Loading...
REVIEWED FIR FIR2021-0123+Fire_Sprinkler_Equipment_Specification_Sheets+11.9.2021_3.42.51_PM+2511709NOR TNWES T FIRE SYSTEMS 2545 83,d Ave. ., Bldg D * Kent, WA 98032 Ph: 206.772.7502 * Fax; 206.772.7504 Www.nwfiresysterns.corn LIC # NORTHF59 8CR RECEIVED FIR2021-0123 Nov 12 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT EQUIPMENT SUBMITTAL LIFESTANCE HEAL TH EDMONDS, WA NWSF JOB NO. 05135C TABLE OF CONTENTS Section 1 - Pipe and Fittings Victaulic_T-922_Firelock Outlet Wheatland _Sch 10 & Sch 40 Pipe Anvil _Cast Iron 90 Degree Anvil —Malleable Iron Coupling Section 2 - Hangers and Sway Bracing Anvil 146 All Thread Rod Sammy_Sidewinders Anvil_69_Hanger Ring Section 5 - Fire Sprinklers Tyco_TY-FRB_QR_SSP,SSU,Rec Pend_K=2.8,5.6,8.0 Section 6 — Miscellaneous VicFlex Braided Flexible Hose All variations used Ah-2 Hose with AB-1 Bracket 00-002 Table Of Contents.xls Page 1 of 1 11/4/2021 SECTION 1 PIPE AND FITTINGS Mechanic.... 1® Bolted Branch Outlets STYLES 920 AND 920N Victaulic Mechanical -TO Outlet provides a direct branch connection at any location a hole can be cut in pipe. The hole is cut oversize to receive a "holefinder" locating collar which secures the outlet in position permanently. A pressure responsive gasket seals on the pipe O.D. Cross -type connections can be achieved by utilizing two upper housings of the same style and size, with the same or differing branch size connections. NOTE: Style 920 and Style 920N housings cannot be mated to each other to achieve a cross connection. Style 920 and Style 920N Mechanical-T outlets are available with grooved or female threaded outlet. Specify choice on order. Units are supplied painted with plated bolts. Galvanized hous- ings are available, supplied with plated bolts. All sizes of Style 920 and 920N are rated at 500psi/3450kPa working pressure on Schedule 10 and 40 carbon steel pipe. They may also be used on high density polyethylene or poly- butylene (HDPE) pipe. Pressure ratings on HDPE are dependent on the pipe rating. Contact Victaulic for ratings on other pipe. Style 920 and 920N are not recommended for use on PVC plastic pipe. Standard piping practices dictate that the Mechanical-T Styles 920 and 920N must be installed so that the main and branch connections are a true 90° angle when permanently attached to the pipeline surface. Additionally, the Vic -Tap II® hole cutting tool, which allows for hole cutting capabilities on pressurized systems, utilizes the Style 920 Mechanical-T in conjunction with the Series 726 Vic -Ball Valve to create the Style 931 Vic -Tap II Mechanical-T unit. See page 8 for further information. & <FM> UDC VdS LPCB SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS STYLES 920 AND 920N STYLE 920 CROSS PATENTED MATERIAL SPECIFICATIONS Housing/Coating: Ductile iron conforming to ASTM A-536, grade 65-45-12, with orange enamel coating. Ductile iron conforming to ASTM A-395, grade 65-45-15, is available upon special request. • Optional: Hot dipped galvanized JOB/OWNER System No. Location Gasket: (Specify choice*) • Grade "E" EPDM EPDM (Green color code). Temperature range —30oF to +230oF/-34oC to +110°C. Recommended for cold and hot water service within the specified temperature range plus a variety of dilute acids, oil -free air and many chemical services. UL Classified in accordance with ANSI/NSF 61 for cold +86°F/+30°C and hot +180°F/+82°C. NOT RECOMMENDED FOR PETROLEUM SERVICES. • Grade "T" nitrile Nitrile (Orange color code). Temperature range —20°F to +180°F/-29°C to +82°C. Recommended for petroleum products, air with oil vapors, vegetable and mineral oils within the specified temperature range. Not recommended for hot water services over +150°F/+66°C or for hot dry air over +140°F/+60°C. *Services listed are General Service Recommendations only. It should be noted that there are services for which these gaskets are not recommended. Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a listing of services which are not recommended. Bolts/Nuts: Heat -treated plated carbon steel, trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. CONTRACTOR Submitted By ENGINEER Spec Sect Date Approved Para www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 0 2007 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. REV_J ✓ctauhcm 11.02_1 IPS CARBON STEEL PIPE - HOLE CUT PRODUCTS Mechanical -TO Bolted Branch Outlets 11.02 STYLES 920 AND 920N DIMENSIONS Iio �a Irl GROOVED OUTLET FEMALE THREADED OUTLET • Provides a direct branch connection at any location where a hole can be cut in the pipe • A pressure responsive gasket provides the seal • Request Publication 11.03 for Mechanical-T cross assemblies • Pressure rated up to 500 psi/3450 kPa on steel pipe; also available for use with HDPE pipe • Sizes from 2 x 1/2750 x 15 mm through 8 x 47200 x 100mm IMPORTANT NOTES: Style 920 and Style 920N housings cannot be mated to one another to achieve cross connections. Size St I le Max. Work No. Pressure Dimensions Nominal Size Inches 920 D. or psi +0.13 Inches Inches Inches Inches Inches InIchesp 2 x '/2 (a) 920N 500 1.50 2.00 2.53 _ 1.61 5.35 2.75 3.1 50 15 3450 38.1 51 64 41 136 70 1.5 3/4 (a) 920N 500 1.50 1.97 2.53 1.61 5.35 2.75 3.1 20 3450 38.1 50 64 41 136 70 1.5 1 (a) 920N 500 1.50 1.85 2.53 _ 1.61 5.35 2.75 3.0 25 3450 38.1 47 64 41 136 70 1.4 1'/4 (a) t 1920N 500 1.75 2.05 2.75 3.00 1.61 5.35 3.00 3.5 3.2 32 3450 44.5 52 70 76 41 136 76 1.7 1.5 g20N 500 2.03 2.75 3.12 1.61 5.35 3.25 3.6 1 Y2 (a) t 1.75 3.2 40 3450 44.5 1.50 52 70 79 41 136 83 1.7 1.5 2Yz x Yz (a) 920N 500 2.21 2.74 _ 91.82 5.64 2.75 3.0 65 15 3450 38.1 56 70 46 143 70 1.4 3/4 (a) g20N 500 1.50 2.18 2.74 _ 1.82 5.64 2.75 3.0 20 3450 38.1 55 70 46 143 70 1.4 1 (a) 920N 500 1.50 2.06 2.74 _ 1.82 5.64 2.75 2.9 25 3450 38.1 52 70 46 143 70 1.4 1 Y4 t (a) g20N 500 1.75 2.30 3.00 3.25 1.82 6.29 3.00 3.5 3.2 32 3450 44.5 58 76 83 46 160 76 1.7 1.5 920N 500 2.28 3.00 3.25 1.82 6.26 3.25 1 Yz t (a) 2.00 3.6 3.3 40 3450 50.8 58 76 83 46 159 83 1.7 1.6 1/2(a) 76.1 x 920 300 1.50 2.22 2.75 _ 2.25 6.46 3.18 3.9 _ 1 15 2065 38.1 56 70 57 164 81 1.8 3/4 (a) 920 300 1.50 2.19 2.75 _ 2.25 6.46 3.18 3.9 1 _ 20 2065 38.1 56 70 57 164 81 1 1.8 1 (a) 920 300 1.50 2.07 2.75 _ 2.25 6.46 3.18 3.8 25 2065 38.1 53 70 57 164 81 1.7 1 Y4 (a) 920 500 1.75 2.30 3.00 3.31 1.92 6.29 3.00 3.5 3.2 32 3450 44.5 58 76 84 49 160 76 1.6 1.5 1'/2 (a) 920 500 2.00 2.28 3.00 3.31 1.92 6.29 3.25 3.5 3.3 40 3450 50.8 58 76 84 49 160 83 1.6 1.5 3 '/2 (a) x 920N 500 1.50 2.52 3.05 _ 2.28 6.15 2.75 3.4 _ 80 15 3450 38.1 64 78 58 156 70 1.6 3/4 (a) 920N 500 1.50 2.49 3.05 _ 2.28 6.15 2.75 3.4 20 3450 38.1 63 78 58 156 70 1.6 1 (a) 920N 500 1.50 2.38 3.06 _ 2.28 6.15 2.75 3.3 25 3450 38.1 61 78 58 156 70 1.6 1 Y4 (a) t) 920N 500 1.75 2.55 3.25 3.56 2.28 6.15 3.00 3.8 3.7 32 (b 3450 44.5 65 83 90 58 156 76 1.8 1.8 920N 500 2.78 3.50 3.56 2.28 6.15 3.25 4.1 1 Yz (a) t 2.00 3.8 40 (b) 3450 50.8 71 89 90 58 156 83 1.9 1.8 920N 500 2.75 3.50 3.56 2.28 6.75 3.88 4.9 2 (a) 2.50 4.6 50 3450 63.5 70 89 90 58 172 99 2.3 2.1 3 /2 x 2 920N 500 2.50 _ _ 3.75 2.44 6.72 3.88 _ 3.8 90 50 3450 63.5 95 62 171 99 1.8 TABLE CONTINUED ON PG. 3 www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 0 2007 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. 11.02_2 ✓ctauliic® REV_J IPS CARBON STEEL PIPE - HOLE CUT PRODUCTS Mechanical -TO Bolted Branch Outlets 11.02 STYLES 920 AND 920N DIMENSIONS St le Max. Work Approx. Size N10. Pressure Dimensions Weight Each Inches or psi +0.13 Inches Inches Inches Inches Inches Inches Lbs. Lbs. Y rf7Z� �� TABLE CONTINUED FROM PAGE 2 if, 4 x � 5 920N 500 1.50 1 3.03 1 3.56 _ 2.69 7.01 2.75 3.7 100 15 3450 38.1 1 77 1 90 68 178 70 1.8 3/4 (a) 920N 500 1.50 3.00 3.56 _ 2.69 7.01 2.75 3.7 T 20 3450 38.1 76 90 68 178 70 1.8 y iT 1 (a) 920N 500 1.50 2.88 3.56 _ 2.69 7.01 2.75 3.6 25 3450 38.1 73 90 68 178 70 1.8 GROOVED OUTLET 1 Y4 (a) t 920N 500 1.75 3.08 3.78 4.00 2.69 7.01 3.00 4.0 3.6 32 (b) 3450 44.5 78 96 102 68 178 76 1.9 1.8 140 /2 (a) t 920N 500 2.00 3.28 4.00 4.00 2.69 7.01 3.25 4.2 3.9 Y Z 2 O t 3450 2.50 .2 1.0 102 .6 101 .8 2.0 1.6 2 (a) t 920N 500 2.50 3.25 4.00 4.00 2.69 7.01 3.88 5.0 4.6 50 3450 63.5 83 102 102 68 178 99 2.3 2.1 V T 2 /z (a) t 500 2.75 2.88 4.00 4.00 2.69 7.34 4.63 5.8 5.0 T 65 920 3450 69.9 73 102 102 68 186 118 2.6 2.3 76.1 mm 920 500 2.75 _ _ 4.00 2.69 7.34 4.63 _ 6.4 j 1? W 3450 69.9 102 68 186 118 2.9 3 (a) t 500 3.50 3.31 4.50 4.12 2.69 7.73 5.12 8.4 6.4 FEMALE THREADED OUTLET 80 920 3450 88.9 84 114 105 68 196 130 3.8 2.9 500 1.75 108.0 x 1,342a) 920N 3450 44.5 3 88 96 67 194 3 8 2.3 1 /2 (a) 920N 500 2.00 3.28 4.00 2.63 7.64 3.25 5.0 • Provides a direct branch connection at 40 3450 50.8 83 102 - 67 194 83 2.3 any location where a hole can be cut 2 (a) 920N 500 2.50 3.25 4.00 _ 2.63 7.64 4.00 4.0 in the pipe 50 3450 63.5 83 102 67 194 102 1.9 76.1 mm 920 500 2.75 2.88 4.00 4.00 2.63 7.64 4.29 8.0 • A pressure responsive gasket provides 3450 69.9 73 102 102 67 194 109 3.6 the seal 3 (a) 920 500 3.50 3.31 4.50 _ 2.63 7.63 4.88 6.8 6.5 80 3450 88.9 84 114 67 194 124 3.1 3.0 • Request Publication 11.03 for 5 11/2 (a) t 500 2.00 4.03 +11'21 5 3.16 9.70 3.69 7.4 7.6 Mechanical-T cross assemblies 125 x 40 920 3450 50.8 102 80 246 94 3.4 3.4 2 (a) t 500 2.50 4.00 5 3.16 9.70 4.38 8.2 8.0 • Pressure rated up to 500psi/345OkPa 50 920 3450 63.5 102 1 80 246 111 3.7 3.6 on steel pipe; also available for use 2Vz (a) t 920 500 2.75 3.63 4.75 4.75 3.16 9.70 4.63 8.3 7.9 with HDPE pipe 65 3450 69.9 92 121 121 80 246 118 3.8 3.6 76.1 mm 920 500 2.75 _ _ 4.75 3.16 9.70 4.63 _ 8.0 • Sizes from 2 x 1/2750 x 15mm 3450 69.9 121 80 246 118 3.6 through 8 x 47200 x 100mm 3 (a)t 920 500 3.50 3.81 5.00 4.63 3.16 9.70 5.31 8.4 8.8 80 3450 88.9 97 127 118 80 246 135 3.8 4.0 2 500 2.50 3.75 4.50 _ 3.17 8.00 3.88 8.0 _ 133.0 x 50 920N 3450 63.5 95 114 81 203 99 3.6 3 500 3.50 3.81 5.00 _ 3.00 9.46 5.31 8.0 _ 80 920 3450 88.9 97 127 76 240 135 3.6 TABLE CONTINUED ON PG. 4 IMPORTANT NOTES: Style 920 and Style 920N housings cannot be mated to one another to achieve cross connections. www.victaulic.com �ctaul�c° VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. ©2007 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. REV_J 11.02_3 IPS CARBON STEEL PIPE - HOLE CUT PRODUCTS Mechanical -TO Bolted Branch Outlets 11.02 STYLES 920 AND 920N DIMENSIONS GROOVED OUTLET oil riu � ` �� ICI FEMALE THREADED OUTLET • Provides a direct branch connection at any location where a hole can be cut in the pipe • A pressure responsive gasket provides the seal • Request Publication 11.03 for Mechanical-T cross assemblies • Pressure rated up to 500 psi/3450 kPa on steel pipe; also available for use with HDPE pipe • Sizes from 2 x 1/2750 x 15 mm through 8 x 47200 x 100mm IMPORTANT NOTES: Style 920 and Style 920N housings cannot be mated to one another to achieve cross connections. St'le Max. Work Size No. Pressure Dimensions Nominal Size 920 D. Inches or psi +0.13 Inches Inches Inches Inches Inches Inches mm 920N kPa 00 mm mm mm mm mm mm TABLE CONTINUED FROM PAGE 3 1 1/2t 139.7 x 920N 500 2.00 3.78 4.50 _ 3.30 8.23 1 3.25 7.0 _ 40 3450 50.8 96 114 84 209 83 3.2 920N 500 2.50 3.75 I 3.3300 8.23 3.88 9.0 2 t 4.50 _ 50 3450 63.5 95 114 84 209 99 4.1 920 2.75 3.63 4.75 _ 3.13 9.85 4.63 8.8 76.1 mm 500 3450 69.9 92 121 80 250 118 4.0 920 500 3.50 _ _ 4.63 76.1 mm 3.16 9.70 5.31 11.0 3450 88.9 118 80 246 135 5.0 920 500 3.50 3.81 3.16 9.85 5.38 14.0 3 5.00 4.63 14.2 88.9 3450 88.9 96.80 127 118 80 250 137 6.4 6.4 6 1 Y4 (a) 920N 500 1.75 4.43 3.79 9.15 3.25 4.8 150 x 32 (b) 3450 44.5 112 _ _ 96 232 83 _ 2.2 920N 500 4.40 5.13 5.13 3.79 9.15 3.25 5.1 1'/2 (a) t 2.00 5.4 40 (b) 3450 50.8 112 130 130 96 232 83 2.4 1 2.3 2 (a) t 920N 500 2.50 4.38 5.13 5.13 3.79 9.15 3.88 6.0 5.6 50 3450 63.5 111 130 130 96 232 99 2.7 2.5 2 Y2 (a) t 920 500 2.75 4.01 5.13 5.12 3.69 10.51 4.63 8.3 7.6 65 3450 69.9 110 130 130 94 267 118 3.8 3.4 76.1 mm 920 500 2.75 _ _ 5.21 3.69 10.51 4.63 _ 8.4 3450 69.9 132 94 267 118 3.8 3 (a) t 920 500 3.50 4.31 5.50 5.13 3.69 10.51 5.31 9.9 8.4 80 3450 88.9 110 140 130 94 267 135 4.5 3.8 920 3.81 5.75 5.38 3.69 10.51 10.1 4 (a) t 500 4.50 6.25 10.1 100 3450 114.3 97 4.43 146 5.13 137 _ 94 3.63 267 9.40 159 3.25 4.6 9.0 4.6 11/4 159.0 x 920N 500 1.75 8.7 32 3450 44.5 113 130 92 239 83 4.1 4.0 920N 500 2.00 4.41 5.13 _ 3.63 9.40 3.25 7.8 1 Y2 (a) 40 3450 1 50.8 112 130 92 239 83 3.5 920N 500 2.50 4.38 5.13 9.40 3.88 8.0 2 (a) _ 3.63 50 3450 63.5 111 130 92 239 99 3.6 920 500 2.75 4.38 5.50 5.13 3.63 76.1 mm 9.40 4.63 9.5 9.5 3450 69.9 111 140 130 92 239 118 4.3 4.3 3 920 500 1 3.50 4.31 5.50 5.13 3.63 9.40 5.31 8.1 14.0 80 3450 88.9 110 140 130 92 239 135 3.7 6.4 920 500 4.50 _ 108.1 mm _ 5.38 3.63 9.40 6.12 _ 10.0 3450 114.3 137� 92 239 155 4.5 500 4.50 3.81 920 9.40 4 5.75 _ 3.63 6.25 18.0 _ 100 3450 114.3 96.80 146 92 239 159 8.2 TABLE CONTINUED ON PG. 5 www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 0 2007 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. 