per C408.3.
fixtures and/or fixtures relocated to new
❑
❑
❑
circuit(s)
New or moved lighting panel
❑
❑
❑
Interior space is reconfigured -
❑
luminaires unchanged or relocated only
New wiring or circuit - For interior lighting, provide required manual controls per C405.2.3, occupancy
sensor controls per C405.2.1, daylight responsive controls per C405.2.4 and application specific lighting
No changes are being made to
controls per C405.2.5. For exterior lighting, provide required controls per C405.2.6.
❑ the interior or exterior lighting
New or moved panel - Provide all applicable lighting controls as noted for New Wiring and automatic
systems and existing space
time switch controls per C405.2.2.
uses and configuration are not
Reconfigured interior space - Provide all required lighting controls that apply to a new interior space.
changed.
Application specific lighting control provisions per C405.2.5 do not apply to reconfigured spaces.
2018 Seattle Energy Code Compliance Forms for Commercial Buildinqs including R2, R3, R4 over 3 stories and all R1 Revised Auq 2021 rev. 3
Project Title: LifeStance Health
Date 9/24/2021
Calculation
Q New Construction Q Addition - O Addition
For SDCI Use
Area NOTE $
stand alone + existing
O Spaces where < 20% of O Spaces where z 20% of O Spaces where the Use
luminaires are replaced luminaires are replaced is changing (C505)
LPA
Q Standard O C406.3.1 Reduced LPA 10% C406.3.2 Reduced LPA 20%
Calculation
User Note
Type
To comply with C406.3.1 or C406.3.2 the Proposed LPD shall be 10% or
20% lower respectively than the Target LPA. Refer to C406.3 for additional requirements.
Maximum Allowed
Lighting Wattage NOTE I
Watts Allowed
Location (plan #,
Gross Interior
Allowed
(watts/ft2 x area)
Building Area
room #, or ALL)
Area Description
Area in ftZ
Watts per ftZ
NOTE 2
Office
E2.0
Entire Space
3658
0.58
2,122
Total
Proposed Lighting Wattage
Building Area
Location (plan #,
room #)
Fixture Description NOTE 3, 4, 5, 6
Number of
Fixtures
Watts per
Fixture NOTE 7
Watts Proposed
Office
E1.0, E2.0
A (6"x4' Linear LED Fixture)
24
40
960
Office
E1.0, E2.0
Al (6"x4' Linear LED Fixture)
30
24
720
Office
E1.0, E2.0
61 (2'x4' Recessed LED Fixture)
1
37
37
Office
E1.0, E2.0
C (6" LED Downlight Fixture)
6
10
60
Office
E1.0, E2.0
D (4' LED Strip Fixture)
1
34
34
Office
E1.0, E2.0
P1 (14" Decorative LED Pendant Fixture)
12
9
108
Office
E1.0, E2.0
P2 (8" Decorative LED Pendant Fixture)
3
9
27
Office
E1.0, E2.0
S1 (12" Decorative LED Sconce Fixture)
12
5
60
Office
JE1.0, E2.0
S2 (5" Decorative LED Sconce Fixture)
1 13
1 7
191
Office
JE1.0, E2.0
IS3 (14" Decorative LED Sconce Fixture)
1 2
1 9
118
Compliance by Building Area""'
Building Area
Warnings
Total Allowed
Watts
Total Proposed
Watts
Interior Lighting
Power Allowance
Office
Exceeds maximum allowed wattage for this building area for C406.3
compliance
2122
2115
COMPLIES
Totalsi 2,122 12 ,115
Note 1 - List all unique building areas per Table C405.4.2(1) that occur in the project scope. Select building area category fro m drop down menu.
Note 2 - When Watts Allowed indicates "Unlit" no proposed lighting has been entered. Enter lighting fixture information for this building area
surface in Proposed Lighting Wattage table to generate Lighting Power Allowance.
Note 3 - Proposed fixtures must be listed in the building area in which they occur. List all proposed lighting fixtures includin g exempt
lighting equipment and existing -to -remain fixtures.
Note 4 - For proposed Fixture Description, indicate fixture type, lamp type (e.g. T-8), number of lamps in the fixture, and ballast type (if included).
For track lighting, list the length of the track (in feet) in addition to the fixture, lamp, and ballast informati on.
