FIR2021-0138+Fire_Alarm_Battery_Calculations_PLANS+12.3.2021_8.39.29_AM+2551282CV ON W M Q 04 0 LEGEND DEVICE QUANTITY DEVICE DESCRIPTION MOUNTING FACP I FIRE ALARM CONTROL PANEL POTTER INCLUDED MODEL: IPA-60 GSM I COMMUNICATOR NAPCO INCLUDED GSM LTES MODEL: SLE-LTE SMOKE DETECTOR POTTER 4SQ. W I GANG - I MODEL: PAD200-PD MUDRING ® 4 HEAT DETECTOR POTTER 4SQ. W I GANG MODEL: PADIOO-HD MUDRING 5 CEILING MOUNTED HORN/STROBE (WHITE) POTTER 4SQ. W I GANG MODEL: CHS-24W MUDRING WALL MOUNTED WEATHERPROOF HORN/STROBE (RED) POTTER �W I MODEL: HS-24WR-WP INCLUDED M = DATA LOOP TWISTED PAIR #16 GAUGE WIRE Q A = SLC DATA 18/2 FPLP LZ LJJ B = NAC CIRCUIT 14/2 FPLP X = ZONE CIRCUIT TWISTED PAIR #16 GAUGE WIRE Nw I..L \ 5 S = SPEAKER CIRCUIT PAIR # 14 GAUGE WIRE FR = RELAY CIRCUIT TWISTED PAIR #16 GAUGE WIRE _J SUBSCRIPT E = EXISTING WP = WEATHER PROOF MOUNT C = CEILING MOUNT R = RELOCATE EXISTING CD = CANDELA SCOPE OF WORK: 1) INSTALL NEW FIRE ALARM SYSTEM. GENERAL NOTES: 1. ALL CEILING HEIGHTS ARE 16' OR LOWER AFF. (DPOTTER Project Name: I Mike's Plumbing I Standby Hours: 24 The Symbol of Protection 121010 - 70th Ave W Edmonds Alarm Mins: 0 IPA-60 Installed By: I Froula Alarm System Inc. Efficiency Factor: 20% Battery & Voltage Drop Designed By: JD SLC Type: Class B Calculations Date: 11/23/2021 NAC Source Voltage: 20.4 Model#: IPA-60 Max Panel Current (amps): 5 Panel ID: FACP User assumes all responsibility to ensure the quantities and Location: Main Entry current draw values in this worksheet are accurate prior to submittal. 1 IPA-60 Analog Addressable FACP 0.130 0.130 0.220 0.220 Panel Standby: 0.130 Panel Alarm: 0.220 1 UD-2000 if UD-1000 DACT Card 0.016 0.016 0.023 0.023 RA-6075R LCD Annunciator 0.020 0.025 RA-6500R(F) Flush Mount LCD Annunciator 0.020 0.050 LED-16(F) Flush Mount LED Annunciator 0.025 0.025 LED-16 LED Annunciator LED Power* 0.015 0.210 CA-6075 Class A Module 0.012 0.044 PSN-1000(E) Power Expander 0.015 0.015 PAD100-SLCE-127 SLC Expander 0.060 0.060 NOHMI-SLCE-127** SLC Expander 0.060 0.060 IDC-6 Initating Zone Expander 0.020 0.020 IDC-6 Initating Zone Expander Power* 0.030 0.270 RLY-5 Relay Expander 0.025 0.035 RLY-5 Relay Expander Power* 0.010 0.135 DRV-50 LED Driver Module 0.025 0.025 DRV-50 LED Driver Module LED Power* 0.010 0.215 FCB-1000 Fire Communications Bridge 0.025 0.025 FIB-1000 Fiber Interface Board 0.030 0.030 MC-1000 Multi -Connect Expander 0.010 0.010 SPG-1000 Serial Parallel Gateway 0.040 0.040 NCE-1000 Network Card Ethernet 0.050 0.050 NCF-1000 Network Card Fiber 0.095 0.095 **REQUIRED IF USING NOHMI PROTOCOL SLC DEVICES (Maximum current draw on P-Link limited to 1 Amp) P-LINK Standby: 0.016 P-LINK Alarm: 0.023 *Only enter quantity if PLINK power is being used