11.02_4 ✓ctauliic® REV_J IPS CARBON STEEL PIPE - HOLE CUT PRODUCTS Mechanical -TO Bolted Branch Outlets 11.02 STYLES 920 AND 920N dimensions sir �� till kka'61-57 111 F051 l" u Irl GROOVED OUTLET FEMALE THREADED OUTLET • Provides a direct branch connection at any location where a hole can be cut in the pipe • A pressure responsive gasket provides the seal • Request Publication 11.03 for Mechanical-T cross assemblies • Pressure rated up to 500psi/3450kPa on steel pipe; also available for use with HDPE pipe • Sizes from 2 x 1/2750 x 15mm through 8 x 47200 x 100mm IMPORTANT NOTES: Style 920 and Style 920N housings cannot be mated to each other to achieve cross connections. St le Max. Work Approx. Size Nyo. Pressure Dimensions Weight Each Nominal Size 920 D. Inches or psi +0.13 Inches Inches Inches Inches Inches Inches Lbs. Lbs. mm 920N kPa 00 mm mm mm mm mm mm kg kg TABLE CONTINUED FROM PAGE 4 1 165.1 x 500 1.50 3.88 4.56 _ 3.79 9.34 2.75 8.0 920 _ 25 3450 38.1 99 116 96 237 70 1 3.6 _ 1 Ya 500 1.75 4.43 5.13 _ 3.79 9.34 3.25 8.4 920 32 3450 44.5 113 130 96 237 83 3.8 1 Y2 (a) t 500 920 2.00 4.41 5.13 _ 3.79 9.34 3.25 8.4 _ 40 3450 50.8 112 130 96 237 83 3.8 2 (a) t 920 500 2.50 4.38 5.13 _ 3.79 9.34 3.88 8.5 50 3450 63.5 111 130 96 237 99 3.9 500 920 4.63 8.6 7.6 2 /2 t 2.75 4.01 5.13 _ 3.63 10.51 65 3450 69.9 110 130 92 267 118 3.9 3.4 920 500 4.63 8.6 7.6 76.1 mm 2.75 4.01 5.13 5.21 3.63 10.51 3450 69.9 110 130 132 92 267 118 3.9 3.4 3 (a) t 500 920 3.50 4.31 5.50 5.13 3.63 10.51 5.31 10.2 8.4 80 3450 88.9 110 140 130 92 267 135 4.6 3.8 4 (a) t 920 500 4.50 3.81 5.75 5.38 3.63 10.51 6.25 10.5 8.4 100 3450 114.3 97 146 137 92 267 159 4.8 3.8 8 2 (a) t x 500 920 2.75 5.44 6.19 6.25 4.81 12.42 4.50 11.6 11.6 200 50 3450 69.9 138 157 159 122 316 114 5.3 5.3 21/2 (a) t 500 920 2.75 5.07 6.19 6.19 4.81 12.42 4.50 11.6 11.6 65 3450 69.9 129 157 157 122 316 114 5.3 5.3 76.1 mm 920 500 2.75 _ _ 6.25 4.81 12.42 1 4.56 _ 11.6 3450 69.9 159 122 316 1 116 5.3 3 (a) t 920 500 3.50 5.31 6.50 6.50 4.81 12.42 5.31 12.6 11.6 80 3450 88.9 135 165 165 122 316 135 5.7 5.3 4 (a) t 920 500 4.50 4.81 6.75 6.38 4.81 12.42 6.25 15.3 12.5 100 3450 114.3 122 171 162 122 316 159 6.9 5.7 ** Center of run to engaged pipe end, female threaded outlet only (dimensions approximate). t Available with grooved or female threaded outlet. Specify choice on order. # Center of run to end of fitting. # Female threaded outlets are available to NPT and BSPT specifications. (a) British Standard female pipe threaded outlet is available as listed. Specify "BSPT" clearly on order. (b)For 76.1 mm threaded outlet, specify 21/2" BSPT clearly on order. www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2007 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. REV J ✓CtaU1ii ° 11.02_5 IPS CARBON STEEL PIPE - HOLE CUT PRODUCTS Mechanical -TO Bolted Branch Outlets STYLES 920 AND 920N 11.02 FLOW DATA Flow test data has shown that the total head loss between point (1) and (2) for the Style 920, 920N and 929 Mechanical-r fittings can best be expressed in terms of the pressure difference across the inlet and branch. The pressure difference can be obtained from the relationship below. O Cv Values Values for flow of water at +60°F/+16°C are shown in the table below. Equivalent Length Equivalent N 0 minal SIZE Actual Feet/meter of Pipe Nominal SIZE Actual Feet/meter Length of Pipe Out. .. Female Diameter Out. Dia. 1O '/2 0.840 2.0 2 2.375 9.0 Female Threaded. 10.5 15 21.3 0.6 50 60.3 2.7 3.2 3/4 1.050 4.0 2 Y2 2.875 11.0 12.5 20 26.7 1.2 65 73.0 3.4 3.8 Exaggerated for clarity 1 1.315 _ 5.0 3 3.500 13.5 15.5 25 33.7 1.5 80 88.9 4.1 4.7 1 Y4 1.660 5.5 6.0 4 4.500 20.0 22.0 32 42.4 1.7 1.8 100 114.3 6.1 6.7 1'/2 1.900 7.0 8.0 40 48.3 2.1 2.4 Formulas for Cv Values: AP = Q2 Where: C 22 Q = Flow (GPM) AP = Pressure Drop (psi) Q = Cv x AP Cv = Flow Coefficient www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 0 2007 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. �CtaUI1Ill 11.02_6 REV_J IPS CARBON STEEL PIPE - HOLE CUT PRODUCTS Mechanical -TO Bolted Branch Outlets 11.02 STYLES 920 AND 920N APPROVED PRESSURE RATINGS The information provided below is based on the latest listing and approval data at the time of publi- cation. Listings/Approvals are subject to change and/or additions by the approvals agencies. Contact Victaulic for performance on other pipe and the latest listings and approvals. NOTES: 10 refers to Listed/Approved Schedule 10 steel sprinkler pipe. 40 refers to Listed/Approved Schedule 40 steel sprinkler pipe. DF refers to Listed/Approved Dyna-Flow steel sprinkler pipe manufactured by American Tube Company. SF refers to Listed/Approved Super -Flo steel sprinkler pipe manufactured by Allied Tube and Conduit Corporation. VIC-TAP II HOLE CUTTING TOOL FOR The Vic -Tap II hole cutting tool is designed for use with the Style 931 Vic -Tap II Mechanical-T unit, 4 - 8"/100 - 200 MM CARBON STEEL PIPE which is a combination of the Style 920 Mechanical-T and Series 726 Vic -Ball Valve. The Vic -Tap II is capable of tapping into carbon steel pipe systems under pressures up to 500psi/3450kPa. The Style 931 Vic -Tap II Mechanical-T unit is a full port ball valve which can be mounted on 47100mm, 57125mm, 67150mm and 87200 mm diameter pipe. The Style 931 comes with a 21/2765mm grooved outlet. The drill motor is an electric motor with ground fault circuit interrupter (GFCl) in accordance with safety codes. For more information, refer to publication 24.01 www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2007 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. REV J ✓ctaul�c° 11.02_7 Mechanical -TO Bolted Branch Outlets STYLES 920 AND 920N INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data, and are available in PDF format on our website at www.victaulic.com. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. III II II I III I III IIIIIIIII I I II IIII I II I III III WCAS-6YCLDG For complete contact information, visit www.victaulic.com 11.02 1480 REV J UPDATED 4/2007 �CtauIlC VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 0 2007 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. 11.02_8 FM Approved and Fully Listed Sprinkler Pipe Wheatland Tube's Schedule 10 steel fire sprinkler pipe is FM Approved and UL" and C-UL Listed. Wheatland Tube is the only manufacturer with FM Approval on 10 NPS Schedule 10 steel fire sprinkler pipe. Approvals and Specifications Schedule 10 meets or exceeds the following standards: • ASTM A135, Type E, Grade A (Schedule 10, 1-10 NPS) • NFPAa 13 and NFPA 14 Manufacturing Protocols Schedule 10 is subjected to the toughest possible testing protocols to ensure the highest quality and long-lasting performance. PROJECT: ENGINEER: LOCATIONS: ❑ BLACK CONTRACTOR: Finishes and Coatings Schedule 10 can be ordered in black or hot -dip galvanized to meet FM/UL requirements for dry systems that meet the zinc coating specifications of ASTM A53 or A795. Schedule 10 receives a proprietary mill coating to ensure a clean, corrosion -resistant surface that outperforms and outlasts standard lacquer coatings. This coating allows the pipe to be easily painted without special preparation. Every black steel Schedule 10 pipe also receives our MIC SHIELDT" antimicrobial coating to limit corrosion from microbes on the interior of the pipe. Product Marking Each length of Wheatland fire sprinkler pipe is continuously stenciled to show the manufacturer, type of pipe, grade, size and length. Bar coding is acceptable as a supplementary identification method. SPECIFICATION REFERENCE: COMMENTS: ❑ HOT -DIP GALVANIZED DATE: SYSTEM TYPE: lit 1 Council Avenue, P.O. Box 608 Wheatland, PA 16161 P 800.257.8182 F 724.346.7260 info@wheatland.com wheatland.com Follow us on Twitter: @WheatlandTube Wheatland Tube A DIVISION OF ZEKELMAN INDUSTRIES W W t 4-hL- -= SCHEDULE 10 WEIGHTS AND DIMENSIONS WT./FT. WT./LIFT WT./LIFT WT./LIFT NIPS NOMINAL OD NOMINAL ID NOMINAL WALL WT./FT. H2O FILLED PCS./LIFT 21' 24' 25' UL in �m in. mrn lbs. lbs. lbs. lbs. CRR• IL 1 1.315 33.4 1.097 27.9 0.109 2.77 1.405 1.814 70 2065 2360 2459 11.4 1 % 1.660 42.2 1.442 36.6 0.109 2.77 1.807 2.514 61 2315 2645 2756 7.3 11/2 1.900 48.3 1.682 42.7 0.109 2.77 2.087 3.049 61 2673 3055 3183 5.8 2 2.375 60.3 2.157 54.8 0.109 2.77 2.640 4.222 37 2051 2344 2442 4.7 21/2 2.875 73.0 2.635 66.9 0.120 3.05 3.354 5.895 30 2226 2544 2651 3.5 3 3.500 88.9 3.260 82.8 0.120 3.05 4.336 7.949 19 1730 1977 2060 2.6 4 4.500 114.3 4.260 108.2 0.120 3.05 5.619 11.789 19 2242 2562 2669 1.6 5 5.563 141.3 5.295 134.5 0.134 3.40 7.780 17.309 13 2124 2427 2529 1.5 6 6.625 168.3 6.357 161.5 0.134 3.40 9.298 23.038 10 1953 2232 2325 1.0 8 8.625 219.1 8.249 209.5 0.188 4.78 16.960 40.086 7 2493 2849 2968 1.7 10** 10.750 273.0 10.374 263.5 0.188 4.78 21.230 57.803 2 892 1019 1062 - * Calculated using Standard UL CPR formula, UL Fire Protection Directory, Category VIZV. The CRR is a ratio value used to measure the ability of a pipe to withstand corrosion. Threaded Schedule 40 steel pipe is used as the benchmark (value of 1.0). 10 NPS Schedule 10 is FM Approved but not UL Listed. UL C UL F M APPROVED 1 Council Avenue, P.O. Box 608 info@wheatland.com WFS-072921 - Wheatland, PA 16161 wheatland.com Wheatland Tube P 800.257.8182 Follow us on Twitter: )RZj F 724.346.7260 @WheatlandTube A DIVISION OF ZEKELMAN INDUSTRIES Cast Iron Threaded Fittings Class 125, (Standard) (q,i)ANVIL INTERNATIONAL, INC. 90° Elbow Straight Figure 351 Size (NPS) A (in) B (in) Weight (Ibs) black galy. T r g4 1/4 '/2 1'/16 .16 .17 % '/16 1'/16 .25 .26 1/2 11/16 1'/8 .40 .41 3/4 "A 6 15/16 .60 .61 1 15/16 1'/2 .92 .95 1 1/4 11/6 13/4 1.44 1.46 11/2 16/16 1"A 6 1.95 2.00 2 1'/16 21/4 3.13 3.21 21/2 113/16 211/16 4.94 5.13 3 21/16 31/6 7.21 7.40 211/1 a 31'/16 12.17 12.67 5 3 6/16 41/2 21.46 — 6 31/6 51/8 31.33 33.33 8 5'/16 016 64.56 67.14 Cast Iron Threaded Fittings Pressure -Temperature Ratings Temp.