Note 5 - For lighting equipment eligible for exemption per C405.4.1, note exception number and leave Watts/Fixture blank.
Note 6 - Existing -to -remain fixtures shall be included in the Proposed Lighting Wattage table in the same manner as new fixtures. Identify as
existing in fixture description.
Note 7 - For proposed Watts/Fixture enter the luminaire wattage for installed lamp and ballast using manufacturer or other appro ved source. For
luminaires with screw -in lamps, enter the input wattage of the installed lamp. For low voltage lighting, enter the wattage of the
transformer. For line voltage track/busway systems, enter the larger of the attached luminaire wattage or 16 wattsdineal foot, or enter
the wattage limit of permanent current limiting device.
Note 8 - Proposed Wattage for each Building Area type shall not exceed the Allowed Wattage for that Building Area type. Trading wattage
between Building Area types is not allowed under the Building Area Method compliance path.
Note 9 - Calculation Area Details:
a. Lighting fixtures in a building addition may comply as a stand alone project, or they may be combined with the overall existing building
lighting systems to demonstrate compliance. Refer to C502.1.
b. For alterations and building additions, provide Building Area types and gross interior areas in the Maximum Allowed Lighting Wattage
table. If a building addition will comply as combined with the overall existing building lighting systems, include all applicable existing
Building Area types and gross interior areas.
c. If less than 20% of existing lighting fixtures will be replaced, use L TG -INT-SPA CE form to document compliance.
PermitLighting, Motor, and Electrical •
2018 Seattle Energy Code Compliance Forms for Commercial Buildings including R2, R3, R4 over 3 stories and all R1 Revised Aug 2021 rev. 3
Project Title: LifeStance Health
Date 9/24/2021
The following information is necessary to check a permit application for compliance with the lighting, motor, and electrical requirements in the
Washington State Energy Code, Commercial Provisions.
Applicability
Location in
(yes,no,na)
Code Section
Component
Compliance information required in permit documents
Documents
SDCI Notes
LIGHTING
CONTROLS
C405.2
Lighting controls,
For all lighting systems, indicate lighting control method on
Yes
general
plans for spaces and lighting zone(s) served, or exception taken
E2.0
C405.2
LLLC required for
For open office areas larger than 5000 sf, provide LLLC fixtures
NA
open office
or enhanced digital lighting control system
C405.2,
Luminaire level
Indicate on plans all fixtures provided with LLLC complying with
NA
Option 2
lighting controls
C405.2 option 2 lighting controls; provide description of control
(LLLC)
capabilities and performance parameters
C405.2.5
Lighting in dwelling
Indicate method of automatic control of all installed luminaires in
Item 3
units (dormitory, hotel
dwelling units in buildings other than multifamily (occupancy or
NA
C405.2.1.1
and all other than
light reduction controls)
C405.2.3.1
multifamily)
C405.2.5
Lighting in sleeping
Indicate method of automatic off control of all installed
NA
Item 2
units
luminaires in sleeping units (vacancy or key card control); also
refer to Receptacles
C405.2.3
Manual controls
Indicate on plans the method of manual lighting control, location
Yes
C405.2.3.1
of manual control device and the area or specific application it
E2.0
C405.2.5
serves
C405.2.1.1
Manual interior light
Indicate on plans which method of manual 50% lighting load
Yes
C405.2.3.1
reduction controls
reduction is provided, or indicate applicable exception
E2.0/E1.2
C405.2.4
C405.2.1
Method of automatic
Indicate on plans the method of automatic shut-off control
C405.2.2.1
shut-off control
during unoccupied periods (occupancy sensor, time switch or
Yes
C405.2.1,
digital timer switch) for all lighting zones;
E2.0/E1.2
Exception 3
