APPROVED FIR FIR2021-0124+Fire_Sprinkler_Plan+11.9.2021_7.07.37_PM+2512075GENERAL NOTES AND DETAILS
NOT TO SCALE
SCOPE OF WORK
FIRE PROTECTION DESIGN AND INSTALL A COMPLETE FIRE PROTECTION
SYSTEM BASED ON NFPA 13D ED.2013.
DESIGN CRITERIA
PROVIDE A WET SYSTEM WITH A MINIMUM DENSITY OF 0.05 GPM/SQ.FT. IN
THE TWO MOST HYDRAULIC REMOTE SPRINKLERS USING STANDARD
RESPONSE SPRINKLERS 155-F & 1757F TEMP.1/2- NPT, K-4.9 FACTOR,
RESIDENTIAL CONCEALED STYLE.
16' SPACING MAXIMUM, 256 FT' MAXIMUM PER HEAD, HEADS AREA TO BE
LOCATED NO FURTHER THAN 8 FT FROM ANY WALL AND NO CLOSER THAN
8 FT BETWEEN SPRINKLERS.
WATER SUPPLY
PRIMARY: CITY WATER SUPPLY
STATIC PSI 70
RESIDUAL: 35 GPM AT 70 PSI
DESIGN NOTES
1. SPRINKLER DEFLECTOR AND LOCATIONS SHALL BE DESIGNED IN
ACCORDANCE TO NFPA 13D-2013 AND MANUFACTURERS LISTING.
2. ALL HANGER ASSEMBLIES TO BE INSTALLED IN ACCORDANCE WITH NFPA
13D-2013 AND MANUFACTURERS LISTING.
3. CPVC PIPE AND FITTINGS FOR ALL AREAS, SHALL BE INSTALLED PER
THE MANUFACTURERS LISTING. THIS INCLUDES HANGING, METHONDS OF
RESTRAINT, BRACING, VERTICAL RESTRAINT, THERMAL EXPANSION,
CONCEALMENT.
4. EACH SYSTEM SHALL BE INSTALL WITH A WATERFLOW AND AUTIBLE
LOCAL ALARM.
5. EACH SPRINKLER SYSTEM SHALL HAVE A MINIMUM V DRAIN ON THE
SYSTEM SIDE OF THE CONTROL VALVE.
6. TEST CONNECTIONS SHALL BE INSTALLED AT LOCATIONS THAT ALLOW
FLOW TESTING OF WATER, SHALL CONTAIN A K-FACTOR EQUAL TO OR
SMALLER THAN THE SMALLEST SPRINKLER K-FACTOR INSTALLED IN THE
SYSTEM.
7. OBSTRUCTIONS TO RESIDENTIAL SPRINKLERS SHALL BE ACCORDANCE
WITH NFPA 13D-2013 SECTION 8.2.5.
8. UNDERGROUND PIPE, ANY TYPE OF PIPE OR TUBE ACCEPTABLE UNDER
THE APPLICABLE PLUMBING CODE FOR UNDERGROUND SUPPLY PIPE
SHALL BE ACCEPTABLE AS AN UNDERGROUND SUPPLY FOR A FIRE
SPRINKLER SYSTEM.
9. ALL MATERIALS TO BE INSTALLED SHALL BE UL LISTED.
10. IT IS THE OWNER'S RESPONSIBILITY TO ENSURE THAT THE STRUCTURE
SHOWN ON THE CONTRACT DRAWINGS CAN ADEQUATELY SUPPORT ALL
FIRE SPRINKLER PIPE AND SEISMIC LOADS.
11. IS THE OWNER'S RESPONSIBILITY FOR MAINTAINING TEMPERATURES
ABOVE 40 DEGREES TO PROTECT THE WET FIRE SPRINKLER SYSTEM
FROM FREEZING.
12. ALL WIRING OF FIRE PROTECTION SYSTEM COMPONENTES TO BE DONDE
BY OTHERS.
13. ALL PIPE AND COMPONENTES TO BE TESTED, INSPECTED AND
MAINTENANCE IN ACCORDANCE WITH NFPA 13D, 13 OR 25.