(°F) Pressure, (psig) Class 125 Class 250 -20° to 150° 175 400 200° 165 370 250° 150 340 300° 140 310 350° 125 300 400° 250 www.anvilinti.com (12/10/01) Malleable Iron Class 150 (standard) Coupling Right Hand Figure 1121 Size (NPS) W (in) Weight (Ibs) black galy. W '/a 1'/16 .06 .06 1/4 11/16 .09 .09 % 1'/16 .13 .13 1/2 16/16 .20 .21 'A 11/2 .29 .31 1 111/16 .48 .49 11/4 116/16 .14 .76 1'/z 2'/8 1.00 1.00 2 21/2 1.45 1.55 21/2 2'/a 2.40 2.45 3 31/16 3.30 3.39 4 V/16 5.65 5.73 Malleable Iron Threaded Pipe With Unions Pressure -Temperature Ratings Temp (OF) Pressure, (psig) Class 150 Class 250 Class 300 -20'to150' 300 500 600 200° 265 455 550 250° 225 405 505 300° 185 360 460 350' 150 315 415 400° 110 270 370 450° 75 225 325 500° -- 180 280 550° r-- 130 230 Note: Unions with Copper or Copper Alloy seats are not intended for use where temperature exceeds 450°F Anvil Class 150 (Standard Weight) Malleable Iron Fittings conform to ASME B16.3 and Unions conform to ASME B16.39. Anvil standard weight banded pattern fittings in this catalog, sizes '/6 NPS to 6 NPS inclusive, are included in the "List of Inspected (q,i)AWIL INTERNATIONAL, INC. Malleable Iron Threaded Fittings Pressure -Temperature Ratings Temp (OF) Pressure, (psig) Class Class 300 150 Sizes '/a" -1 " Sizes 1'/4" - 2" Sizes 2'/z" - 3" -20°to 150° 300 2,000 1,500 1,000 200' 265 1,785 1,350 910 250° 225 1,575 1,200 825 300° 185 1,360 1,050 735 350' 150 1,150 900 650 400' -- 935 750 560 450° -- 225 600 475 500' -- 510 450 385 550° -- 300 300 300 Fire Protection Equipment and Materials" issued by the Underwrit- ers' Laboratories, Inc. ALL ELBOWS & TEES Y AND LARGER ARE 100% GAS TESTED AT A MINIMUM OF 100 PSI. www.anvilinti.com (12/10/01) SECTION 2 HANGERS AND SWAY BRACING HANGER RODS Z /ANVIL Fig. 146 Size Range:'/4 through 11/2" Stocked in six, ten, and twelve foot lengths. Other even foot lengths can be furnished to order. Material: Carbon steel or Stainless Steel Gr 304 Threads: National Coarse (USS), rod threaded complete length. Finish: ❑ Plain or❑ zinc Plated (Hot -Dip Galvanized optional) Maximum Temperature: 650' F. Ordering: Specify rod diameter and length, figure number, name and finish. Note: The acceptability of galvanized coatings at temperatures above 450°F is at the discretion of the end user. 1,1111111111111111111111111�11111111�111111111111�11111111111111�11�1111111111111111111111111111�11111111111111111111�11111111�111111�111111111111�111111�111111�111111�11�11�11�11�111111�11�11�111111�111111111111111111111111�111111111111 Continuous Threaded Rod FIG.146: LOADS (LBS) • WEIGHTS (LBS) • DIMENSIONS (IN) Rod Size A Threads per Inch Max Load 650° F Weight per Ft. 'A 20 240 0.12 % 16 730 0.30 '/2 13 1,350 0.53 % 11 2,160 0.84 3/a 10 3,230 1.20 7/8 9 4,480 1.70 1 8 5,900 2.30 1'/a 7 9,500 3.60 1'/2 6 13,800 5.10 Note: Other rod sizes available upon request. Class 2 fit is available upon request. PROJECT1 1APPROVAL Project: []Approved Address: []Approved as noted Contractor: ❑ Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: PH-1.15 SIDEWINDERS 0 horizontal mount Screw Box V1wCase Size Wood Approvals Descriptions Qt= 5) Qty 1/4" 8018957 SWG 100 1/4 X 1 25 9.32 125 1/4" 8019957 SWG 200 1/4 X 2 25 10.78 125 UL 3/8" 8020957 SWG 10 1/4 X 1 25 7.88 125 ! UL 3/8" 8021957 SWG 20 1/4 X 2 25 9.45 125 UL 3/8" 8022925 SWG 25-380 3/8 X 2-1/2 25 12.54 125 3/8" 8023925 SWG 30 1/4 X 3 25 10.70 125 �{ Approvals Rod Part Model Screw Box eight Ste e Size No. Descriptions 2L. (per 125) 1/4" 8047957 SWD 100 1 /4-14 X 1 25 9.35 125 1/4" 8049957 SW DR 100 1/4-20 X 1 25 10.37 125 3/8" 8050957 SWD 10 _ 114-14 X 1 25 8.04 125_ 3/8" 8051957 SWD 15 1/4-14 X 1-1/2 25 8.47 125 �r— Part 4 8114910 3/877'1 8052957 ' SWD 20 ' 1/4-14 X 2 25r9.10 3/8" 8053957 SWD 516 5/16-18 X 1-1/4 25 8.94 125 UL-FM 3/8"�054957 ISWDR1-1/2 1/4-20X1-1/2 4^`1111 UL-FM 3/8" 8055957 SWDR 1 1/4-20 X 1 25 9.07 125 56957 - - 3/8" 8057957 SWT 15 12-24 X 1-1/2 25 8.28 125 Approvals Rod V Part M Screw Box W ht Cas Size No. Descriptions Qty. (per 125) Qty Concrete FM 1/4" 8062957 SWC 200 5/16 X 1-3/4 25 11.18 125 3/8" 8061957 SWC 20 5/16 X 1-3/4 25 9.81 125 May e-V41 & -4. S w SxeeQ rat Ott rat ,,� . Head'2MM01001111, Swivel Use with 3/8" '11 Part Screw Box Weight Case • Use #14 Nut Driver (black) Approvals No. Model Descriptions Qty. (per 125) Qty Part No. 8113910. UL-FM 8139957 SH-GST 20 1/4 x 2 25 8.94 125 • 17' deflection from vertical. UL-FM 8141957 SH-GST 30 1/4 x 3 25 10.15 125 U.S. Patent No. UL-FM 8137957 SH-DS roof. 25 125 ' Accommodates to 6,443,680 3-1/2 x 12 pitch roof. SAMMYX-PRESS' Use with 1/4" or : Rod Hang Threaded Rod Approvals Steel Ga. Part No. Model Screw Descriptions Rod Size Max Pipe Size Application Directly from L FM 12 ga. 8150922 XP 20 Sammy X-Press 20 3/8-16 4" Metal Deck Thin Gauge Metal Deck FM 12 ga. 8153922 XP 35 Sammy X-Press 35 3/8-16 4" Purlin & Purlin UL 22 ga. 8150922 XP 20 Sammy X-Press 20 3/8-16 2-1/2" Metal Deck EP M = UL 18 ga. 8153922 XP 35 Sammy X-Press 35 3/8-16 3 112" Purlin o a UL t 16-12 ga. 8293957 SWXP 35 Sidewinder X-Press 35 3/8-16 3-1/2" Purlin Z UL 22-20 ga. 8294922 SXP 20 Swivel X-Press 20 3/8-16 2" Metal Deck a Ir UL 16-12 ga. 8295922 SXP 35 Swivel X-Press 35 3/8-16 3-1/2" Purlin m Approvals Concrete Part No. Model Screw Descriptions Rod Size Max Pipe Size Thickness Ihm Structural 8150922 XP 20 Sammy X-Press 20 3/8-16 2-1/2" 3000PSI a UL LWC Concrete 8150922 XP 20 Sammy X-Press 20 3/8-16 2-1/2" 35 PCF Approvals Steel Ga. Part No. Model Screw Descriptions Rod Size Load Rating - 22 ga. 8150922 XP 20 Sammy X-Press 20 3/8-16 185 lbs. UL 22 ga. 8153922 XP 35 Sammy X-Press 35 3/8-16 185 lbs. - 22 ga. 8181922 XP 200 Sammy X-Press 200 1/4-41 185 lbs. UL 16 ga. 8150922 XP 20 Sammy X-Press 20 3/8-16 250 lbs. 3 16 ga. =8153922 XP 35 Sammy X-Press 35 _/8-16 250 lbs. UL 16 ga. 8181922 XP 200 Sammy X-Press 200 1/4-20 250 lbs. Universal X-Press 8194910 UXPIT Universal X-Pr4s It Tool Installation Tool = 8 8151910 RXPIT Retro Socket for 8151910 - -10 XPDB 25/64 Drill Bit - JUL..,SAMMYS 0 ul eX vertical mount Approvals Screw Weight Case S��p Qty. (per 125) Qty 1/4" 8002957 GST 100 1/4 x 1 _ 25 7.12 125 1/4" 8003957 GST 200 114 x 2 25 8.64 125 80049L7§EILST, 1/4 x 3 25 9.91 125 3/8" 8006957 GST .75 1/4 x 3/4 25 6.24 125 80079577MOCST 10 1/4 x411111irW 25 6.68 125 UL • FM 3/8" 8008957 GST 20 1/4 x 2 25 8.17 125 /8" 80099250- GST 25-380 3/8 x 2-1/2 25 11.27 j&25 UL • FM 3/8" 8010957 GST 30 1/4 x 3 25 9.41 125 Part # 8113910 3/8" 8011925 111111j_ 1/4 x 4 25 10.01 _ 3/8" 8012925 GST 60 1/4 x 6 25 12.72 125 1/2" 8013925 � 1/4 X 2 25 8.99 _ 1/2" 8014925 GST 2.5-380 3/8 X 2-1/2 25 11.99 125 1/2" 8015925 jNEEE&1/4 X 3 25 10.22 125 1/2" 8016925 GST 4 1/4 X 4 25 13.25 125 1/2" 8017925 GS 25 13.69 125 Part # 8114910 Rod ScreA Box Weight Case 1W Model Steel Size Description Qty. (per 125) Qty 1/4" 8024957 DSTR 100 1/4-20 X 1 25 8.20 125 1/4" 8025957 DST 100 1/4-14 X 1 25 7.23 125 /4" Ej,DST 150 1/4-14 X 1-1/2� 125 1/4" 8027957 DST 200 1/4-14 X 2 25 8.31 125 wpm 8 ST 250 1/4-14 X 2-1/2 125 1/4" 8029957 DST 300 1/4-14 X 3 25 9.41 125 030 0 12-24 X 1� � 125 UL • FM 3/8" 8037957 DSTR 1-1/2 12-24 X 1-1/2 25 8.18 125 125 UL • FM 3/8" 8039957 DSTR 516 5/16-18 X 1-1A 25 9.35 125 8040957 -14 X 1 125 3/8" 8041957 DST 15 1/4-14 X 1-1/2 25 7.20 125 8042957 -14 X YjjW 125 3/8" 8043957 DST 25 1/4-14 X 2-1/2 25 8.42 125 8044957 4-14 X � 125 UL • FM 3/8" 8045957 DST 516 5/16-18 X 1-1/4 25 7.79 125 8046957 12-24 X 1' 125 _ 1/2" 8031925 DST 2.0 1 /4-14 X 2 25 8.61 125 I 8032925 4-14 X_� 125 1/2" 8033925 DSTR 1.0 1/4-20 X 1 25 8.61 125 f 2" 8034925 5/16-18 X 1-1A 125 1/2" 8035925 DST 5.16 5/16-18 X 1-1/4 25 8.51 125 M 1/2" 8036925 12-24 X 1-1/2 25 7.75 125 - Concrete Approvals Rod Part Model Screw �ffox Weight Case Size No. Descriptions Qty. (per 125) Qt 1/4" 8058957 CST 200 5/16 x 1-3/4 25 8.44 125 black nut FM 3/8" 8059957 CST 20 5/16 X 1-3/4 25 7.81 125 driver 1/2" 8060925 CST 2 5116 X 1-3/4 8.75 - -red nut driver I I Sammyss, Sammy Super Screws, Sammy Swivel Head'", Sammy X-Press®, Sammy X-Press ITs, Sidewinders®, 800-BUILDER 97 L Swivel X-Press'", and Sidewinder X-Press'" are trademarks of ITW Buildex and Illinois Tool Works, Inc. www.itwbuildex.com © 2007 Illinois Tool Works, Inc. SSS30 PIPE RINGS Z /ANVIL Fig. 69 Adjustable Swivel Ring, Tapped Per NFPA Standards Size Range:'/2" through 8" Material: Carbon steel Finish: ❑ Galvanized Service: Recommended for suspension of non -insulated stationary pipe line. Maximum Temperature: 650° F Approvals: Complies with Federal Specification A-A-1192A (Type 10) WW-H-171-E (Type 70), ANSI/MSS SP-69 and MSS SP-58 (Type 10). UL Listed and FM Approved (Sizes 3/4" - 811). Features: • Threads are countersunk so that they cannot become burred or damaged. • Knurled swivel nut provides vertical adjustment after piping is in place. • Captured swivel nut in the'/2" through 6" sizes. The capture is permanent in the bottom portion of the band, allowing the hanger to be opened during installation if desired, but not allowing the nut to fall completely out. Ordering: Specify size, figure number and name. Note: The acceptability of galvanized coatings at temperatures above 450°F is at the discretion of the end user. Metric nut available upon request. Non -captured nut also available upon request. A i F B C '/z" through 1" pipe through 8" pipe FIG. 69: LOADS (LBS) • WEIGHT (LBS) • DIMENSIONS (IN) Pipe Size Max Load Weight Rod Size A B C F 1/2 300 0.10 % 2'/8 2 19/ 6 % 0.10 2% 17/8 16/16 1 0.10 29/ 6 111/ 6 1 11/4 0.10 2% 1 % 7/8 1 1/2 0.10 23/4 17/8 2 0.11 31/4 2% 11/8 21/2 525 0.20 4 2% 16/ 6 3 0.20 313/16 215/ s 13/ s 4 650 0.30 411/16 313/1s 5 1,000 0.54 1/2 5s/6 4% 19/,s 6 0.65 611/16 59/s 21/4 8 1.00 8 7 211/16 Note: Reflects changes in rod diameter from previously published data per recent revisions in MSS-SP-58 & 69 PROJECT INFORMATION Project: APPROVAL STAMP ❑ Approved Address: ❑ Approved as noted Contractor: ❑ Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: Catalog PH-2008 SECTION 5 FIRE SPRINKLERS tqC00 Worldwide I www.tyco-fire.com Contacts Series TY-FRB - 2.85 4.25 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description The TYCO Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers described in herein are quick response, standard coverage, decorative 3 mm glass bulb -type spray sprinklers. They are designed for use in light or ordinary hazard, commercial occupancies such as banks, hotels, and shopping malls. The TY-FRB Recessed Pendent Sprin- kler, where applicable, is intended for use in areas with a finished ceiling. This recessed pendent sprinkler uses one of the following Recessed Escutcheons: • A two-piece Style 10 (1/2 in. NPT) or Style 40 (3/4 in. NPT) Recessed Escutcheon with 1/2 in. (12,7 mm) of recessed adjustment or up to 3/4 in. (19,1 mm) of total adjustment from the flush pendent position. • A two-piece Style 20 (1/2 in. NPT) or Style 30 (3/4 in. NPT) Recessed Escutcheon with 1/4 in. (6,4 mm) of recessed adjustment or up to 1/2 in. (12,7 mm) of total adjustment from the flush pendent position. The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the fixed pipe drops to the sprinklers must be cut. Corrosion -resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond what would be obtained when exposed IMPORTANT Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information. Always