BLD2022-0441_Manufacturer_Specifications_and_Installation_Instructions_3.29.2022_1.41.16_PM_2768285A
ELECTRICAL DATA
UNIT SIZE -
SERIES
(VOLTAGE)
V/PH
OPER VOLTS*
COMPR
FAN
MCA
MAX FUSE** or
CKT BRK AMPS
MAX
MIN
LRA
RLA
FLA
j 018-A (N)
208/230/1
253
197
56.3
9.0
0.50
11.8
20
024-A (N)
62.9
10.9
0.50
14.1
25
030-A N
73.0
14.1
0.70
18.3
30
036-A (N)
77.0
14.1
1.20
18.8
30
048-A (N)
124.0
18.5
1.20
24.3
40
060-A (N)
152.5
23.7
1.45
31.1
50
036-A (P)
208/230/3
253
197
71.0
9.0
1.20
12.5
20
048-A (P)
83.1
13.7
1.20
18.3
30
060-A (P)
110.0
15.9
I 1.45
21.4
35
036-A (E)
460/3
506
414
38.0
5.6
0.60
7.6
15
048-A (E)
41.0
6.2
0.60
8.4
15
060-A (E
5i .
7.1
0.80
1 9.7
115
LEGEND:
FLA - Full Load Amps
HACR - Heating, Air Conditioning, Refrigeration
LRA - Locked Rotor Amps
NEC - National Electrical Code
RLA - Rated Load Amps (compressor)
* Permissible limits of the voltage range at which the unit will operate satisfactorily
** Time -Delay fuse.
Complies with 2007 requirements of ASHRAE Standards 90.1
A -WEIGHTED SOUND POWER (dBA)
Standard
Unit Size Rating
(dBA)
18 69
24 66
30 j 68
36
71
48
70
60
73
Typical Octave Band Spectrum (dBA, without tone adjustment)
125
250
500
1000
2000
4000
8000
50.5
57.0
59.5
64.5
60.5
53.5
43.0
50.5
58.5
60.5
59.5
56.5
51.0
41.5
55.5
59.5
61.5
63.5
60.0
58.0
49.5
59.5
59.5
62.0
65.5
63.5
62.0
55.0
57.5
59.5
64.0
66.0
63.0
60.5
54.5
60.0
61.5
64.5
67.0
66.0
65.5
58.0
NOTE: Tested in accordance with AHRI Standard 270-08 (not listed in AHRI.
A -WEIGHTED SOUND POWER (dBA) WITH ACCESSORY SOUND SHIELD
Unit Size
Standard
Rating
(dBA)
Typical Octave Band Spectrum (dBA, without tone adjustment)
125
250
500
1000
2000
4000
8000
18
68
52.5
58.0
58.5
64.5
59.5
52.5
42.5
24
65
54.5
57.5
59.5
59.0
56.0
50.5
40.5
30
68
55.0
60.0
61.5
62.5
60.0
58.0
49.5
36
71
59.5
59.5
62.5
65.0
63.0
61.5
55.0
48
70
57.5
59.5
63.0
1 65.0
62.5
60.0
54.0
60
73
61.0
62.0
64.0
67.0
65.5
65.5
57.5
NOTES:
Tested in accordance with AHRI Standard 270-08 (not listed in AHRI).
Accessory sound shield will not accommodate unit sizes 18 and 24.
CHARGING SUBCOOLING (TXV-TYPE EXPANSION DEVICE)
UNIT SIZE -SERIES
REQUIRED SUBCOOLING ° F ° C
18
12(6.7)
24
12(6.7)
30
12(6.7)
36
8(4.4)
48
12(6.7)
60
10(5.6)
DIMENSIONS - ENGLISH
A
00
n
o
c%l
>t = rE5
O=NO
C.4
m
N
ap
C
N
N
MINIMUM
UNIT SIZE
MOUNTING PAD
DIMENSIONS
18,24
il' % 42'
30.36.48,60
24, N 50,
m
1 CLEARANCE REOUIREMENTS• SINGLE UNIT APPLICATIONS' WITH COIL FACING WALL: ALLOW 6 IN. MINIMUM CLEARANCE
ON COIL SIDE AND COIL END AND 20 IN MINIMUM CLEARANCE ON FAN SIDE WITH FAIL FACING WALL ALLOW 8 IN
MINIMUM CLEARANCE ON FAN SIDE AND 6 IN ON COIL END AND 20 IN MINIMUM CLEARANCE ON COIL '111
MULTI - UNIT APPLICATIONS: ALLOW 24 IN ON
CLEARANCE BETWEEN FAN AND COIL SIDES OF MOLTIHEE UNITS
ARRANGE UNITS 50 DISCHARGE OF ONE DOES NUT LNIER [MEET OF ANOTHER WHEN TWO UNITS ARE 1NCIALLED END TO END
WITH THE COIL ENDS FACING EACH OTHER ALLOW 12 IN MINIMUM CLEARANCE BETWEEN UNITS
C OMPRESSOA ENU SEA4ICE CLEARANCE: ALLOW 24 IN MINIMUM CLEARANCE ON COMPRESSOR ENU W'H EN UNITS ARE STACKED OR
IERE IS LESS THAN 40 IN OF CLEARANCE ABOVE THE TOP OF THE UNIT IF fHI RE IS 40 IN CLEARANCE ABOVE UN
AND
THE TOP PANEL IS ACCESSIBLE FOR REMOVAL ALLOW B IN. MINIMUM CLEARANCE ON COMPRESSOR END FOR ;ERVICE.
IMPORIANI: WHEN INSTALLING SINGLE OR 14ULTIFEE UNITS IN AN ALCOVE. ROOF WELL. OR PARIIALLY ENCLOSED AREA.
EN`.URE THERE IS ADEOUATE VENTILATION TO PREVENI RLCI RC UL AT I ON OF DISCHARGE AIR.
2 MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING
1 l2" MODE IS 55�F, MAX. 125'F.
3. SEHIES DESIGNATION IS THE 13TH POLITION OF THE
UNIT MODEL NUMBER.
4. CENIEN OF GRAVITY
4 3/16" 5. ALL DIMENSIONS ARE 1N "INCHES" UNLESS NOTED.
FIELD CONTROL SUPPL
'IRE ENTRY
7ld" HOLE W/GROMMET
—OM VAPOR LINE CONN.
FEMALE SWEAT CONN.
--03/E" LIOUID LINE
FEMALE SWEAT CONN
/—TfELD POWER SUPPLY CONN.
%HOLE SIZES PH OVIDED:
/&" HOLE WITH
0 I 1/6" KNOC KOUI AND
IONS 0 1 3/E" KNOCKOUT
1 7/1D"
w