1574_001)� 1 ; 4 I N 111111111 ...� FIRE PROTECTION BUREAU —PLAN REVIEW PO Box 42642 5 No 11111111111116, Olympia WA 98504-2642 (360) 596-3900 FAX: (360) 596-3934 War CONTRACTORS' MATERIALS AND TEST CERTIFICATE FOR PRIVATE FIRE SERVICE MAINS PROCEDURE Upon completion of work, inspection and test shall be made by the contractor's representative and witnessed by an owner's representative. All defects shall be corrected and system left in service before contractors personnel finally leave the job. A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners, and contractor. It is understood the owners representative's signature in no way prejudices any claim against contractor for faulty material, poor workmanship,or failure to comply with approving authority's re uiremenIS or local ordinances. PROPERTY NAME DATE Dougs Lynnwood Hyundai 19/28/2020 PROPERTY ADDRESS 22130 WA-99 ACCEPTED BY APPROVING AUTHORITIES (NAMES) City of Edmonds ADDRESS PLANS 121 5th Ave N. Edmonds, WA. 98020 INSTALLATION CONFORMS TO ACCEPTED PLANS ❑✓ YES ONO EQUIPMENT USED IS APPROVED [DYES ❑ NO IF NO, STATE DEVIATIONS: HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION OF CONTROL VALVES AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT? (DYES ❑ NO INSTRUCTIONS IF NO, EXPLAIN: SUPPLIES BUILDINGS Yes LOCATION PIPE TYPES AND CLASS 6" DI Class 52 TYPE JOINT Tyton Joint PIPE CONFORMS TO City of Edmonds STANDARD ❑ YES ❑ NO FITTINGS CONFORM TO City of Edmonds STANDARD [D YES ❑ NO IF NO, EXPLAIN: PIPES AND JOINTS BURIED JOINTS NEEDING ANCHORAGE CLAMPED, STRAPPED OR BLOCKED IN ACCORDANCE WITH City of Edmonds STANDARD ❑✓ YES ❑ NO IF NO, EXPLAIN FLUSHING: Flow the required rate until water is dear as indicated by no collection of foreign material in burlap bags at outlets such as hydrants and blow -offs. Flush at flows not less than 390 gpm (1476 Umin) for 4-inch pipe, 610 gpm (2309 Umin) for 5-inch pipe, 8W gpm (3331 Umin) for 6-inch pipe, 1560 gpm (5905 Unim) for 8-inch pipe, 2440 gpm (9235 Umin) for 10-inch pipe, and 3520 gpm (13323 Umin) for 12-inch pipe. When supply cannot produce stipulated flow rate, obtain maximum available. TEST HYDROSTATIC- Hydrostatic tests shall be made at not less than 200 psi (13.8 bars) for two hours or 50 psi (3.4 bars) above static pressure in DESCRIPTION excess of 150 psi (10.3 bars) for two hours. LEAKAGE: New pipe laid with rubber gasketed joints shall, if the workmanship is satisfactory, have little or no leakage at the joints. The amount of leakage at the joints shall not exceed 2 qts. per hr. (1.89 Uh) per 100 joints, irrespective of pipe diameter_ The amount of allowable leakage spedW above may be increased by 14 oz_ per in. valve diameter per Iv. (30 mL125 mmfh) for each metal -seated valve isolating the test section. If dry barrel hydrants are tested with We main valve open so the hydrants are under pressure, an additional 5 oz- per minute (150 mL/min) leakage is pennitted for each hydrant NEW PIPING FLUSHED ACCORDING TO City of Edmond STANDARD BY Grade Inc. (company) a YES ❑ NO IF NO, EXPLAIN: HOW FLUSHING FLOW WAS OBTAINED THROUGH WHAT TYPE OPENING: ✓❑ PUBLIC WATER ❑✓ HYDRANT BUTT ❑ TANK OR RESERVOIR ❑ OPEN PIPE FLUSHING TESTS ❑ FIRE PUMP LEAD-INS FLUSHED ACCORDING TO STANDARD 0 YES ❑ NO HOW FLUSHING FLOW WAS OBTAINED- THROUGH WHAT TYPE OPENING ❑✓ PUBLIC WATER ❑ Y CONNECTION TO FLANGE & SPIGOT ❑ TANK OR RESERVOIR ❑✓ OPEN PIPE FIRE PUMP 3000-420-242 (R 8/15) Page 1 JOINT COVERED HYDROSTATIC TEST ALL NEW PIPING HYDROSTATICALLY TESTED AT 2550 PSI FOR 2 ALL HOURS ❑✓ YES ❑ NO TOTAL AMOUNT OF LEAKAGE MEASURE 0 2 LEAKAGE NO LEAKAGE ALLOWED FOR VISIBLE JOINTS GALS. HOURS TEST ALLOWABLE LEAKAGE (BURIED) 0 2 NO LEAKAGE ALLOWED FOR VISIBLE JOINTS GALS. HOURS NUMBER INSTALLED TYPE AND MAKE ALL OPERATED SATISFACTORILY HYDRANTS 0 N/A ❑ YES ❑ NO WATER CONTROL VALVES LEFT WIDE OPEN ❑✓ YES ❑ NO IF NO, STATE REASON: CONTROL VALVES HOSE THREADS OF FIRE DEPARTMENT CONNECTION AND HYDRANTS INTERCHANGEABLE WITH THOSE YES ❑ NO OF FIRE DEPARTMENT ANSWERING ALARM DATE LEFT IN SERVICE 9/28/2020 REMARKS ADDITIONAL COMMENTS NAME OF INSTALLING CONTRACTOR Grade Inc. TESTS WITNESSED BY SIGNATURES FOR PROPERTY OWNER (SIGNED) TITLE DATE FO I ALLING CONTRACTOR (SIGNED) TITLE DATE Presideint 9/28/2020 t. ADDITIONAL EXPLANMhON AND N ......................... . . ' WASHINGTON STATE ' CERTIFICATE OF COMPETENCY FIRE PROTECTION SPRINKLER SYSTEMS ; Krep P. Oveson 4909-0519-D Level try ; c. 'A 1Z1p4 ....,....,................. 3000-420-242 (R 8/15) Page 2