refer to Technical Data Sheet TFP700 for the "INSTALLER WARNING" that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. to corrosive atmospheres. Although corrosion -resistant coated sprinklers have passed the standard corrosion tests of the applicable approval agen- cies, the testing is not representative of all possible corrosive atmospheres. Consequently, it is recommended that the end user be consulted with respect to the suitability of these coatings for any given corrosive environment. The effects of ambient temperature, con- centration of chemicals, and gas/ chemical velocity, should be consid- ered, as a minimum, along with the cor- rosive nature of the chemical to which the sprinklers will be exposed. An intermediate level version of the Series TY-FRB Pendent Sprinklers is detailed in Technical Data Sheet TFP356. Sprinkler Guards are detailed in Technical Data Sheet TFP780. NOTICE I The Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers described herein must be installed and maintained in compliance with this document and with the applicable standards of the National Fire Protec- tion Association (NFPA), in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for maintain- ing their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. NFPA 13 prohibits installation of 112 in. NPT sprinklers with K-factors greater than 5.6 in new construction. They are intended for retrofit in existing sprinkler systems only. Sprinkler Identification Number (SIN) TY1131 ... Upright 2.8K, 1/2 in. NPT TY1231 .. Pendent 2.8K, 1/2 in. NPT TY2131 ... Upright 4.2K, 1/2 in. NPT TY2231 .. Pendent 4.2K, 1/2 in. NPT TY3131 ... Upright 5.6K, 1/2 in. NPT TY3231 .. Pendent 5.6K, 1/2 in. NPT TY4131 ... Upright 8.OK, 3/4 in. NPT TY4231 .. Pendent 8.OK, 3/4 in. NPT TY4831 ... Upright 8.OK, 1/2 in. NPT TY4931 .. Pendent 8.OK, 1/2 in. NPT Technical Data Approvals UL and C-UL Listed FM, LPCB, and NYC Approved See Tables A, B, C and D for complete approval information including corrosion - resistant status. Maximum Working Pressure See Table E Page 1 of 12 DECEMBER 2020 TFP171 TFP171 Page 2 of 12 * Temperature rating ** Pipe thread connections per 1 - Frame is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Deflector. special request. PLATE SEATING SURFACE 7/16" (11,1 mm) NOMINAL 2-1/4" MAKE -IN (57,2 mm) l2-3/16" (55,6 mm) 1-9/16" (39,7 mm) 1/2" NPT** WRENCH STYLE 10 or 20 FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON 3 - Sealing 5 Compression Assembly Screw 4 - Bulb 6 Deflector* 7 Bushing 2-7/8" (73,0 mm) DIA. - RECESSED PENDENT CROSS SECTION FIGURE 1 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS 2.8 K-FACTOR, 1121N. NPT * Temperature rating ** Pipe thread connections per is indicated on ISO 7-1 can be provided on ESCUTCHEON Deflector. special request. PLATE SEATING SURFACE 7/16" (11,1 mm) NOMINAL 2-3/16" MAKE -IN (55,6 mm) 2-3/16" 1-1/2" (55,6 mm) (38,1 mm) 1/2" NPT** WRENCH STYLE 10 or 20 FLATS RECESSED 1 - Frame 3 - Sealing 5 - Compression 2 - Button Assembly Screw 4 - Bulb 6 - Deflector* 2-7/8" (73,0 mm) DIA. - 3 -2 4 - 5 6* UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 2 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS 4.2 K-FACTOR, 112 IN. NPT Discharge Coefficient K=2.8 GPM/psi' (40,3 LPM/bars) K=4.2 GPM/psi'/2 (60,5 LPM/bari) K=5.6 GPM/psi/2 (80,6 LPM/bar'/2) K=8.0 GPM/psii (115,2 LPM/bar'/2) Temperature Rating See Tables A and B Finishes Sprinkler: See Table D Recessed Escutcheon: Signal or Pure White, Grey Aluminum, Jet Black, Chrome Plated, or Natural Brass Physical Characteristics Frame ............................Bronze Button......................Brass/Copper Sealing Assembly. Beryllium Nickel w/TEFLON Bulb...............................Glass Compression Screw ................. Bronze Deflector ................... Copper/Bronze Bushing (K=2.8) ....................Bronze Poly -Stainless Physical Characteristics Frame ............................Bronze Button ................ L316 Stainless Steel' Bulb...............................Glass Compression Screw ..... L316 Stainless Steel* Deflector ................... Copper/Bronze Sealing Assembly. Gold Plated Beryllium Nickel w/TEFLON 'Type L316 stainless steel (UNS 31603) per ASTM A479/479M or BS EN 1008 WN1.4404. Operation The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and water to flow. Design Criteria The TYCO Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers are intended for fire protection systems designed in accordance with the stan- dard installation rules recognized by the applicable Listing or Approval agency, such as UL Listing based on the requirements of NFPA 13 and FM Approval based on the requirements of the FM Global Loss Prevention Data Sheets. Use only the style 10, 20, 30, or 40 Recessed Escutcheon, as applica- ble, for recessed pendent installations. TFP171 Page 3 of 12 * Temperature rating is indicated on Deflector. ** Pipe thread connections per ISO 7-1 can be provided on special request. ESCUTCHEON PLATE SEATING SURFACE 7/16" (11,1 mm) NOMINAL 2-3/16" MAKE -IN (55,6 mm) 2-3/16" 1-1/2" (55,61mm) (38,1 mm) 1 1/2" NPT** WRENCH STYLE 10 or 20 FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON UPRIGHT 1 - Frame 3 - Sealing 5 - Compression 2 - Button Assembly Screw 4 - Bulb 6 - Deflector* 2-7/8" (73,0 mm) DIA. — RECESSED PENDENT ALL FINISHES EXCEPT POLY -STAINLESS WRENCH 1/2" ESCUTCHEON FLATS NPT PLATE SEATING SURFACE 7/16" _/7 1,1 mm) OM I NAL 2-3/16" 4AKE-IN (55,6 mm) 2-3/16" 1-1/2" (55,6 mm) 2 (38,1 mm) 1 PENDENT STYLE 1( RECESSEu ESCUTCHEON 3 2 4 — 5 6* CROSS SECTION 1 - Frame 3 Sealing 5 - Compression *Temperature 2 - Button Assembly Screw rating indicated 4 Bulb 6 - Deflector* on Deflector. RECESSED PENDENT POLY -STAINLESS FINISH ONLY 1 3 — 2 4 — 5 6* CROSS SECTION FIGURE 3 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS 5.6 K-FACTOR, 112 IN. NPT Installation The TYCO Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers must be installed in accordance with this section. General Instructions Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin- kler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 in. (1,6 mm) for the 135°F (57°C) and 3/32 in. (2,4 mm) for the 286°F (141°C) temperature ratings. A leak -tight 1/2 in. NPT sprinkler joint should be obtained by applying a minimum -to -maximum torque of 7 to 14 lb-ft (9,5 to 19,0 N•m). A leak tight 3/4 in. NPT sprinkler joint should be obtained with a torque of 10 to 20 lb-ft (13,4 to 26,8 N•m). Higher levels of torque can distort the sprinkler inlet and cause leakage or impairment of the sprinkler. Do not attempt to com- pensate for insufficient adjustment in the escutcheon plate by under- or over - tightening the sprinkler. Re -adjust the position of the sprinkler fitting to suit. Series TY-FRB Upright and Pendent Sprinklers The Series TY-FRB Upright and Pendent Sprinklers must be installed in accordance with the following instructions: Step 1. Install pendent sprinklers in the pendent position. Install upright sprin- klers in the upright position. Step 2. With pipe thread sealant applied to the pipe threads, hand - tighten the sprinkler into the sprinkler fitting. Step 3. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (Ref. Figure 14). With reference to Figure 1 to Figure 5, apply the W-Type 6 Sprinkler Wrench to the sprinkler wrench flats. Series TY-FRB Recessed Pendent Sprinklers The Series TY-FRB Recessed Pendent Sprinklers must be installed in accor- dance with the following instructions: Step 1. After installing the Style 10, 20, 30, or 40 Mounting Plate, as applica- ble, over the sprinkler threads and with pipe -thread sealant applied to the pipe threads, hand -tighten the sprinkler into the sprinkler fitting. Step 2. Tighten the sprinkler into the sprinkler fitting using only the W-Type 7 Recessed Sprinkler Wrench, see Figure 15. With reference to Figure 1 to 4, apply the W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats. Step 3. After the ceiling is installed or the finish coat is applied, slide on the Style 10, 20, 30, or 40 Closure over the Series TY-FRB Recessed Pendent Sprinkler and push the Closure over the Mounting Plate until its flange comes in contact with the ceiling. TFP171 Page 4 of 12 * Temperature rating ** Pipe thread connections per 1 Frame 3 - Sealing 5 - Compression is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 Button Assembly Screw Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector* SURFACE 112" (12,7 mm) NOMINAL 2-5/16" MAKE -IN (58,7 mm) 2-1/4" 1-9/16" (57,2 mm) (39,7 mm) 3/4" NPT** WRENCH STYLE 30 or 40 FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON UPRIGHT 2-7/8" (73,0 mm) DIA. RECESSED PENDENT ALL FINISHES EXCEPT POLY -STAINLESS WRENCH 3/4" ESCUTCHEON FLATS NPT PLATE SEATING SURFACE 1/2" (12,7 mm) NOMINAL MAKE -IN 2-5/16" (58,7 mm) 2-1/4" 1-9/16" (57,2 mm) (39,7 mm) PENDENT STYLE 4( RECESSEu ESCUTCHEON CROSS SECTION 1 - Frame 3 - Sealing 5 - Compression *Temperature 2 - Button Assembly Screw rating indicated 4 - Bulb 6 - Deflector* on Deflector. RECESSED PENDENT CROSS SECTION FIGURE 4 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS 8.0 K-FACTOR, 314 IN. NPT CEILING PLATE 1 - Frame 5 - Compression SEATING SURFACE 2 - Button Screw 1 3 - Sealing 6 Deflector Assembly 7 3 4 - Bulb 7/16 2-1/4" (11,1 mm) (57,2 mm) 2 NOMINAL MAKE -IN * Temperature rating is 2-3/16" 1-9/16" 4 indicated on Deflector. (55,6 mm) 1 (39,7 mm) 1 5 ** Pipe thread connections \ per ISO 7-1 can be 6 * provided on special 1/2" NPT** WRENCH request. FLATS UPRIGHT PENDENT CROSS SECTION FIGURE 5 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4831) AND PENDENT (TY4931) SPRINKLERS 8.0 K-FACTOR, 112 IN. NPT TFP171 Page 5 of 12 2-7/8" DIA. 5/8±1/4" (73,0 mm) 3/4" (19,1 mm) (15,9±6,4 mm) 2-1/4" DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE FITTING 1/8" (3,2 mm) MOUNTING SURFACE C1-5/16" (33,3 CLOSURE SERIES mm) TY-FRB 13/16" (20,6 mm) FIGURE 6 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON 2.8 K-FACTOR, 112 IN. NPT 5/8±1 /4" (15,9±6,4 mm) FACE OF SPRINKLER FITTING MOUNTING SURFACE 2-7/8" DIA. (73,0 mm) 3/4" (19,1 mm) 2-1/4" DIA. 1/4" (6,4 mm) (57,2 mm) 7-j MOUNTING - PLATE CLOSURE SERIES TY-FRB 'r7.