Indicate on plans all luminaires that are controlled by occupant
sensor controls; indicate controls are configured to turn
E2.0
luminaires 100% off when the space is unoccupied;
Indicate if occupant sensor controls are configured to be
C405.2.1
Occupancy sensor
manual on or automatic on to not more than 50% power;
Occupancy
Yes
C405.2.1.1
controls
indicate spaces eligible for exception that allows automatic on
sensors shall be
to 100% power
programmed as
Automatic on/
Automatic off and
lights to "Full On"
C405.2.1.2
Occupant sensor
Indicate each aisleway and corridor within a warehouse space
NA
controls -
are designated as separate zones that are independently
warehouses spaces
controlled
C405.2.1.2
Occupant sensor
Indicate occupant sensors are configured to automatically
controls - warehouse
reduce lighting power by 50% within 20 minutes of all occupants
spaces, storage
leaving the zone; indicate controls are configured to
NA
areas and service
automatically restore full power when the zone is occupied;
corridors
indicate occupant sensors turn lighting off within 20 minutes of
all occupants leaving the space, or time switch controls
provided
C405.2.1.3
Occupant sensor
For open plan office areas larger than 300 sf, indicate general
controls - open plan
lighting is provided with vacancy controls that reduce lighting
NA
office areas
power by not less than 80% and are configured to turn
luminaires 100% off when the open plan office area is
unoccupied; indicate that no individual control zone area
C405.2.1.4
Occupant sensor
Indicate parking garage general lighting is provided with
controls - parking
vacancy controls to automatically reduce lighting power by not
garages
less than 30% within 20 minutes of no activity being detected;
NA
indicate that no control zone exceeds 3,600 sf; indicate
occupancy sensors turn lighting off within 20 minutes of space
vacancy, or time switch controls provided
C405.2.1.5
Occupant sensor
Indicate stairway lighting is provided with vacancy controls that
NA
controls - enclosed
reduce lighting power by not less than 50% when the stairway in
fire -rated stairwells
unoccupied
Indicate spaces on plans where time switch controls turn
luminaires 100% off during unoccupied hours
E2.0/E1.2
Indicate locations where automatic shutoff is provided by other
methods (occupancy sensor or digital timer switch) or which
E2.0/E1.2
Automatic time
time switch control exception applies
Yes
C405.2.2.1
switch controls
Indicate spaces on plans where time switch controls are
configured to turn on lighting to full power versus 50% power
E2.0/E1.2
Indicate locations of override switches on plans and the lighting
zone(s) served; indicate that the area(s) served by each
E2.0/E1.2
override switch does not exceeds 5,000 sf
C405.2.1,
Digital timer switch
Indicate digital timer switch control includes: manual on/off, time
Yes
Exception 3
delay, audible and visual indication of impending time-out
E2.1
Indicate primary and secondary sidelit daylight zone floor areas
E2.0
on plans;
Indicate toplit daylight zone floor areas on plans;
NA
C405.2.4.2
Daylight zones -
For small vertical fenestration assemblies (rough opening less
( 9 P 9
Yes
C405.2.4.3
Sidelit and toplit
than 10 percent of primary daylight zone floor area) where
NA
daylight responsive controls are not required, provide
fenestration area to daylight zone floor area calculation(s)
PermitLighting, Motor, and Electrical •
2018 Seattle Energy Code Compliance Forms for Commercial Buildings including R2, R3, R4 over 3 stories and all R1 Revised Aug 2021 rev. 3
Project Title: LifeStance Health
Date 9/24/2021
The following information is necessary to check a permit application for compliance with the lighting, motor, and electrical requirements in the
Washington State Energy Code, Commercial Provisions.
Applicability
Location in
(yes,no,na)
Code Section
Component
Compliance information required in permit documents
Documents
#REF!