to power devices DevicesSLC AFC / ARC ifIPA Series 1 PAD100-PD Analog Photo Smoke 0.000300 0.000300 0.000300 0.000300 PAD100-PHD Analog Photo Smoke/Heat 0.000300 0.000300 4 PAD100-HD Analog Fixed Temp Heat 0.000300 0.001200 0.000300 0.001200 PAD100-CD Analog Carbon Monoxide Detector 0.000300 0.000300 PAD100-DUCT Addressable Duct Detector 0.000300 0.000300 PAD100-DRTS Duct Remote Test Switch 0.010000 0.015000 PAD100-DUCTR* Addressable Duct Detector w/Relay 0.000500 0.000500 PAD100-PSSA/PSDA Addressable Pull Station Single/Dual Action 0.000200 0.000200 PAD100-MIM Micro Input Module 0.000200 0.000200 PAD100-SIM Single Input Module 0.000240 0.000240 PAD100-DIM Dual Input Module 0.000240 0.000240 PAD100-RM Relay Module 0.000240 0.000240 PAD100-OR01 One Relay One Input Module 0.000240 0.000240 PAD100-TRTI Two Relay Two Input Module 0.000240 0.000240 PAD100-ZM* Conventional Zone Module 0.000240 0.000240 PAD100-NAC* Notification Appliance Circuit 0.000200 0.000200 PAD100-SM Speaker Module 0.000240 0.000240 PAD100-IM Isolator Module 0.000150 0.000150 PAD100-LED LED Module 0.000240 0.000240 PAD100-LEDK Addressable LED w/ Key Switch 0.000200 0.000200 PAD100-SB* Addressable Sounder Base 0.000200 0.000200 PAD100-LFSB* Addressable Low Frequency Sounder Base 0.000200 0.000200 PAD100-RB* Addressable Relay Base 0.000200 0.000200 PAD100-IB Addressable Isolator Base 0.000150 0.000150 PFC-6000 / P Series PSA Analog Photo Smoke 0.000325 0.000325 PSHA Analog Photo Smoke/Heat 0.000325 0.000325 RHA Analog Rate of Rise Heat 0.000325 0.000325 FHA Analog Fixed Temp Heat 0.000325 0.000325 DDA Addressable Duct Detector 0.000325 0.000325 APS-SA/APS-DA MCM SCM-4 DCM-4 TRM-4 CIZM-4 * MOM-4 * B * B * is*Signal (C)2017 /IB/SCl/AIB Class B ** Addressable Pull Station Single/Dual Action Mini Contact Input Module Single Contact Input Module Dual Contact Input Module Twin Relay Output Module Conventional Zone Input Mod Monitored Output Module Detector Base w/Relay Detector Base w/Sounder Short Circuit Isolator (Class A) Detector Base w/Isolator (Class A) Current Draw from Install Manual SLC Loop Alarm LED Current 0.000325 0.000325 0.000325 0.000325 0.000325 0.000325 0.000325 0.000325 0.000325 0.00PAA 0.000325 0 0.000000 0.000000 0.000325 0.000325 0.001000 0.001000 0.001000 0.001000 0.001000 0.000325 0.000325 0.002340 0.002340 0 0.036000 0.036000 4IA * Requires Aux Power (Configure Below) ** See the installation manual for special considerations when installing Al B, SCI devices on Class B loops. SLC Standby: 0.0015M SLC Alarm: 0.037500 1 Notification NAC 1 0.00000 0.73400 2 Notification NAC 2 0.00000 0.79000 NAC Standby: 0.00000 NAC Alarm: 1.52400 1 2 0.00000 0.00000 0.00000 0.00000 1/0 Standby: 0.00000 1/0 Alarm: 0.00000 