� 1/8" (3,2 mm) 1-1/4" (31,8 mm) 3/4" (19,1 mm) FIGURE 8 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON 4.2 K-FACTOR, 112 IN. NPT 2-7/8" DIA. 1/2±1/8" (73,0 mm) 1/2" (12,7 mm) (12,7±3,2 mm) 2-1/4" DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE FITTING (3,2 mm) MOUNTING SURFACE CLOSURE SERIES 1-5/16" (33,3 mm) TY-FRB 1-1/16" (27,0 mm) FIGURE 7 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 112 INCH TOTAL ADJUSTMENT STYLE 20 RECESSED ESCUTCHEON 2.8 K-FACTOR, 112 IN. NPT 2-7/8" DIA. 1/2±1/8" (73,0 mm) 1/2" (12,7 mm) (12,7±3,2 mm) 2-1/4" DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE FITTING 1/8" (3,2 mm) MOUNTING SURFACE 7 CLOSURE SERIES 1-1/4" (31,8 mm) TY-FRB 1" (25,4 mm) FIGURE 9 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 112 INCH TOTAL ADJUSTMENT STYLE 20 RECESSED ESCUTCHEON 4.2 K-FACTOR, 112 IN. NPT TFP171 Page 6 of 12 2-7/8" DIA. 5/8±1/4" (73,0 mm) 3/4" (19,1 mm) (15,9±6,4 mm) 2-1/4" DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE FITTING (3,2 mm) MOUNTING SURFACE CLOSURE SERIES 1-1/4" (31,8 mm) TY-FRB 3/4" (19,1 mm) FIGURE 10 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON 5.6 K-FACTOR, 112 IN. NPT 2-7/8" DIA. _ 5/8±1/4" (73,0 mm) 3/4" (19,1 mm) (15,9±6,4 mm) 2-1/4" DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE FITTING 1/8" (3,2 mm) MOUNTING SURFACE CLOSURE SERIES 1-5/16" (33,3 mm) TY-FRB 13/16" (20,6 mm) FIGURE 12 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON 8.0 K-FACTOR, 314 IN. NPT WRENCH RECESS (END "A" USED FOR 1/2" NPT MODELS) WRENCH RECESS (END "B" USED FOR 3/4" NPT MODELS) FIGURE 14 W-TYPE 6 SPRINKLER WRENCH 2-7/8" DIA. _ (73,0 mm) 1/2" 12,7 mm (12,7±3,2 mm) 2-1/4" DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE FITTING (3,2 mm) / F77_ T 1 I MOUNTING SURFACE CLOSURE SERIES 1-1/4" (31,8 mm) TY-FRB 1 " (25,4 mm) FIGURE 11 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 112 INCH TOTAL ADJUSTMENT STYLE 20 RECESSED ESCUTCHEON 5.6 K-FACTOR, 112 IN. NPT 2-7/8" DIA. _ 1/2±1/8" (73,0 mm) 1/2" (12,7 mm) (12,7±3,2 mm) 2-1/4" DIA. 1/4" (6,4 mm) FACE OF r (57,2 mm) MOUNTING SPRINKLER PLATE FITTING 1/8" (3,2 mm) MOUNTING SURFACE 1 1 CLOSURE SERIES 1-5/16" (33,3 mm) TY-FRB 1-1/16" (27,0 mm) FIGURE 13 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 112 INCH TOTAL ADJUSTMENT STYLE 30 RECESSED ESCUTCHEON 8.0 K-FACTOR, 314 IN. NPT WRENCH RECESS PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH SPRINKLER WRENCHING AREA FIGURE 15 W-TYPE 7 RECESSED SPRINKLER WRENCH TFP171 Page 7 of 12 Sprinkler Finish5 K-Factor Type Temperature Bulb Liquid Color Natural Brass Chrome Plated Polyesters 135°F(57°C) Orange 155°F (68°C) Red Pendent (TY1231) 175°F (79°C) Yellow 200°F(93°C) Green 286°F (141°C) Blue 1,2,3,4 135°F(57°C) Orange 155°F (68°C) Red Upright (TY1131) 175°F (79°C) Yellow 200°F (93°C) Green 2.8 1/2 in. NPT 286°F (141°C) Blue 135°F(57°C) Orange Recessed Pendent 155°F( 68°C) Red (TY1231)a Figure 6 175°F (79°C) Yellow 200°F (93°C) Green 1, 2, 4 135°F (57°C) Orange Recessed Pendent 155°F( 68°C) Red (TY1231)b Figure 7 175°F (79°C) Yellow 200°F (93°C) Green NOTES a. Installed with Style 10 (1/2 in. NPT) or Style 40 (3/4 in. NPT) 3/4 in. Total Adjustment Recessed Escutcheon, as applicable. b. Installed with Style 20 (1/2 in. NPT) or Style 30 (3/4 in. NPT) 1/2 in. Total Adjustment Recessed Escutcheon, as applicable. c. Frame and Deflector only. 1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. Approved by the City of New York under MEA 354-01-E. 5. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed, the sprinklers are UL and C-UL Listed as corrosion -resistant sprinklers. TABLE A LABORATORY LISTINGS AND APPROVALS FOR 2.8 K-FACTOR SPRINKLERS TFP171 Page 8 of 12 Sprinkler Finish3 K-Factor Type Temperature Bulb Liquid Color Natural Brass Chrome Plated Polyester 135°F(57°C) Orange 155°F (68°C) Red Pendent (TY2231) 175°F (79°C) Yellow 200°F (93°C) Green 286°F (141°C) Blue 135°F(57°C) Orange 155°F (68°C) Red Upright (TY2131) 175°F (79°C) Yellow 4.2 1/2 in. NPT 200°F (93°C) Green 1,2 286°F (141°C) Blue 135°F(57°C) Orange Recessed Pendent ° ° 155F 68C ( ) Red (TY2231)a Figure 8 175°F (79°C) Yellow 200°F (93°C) Green 135°F(57°C) Orange Recessed Pendent ° ° 155F 68C ( ) Red (TY2231)b Figure 9 175°F (79°C) Yellow 200°F (93°C) Green NOTES a. Installed with Style 10 (1/2 in. NPT) or Style 40 (3/4 in. NPT) 3/4 in. Total Adjustment Recessed Escutcheon, as applicable. b. Installed with Style 20 (1/2 in. NPT) or Style 30 (3/4 in. NPT) 1/2 in. Total Adjustment Recessed Escutcheon, as applicable. c. Frame and Deflector only. 1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers. 3. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed, the sprinklers are UL and C-UL Listed as corrosion -resistant sprinklers. TABLE B LABORATORY LISTINGS AND APPROVALS FOR 4.2 K-FACTOR SPRINKLERS TFP171 Page 9 of 12 Sprinkler Finish$ K-Factor Type Temperature Bulb Liquid Color Natural Brass Chrome Plated Polyesters Poly -Stainless Lead Coated 135°F(57°C) Orange 155°F (68°C) Red Pendent (TY3231) 1, 2, 3, 4, 5, 6, 7 1,2 1, 2, 3, 5 175°F (79°C) Yellow 200°F (93°C) Green 286°F (141°C) Blue 135°F(57°C) Orange 155°F (68°C) Red Upright (TY3131) 1, 2, 3, 5, 6 1,2 1, 2, 3, 5 175°F (79°C) Yellow 200°F (93°C) Green 5.6 286°F (141°C) Blue 1/2 in. NPT 135°F (57°C) Orange 155°F (68°C) Red Recessed Pendent (TY3231)a 1, 2, 4, 5 1,2 N/Ad 175°F (79°C) Yellow 200°F (93°C) Green Figure 10 286°F (141°C) Blue 135°F(57°C) Orange 155°F (68°C) Red Recessed Pendent (TY3231)b 1, 2, 3, 4, 5 N/A N/A 175°F (79°C) Yellow 200°F (93°C) Green Figure 11 286°F (141°C) Blue NOTES a. Installed with Style 10 (1/2 in. NPT) or Style 40 (3/4 in. NPT) 3/4 in. Total Adjustment Recessed Escutcheon, as applicable. b. Installed with Style 20 (1/2 in. NPT) or Style 30 (3/4 in. NPT) 1/2 in. Total Adjustment Recessed Escutcheon, as applicable. c. Frame and Deflector only. d. Not available (N/A). 1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers. However, _PCB does not rate the thermal sensitivity of recessed sprinklers. 5. Approved by the City of New York under MEA 354-01-E. 6. VdS Approved (For details, contact Johnson Controls, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377.) 7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers. 8. Where Polyester Coated and Lead -Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion -Resistant Sprinklers. Where Lead -Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a Corrosion -Resistant Sprinklers. TABLE C LABORATORY LISTINGS AND APPROVALS FOR 5.6 K-FACTOR SPRINKLERS TFP171 Page 10 of 12 Sprinkler Finish$ K-Factor Type Temperature Bulb Liquid Color Natural Brass Chrome Plated Polyesters Poly -Stainless Lead Coated 135°F(57°C) Orange 155°F (68°C) Red Pendent (TY4231) 175°F (79°C) Yellow 200°F (93°C) Green 286°F (141°C) Blue 1, 2, 3, 4, 5, 6, 7 1,2 1, 2, 5 135°F (57°C) Orange 155°F (68°C) Red Upright (TY4131) 175°F (79°C) Yellow 200°F (93°C) Green 8.0 286°F (141°C) Blue 3/4 in. NPT 135°F (57°C) Orange 155°F(68°C) Red Recessed Pendent (TY4231)a 1, 2, 5 1,2 N/Ad 175°F (79°C) Yellow 200°F (93°C) Green Figure 12 286°F (141°C) Blue 135°F(57°C) Orange 155°F (68°C) Red Recessed Pendent (TY4231)b 1, 2, 3, 5 N/A N/A 175°F( 79°C) Yellow 200°F (93°C) Green Figure 13 286°F (141°C) Blue 135°F(57°C) Orange 155°F (68°C) Red Pendent (TY4931) 175°F (79°C) Yellow 200°F (93°C) Green 8.0 1/2 in. NPT 1, 2, 4, 5, 6 N/A 1, 2, 5 286°F (141°C) Blue 135°F (57°C) Orange 155°F (68°C) Red Upright (TY4831) 175°F (79°C) Yellow 200°F (93°C) Green 286°F (141°C) Blue NOTES a. Installed with Style 10 (1/2 in. NPT) or Style 40 (3/4 in. NPT) 3/4 in. Total Adjustment Recessed Escutcheon, as applicable. b. Installed with Style 20 (1/2 in. NPT) or Style 30 (3/4 in. NPT) 1/2 in. Total Adjustment Recessed Escutcheon, as applicable. c. Frame and Deflector only. d. Not available (N/A). 1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers. However, LPCB does not rate the thermal sensitivity of recessed sprinklers. 5. Approved by the City of New York under MEA 354-01-E. 6. VdS Approved (For details, contact Johnson Controls, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377.) 7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers. 8. Where Polyester Coated and Lead -Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion -Resistant Sprinklers. Where Lead -Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a Corrosion -Resistant Sprinklers. TABLE D LABORATORY LISTINGS AND APPROVALS FOR 5.6 AND 8.0 K-FACTOR SPRINKLERS TFP171 Page 11 of 12 Sprinkler Finish K-Factor Type Natural Chrome Polyester Lead Coated Brass Plated Pendent (TY1231) and 2.8 Upright (TY1131) 1/2 in. 175 psi (12,1 bar) N/A2 NPT Recessed Pendent (TY1231) Pendent (TY2231) and 4.2 Upright (TY2131) 1/2 in. 175 psi (12,1 bar) N/A Recessed NPT Pendent (TY2231) Pendent (TY3231) and 5.6 1/2 in. Upright (TY3131) 250 psi (17,2 bar) NPT or 175 psi (12,1 bar)' Recessed Pendent (TY3231) Pendent (TY4231) 175 psi 8.0 and Upright (TY4131) (12,1 bar) 3/4 in. 175 psi (12,1 bar) Recessed N/A NPT Pendent(TY4231) 8.0 Pendent (TY4931) 175 psi 1/2 in. and 175 psi (12,1 bar) (12,1 bar) NPT Upright (TY4831) NOTES 1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by Underwriters Laboratories, Inc. for use in Canada (C-UL); and, the Approval by the City of New York. 2. Not available (N/A). TABLE E MAXIMUM WORKING PRESSURE Care and Maintenance The TYCO Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers must be maintained and serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire pro- tection system that it controls, obtain permission to shut down the affected fire protection systems from the proper authorities and notify all personnel who may be affected by this action. Absence of the outer piece of an escutcheon, which is used to cover a clearance hole, can delay sprinkler operation in a fire situation. Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or other- wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be taken to avoid damage to the sprinklers before, during, and after installation. Sprinklers damaged by dropping, striking, wrench twist/ slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. For more information, see Installation section. The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Associ- ation such as NFPA 25, in addition to the standards of any other authorities having jurisdiction. Contact the install- ing contractor or sprinkler manufac- turer regarding any questions. Automatic sprinkler systems are rec- ommended to be inspected, tested, and maintained by a qualified Inspec- tion Service in accordance with local requirements and/or national codes. Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprin- klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. For more informa- tion, see Installation section. Initial and frequent visual inspections of random samples are recommended for corrosion -resistant sprinklers to verify the integrity of the corrosion -resis- tant material of construction. There- after, annual inspections per NFPA 25 should suffice. Inspections of corro- sion -resistant sprinklers are recom- mended at close range, instead of from the floor level per NFPA. Inspection at close range can better determine the exact sprinkler condition and the long- term integrity of the corrosion -resistant material, which can be affected by the corrosive conditions present. TFP171 Page 12 of 12 P/N 57 - XXX - X - XXX SIN 330 2.8K UPRIGHT (1/2 in. NPT) TY1131 331 2.8K PENDENT (112 in. NPT) TY1231 340 4.2K UPRIGHT (1/2 in. NPT) TY2131 341 4.2K PENDENT (1/2 in. NPT) TY2231 370 5.6K UPRIGHT (1/2 in. NPT) TY3131 371 5.6K PENDENT (112 in. NPT) TY3231 390 8.OK UPRIGHT (3/4 in. NPT) TY4131 391 8.OK PENDENT (3/4 in. NPT) TY4231 360 8.OK UPRIGHT (1/2 in. NPT) TY4831 361 8.0K PENDENT (1/2 in. NPT) TY4931 SPRINKLER FINISH 1 NATURAL BRASS POLY -STAINLESS GREY 2 ALUMINUM (RAL9007)1 POLYESTER 3 PURE WHITE POLYESTER (RAL9010)2 4 SIGNAL WHITE POLYESTER (RAL9003) 5 JET BLACK POLYESTER (RAL9005)3 7 LEAD COATED 9 1 CHROME PLATED TEMPERATURE RATINGS 135 135°F (57°C) 155 155°F(68°C) 175 175°F(79°C) 200 200°F (93°C) 286 286°F (141°C) NOTES 1. Available only on TY3131, TY3231, TY4131, and TY4231 2. Eastern Hemisphere sales only. 3. Available in only 2.8K, 4.21K, and 8.01K, 155°F (68°C) and 200°F (93°C); requires longer lead time to manufacture. TABLE F SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS PART NUMBER SELECTION Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure Contact your local distributor for availability. When placing an order, indicate the full product name and Part