Indicate on plans lighting zone(s) served by daylight responsive
controls; indicate that the area served by each control device
does not exceeds 2,500 sf;
Identify sidelit and toplit daylight zones that are not provided
NA
C405.2.4
Daylight responsive
with daylight sensing controls and the exception(s) that apply;
controls
Indicate on plans the lighting load reduction method (continuous
dimming, or stepped dimming that provides at least two even
steps between 0%-100% of rated power);
Indicate that daylight sensing controls are configured to
completely shut off all controlled lights in the lighting zone
Additional controls -
Identify spaces and lighting fixtures on plans that require
NA
C405.2.5
Specific application
specific application lighting controls per this section
lighting controls
Indicate on plans that manual controls are provided that control
display, accent lighting and display case lighting independently
NA
C405.2.5 -
Display and accent
from both general area lighting and other lighting applications
Item 1
lighting
within the same space;
Indicate manual and automatic (occupant sensor or time switch)
lighting control methods
C405.2.5 -
Hotel/motel guest
Indicate method of automatic control - vacancy or captive key
NA
Item 2
control of all installed luminaires and switched receptacles in
rooms
guest room
C405.2.5 -
Supplemental task
Indicate method and location of manual and automatic shut-off
NA
Item 1
lighting
control (occupant sensor or time switch) for supplemental task
lighting, including under -shelf or under -cabinet lighting
Indicate on plans that lighting equipment for sale or
demonstration are controlled independently from both general
NA
C405.2.5 -
Supplemental task
area lighting and other lighting applications within the same
Item 1
lighting
space;
Indicate manual and automatic (occupant sensor or time switch)
lighting control methods
Identify all eligible non -visual lighting applications on plans;
indicate that the area served by each control device does not
exceeds 4,000 sf;
NA
C405.2.5 -
Lighting for non-
Indicate on plans that non -visual lighting are controlled
Item 4
visual applications
independently from both general area lighting and other lighting
applications within the same space;
Indicate method of manual lighting control and applicable
automatic lighting control
Identify on plans egress fixtures that function as both normal
E2.0
and emergency means of egress illumination;
Provide calculation of lighting power density of total egress
lighting operating 24/7 and demonstrate that is is equal to or
less than 0.01 W/ft2;
BG1/SC1
Yes
C405.2.5 -
Means of egress
Item 5
lighting
Automatic time
Indicate method of automatic shut-off control
switch or
occupant sensing
within room
For decorative exterior lighting, indicate on plans automatic
daylight shut-off controls, or exception taken
For exterior lighting that is not decorative, indicate on plans
Exterior lighting
automatic daylight or time -switch shut-off controls and setback
NA
C405.2.6
controls
controls; or indicate exception taken
For lighting requiring setback controls, include control sequence
that reduces lighting power by at least 30% between 12am-6am,
or from 1 hour after closing to 1 hour before opening, or based
upon motion sensor
Exterior lighting
For building facade and landscape lighting, indicate control
NA
C405.2.6
controls - Building
sequence for shut-off control is based on dawn -to -dusk and
facade and
business opening/closing schedule; indicate whether automatic
landscape
or time switch controls will be provided for this function
NA
C405.5.4
Exterior gas -fired
Indicate ignition system is a method other then continuously
lighting appliances
burning pilot light
Area controls -
Indicate location(s) of master control switch(es) intended to
Master control
control multiple independent switches; circuit breaker may not
NA
C405.2.7
switches and circuit
be used as a master control switch;
Verify that no single switch controls more than one 20-amp
E1.0
power limit
circuit, loaded to maximum 80% capacity
ADDITIONAL
EFFICIENCY
PACKAGE OPTION - ENHANCED DIGITAL LIGHTING CONTROLS
To comply with additional efficiency credit, indicate on plans
that interior lighting fixtures are configured with all of the
following control functions, as applicable: 1) Each fixture is
individually addressed, or exception taken; 2) Fixtures are
configured for continuous dimming; 3) No more than eight
fixtures are controlled by a single daylight sensor; 4) In
Enhanced digital
enclosed and open office areas, illumination levels of overhead
NA
C406.4
lighting controls
general area lighting is configured to be individually adjusted by
occupants;
Include calculations that demonstrate the total lighting power of
all interior lighting fixtures configured with enhanced lighting
controls is no less than 90% of the total interior lighting power
for the area the enhanced lighting controls credit is being
applied to
PermitLighting, Motor, and Electrical •
2018 Seattle Energy Code Compliance Forms for Commercial Buildings including R2, R3, R4 over 3 stories and all R1 Revised Aug 2021 rev. 3
Project Title: LifeStance Health
Date 9/24/2021
The following information is necessary to check a permit application for compliance with the lighting, motor, and electrical requirements in the
Washington State Energy Code, Commercial Provisions.