Battery Calculation Summary Standby (amps) Alarm Panel Current: 0.13000 (amps) 0.22000 P-Link Current: 0.01600 0.02300 SLC Device Current: 0.00150 0.03750 NAC Circuit Current: 0.00000 1.52400 1/0 Circuit Current: 0.00000 0.00000 SLC Loop Type: Class B Total Standby: - Total Alarm: - Device Addresses Used: - Standby Hours: 24 Alarm Mins: 5 Device Addresses Available: 60 AH Required: 3.54 AH Required: 0.26 Total Combined Standby & Alarm AmpHours Required: 3.70 Efficiency Factor: 20% Required Battery AmpHours: 4.44 Battery AmpHours Provided: Note: The cabinet will house two 8 AH or I8 AH batteries. The charging circuit is rated far up to two ss AH batteries. Approved by Fire 12/13/2021 AFM l,_'F�'tterer tKn oxkeybox required ox standard attached QPOTTFR NAC Circuit Configuration & Voltage Drop Mike's Plumbing 1112312021 Usage: � Notification Description: Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amp Volts @ EOL Min Volts Req'd 1 Lookup Type Horn Strobes vices Circuit DeQty Potter H - 4-WP, H LP- 4-WP 75c , Hi Standby (amps) Alarm (amps) 0.000000 0.000000 0.198000 Total 0.198000 1 Horn Strobes Potter CHS-24, 115cd, Hi db 0.000000 0.000000 0.313000 0.313000 1 Horn Strobes Potter CHS-24, 75cd, Hi c1b 0.000000 0.000000 0.223000 0.223000 User can add devices on the fly to these bottom 5 rows (No lookup function) Total Standby: Total Alarm: Usage: � Notification 7 .- Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amp Volts @ EOL Min Volts Req'd . 2 Horn Strobes Devices Potter CHS-24, 75c , Hi CIb 0.000000 0.000000 0.223000 Total 0.446000 1 Horn Strobes Potter CHS-24, 150cd, Hi db 0.000000 0.000000 0.344000 0.344000 User can add devices on the fly to these bottom 5 rows No lookup unction Total Standby: imomi Total Alarm: (DPOTTER 1/0 Circuit Configuration & Voltage Drop Mike's Plumbing 1112312021 usage: F_ Description: Wire Type Ohms/1000ftIIIIIIIIIIIIIIIIIIIII�ngth 1-Way Actual Ohms Max Load (amp Volts @ EOL Min Volts Req'd City Lookup Type Circuit Devices 11111W Standby (amps) Each Alarm (amps) Total Each Total User can add devices on the fly ---- to these bottom 5 rows ---- Description: in Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amp Volts @ EOL Min Volts Req'd Qty Lookup Type Circuit Devices Description Standby (amps) Each Alarm (amps) Total Each Total User can add devices on the fly to these bottom 5 rows (No lookup function) ---- Total Standby: LEM= CTRL. UNIT ANNUNCIATION NOTIFICATION C COP`�O \�C) 5 O�GP O�PO�P� \gyp `.) J\c� OJ \O�Q OAP G,O� OQ��O ��C� `�O ��'� �JQ JR �05 JAG'GP �O J`' '�O OG' �. Qt` JQ�OJ�O��OGJP� O� O O�P�� JP JP JP JP JP JP JP JP �P PGA PGA PGA PGA PGA PGA PGA PGA O��e ,`�3',��P,`�P SYSTEM INPUTS A B C D E F G H I J K L M N 1 SMOKE SENSOR/DETECTOR • • 1 • • o 2 MANUAL PULL STATION • • • • • • 3 HEAT SENSOR/DETECTOR • • • • • • 4 KITCHEN HOOD SUPPRESSION SYSTEM • • • • • 5 SPRINKLER WATERFLOW SWITCH • • • • • • 6 SPRINKLER VALVE SUPERVISORY SWITCH • • • • • 7 8 FIRE ALARM AC POWER FAILURE • • • • 9 FIRE ALARM SYSTEM LOW BATTERY • • • • 10 OPEN CIRCUIT OR GROUND FAULT • • • • 11 CLASS B NOTIFICATION CIRCUIT (NAC) - SHORT • • • • 12 FIRE ALARM MATRIX F I R2021-0138 RECEIVED Dec 06 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT W W U SYSTEM DESIGN REVIEWED BY: DESIGNER OF RECORD Howard Williamson NICET IV NICET # 82289 Froula Alarm Systems, Inc. 861 Industry Drive Tukwila, Washington 98188 Phone:206-575-1962 Fax:206-575-8168 HowardW@froulaalarms.com J W co U_ 6 M C W V z .z _�O �-- co V W Z W VJ InnJ V ) w oZ O G r C- O G N W Cl W F- 0 Z CO Q LLI J Q U W W Z 0 to W 0 2 LL Ib W H LL a 0 N p04 o N N O ao 04 00 Q s_ X O j � W U i 0M � 00 LO Ca 00 Cq N �Q�� U00 to : o (0 U) 0O 00 LL N W � FAO. 1 i F II / N MIKE'S PLUMBING FIRE ALARM - TI SCALE: 3/6" = 1'-0" ,S LEGEND DEVICE QUANTITY DEVICE DESCRIPTION MOUNTING FACP I FIRE ALARM CONTROL PANEL POTTER INCLUDED MODEL: IPA -CEO GSM I COMMUNICATOR WIRELESGSM NAPCO INCLUDED LTES MODEL: SLE-LTE I SMOKE DETECTOR POTTER 4SQ. W I GANG O MODEL: PAD200-PD MUDRING ® 4 HEAT DETECTOR POTTER 4SQ. W I GANG MODEL: PADIOO-HD MUDRING 5 CEILING MOUNTED HORN/STROBE (WHITE) POTTER 4SQ. W I GANG MODEL: CHS-24W MUDRING WALL MOUNTED WEATHERPROOF HORN/STROBE (RED) POTTER � W I MODEL: HS-24WR-WP INCLUDED M = DATA LOOP TWISTED PAIR #16 GAUGE WIRE 0 A = SLC DATA 18/2 FPLP z w w B = NAC CIRCUIT 14/2 FPLP J w X = ZONE CIRCUIT TWISTED PAIR #16 GAUGE WIRE \ S S = SPEAKER CIRCUIT PAIR # 14 GAUGE WIRE R = RELAY CIRCUIT TWISTED PAIR #16 GAUGE WIRE SUBSCRIPT E = EXISTING WP = WEATHER PROOF MOUNT C = CEILING MOUNT R = RELOCATE EXISTING CD = CANDELA SCOPE OF WORK: 1) INSTALL NEW FIRE ALARM SYSTEM. GENERAL NOTES: 1. ALL CEILING HEIGHTS ARE 16' OR LOWER AFF. 2C DEDICATED 120VAC PROJECT SITE NEW WORK RISER DIAGRAM: 21M St SW .. _. 21'HlStSW �qw 1.SJ�SI.W F N<\\ �► P ROJ E O WE © 2021 Microsoft Corporation © 2021 TornTorn q 1 frt, I RECEIVED CT SITE UAR021 DS DEVELOPMENT SERVICES DEPARTMENT J O �U) Q w O 2 LL O 0 U LU 0 U) Q J Q W 0� LL wLU T 0 SYSTEM DESIGN REVIEWED BY. DESIGNER OF RECORD Howard Williamson NICET IV NICET # 82289 Froula Alarm Systems, Inc. 861 Industry Drive Tukwila, Washington 98188 Phone:206-575-1962 Fax:206-575-8168 HowardW@froulaalarms.com 75 Q J W co — U— 6 M C W V Z .z —�O �-- co V W 75 L Z) Z W VJ J / Q In Q U) o � LLJ Z o � 0 G N W 0 LIJ I- O z C0 Q LLI J Q U 0 LU Z 0 U) LU 0 2 LL m w LL a 0 a N O N N O 00 � 00 � Q O X j00 M CO U L 0 M � DD LO Ca 00 Cq N �Q�� U00 U) Q `►J 00 0000 � CU LL 2 w 1 FA1.0