Number (P/li Sprinkler Assemblies with NPT Thread Connections Specify: Series TY-FRB (Specify SIN), (specify K-factor), (specify Pendent or Upright) Sprinkler (specify) temperature rating, (specify) finish or coating, P/N (specify from Table F) Recessed Escutcheon Specify: Style (10, 20, 30, or 40) Recessed Escutcheon with (specify`) finish, P/N (specify) Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 1400 Pennbrook Parkway, Lansdale, PA 19446 1 Telephone +1-215-362-0700 m 2020 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. Johnson 1 nson ORO NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association; Contro�S TEFLON Is a registered tratlemark of DuPont SECTION 6 MISCELLANEOUS Victaulic° VicFlexTm Sprinkler Fittings ✓ctaullcg Series AH2 and AH2-CC Braided Flexible Hoses 10.85 Flex Series AH2 Series AH2-CC 1.0 PRODUCT DESCRIPTION Available Sizes by Component • Series AH2 Braided Hose: 31, 36, 48, 60, 727790, 915, 1220, 1525, 1830mm. Note: length includes adapter nipple and 5.75"/140mm straight reducer. • Series AH2-CC Braided Hose: 31, 36, 48, 60, 727790, 915, 1220, 1525, 1830 mm. Note: length includes captured coupling and 5.757140 mm straight reducer. • Sprinkler Reducers: • Sprinkler Connections: 1/2 and 3/4715 and 20mm • Straight Lengths: 5.75, 9, 137140, 230, 330 mm • 90' Elbows: • Short (typically used with concealed sprinklers) • Long (typically used with recessed pendent sprinklers) • Low Profile Short (for use with Style AB5, AB11 and AB12 Bracket) • Low Profile Long (for use with Style AB5, AB11 and AB12 Bracket) • Inlet Connections: • 1725 mm Grooved IGS • 1'725 mm NPT or BSPT adapter nipples for attaching to pipe and fittings outlined in NFPA standards. • 3/4720 mm NPT or BSPT adapter nipples available for VdS. • 1 1/47 32mm BSPT adapter nipples available for LPCB. ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT. System No. Location Spec Section Paragraph Submitted By Date Approved Date victaulic.com 10.85 5839 Rev AD Updated 08/2018 © 2018 Victaulic Company. All rights reserved. 1 �ctauliic® victaulic.com 1.0 PRODUCT DESCRIPTION (Continued) • Brackets: • Style A131 for suspended and hard -lid ceilings and sidewalls, allows installation before most ceiling tiles in place • Style A132 for suspended and hard -lid ceilings and sidewalls, allows for vertical sprinkler adjustment, and installation before most ceiling tiles in place • Style A133 for surface mount applications, wood, metal and block walls, or ceilings • Style A134 for hard -lid ceilings with hat furring channel grid systems, allows for vertical sprinkler adjustment • Style A135 for hard -lid ceilings and sidewalls, allows for vertical sprinkler adjustment • Style A137 for suspended and hard -lid ceilings • Style A137 Adjustable for suspended and hard -lid ceilings • Style A138 for hard -lid ceilings with CD 60/27 profile metal studs (regionally available) • Style A139 for hard -lid ceilings with hat furring channel grid systems • Style AB10 for Armstrong@ TechZoneTM ceilings • Style AB11 for lay -in panel suspended t-grid ceilings or drywall suspended t-grid ceilings, allows for low profile installations (use only with 90' low profile elbows) • Style AB12 for suspended and hard -lid ceilings, allows for vertical sprinkler adjustment, and allows for low profile installation down to 47100mm. Maximum Working Temperature • 225°F/1070C Maximum Working Pressure • 200 psi/1375 kPa (FM Approval) • 175 psi/1206 kPa (cULus Listed) • 1600 kPa/232 psi (VdS/LPCB Approved) • 1.4 MPa (CCCf Approved) Connections • To adapter nipple (inlet) via • 1725.4 mm Grooved IGS • 1725.4 mm NPT or BSPT male thread • 3/4720 mm BSPT male thread (VdS only) • 11/4732 mm BSPT male thread (LPCB only) • To sprinkler head (outlet) via 1/2" or 3/4715 mm or 20 mm Minimum Bend Radius • 77178 mm (FM/CCCf Approval) • 2751 mm (cULus Listed) • 3776.2 mm (VdS/LPCB Approved) Maximum Allowable Sprinkler K-Factors • FM (1/2"/15mm reducer) K5.6/8,1 (S.I.), (3/4720mm reducer) K14.0/20,2 (S.I.) • cULus (1/2715mm reducer) K8.0/11,5 (S.I.), (3/4720mm reducer) K14.0/20,2 (S.I.) • VdS/LPCB (1/2715mm reducer) K5.6/8,1 (S.I.), (3/4720mm reducer) K8.0/11,5 (S.I.) 2.0 CERTIFICATION/LISTINGS FM C L STEU OS VdS FL -PCB] O nu OM& NOTE • The Vic Flex-rmSeries AH2 Hose has been tested and evaluated by Spears® for acceptable use with Spears® CPVC Products and is therefore covered under the Spears(R) FlameGaurdO Installer Protection Plan. 10.85 5839 Rev AD Updated 08/2018 © 2018 Victaulic Company. All rights reserved. victaulic.com 2 ✓ctaUliic' victaulic.com 3.0 SPECIFICATIONS — MATERIAL Series AH2 • Flexible Hose: 300-series Stainless Steel • Collar/Weld Fitting: 300-series Stainless Steel • Gasket Seal: Victaulic EPDM • Isolation Ring: Nylon • Nut and Nipple: Carbon Steel, Zinc Plated • Reducer (1/z'Y15 mm or 3/4 Y20 mm): Carbon Steel, Zinc -Plated • Low Profile Elbows: Ductile Iron, Zinc -Plated Brackets: Carbon Steel, Zinc -Plated Series AH2-CC • Flexible Hose: 300-series Stainless Steel • Collar/Weld Fitting: 300-series Stainless Steel • Gasket Seal: Victaulic EPDM • Isolation Ring: Nylon • Coupling Retainer Ring: Polyethelene • Nut and Nipple: Carbon Steel, Zinc Plated • Reducer (1/2715 mm or 3/4720 mm): Carbon Steel, Zinc -Plated • Housing: Ductile iron conforming to ASTM A 536, Grade 65-45-12. Ductile iron conforming to ASTM A 395, Grade 65-45-15, is available upon special request. Coupling Housing Coating: • Orange enamel (North America, Asia Pacific). • Red enamel (Europe). • Hot dipped galvanized. Gasket:' • Grade "E" EPDM (Type A) Fire Lock EZ products have been Listed by Underwriters Laboratories Inc., Underwriters Laboratories of Canada Limited, and Approved by Factory Mutual Research for wet and dry (oil free air) sprinkler services within the rated working pressure. 1 Services listed are General Service Guidelines only. It should be noted that there are services for which these gaskets are not compatible. Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service guidelines and for a listing of services which are not compatible. • Bolts/Nut: Zinc electroplated carbon steel, trackhead meeting the physical and chemical requirements of ASTM A 449 and physical requirements of ASTM A 183. • Linkage: CrMo Alloy Steel zinc electroplated per ASTM B633 Zn/Fe 5, Type III Finish 10.85 5839 Rev AD Updated 08/2018 © 2018 Victaulic Company. All rights reserved. vid4midir rnm 3 ✓ctsulicr victaulic.com 4.0 DIMENSIONS Product Details - Series AH2 Braided Hose 2 B 5 1 6 7 3 4 C B Hose Length Dimensions Hose Length inches mm A inches mm B inches mm 31/790 25.3/641 31/790 36/915 31.3/794 36/915 48/1219 42.3/1073 48/1220 60/1525 54.3/1378 60/1525 72/1830 66.3/1683 72/1830 Series AH2-CC Braided Hose 1 6 8 34 A _ B Hose Length inches mm A inches mm B inches mm 31/790 24.5/622 29.8/757 36/915 29.5/749 34.8/884 48/1219 41.5/1054 46.8/1189 60/1525 53.5/1359 58.8/1494 72/1830 65.5/1664 70.8/1798 Item Description 1 Flexible Hose 2 Isolation Ring 3 Gasket 4 Nut 5 Adapter Nipple 6 Braid 7 Collar/Weld Fitting 8 Sleeve Item Description 1 Flexible Hose 2 Isolation Ring 3 Gasket 4 Nut 5 Captured Coupling 6 Braid 7 Collar/Weld Fitting 8 Sleeve 10.85 5839 Rev AD Updated 08/2018 © 2018 Victaulic Company. All rights reserved. victaulic.com M ✓ctauliic' victaulic.com 4.0 DIMENSIONS (Continued) Standard Reducer 5.757140 mm straight reducer Optional Reducers HMWEE��111 9.0"/229 mm straight reducer 13.07330 mm straight reducer 2.62"/ 66.5 mm 4.83"/ 122.7 mm Short 90' elbow reducer 2.62/ 66.5 mm 6.57"/ 166.9 mm Long 90' elbow reducer NOTE • The Short 90' elbow reducer is typically used with concealed sprinklers while the longer 90 elbow is typically used in the installation of recessed pendent sprinklers. • FM/VdS Approved only. Low Profile 1.4"/ 36 mm 0 4.597 1 116 mm 1.4"/ 36 mm Short 90' elbow reducer Long 90° elbow reducer NOTE • Style AB11: When low profiles elbows are used with the Style AB11 bracket, the Low Profile Short Elbow is typically used with concealed sprinklers while the Low Profile Long Elbow is typically used in the installation of recessed pendent sprinklers. 10.85 5839 Rev AD Updated 08/2018 © 2018 Victaulic Company. All rights reserved. vid4midir rnm 5 ✓ctsulic' vir+nl Jir rnm 4.1 DIMENSIONS VicFlex Brackets Style AB1 • Suspended Ceilings • Hard -Lid Ceilings (FM Only) Item Description 1 24"/610 mm or 48'71219 mm Square Bar 2 Patented Center Bracket 3 End Bracket NOTE • Both sizes FM/VdS/LPCB Approved, cULus listed Style AB2 • Suspended Ceilings • Hard -Lid Ceilings Item Description 1 24V 10 mm or 48'71219 mm Square Bar 2 Patented Vertically Adjustable Center Bracket 3 End Bracket NOTE • Both sizes FM/VdS/LPCB Approved, cULus listed Style AB3 • Surface Mount Applications • FM/LPCB Approved 10.85 5839 Rev AD Updated 08/2018 © 2018 Victaulic Company. All rights reserved. vir+midir rnm 0 ✓ct:auliic' vir+nl Jir rnm 4.2 DIMENSIONS VicFlex Brackets Style AB4 • Hard -Lid Ceilings with Hat furring channel grid system Item Description 1 24"/610 mm or 48"/1219 mm Square Bar 2 Patented Vertically Adjustable Center Bracket 3 End Bracket for Hat Furring Channel NOTE • Both sizes FM/VdS/LPCB Approved, cULus listed. Style AB5 • Hard -Lid Ceilings Item Description 1 24"/610 mm or 48"/1219 mm Square Bar 2 Patented Vertically Adjustable Center Bracket 3 End Bracket NOTE • Both sizes FM/VdS/LPCB Approved, cULus listed. Style AB7 • Suspended Ceilings • Hard -Lid Ceilings Item Description 1 24"/610 mm or 48'/1219 mm Square Bar 2 Patented 1-Bee2® Center Bracket 3 End Bracket NOTE • Both sizes FM/VdS/LPCB Approved. Style AB7 Adjustable • Suspended Ceilings • Hard -Lid Ceilings Item Description 1 700 mm or 1400 mm Square Bar 2 Patented 1-Bee2® Center Bracket 3 End Bracket (adjustable) NOTE • Both sizes FM/VdS/LPCB Approved. 10.85 5839 Rev AD Updated 08/2018 © 2018 Victaulic Company. All rights reserved. vir+midir rnm 7 ✓ctsulic' vir+nl Jir rnm 4.3 DIMENSIONS VicFlex Brackets Style AB8 • Hard -Lid Ceilings Item Description 1 700mm or 1400mm Square Bar 2 Patented Vertically Adjustable Center Bracket 3 End Bracket NOTE • Both sizes FM/VdS/LPCB Approved. Style AB10 • Suspended ceilings • Armstrong® TechZoneTM Item Description 1 6"/152 mm Square Bar 2 Patented 1-Bee2® Center Bracket 3 End Bracket NOTE • FM/VdS/LPCB Approved, cULus listed. Style AB11 • Suspended ceilings • Hard -Lid ceilings Item Description 1 24"/610 mm or 48"/1219 mm Square Bar 2 Patented 1-Bee2® Center Bracket 3 End Bracket NOTE • FM/VdS Approved, cULus listed. Style AB12 • Suspended ceilings • Hard -Lid ceilings Item Description 1 Style AB12 Bracket Body 2 #2 Square Drive Set Screw NOTE • FM/VdS Approved. 10.85 5839 Rev AD Updated 08/2018 © 2018 Victaulic Company. All rights reserved. vir+midir rnm i ✓ct:auliic' victaulic.com 4.4 DIMENSIONS Clearances Series AH2 Braided Hose and Style AB1 Bracket A Bracket See Chart Assembly 21/a"/60 mm 21H6'/68 mm Style AB1 max, hole max. hole 2/51 mm 21/8760 mm s 4.47 min. hole min. hole /a"/ 15.9 mm 113 mm Typical 1.7"/43 mm ceiling the Typical ceiling grid' Finished See note ceiling face 247610 mm or 48"/1219 mm on Center Hose Clearance Chart Straight Reducer Long Elbow Short Elbow V2707 V3802 V2707 V3802 3/4" 1/2" 3/a" 1/2' V2707 V3802 V2707 V3802 Max Recess Max Recess Max Recess Max Recess 3/4' Max Recess 1/2" Max Recess 3/4" Max Recess 1/2" Max Recess inches inches inches inches inches inches inches inches mm mm mm mm mm mm mm mm "R" Minimum 2.0 3.0 7.0 Bend Radius 50 80 175 _ "A" Minimum Required 8.6 10.1 9.6 11.1 13.6 15.1 5.8 5.8 Installation 218 269 244 281 345 383 147 147 Space NOTE • Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance differences from the figures above. 