Applicability
Location in
(yes,no,na)
Code Section
Component
Compliance information required in permit documents
Documents
SDCI Notes
INTERIOR
LIGHTING POWER & EFFICACY
Include all luminaires in interior lighting fixture schedule;
E1.0 Luminalire
indicate fixture types, lamps, ballasts, and manufacturer's watts
Schedule
per fixture for the installed lamp;
Identify spaces eligible for lighting power exemption on plans
C405.4.1
Total connected
Yes
C405.4.2
interior lighting power
and in SEC interior lighting compliance reports; indicate the
NA
exception applied;
Identify lighting equipment eligible for lighting power exemption
in fixture schedule and in SEC interior lighting compliance
NA
reports; indicate the exception applied;
Total connected
Indicate on plans any areas where proposed wattage is
NA
C405.4.1
interior lighting power
calculated as the total dedicated lighting branch wattage; detail
alternative
rated wattage and proposed lighting power for each branch
For all installed luminaires, include lamp type and number of
NA
C405.1
Lighting in dwelling
lamps in lighting fixture schedule; for lamps that are not LED, T-
C405.1.1
units (multifamily)
8 or small diameter fluorescent, indicate efficacy of other lamp
types is 65 lumens per watt or greater
Lighting in dwelling
For all installed luminaires, indicate in lighting fixture schedule
NA
C405.1
units (dormitory, hotel
whether complying via lighting power density or by qualifying
gC405.1.1
and all other than
lamp type; if by lamp type, include number of lamps
multifamily)
Lighting in sleeping
For all installed luminaires, indicate in lighting fixture schedule
NA
JC405.1
C405.1.1
units
whether complying via lighting power density or by qualifying
lamp type; if by lamp type, include number of lamps
Interior Lighting Power Calculation - Indicate compliance path taken
Demonstrate that total proposed wattage per building area does
Yes
C405.4.2.1
Building Area Method
not exceed maximum allowed wattage per building area; identify
LTG-INT-BLD
locations of building areas on plans; provide SEC exterior
lighting compliance reports
Demonstrate that total proposed wattage does not exceed
Space -By -Space
maximum allowed wattage; identify locations of space types on
NA
C405.4.2.2
Method
plans, including retail display areas and areas with display,
highlight and decorative lighting; provide SEC exterior lighting
compliance reports
ADDITIONAL
EFFICIENCY PACKAGE OPTION - REDUCED INTERIOR LIGHTING POWER DENSITY
To comply with additional efficiency credit, demonstrate that
total connected interior lighting wattage is 10% or 20% less than
C406.3.1
Reduced interior
the total maximum allowed lighting wattage for the area the
NA
C406.3.2
lighting power density
reduced lighting power credit is being applied to; indicate
whether lighting power allowance is based on the building area
method or space -by -space method; provide SEC exterior
lighting compliance reports
For project with dwelling units, to comply with additional
Reduced interior
efficiency credit indicate in lighting fixture schedule that lamps
NA
C406.3
lighting power density
within installed interior luminaires have an efficacy rating of at
- dwelling unit lamp
least 65 lumens per watt; include number of lamps and provide
efficacy
calculations that demonstrate at least 95% of lamps have this
efficacy rating
EXTERIOR
LIGHTING POWER & EFFICACY
Include all luminaires in exterior lighting fixture schedule;
indicate fixture types, lamps, ballasts, and manufacturer's watts
per fixture for the installed lamp;
Identify exterior applications eligible for lighting power
Total connected
NA
C405.5.2
exterior lighting
exemption on plans and in SEC exterior lighting compliance
reports; indicate exception applied;
power
Indicate that exempt exterior lighting and lighting located within
exterior areas/surfaces that eligible for a lighting power
exemption are controlled independently from non-exempt
exterior lighting;
NA
C405.5.3(1)
Exterior lighting zone
Indicate building exterior lighting zone as specified by the AHJ
Exterior building
For building grounds fixtures rated at greater than 50 watts,
NA
C405.5.1
grounds lighting
indicate rated lamp efficacy (in lumens per watt) in fixture
schedule
Identify locations of tradable and non -tradeable surfaces on
plans
NA
C405.5.3
Exterior lighting
power calculations
Complete required compliance form —proposed wattage for
exterior lighting plus base site allowed does not exceed
maximum allowed
For open parking, outdoor area, and roadway luminaires
NA
C405.5.5
Full cutoff luminaires
mounted more than 15 feet above the ground, indicate fixture
with zero candela at an angle of 90 degrees.
Lighting, Motor, and Electrical Permit Checklist, Pg. 4 LTG-CHK
2018 Seattle Energy Code Compliance Forms for Commercial Buildings including R2, R3, R4 over 3 stories and all R1 Revised Aug 2021 rev. 3
Project Title: LifeStance Health
Date 9/24/2021
The following information is necessary to check a permit application for compliance with the lighting, motor, and electrical requirements in the
Washington State Energy Code, Commercial Provisions.
