APPROVED FIR FIR2021-0123+Calculations+11.9.2021_3.42.59_PM+2511710N TENANT IMPROVEMENT SPRINKLER PLAN
SCALE 1/4 =1 -0
FITTER NOTES
1. EXISTING PIPE SHOWN DASHED TO REMAIN U.O.N
2. EXISTING UPRIGHTS TO REMAIN, NOT SHOWN FOR CLARITY
3. FOR HANGER USE '15W', TYP. SEE DETAIL THIS SHEET
FLAG NOTES
DRELOCATE EXISTING PENDENT
2D OFF EXISTING SPRIG, CUT IN TEE, ARMOVER FLEX AND PENDENT
DPLUG EXISTING PENDENT
CADD 1'/4x1 MECH TEE, FLEX AND PENDENT
H
r)
SAMMY SIDEWINDER
O
O
0
0
J
CD
3/8" ALL-0—
THREAD ROD
SCOPE OF WORK
NORTHWEST FIRE SYSTEMS (NWFS) WILL PROVIDE PROPER COVERAGE
FOR NEW WALLAND CEILING LAYOUT
ALLAREAS PROTECTED BYA WET SYSTEM MUST BE MAINTAINED BY
OTHERS ATA MINIMUM 40OF TO PREVENT FREEZING.
EXCLUSIONS
PAINTING OR LABELING OF PIPE AND/OR EQUIPMENT
ELECTRICAL WIRING OFANY KIND INCLUDING BUT NOT LIMITED TO
WATERFLOW SWITCH, ELECTRIC BELL, AND TAMPER SWITCHES
RING HANGER �� �_— PIPE CENTRAL STATION MONITORING EQUIPMENT, WIRING AND SERVICES
HANGER NO. 15W
SAMMY SCREW
KEY PLAN
ALL UNDERGROUND WORK INCLUDING BUT NOT LIMITED TO: BACKFILL,
SELECT FILL, BREAKING PATCHING, SAW CUTTING, LAWN REPAIR,
LANDSCAPING, TREE REMOVAL, STERILIZATION, DEVELOPMENT FEES
AND CITY CONNECTION.
DESIGN CRITERIA
PER NFPA 13 (2016), CITY OF EDMONDS
WET SYSTEM (EXISTING)
LIGHT HAZARD- OFFICE
DESIGN DENSITY. 0.10 GPM / 900 SF
REMODEL DOES NOT EXCEED CURRENT LIMITATIONS
NO NEW HYDRAULIC CALCULATIONS WERE PERFORMED
SYMBOLS
'4=1I► IFIX 4=I:4;jWTI ► h'3461=163��
SWAY BRACING
0
f
PIPE HANGER
AF
BRANCHLINE RESTRAINT
FLEXIBLE COUPLING
RIGID COUPLING
OHYDRAULIC
NODE
RDXX
LINE PIPE DESIGNATION LABEL
RED
13a
MAIN PIPE DESIGNATION LABEL
FLOW SWITCH (FS)
It CHECKVALVE
j BUTTERFLY VALVE
f
BALL VALVE
HOSE VALVE
�—!
�1
-0r
X-X TS
X-X BB
X-X FF
GROOVED ELL (LOOKING SIDEWAYS)
GROOVED ELL (LOOKING DOWN)
GROOVED 450 ELL VERTICAL OFFSET
GROOVED 450 ELL LATERAL OFFSET
THREADED PIPE VERTICAL OFFSET
EXISTING SPRINKLER PIPING
NEW SPRINKLER PIPING
CENTERLINE OF PIPE TO BOTTOM OF DECK
CENTERLINE OF PIPE TO BOTTOM OF BEAM OR JOIST
CENTERLINE OF PIPE ABOVE FINISHED FLOOR
SITE PLAN SYMBOLS
L, s
GATE VALVE-N.R.S. (GV)
Ls
OS&Y GATE VALVE (OS&Y)
ELECTRIC BELL
`
CHECK VALVE
FIRE DEPARTMENT CONNECTION
(WALL MOUNT)
FIRE DEPARTMENT CONNECTION
(YARs?--=
EXISTING FIRE HYDRANT
�pz
NEW FIRE HYDRANT
POST INDICATOR VALVE (PIV)
4THRUST
BLOCK
TB
EXISTING UNDERGROUND PIPING
NEW UNDERGROUND PIPING BY OTHERS
NEW UNDERGROUND PIPING BY RHFP
ABBREVIATIONS
Sprinkler Legend -Existing
ATR
ALL -THREAD ROD
SN
GROOVED SHAPED NIPPLE
SYM
MAN
SIN
ORIENT
TYPE
K-FACT
THD
TEMP
FIN.
Quantity
(t'
CENTERLINE
SS
STAINLESS STEEL
Tyco
TY3131
Upright
Quick
5.6
'/
1550F
Chrome
1
CTS
CUTTO SUIT
TYP
TYPICAL
Total = 1
FDC
FIRE DEPARTMENT CONNECTIC
NUNO
UNLESS NOTED OTHERWISE
Sprinkler Legend -New
GAL
GALVANIZED
RN
RISER NIPPLE
IFOW
INSIDE FACE OF WALL
DR
DROP
SYM
MAN
SIN
ORIENT
TYPE
K-FACT
THD
TEMP
FIN.
Quantity
MT
MECHANICALTEE
DN
PIPE DOWN
Tyco
TY323
Pendent
Quick
5.6
'/
1550F
Chrome
40
O.C.
ON CENTER
UP
PIPE UP
Total = 40
POL
PIPE-O-LET
THR
THREAD
RC
REDUCING COUPLING
NANTNJVAfSTANSYSrANIS
22645 83rd ave. S., Bldg D *Kent, WA 98032
Ph:206.772.7502 * Fax: 206.772.7504
www.nwfiresystems.com LIC # NORTHFS928CR
NICET Stamp
P----------------------------+
WASHINGTON STATE
1 CERTIFICATE OF COMPETENCY ■
FIRE PROTECTION SPRINKLER STSTMIS
Byron Richard Moye �I
1 9419-0815-C Level N ■
Northwest Fire Systems, LLC o *�
1 NORTHFS928CR■
1 ■
i .�. xpirn i
Sign lui 12131/27
L............«........... momi
Approvals Required
EDMONDS
OWNER /ARCHITECT
Revisions
Contract With:
FERRISJURNEY
GENERAL
A/\LITP1 A AT/1P1A
PO BOX 31109
SEATTLE, WA 98103
SUPERINTENDENT: SEAN RANKIN
Phone: 206-889-0102
Fax:
Contract Name:
LIFESTANCE
.1A_INII.
21727 76TH AVE WEST
EDMONDS, WA 98026
Drawing Title
TENANT IMPROVEMENT
SPRINKLER PLAN
Key Plan
RECEIVED
Nov 12 2021
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
FIR2021-0123
Date:
Job Number:
Designer:
Building Permit:
Drawing No.
November 04, 2021
05135C
BRYAN FARMER
FP1m10