10.85 5839 Rev AD Updated 08/2018 0 2018 Victaulic Company. All rights reserved. vid4midir rnm 9 ✓ctauliic' virfanlir rnm 4.5 DIMENSIONS Clearances Series AH2 Braided Hose and Style AB2 Bracket 1�11 oe Yr r =- 1�■ A See Chart 1.8 / 2'Md/68 mm RV/60 mm R.760 mm 45 mm max. hole max. hole max. hole RV/60 mm 2751 mm 2751 mm a min. hole min. hole min. hole 1 I I I f Finished ceiling Hose Clearance Chart Straight Reducer "V2707 V3802 V2709 V2707 V3802 V2709 V2707 V3802 V2709 3/4" 1 20mm 1/2' 1 13 mm 3/4" 1 20mm 3/4" 1 20mm 1/2" 1 13 mm 3/4" 1 20mm 3/4" 1 20mm 1/2" 1 13 mm 3/4" 1 20mm Max Recess" Max Recess Sidewall Max Recess Max Recess Sidewall Max Recess Max Recess Sidewall inches inches inches inches inches inches inches inches inches mm mm mm mm mm mm mm mm mm "R" Minimum 2.0 3.0 7.0 Bend Radius 50 80 175 "A" Minimum Required 6.2 7.6 6.1 7.2 8.6 7.1 11.2 12.6 11.1 Installation 158 193 155 183 218 180 285 320 282 Space Hose Clearance Chart Long Elbow Short Elbow V2707 V2709 V3802 3/4' 1 20mm 3/4!' 120mm 1/2" 113 mm Max Recess Sidewall Max Recess inches inches inches mm mm mm "R" Minimum Bend Radius _ "A" Minimum Required 3.3 3.6 3.3 Installation 84 91 84 Space NOTE • Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance differences from the figures above. 10.85 5839 Rev AD Updated 08/2018 © 2018 Victaulic Company. All rights reserved. victaulic.com 10 ✓ctsulicr virtni lir rnm 4.6 DIMENSIONS Clearances Series AH2 Braided Hose and Style AB4 Bracket 00 A 23/8760 mm 2%768 mm See Chart max. hole max. hole 2751 mm 23/8"/60 mm min. hole min. hole /sVI5.9mm Typical Typical finished ceiling tile ceiling face See note Typical 16"/406 mm - 1/8723 mm 24"/610 mm on Center Typical ceiling and Hose Clearance Chart Straight Reducer Long Elbow Short Elbow V2707 V3802 V2707 V3802 3/4' 1/i' 3/a" 1/2" V2707 V3802 V2707 V3802 Max Recess Max Recess Max Recess Max Recess 3/4" Max Recess 1/2" Max Recess 3/4' Max Recess 1/2" Max Recess inches inches inches inches inches inches inches inches mm mm mm mm mm mm mm mm "R" Minimum 2.0 3.0 3.0 7.0 7.0 Bend Radius 50 50 80 80 175 175 _ "A" Minimum Required 8.8 10.2 9.8 11.2 13.8 15.2 8.0 5.9 Installation 224 259 249 285 351 386 203 150 Space NOTE Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance differences from the figures above. 10.85 5839 Rev AD Updated 08/2018 © 2018 Victaulic Company. All rights reserved. victaulic.com 11 ✓ctSU1ilc' 14r+nrllir rnm 4.7 DIMENSIONS Clearances Series AH2 Braided Hose and Style AB5 Bracket See Chart Bracket Assembly R.760 mm 21N768 mm 23W760 mm StylfAB� 7 max. hole max. hole max. hole mm2"/51 mm R.760 mm 2"/51 mm min. hole min. hole min. hole m 2x4" ii ii iMetalStud IAl/ Finished 15.9 mm ceiling face Drywall 16"/406 mm Stud C/C Hose Clearance Chart Straight Reducer "V2707 V3802 V2709 V2707 V3802 V2709 V2707 V3802 V2709 3/4" 1 20mm 1/2" 1 13 mm 3/4" 1 20mm 3/4" 1 20mm 1/2" 1 13 mm 3/4' 1 20mm 3/4" 1 20mm 1/2" 1 13 mm 3/4" 1 20mm Max Recess" Max Recess Sidewall Max Recess Max Recess Sidewall Max Recess Max Recess Sidewall inches inches inches inches inches inches inches inches inches mm r mm mm mm mm mm mm mm "R" Minimum 2.0 3.0 7.0 Bend Radius 50 80 175 "A" Minimum Required 6.0 7.7 6.1 7.0 8.7 7.1 11.0 12.7 11.1 Installation 158 196 155 178 221 180 279 323 282 Space Hose Clearance Chart Long Elbow Short Elbow V2707 V3802 V2709 V3802 3/4" 1 20mm 1/2" 113 mm 3/4!' 120mm 1/2" 1 13 mm Max Recess Max Recess Sidewall Max Recess inches inches inches inches mm mm mm mm "R" Minimum _ Bend Radius "A" Minimum Required 3.5 4.9 3.6 3.3 Installation 89 124 91 84 Space NOTE • Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance differences from the figures above. 10.85 5839 Rev AD Updated 08/2018 © 2018 Victaulic Company. All rights reserved. 12 ✓ctsulic' victaulic.com 4.8 DIMENSIONS Clearances Series AH2 Braided Hose and Style AB11 Bracket (LOW PROFILE SOLUTION) 21/8760 mm 21Y,6'/68 mm 11 Bracket max. hole max. hole Assembly 2751 mm 21/8760 mm A Style ABI I min. hole min. hole 07 See Chart 3.r 76 mm rr {r 1.7743 mm Finished Typical 5/8"/15.9 mm ceiling face ceiling grid Typical ceiling the See Note 247610 mm or 4871219 mm on center Hose Clearance Chart Low -Profile Low -Profile Long Elbow Short Elbow "V2707 V3802 3/4" 1 20mm 1/2" 113 mm Max Recess" Max Recess inches inches mm mm "A"Minimum Required 4.0 3.9 Installation 102 99 Space NOTE • Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance differences from the figures above. 10.85 5839 Rev AD Updated 08/2018 0 2018 Victaulic Company. All rights reserved. victaulic.com 13 ✓ctauliiic' vir+Mlllir rnm 4.9 DIMENSIONS Clearances Series AH2 Braided Hose and Style AB12 Bracket Suspended Ceiling Grid with Recessed Sprinkler with Low Profile Short Elbow i I I V/ Inch/M10 1Ye inch/ 9mm Threaded Rod /n.9-meter Maximax1m um Length)/i A inch/ 3m Typical Ceiling V27071/:" /12.7 mm MAX. RECESS Suspended Ceiling Grid with Recessed Sprinkler and Straight 5.75"/140mm Reducer Im iypica Bening V2707 A' /19 mm MAX. RECESS Low Profile Dimension Short Elbow 3/4'719mm Low Profile Long Elbow 3/4'Y19mm Standard Short Elbow Standard Long Elbow Standard Straight Reducer 3/4719mm 3/a'719mm 3/a'719mm Recessed* Concealed Recessed Concealed Recessed Concealed Recessed Concealed Recessed Concealed inches inches inches inches inches inches inches inches inches inches mm mm mm mm mm mm mm mm mm mm A Minimum Required 4.0 5.5 5.6 7.2 5.9 7.5 7.7 9.3 15.0 16.6 Installation Space 101.6 139.7 142.2 182.9 149.9 190.5 195.6 236.2 381.0 421.6 rBDistance from Top of 0.5 2.0 1.5 1.5 1.5 1.5 3.0 3.0 3.0 3.0 Typical Ceiling Tile to 12.7 50.8 38.1 38.1 38.1 38.1 76.2 76.2 76.2 76.2 Bottom of Gate * Adjustability will be limited NOTE • Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance differences from the figures above 10.85 5839 Rev AD Updated 08/2018 © 2018 Victaulic Company. All rights reserved. 14 ✓ctauliic' victaulic.com 4.10 DIMENSIONS Clearances Series AH2 Braided Hose and Style AB3 Bracket Surface Mount Application with Recessed Sprinkler 2751 mm min. hole Hose Clearances inches inches inches inches inches inches inches inches inches inches Dimension mm mm mm mm mm mm mm mm mm mm Wall Thickness 2 4 6 8 10 2 4 6 8 10 "A" 50 100 150 200 250 50 100 150 200 250 Outlet Length 5.75 9 1 13 5.75 1 9 1 13 9 13 13 13 5.75 9 13 5.75 9 13 9 13 13 13 "B" 146.1 228.6 330.2 146.1 228.6 330.2 228.6 330.2 330.2 330.2 146.1 228.6 330.2 146.1 228.6 330.2 228.6 330.2 330.2 330.2 Hose Clearance 11.6 14.8 18.8 9.6 1 12.8 16.8 10.8 14.8 12.8 10.8 12.6 15.8 19.8 10.6 13.8 17.8 11.8 15.8 13.8 11.8 "C" 294 376 478 243 325 427 275 376 325 275 319 402 503 268 351 452 300 402 351 300 Bend Radius 7 8 "R" 175 200 NOTE • Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance differences from the figures above. 10.85 5839 Rev AD Updated 08/2018 © 2018 Victaulic Company. All rights reserved. victaulic.com 15 ✓ctsulic' vir+nlllir rnm 4.11 DIMENSIONS Branchline clearances Series AH2 Braided Hose with female threaded outlet 'Ta Hose Clearance Chart Dimension inches inches inches inches inches inches mm mm mm mm mm mm R Minimum 1 2 3 4 5 6 7 Bend Radius 50 80 100 125 150 175 A Min. 8.4 9.4 10.4 11.4 12.4 13.41 214 239 264 290 315 341 Series AH2-CC Braided Hose with grooved outlet W Hose Clearance Chart Dimension inches inches inches inches inches inches mm mm mm mm mm mm R Minimum 2 3 4 5 6 7 Bend Radius 50 80 100 125 150 175 A Min. 7.1 8.1 9.1 10.1 11.1 12.1 180 205 231 256 281 307 10.85 5839 Rev AD Updated 08/2018 © 2018 Victaulic Company. All rights reserved. 16 ✓ctsulic' victaulic.com 5.0 PERFORMANCE — FRICTION LOSS DATA c@us Series AH2 and AH2-CC Braided Hoses with Straight 5.757140 mm Reducers LISTED Style AB1, AB2, AB4, AB5 and AB10 Brackets Maximum Equivalent Length Number of of 1'733.7mm 90' Bends at 2751 Trim Sch. 40 Pipe (C=120) Bend Radius inches/mm inches/mm/type feet/meters 31 /790 1/z"M 5/Straight 16/4.9 4 4 3/4"/20/Strai ht 17/5.2 36/915 1/2"/15/Straight 21 /6.4 5 3/4"/20/Straight 23/7.0 5 48/1220 1/z"/15/Straight 32/9.8 8 3/4"/20/Strai ht 37/11.3 8 60/1525 1/z"/15/Straight 46/14.0 10 3/4"/20/Strai ht 46/14.0 10 72/1830 1/z'/15/Straight 3/4"/20/Straight 55/16.8 12 53/16.2 12 c �L us Series AH2 and AH2-CC Braided Hose with 90' Low Profile Elbows LISTED Style AB11 VicFlex Bracket Maximum Equivalent Length Number of of 1733.7 mm 90' Bends at 2751 Trim Sch. 40 Pipe Bend Radius inches/mm inches/mm feet/meters 31 /790 1/z'715 24/7.3 4 4 3/4"/20 24/7.3 36/915 1/z"/15 26/7.9 5 5 3/4"/20 28/8.5 48/1220 1/z"/15 43/13.1 8 3/4"/20 42/12.8 8 60/1525 1/z"/15 49/14.9 10 3/4"/20 50/15.2 10 72/1830 1/z"/15 65/19.8 12 3/4"/20 63/19.2 12 10.85 5839 Rev AD Updated 08/2018 © 2018 Victaulic Company. All rights reserved. victaulic.com 17 ✓ctauliic' victaulic.com 5.0 PERFORMANCE — FRICTION LOSS DATA (CONTINUED) Series AH2 and AH2-CC Braided Hoses Equivalent Length Design Guide Equivalent length values at various numbers of 90 degree bends at 2751 mm center line bend radius Length of Stainless Steel Flexible Outlet 1 2 3 4 5 6 7 8 9 10 11 12 Hose Size Bend Bends Bends Bends Bends Bends Bends Bends Bends Bends Bends Bends inches/ inches/ feet/ feet/ feet/ feet/ feet/ feet/ feet/ feet/ feet/ feet/ feet/ feet/ mm mm meters meters meters meters meters meters meters meters meters meters meters meters 1/2"/15 8.5/2.6 11.0/3.4 13.0/4.0 16.0/4.9 N.A N.A N.A N.A N.A N.A N.A N.A 31/790 3/4720 10.0/3.0 12.5/3.8 14.0/4.3 17.0/5.2 N.A N.A N.A N.A N.A N.A N.A N.A 1/2 /15 13.5/4.1 16.0/4.9 18.0/5.5 19.0/5.8 21.0/6.4 N.A N.A N.A N.A N.A N.A N.A 36/915 3/4'720 14.0/4.3 17.0/5.2 19.5/5.9 20.0/6.1 23.0/7.0 N.A N.A N.A N.A N.A N.A N.A 1/2 /15 15.5/4.7 17.0/5.2 19.5/5.9 20.0/6.1 21.0/6.4 22.0/6.7 28.0/8.5 32.0/9.8 N.A N.A N.A N.A 418/1220 3/4720 17.0/5.2 19.0/5.8 21.5/6.6 24.5/7.5 26.0/7.9 27.0/8.2 30.0/9.1 37.0/11.3 N.A N.A N.A N.A 1/2 /15 21.5/6.6 24.0/7.3 27.0/8.2 28.5/8.7 30.0/9.1 31.0/9.4 37.0/11.3 42.0/12.8 44.0/13.4 46.0/14.0 N.A N.A 60/1525 3/4720 23.0/7.0 24.0/7.3 28.0/8.5 29.5/9.0 30.5/9.3 31.0/9.4 38.0/11.6 42.0/12.8 44.0/13.4 46.0/14.0 N.A N.A 1/2 /15 30.0/9.1 32.0/9.8 36.5/11.1 37.5/11.4 40.5/12.5 41.0/12.8 42.0/12.8 46.0/14.0 49.0/14.9 52.0/15.8 54.0/16.5 55.0/16.8 72/1830 3/4720 32.0/9.8 32.5/9.9 35.0/10.7 35.5/10.8 40.0/12.3 40.5/12.3 41.0/12.5 46.0/14.0 50.0/15.2 51.0/15.5 52.0/15.8 53.0/16.2 NOTES: • Values for use with 5.757140 mm straight reducers. How to use this Design Guide: • For some systems, it may be advantageous for the designer to calculate the system hydraulics using shorter equivalent lengths associated with fewer than the maximum allowable number of bends. In this case, the designer may select a design number of bends for the job and use the associated equivalent length from the design guide to determine the system hydraulics. • It is possible that the actual installed condition of some of the flexible drops may have more bends than the designer selected. When this happens, the design guide may be used to find equivalent lengths based on the actual installed number of bends for particular sprinkler installations. The system hydraulics can be recalculated using actual equivalent lengths to verify the performance of the system. 