Applicability
Location in
(yes,no,na)
Code Section
Component
Compliance information required in permit documents
Documents
SDCI Notes
LIGHTING
ALTERATIONS
Where >_ 20% of existing luminaires in an interior space or
parking garage are replaced; indicate compliance path (building
area or space -by -space method); include all new and existing -to -
remain luminaires in SEC interior lighting compliance reports;
indicate proposed lighting wattage does not exceed maximum
Interior and parking
allowed per compliance path
Where < 20% of existing luminaires in an interior space or
NA
C503.6.1
garage lighting fixture
alterations
parking garage are replaced; indicate total existing lighting
wattage in each space prior to alteration; include all new and
existing -to -remain luminaires in SEC interior lighting compliance
reports; indicate proposed total lighting wattage in alteration
area does not exceed total existing lighting wattage prior to
alteration
Where z 20% of existing exterior lighting wattage is replaced;
include all new and existing -to -remain luminaires in SEC
exterior lighting compliance reports; indicate proposed total
exterior lighting wattage does not exceed maximum allowed
NA
C503.6.1
Exterior lighting
fixture alterations
o
Where < 20% of existing exterior lighting wattage is replaced;
indicate total existing lighting wattage prior to alteration; include
all new and existing -to -remain luminaires in SEC interior
exterior compliance reports; indicate proposed total exterior
lighting wattage does not exceed total existing wattage prior to
alteration
Where new wiring is installed to serve new interior luminaires
and /or luminaires are relocated to a new circuit; indicate
NA
C503.6.2
Interior lighting wiring
manual and automatic lighting controls are provided (as
alterations
applicable) - manual (C405.2.3); occupancy sensor (C405.2.1);
light reduction (C405.2.3); daylight responsive (C405.2.4);
specific application (C405.2.5);
Exterior lighting
Where new wiring is installed to serve new exterior luminaires
NA
C503.6.2
wiring alterations
and /or luminaires are relocated to a new circuit; indicate
automatic lighting controls are provided (C405.2.6)
Where a new interior and/or exterior lighting panel is installed or
NA
C503.6.3
Lighting panel
an existing panel is moved (all new raceway and conductor
alterations
wiring), indicate all applicable lighting controls requirements
apply
Where interior space(s) is reconfigured (permanently installed
Yes
C503.6.4
Newly -created rooms
walls or ceiling -height partitions) to create new enclosed
E2.0
spaces, indicate all applicable lighting controls requirements
apply
Identify spaces on plans where the building area type or space
use type is being changed from one type to another per Tables
Entire Space
C405.4.2(1) or (2)
Indicate compliance method (building area or space -by -space);
Yes
C505.1
Change of interior
space use
include all new and existing -to -remain luminaires in SEC interior
LTG-INT-BLD
lighting compliance reports; indicate proposed lighting wattage
does not exceed maximum allowed per compliance path
Indicate lighting controls provided per C405.2
E2.0/E1.2
RECEPTACLES
Identify all controlled and uncontrolled receptacles on electrical
plans in each space in which they are required; include
receptacle configuration such as spacing between controlled
and uncontrolled, duplex devices, etc;
Provide schedule that lists the number of controlled and
Controlled
uncontrolled receptacles in each space where controlled
NA
C405.10
receptacles
receptacles are required - classrooms, private offices, open
office areas, conference rooms, copy rooms, break rooms and
modular partitions/workstations
Indicate on plans the method of automatic control for each
controlled receptacle zone (occupant sensor or programmable
time -of -day control); indicate that each zone served by a single
controller does not exceed 5,000 sf;
NA
C405.2.5
Switched receptacles
Indicate method of automatic off control of all switched
Item 2
in sleeping units
receptacles in sleeping units (vacancy or key card control)
Where new receptacles are added or replaced within an
NA
C503.6.6
Electrical receptacle
alteration project that is 5,000 sf or larger, indicate new or
alerations
altered receptacles are provided with automatic controls per
C405.10, or exception taken
PermitLighting, Motor, and Electrical •
2018 Seattle Energy Code Compliance Forms for Commercial Buildings including R2, R3, R4 over 3 stories and all R1 Revised Aug 2021 rev. 3
Project Title: LifeStance Health
Date 9/24/2021
The following information is necessary to check a permit application for compliance with the lighting, motor, and electrical requirements in the
Washington State Energy Code, Commercial Provisions.