POSITIONING OF SPRINKLER TO AVOID OBSTRUCTION AGAINST WALLS
RESIDENTIAL UPRIGHT AND PENDENT SPRINKLERS
POSITIONING OF SPRINKLER TO AVOID OBSTRUCTION DISCHARGE
RESIDENTIAL UPRIGHT AND PENDENT SPRINKLERS
Celing
on
A
See Table 8.2.5.3.2 NFPA 13D - 2019
HANGER NOTES
HANGERS AND STRAPS SHALL NOT COMPRESS, DISTORT, CUT OR ABRADE THE PIPING AND SHALL
ALLOW FOR FREE MOVEMENT OF THE PIPE TO COMPENSATE THERMAL EXPANSION AND CONTRACTION
OF CPVC PIPE AND FITTINGS.
INSTALLATION SHALL BE IN ACCORDANCE WITH MANUFACTURER LISTING THAT INCLUDES DISTANCE
BETWEEN HANGERS AND LOADS.
HANGER DETAILS
angerNo.1—
Olhet Pipe Herger
rrrri rrrr rrrr
rrrrr rrrrrrrrr
HANGER TYPICAL INSTALLATION DETAILS
HeHp 11 & .1aW
stomp
9PwwA
i(�) wae.0
O
Hunorn.mnln.r
sple.r
as
Horpar and Raatraint
Application
STANDARD SUPPORT SPACING
MAXIMUM DISTANCE BETWEEN HANGER (Fr -IN
IA11eNY
792E
1
1 1 4
1 I P
rn1c
5- e
I a -o 1 e - a
T-p
a -o
TABLE A - MAXIMUM SUPPORT SPACING TABLE B - MAXIMUM SUPPORT SPACING
DISTANCE IN LINE SPRINKLER HEAD DROP DISTANCE END SPRINKLER HEAD DROP
TEE OR TWO POINTS OF RESTRAINT (R) ELBOW OR ONE POINT OF RESTRAINT (R)
12P4-1101W1 am
WE N
Lee 7"'00 PA
LM TW1100 P9
0/4
4'
r
1
r
e
1 1/4
r
r
1 1/2 - e
r
Y
VIKING RESIDENTIAL CONCEALED
PENDENT SPRINKLER K-4.9
R
1�MAX.
ANY DISTANCE
OPVC - Whi !=
PPE (N)
LOS itetl 100 Pel
TINE TIVI 100 PSI
y4
r
r
1
tr
r
1 1/4
1r
tr
1 1/2 -J
x'
tr
�Itttt��tttt� �IIII�Itttta
11-23-2021
PLAN REVIEW
NOTES: Approved with condition
1. Valve at riser to shut off both
fire and domestic water supply.
DFM Burt
INSULATION RECOMENDATIONS FOR MORE OPTIONS SEE
NFPA 13D SECTIONS A9.1.1 (a) - (f)
Caution-: It is importante that the
insulation be installed tight against the
joist. In unheated areas, any spaces or
voids between the insulation and the joist
causes the water in the fire sprinkler
piping to freeze
NFPA 13D - FIGURE A.9.1.1 (a) INSULATION RECOMMENDATIOS
RISER CPVC ASSEMBLY
CPVC RISER SHALL NOT BE EXPOSED
1
TO SPRINKLER SYSTEM
STAND ALONE TYPE
INSPECTOR, TEST
AND DRAIN VALVE
Unheated FLOW SWITCH
Blown -in attic
insulatlo space
1" BACK FLOW
PREVENTER
� l
Tenting material Tent' spacqq keeping_
insulation dbove piping
DOMWTIC WATER
FI•
/ SYSTEM
TEED 22MjwnC WATER SHUT
Heated OFF VALVE
space
TO WATER METER AND
CITY CONNECTION
NFPA 13D - FIGURE A.9.1.1 (f) INSULATION RECOMMENDATIOS , I , I I I I ,
ALL RISER ASSEMBLIES SHALL BE ENCLOSED IN A WALL /
BUILD UP WITH EASY ACCESS AND WITH AND APPROVED
ACCESS DOOR, UNLESS OTHERWISE APPROVED BY THE
FIRE DEPARTMENT.
CPVC RISER SUPPORT NOTES
RISERS SHALL BE SUPPORTED BY PIPE CLAMPS OR BY
HANGERS LOCATED ON THE HORIZONTAL CONNECTION
CLOSE TO THE RISER.
ONLY LISTED HANGERS AND CLAMPS SHALL BE USED.