10.85 5839 Rev AD Updated 08/2018 © 2018 Victaulic Company. All rights reserved. victaulic.com 10 ✓ctsulic' victaulic.com 5.1 PERFORMANCE - FRICTION LOSS DATA FM Series AH2 and AH2-CC Braided Hoses Style AB1, AB2, AB3, AB4, ABS, AB7, AB7 Adj., ABB, AB1O and AB12 VicFlex Brackets Length of Stainless Steel Flexible Hose inches/mm K-Factor Imperial/S.I. Outlet Size inches/mm/type Equivalent Length of 1733.7mm Sch. 40 Pipe feet/meters Maximum Number of 90' Bends at 7/178mm Bend Radius 31/790 5.6/8.1 '/2"/15/Straight 13.8/4.2 2 '/2"/15/90° Elbow 23.5/7.1 36/915 5.6/8.1 '/2"/15/Strai ht 16.6/5.1 2 '/2"/15/90° Elbow 25.6/7.8 48/1220 5.6/8.1 '/2"/15/Straight 23.4/7.1 3 Y2"/15/90° Elbow 30.7/9.3 60/1525 5.6/8.1 '/2"/15/Straight 30.2/9.2 4 1/2715/90* Elbow 35.9/10.9 72/1830 5.6/8.1 '/2"/15/Straight 37.0/11.3 4 '/2715/90* Elbow 41.1/12.5 31/790 8.0/11.5 3/4"/20/Strai ht 16.8/5.1 2 3/4"/20/90° Elbow 16.8/5.1 36/915 8.0/11.5 3/4"/20/Strai ht 20/6.0 2 3/4"/20/90° Elbow 19.7/6.0 48/1220 8.0/11.5 3/4"/20/Strai ht 27.8/8.4 3 3/a"/20/90° Elbow 26.6/8.1 60/1525 8.0/11.5 3/4"/20/Strai ht 35.7/10.9 4 3/4"/20/90° Elbow 33.6/10.2 72/1830 8.0/11.5 3/4"/20/Strai ht 43.5/13.2 4 3/4"/20/90° Elbow 40.6/12.2 31/790 11.2/16.1 3/4"/20/Strai ht 16.5/5.0 2 3/4"/20/90° Elbow 17.8/5.4 36/915 11.2/16.1 3/4"/20/Strai ht 19.5/5.9 2 3/4"/20/90° Elbow 20.7/6.3 48/1220 11.2/16.1 3/4"/20/Strai ht 26.7/8.1 3 3/4"/20/90° Elbow 27.9/8.5 60/1525 11.2/16.1 3/4"/20/Strai ht 33.9/10.3 4 3/4"/20/90° Elbow 35/10.7 72/1830 11.2/16.1 3/4"/20/Strai ht 41.3/12.5 4 3/4"/20/90° Elbow 42.2/12.8 31/790 14.0/20.2 14.0/20.2 3/4"/20/Strai ht 14.9/4.5 2 3/4"/20/90° Elbow 15.5/4.72 36/915 3/4"/20/Strai ht 19.4/5.9 2 3/4"/20/90° Elbow 19.6/5.9 48/1220 14.0/20.2 3/4"/20/Strai ht 30.3/9.2 3 3/4"/20/90° Elbow 29.5/8.9 60/1525 14.0/20.2 3/4"/20/Strai ht 33.9/10.3 4 3/4"/20/90° Elbow 34.1/10.4 72/1830 14.0/20.2 3/4"/20/Strai ht 37.5/11.4 4 3/4"/20/90° Elbow 38.6/11.7 FM NOTES: • The Series AH2 hose has been tested and Approved by FM Global for use in wet, dry and preaction systems per NFPA 13, 13R, and 13D and FM data sheets 2-0, 2-5, and 2-8. FM 1637 standard for safety include, but are not limited to, pressure cycling, corrosion resistance, flow characterisitics, vibration resistance, leakage, mechanical and hydrostatic strength. • EXAMPLE: A 48-inch hose installed with two 30' bends and two 90' bends is permitted and considered equivalent to the data in the table shown above. In this example, the total number of degrees is 240°, which is less than the allowable 270°. 10.85 5839 Rev AD Updated 08/2018 © 2018 Victaulic Company. All rights reserved. victaulic.com 19 ✓ctauliic' victaulic.com 5.2 PERFORMANCE - FRICTION LOSS DATA FM Series AH2 Braided Hose with 90' Low Profile Elbows Style AB5, AB11 and AB12 VicFlex Bracket Length of Stainless Steel Flexible Hose inches/mm K-Factor Imperial/S.I. Outlet Size inches/mm Equivalent Length of 1733.7mm Sch. 40 Pipe feet/meters Maximum Number of 90' Bends at 7/178mm Bend Radius 31 /790 5.6/8.1 1/2715 13.7/4.2 2 36/915 5.6/8.1 1/2715 17.0/5.2 2 48/1220 5.6/8.1 1/2715 25.0/7.6 3 60/1525 5.6/8.1 1/2715 33.0/10.1 4 72/1830 5.6/8.1 1/2715 41.1 /12.5 4 31 /790 8.0/11.5 3/4720 13.6/4.14 2 36/915 8.0/11.5 3/4720 16.9/5.2 2 48/1220 8.0/11.5 3/4720 27.8/8.5 3 60/1525 8.0/11.5 3/4" /20 32.6/9.9 4 72/1830 8.0/11.5 3/4720 40.6/12.4 4 31 /790 11.2/16.1 3/4720 13.7/4.2 2 36/915 11.2/16.1 3/4720 17.0/5.2 2 48/1220 11.2/16.1 3/4720 24.9/7.6 3 60/1525 11.2/16.1 3/4720 32.9/10.0 4 72/1830 11.2/16.1 3/4720 40.9/12.5 4 31 /790 14.0/20.2 3/4720 13.5/4.1 16.8/5.1 2 36/915 14.0/20.2 3/4720 2 48/1220 14.0/20.2 3/4720 24.7/7.5 3 60/1525 14.0/20.2 3/4" /20 32.7/9.9 4 72/1830 14.0/20.2 3/4720 40.7/12.4 4 FM NOTES: • The Series AH2 hose has been tested and Approved by FM Global for use in wet, dry and preaction systems per NFPA 13, 13R, and 13D and FM data sheets 2-0, 2-5, and 2-8. FM 1637 standard for safety include, but are not limited to, pressure cycling, corrosion resistance, flow characterisitics, vibration resistance, leakage, mechanical and hydrostatic strength. • EXAMPLE: A 48-inch hose installed with two 30' bends and two 90' bends is permitted and considered equivalent to the data in the table shown above. In this example, the total number of degrees is 240°, which is less than the allowable 270°. 10.85 5839 Rev AD Updated 08/2018 © 2018 Victaulic Company. All rights reserved. victaulic.com 20 ✓ctsulic' 5.3 PERFORMANCE - FRICTION LOSS DATA VdS Series AH2 and AH2-CC Braided Hose Style AB1, AB2, AB4, AB5, AB7, AB7 Adj., AB8, AB10, AB11 and AB12 Brackets Length of Stainless Steel Outlet Flexible Hose Size mm/inches mm/inches 15mm/'/2" 31 /790 20 mm/3/4" 15mm/'/2" 36/915 20 mm/3/4" 15mm/'/2" 48/1220 20 mm/3/4" 15mm/'/2" 60/1525 20 mm/3/4" 15mm/l/2" 72/1830 20 mm/3/4" VDS CEILING MANUFACTURERS LIST AB1, AB2, AB7, AB10 ,AB11 AB4 AB5, AB8 1. AMF No specific approval 1. Hilti 2. Armstrong 2. Knauf 3. Chicago Metallic 3. Lafarge 4. Dipling 4. Lindner S. Durlum 5. Rigips 6. Geipel 7. Gema-Armstrong 8. Hilti 9. Knauf 10. Lafarge 11. Linder 12. Odenwald 13. Richter 14. Rigips 15. Rockfon Pagos 16. Suckow & Fischer 17. USG Donn Series AH2 and AH2-CC Braided Hose LPCB Style AB1, AB2, AB3, AB4, AB5, AB7, AB8, and AB10 Brackets Length of Equivalent Length Maximum Stainless of steel pipe Number of Steel according to 90' Bends at Flexible Outlet EN 10255 ON 25 3'776.2mm Hose Size (33,7 x 3,25) Bend Radius mm/inches mm/inches/type meters/feet 15mm/'/2"/Strai ht 790/31 1.8/6.0 2 20 mm/3/4"/Straight 15mm/'/2"/Strai ht 915/36 3.6/11.9 3 20 mm/3/4"/Straight 15mm/'/2"/Strai ht 1220/48 4.3/14.0 3 20 mm/3/4"/Straight 15mm/'/2"/Strai ht 1525/60 4.1/13.6 3 20 mm/3/4"/Straight 15mm/'/2"/Strai ht 1830/72 5.5/18.1 3 20 mm/3/4"/Straight Equivalent Length of Maximum Number steel pipe according to of 90' Bends at EN 10255 ON 25 3"/76.2mm Bend (33,7 x 3,25) Radius meters/feet meters/feet 5.5/1 8.0 3 6.4/21.0 3 8.5/27.9 3 10.7/35.1 4 4 Series AH2 Braided Hose Style AB1, AB2, AB3, AB4, AB5, AB7, AB8, AB10 and AB12 Brackets Length of Flexible Equivalent Length of Hose 1'733.7 mm Sch. 40 Pipe mm inches Straight Configuration Bend Configuration 790 0.87 2.70 31 2.9 8.9 915 1.00 2.80 36 3.3 9.2 1220 2.23 4.66 48 7.3 15.3 1525 2.90 6.5 60 9.5 21.3 1830 3.31 7.16 72 10.9 23.5 CCCF NOTE • Friction loss data is in accordance with GB5135.16 tested at a flow rate of 114 liters per minute (30 gallons per minute). 10.85 5839 Rev AD Updated 08/2018 © 2018 Victaulic Company. All rights reserved. victaulic.com 21 ✓ctauliic' victaulic.com 6.0 NOTIFICATIONS A WARNING • It is the responsibility of the system designer to verify suitability of 300-series stainless steel flexible hose for use with the intended fluid media within the piping system and external environments. • The effect of chemical composition, pH level, operating temperature, chloride level, oxygen level, and flow rate on 300-series stainless steel flexible hose must be evaluated by the material specifier to confirm system life will be acceptable for the intended service. Failure to follow these instructions could cause product failure, resulting in serious personal injury and/or property damage. 7.0 REFERENCE MATERIALS - CHARACTERISTICS VicFle)Jm Maximum Load Values Series AH2 Hose with 24" Bracket Actual Length Total Load Max. Uniform Load ft Model Size m Ib N Ib/linearft N/linearm 31 /790 2.6 5.2 23 2.6 38 � 25 40 36/915 5.5 2.8 9 6.3 3.1 48/1220 z 28 46 1 7.0 3.5 60/1525 5 31 51 1 7.7 3.9 72/1830 8 34 57 1 Series AH2 Hose with 48" Bracket Actual Length Total Load Max. Uniform Load ft Model Size m lb N Ib/linearft N/linearm 31 /790 2.6 6.1 27 1.5 22 36/915 � 6.4 29 1.6 23 9 48/1220 2 7.2 32 1.8 26 1 60/1525 7.9 35 2.0 29 ,5 72/1830 8 8.7 39 2.2 32 1 Total Load is defined as the sum of the weights of the following: • water -filled flexible sprinkler hose with threaded end fittings, including a typical fire sprinkler • bracket assembly (any applicable Victaulic bracket model of the relevant associated size) ASTM C 635: Suspension System Load -Carrying Capabilities (excerpted) Actual Length Min. Allowable Uniform Load Suspension System ft/m Ib/linearft N/linearm Light 5.0 75.7 Direct Hung Intermediate 12.0 181.0 Heaw 16.0 241.7 SUMMARY: All direct -hung suspension system duty classifications per ASTM C 635 are able to withstand the maximum water -filled weight of the VicFlex sprinkler hose and bracket. 10.85 5839 Rev AD Updated 08/2018 © 2018 Victaulic Company. All rights reserved. victaulic.com 22 ✓ctauliic® victaulic.com 7.0 REFERENCE MATERIALS — CHARACTERISTICS (CONTINUED) Flexible Hose In -Plane Bend Characteristics One Bend I \ I I \ I I Minimum bend radius I I I 90. I _—�— Two Bends fi OR Minimum I bend radius Minimum bend radius Minimum bend radius Three Bends OR Minimum bend radius NOTE For out -of -plane (three-dimensional) bends, care must be taken to avoid imparting torque on the hose. I-VicFlex-AB1-AB2-AB10 I-VicFlex-AB3 I-VicFlex-AB7 I-VicFlex-AB8 I-VicFlex-AB4 I-VicFlex-AB12 Minimum bend radius ,imum d radius User Responsibility for Product Selection and Suitability Note Each user bears final responsibility for making a determination as to the suitability of This product shall be manufactured by Victaulic or to Victaulic specifications. All products Victaulic products for a particular end -use application, in accordance with industry to be installed in accordance with current Victaulic installation/assembly instructions. standards and project specifications, and the applicable building codes and related Victaulic reserves the right to change product specifications, designs and standard regulations as well as Victaulic performance, maintenance, safety, and warning equipment without notice and without incurring obligations. instructions. Nothing in this or any other document, nor any verbal recommendation, Installation advice, or opinion from any Victaulic employee, shall be deemed to alter, vary, supersede, Reference should always be made to -VICFLEX-AB1-AB2-AB10, I-VICFLEX-AB4, or waive any provision of Victaulic Company's standard conditions of sale, installation I-VICFLEX-AB7, or I-VICFLEX-AB8 for the product you are installing. Handbooks are guide, or this disclaimer. included with each shipment of Victaulic products for complete installation and assembly Intellectual Property Rights data, and are available in PDF format on our website at www.victaulic.com. No statement contained herein concerning a possible or suggested use of any material, Warranty product, service, or design is intended, or should be constructed, to grant any license Refer to the Warranty section of the current Price List or contact Victaulic for details. under any patent or other intellectual property right of Victaulic or any of its subsidiaries or affiliates covering such use or design, or as a recommendation for the use of such Trademarks material, product, service, or design in the infringement of any patent or other intellectual Victaulic and all other Victaulic marks are the trademarks or registered trademarks of property right. The terms "Patented" or "Patent Pending" refer to design or utility patents Victaulic Company, and/or its affiliated entities, in the U.S. and/or other countries. or patent applications for articles and/or methods of use in the United States and/or other countries. 10.85 5839 Rev AD Updated 08/2018 © 2018 Victaulic Company. All rights reserved. victaulic.com 23 ✓ctaUliic'