Loading...
APPROVED FIR FIR2021-0123+Fire_Sprinkler_Plan+11.9.2021_3.42.44_PM+2511708N TENANT IMPROVEMENT SPRINKLER PLAN SCALE 1/4 =1 -0 FITTER NOTES 1. EXISTING PIPE SHOWN DASHED TO REMAIN U.O.N 2. EXISTING UPRIGHTS TO REMAIN, NOT SHOWN FOR CLARITY 3. FOR HANGER USE '15W', TYP. SEE DETAIL THIS SHEET FLAG NOTES DRELOCATE EXISTING PENDENT 2D OFF EXISTING SPRIG, CUT IN TEE, ARMOVER FLEX AND PENDENT DPLUG EXISTING PENDENT CADD 1'/4x1 MECH TEE, FLEX AND PENDENT 11-24-2021 PLAN REVIEW NOTES: Approved DFM Burt Approved D F M C lk r'Ls -P>u.rt South County Fire Date: 11 /24/2021 H r) SAMMY SIDEWINDER O O 0 0 J CD 3/8" ALL-0— THREAD ROD SCOPE OF WORK NORTHWEST FIRE SYSTEMS (NWFS) WILL PROVIDE PROPER COVERAGE FOR NEW WALLAND CEILING LAYOUT ALLAREAS PROTECTED BYA WET SYSTEM MUST BE MAINTAINED BY OTHERS ATA MINIMUM 40OF TO PREVENT FREEZING. EXCLUSIONS PAINTING OR LABELING OF PIPE AND/OR EQUIPMENT ELECTRICAL WIRING OFANY KIND INCLUDING BUT NOT LIMITED TO WATERFLOW SWITCH, ELECTRIC BELL, AND TAMPER SWITCHES RING HANGER �� �_— PIPE CENTRAL STATION MONITORING EQUIPMENT, WIRING AND SERVICES HANGER NO. 15W SAMMY SCREW KEY PLAN ALL UNDERGROUND WORK INCLUDING BUT NOT LIMITED TO: BACKFILL, SELECT FILL, BREAKING PATCHING, SAW CUTTING, LAWN REPAIR, LANDSCAPING, TREE REMOVAL, STERILIZATION, DEVELOPMENT FEES AND CITY CONNECTION. DESIGN CRITERIA PER NFPA 13 (2016), CITY OF EDMONDS WET SYSTEM (EXISTING) LIGHT HAZARD- OFFICE DESIGN DENSITY: 0.10 GPM / 900 SF REMODEL DOES NOT EXCEED CURRENT LIMITATIONS NO NEW HYDRAULIC CALCULATIONS WERE PERFORMED SYMBOLS 'Ll;j:II►IFIX 4=I:a;jWTI h'3461**]%� SWAY BRACING 0 f PIPE HANGER BRANCHLINE RESTRAINT FLEXIBLE COUPLING RIGID COUPLING OHYDRAULIC NODE RDXX LINE PIPE DESIGNATION LABEL RED 13a MAIN PIPE DESIGNATION LABEL FLOW SWITCH (FS) It CHECKVALVE j BUTTERFLY VALVE f BALL VALVE HOSE VALVE �—! �1 —0r X-X TS X-X BB X-X FF GROOVED ELL (LOOKING SIDEWAYS) GROOVED ELL (LOOKING DOWN) GROOVED 450 ELL VERTICAL OFFSET GROOVED 450 ELL LATERAL OFFSET THREADED PIPE VERTICAL OFFSET EXISTING SPRINKLER PIPING NEW SPRINKLER PIPING CENTERLINE OF PIPE TO BOTTOM OF DECK CENTERLINE OF PIPE TO BOTTOM OF BEAM OR JOIST CENTERLINE OF PIPE ABOVE FINISHED FLOOR SITE PLAN SYMBOLS L, s GATE VALVE-N.R.S. (GV) Ls OS&Y GATE VALVE (OS&Y) ELECTRIC BELL CHECK VALVE FIRE DEPARTMENT CONNECTION (WALL MOUNT) FIRE DEPARTMENT CONNECTION (YARs?--= EXISTING FIRE HYDRANT �pz NEW FIRE HYDRANT POST INDICATOR VALVE (PIV) 4THRUST BLOCK TB EXISTING UNDERGROUND PIPING NEW UNDERGROUND PIPING BY OTHERS NEW UNDERGROUND PIPING BY RHFP ABBREVIATIONS Sprinkler Legend -Existing ATR ALL -THREAD ROD SN GROOVED SHAPED NIPPLE SYM MAN SIN ORIENT TYPE K-FACT THD TEMP FIN. Quantity (t' CENTERLINE SS STAINLESS STEEL Tyco TY3131 Upright Quick 5.6 '/ 155°F Chrome 1 CTS CUTTO SUIT TYP TYPICAL Total = 1 FDC FIRE DEPARTMENT CONNECTIC NUNO UNLESS NOTED OTHERWISE Sprinkler Legend -New GAL GALVANIZED RN RISER NIPPLE IFOW INSIDE FACE OF WALL DR DROP SYM MAN SIN ORIENT TYPE K-FACT THD TEMP FIN. Quantity MT MECHANICALTEE DN PIPE DOWN Tyco TY323 Pendent Quick 5.6 '/ 1550F Chrome 40 O.C. ON CENTER UP PIPE UP Total = 40 POL PIPE-O-LET THR THREAD RC REDUCING COUPLING NANTNJVAfSTANSYSrANIS 22645 83rd ave. S., Bldg D *Kent, WA 98032 Ph:206.772.7502 * Fax: 206.772.7504 www.nwfiresystems.com LIC # NORTHFS928CR NICET Stamp P----------------------------+ WASHINGTON STATE 1 CERTIFICATE OF COMPETENCY ■ FIRE PROTECTION SPRINKLER STSTMIS Byron Richard Moye �I 1 9419-0815-C Level N ■ Northwest Fire Systems, LLC o *� 1 NORTHFS928CR■ 1 ■ i .�. xpirn i Sign lui 12131/27 L............«........... momi Approvals Required EDMONDS OWNER /ARCHITECT Revisions Contract With: FERRISJURNEY GENERAL A/\LITP1 A AT/1P1A PO BOX 31109 SEATTLE, WA 98103 SUPERINTENDENT: SEAN RANKIN Phone: 206-889-0102 Fax: Contract Name: LIFESTANCE :IA_INI: 21727 76TH AVE WEST EDMONDS, WA 98026 Drawing Title TENANT IMPROVEMENT SPRINKLER PLAN Key Plan RECEIVED Nov 12 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT F I R2021-0123 Date: Job Number: Designer: Building Permit: Drawing No. November 04, 2021 05135C BRYAN FARMER FPlmlO