Applicability
Location in
(yes,no,na)
Code Section
Component
Compliance information required in permit documents
Documents
SDCI Notes
MOTORS, TRANSFORMERS,
ELECTRIC
METERS, INTERIOR TRANSPORTATION
NA
C405.6
Electrical
Include electrical transformer schedule on electrical plans;
transformers
indicate transformer type, size, efficiency, or exception taken
Yes
C405.11
Feeders and branch
Provide documentation that demonstrates maximum voltage
E2.0
circuits
drop across feeders and branch circuits does not exceed 5%
Dwelling unit
Indicate on electrical plans that each dwelling unit in Group R-2
NA
C405.7
electrical energy
has a separate electrical energy meter
consumption
NA
C405.7.1
Receptacles at gas
provide 240/208 volt receptacle at each gas appliance
appliances
Electric motor
Include all motors, including fractional hp motors, in electric
NA
C405.8
efficiency
motor schedule on electrical plans; indicate motor type,
horsepower, rpm, rated efficiency, or exception applied
For luminaires in each elevator cab, provide calculations that
demonstrate average efficacy is not less than 35 lumens/W;
Indicate rated watts per cfm for elevator cab ventilation fans do
NA
C405.9.1
Elevator cabs
not exceed 0.33 watts per cfm;
Indicate automatic controls that de -energize lighting and
ventilation fans when elevator is stopped and unoccupied for a
period of 15 minutes or more
Indicate escalators comply with ASME A17.1/CSA B44;
NA
C405.9.2
Escalators and
automatic controls are configured to reduce operational speed
moving walks
to the minimum permitted when not in use or uses a variable
voltage drive system
NA
C405.9.3
Regenerative drive
Indicate all one-way down or reversible escalators are provided
with a variable frequency regenerative drive
DOCUMENTATION
AND SYSTEM REQUIREMENTS TO SUPPORT COMMISSIONING (Cx)
Indicate that controlled receptacles are required to be
commissioned
Scope of electrical
p
Where total building lighting load is > 20 kW, or where total
Commissioning of
Lighitng System is
Yes
C408.4
power and lighting
lighting load of luminaires requiring daylight sensing and / or
exempt as total
systems
occupancy control > 10 kW, indicate that all automatic lighting
lighting is <20kw
commissioning
control systems are required to be commissioned; or provide
and daylight
building lighting power calculation demonstrating eligibility for
exception;
and/or occupancy
controls is <10kw
E1.0
Commissioning
Notes. Lighting
and Lighting
Indicate Cx requirements in plans and specifications for all
Control Systems
applicable electrical and lighting control systems per C408;
are exempt from
commissioning
due to the total
C405.13
Commissioning
installed lighitng
C408.1.1
requirements in
load is less than
Yes
C408.1.2
construction
20kw
C408.1.4
C103.6
documents
Include general summary of Cx plan per C408.1.2 including: 1)
Narrative description of activities; 2) Responsibilities of the Cx
E1.0
team; 3) Schedule of activities including verification of project
Commissioning
close out documentation per C103.6; 4) Conflict of interest plan
Notes
(if required);
Include in general summary that a Cx project report and
E1.0
Compliance Checklist (Figure C408.1.4.1) shall be completed
Commissioning
by the Certified Cx Professional and provided to the owner prior
to the final electrical inspection
Notes
Functional
Identify in plans and specifications the intended operation of all
E1.0
Yes
C408.4.1
performance testing
equipment and controls during all modes of operation, including
Commissioning
criteria
interfacing between new and existing -to -remain systems
Notes
PROJECT CLOSE OUT DOCUMENTATION
Indicate in plans that project close out documentation is
Project close out
required including SEC lighting compliance forms and
E1.0
Yes
C103.6.3
documentation
calculations that document all interior and exterior lighting area
Commissioning
requirements
and / or surface types, lighting power allowances and installed
Notes
densities
If "no" is selected for any question, provide explanation:
End of Lighting, Motor & Transformer Permit Documents Checklist