VERTICAL LINES MUST BE SUPPORTED AT INTERVALS TO
AVOID PLACING EXCESSIVE LOAD ON ANY FITTING AT THE
LOWER END OF THE RISER.
VERTICAL PIPING SHALL BE SUPPORTED AT EACH FLOOR
OR AT 10 FT INTERVALS, WHICHEVER IS LESS, SUPPORT
CAN BE ACHIEVED BY USING RISER CLAMPS OR DOUBLE
BOLT PIPE CLAMPS LISTED FOR THIS SERVICE. DO NOT
USE RISER CLAMPS WHICH SQUEEZE THE PIPE OR DEPEND
ON COMPRESSION FOR SUPPORT.
1.Approved set of plans must be on site at the time of inspection.
Failure to provide the approved set may result in a re -inspection
fee. System drain(s) required at riser and must drain to the
exterior. If riser is above lowest grade, 2nd drain required and
signage at riser indicating location. Systems require signage IAW
NFPA 13D.
2.Coverage required to the following areas: Clothes closets, linen
closets and pantries exceeding 24 square feet in area, with the
smallest dimension greater the 3' and having wall and ceiling
surfaces of gypsum board. Bathrooms more than 55 square feet
in area. When fuel fired equipment is present on covered decks or
porches, or if living space above, at least one quick -response
intermediate temperature sprinkler shall be installed above the
equipment or area under living space. All fuel fired appliances,
except attics if above all living areas.
3.Residential 13R add: Vertical back flow preventer must be
tested annually. Strongly recommend system be monitored by fire
alarm
FI R2021-0124
CONDITION: Install shut
off valve so that both
systems are shut off
simultaneous.
RECEIVE'
Nov 10 2021
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
DESIGNER LOGO Q,_..SPACE FOR SEAL/STAMP REVISIONS
�... 1 M FIRE PROTECTION LCC SPRINKLER DISTRIBUTION
............... . . . . . . N0. DESCRIPTION DATE
A 1007G FOR REVISION 11 OB 21
6O20607 94TH AVE EAST a.`:. E'o:aP`�K�E:a.a=a 7615 201 ST ST SW CONTRACT GRAHAM, WA 98338 ; Byron Ranfferi Morales -Mora NC , CONROVAL NO
40M Fire 209-AG Level, _ EDMONDS, WA 98026 APPROVAL /IAA � '/ K 7�6 ' M Fire Protection System, LLC DRAWN 8Y IOC
MFIREFP810B 11-8-21
sm=n iaeu, singe sdunaa � "' SCALE INDICTED
253-315-9266 ' sie. .• DATE NOV/08/2021
M.E. FRANCISCO GUZMAN FIRE PROTECTION SYSTEMS LLC r �$ SHEET No.1 FPS02
SPRINKLER DISTRIBUTION - FIRTS FOOR PLAN
1 /4" = 1 r—Orr NORTH
DESIGNER LOGO
. eo
sm,n is �, s-mpisowno:
M.E. FRANCISCO GUZMAN FIRE PROTECTION SYSTEMS LLC
M FIRE PROTECTION LCC
20607 94TH AVE EAST
GRAHAM, WA 98338
r r� 253-315-9266
PEX
M
PEX
�I ll
6" CITY WATER MAIN Z
UNDERGROUND PIPE DISTRIBUTION
1 /8" = 1 r-0"
SPACE FOR SEAL/STAMP
Byron Ranlferi Morales -Mora
. 2901-0209-AG Level
' M Fire Protection System, LLC
MFFII�R,E,F��P810B 11 88AL 0 -21
DESIGN CRITERIA
PROVIDE A WET SYSTEM WITH A MINIMUM DENSITY OF 0.05 GPM/SQ.FT. IN THE TWO MOST HYDRAULIC
REMOTE SPRINKLERS USING STANDARD RESPONSE SPRINKLERS 155-F & 175-F TEMP.1/2" NPT, K-4.9
FACTOR, RESIDENTIAL, CONCEALED AND RECESSED STYLE. 16' SPACING MAXIMUM, 256 FT' MAXIMUM PER
HEAD, HEADS AREA TO BE LOCATED NO FURTHER THAN 8 FT FROM ANY WALL AND NO CLOSER THAN 8
FT BETWEEN SPRINKLERS. HYDRAULICALLY DESIGNED WITH TWO HEADS FLOWING.
1. SPRINKLER SHALL NOT BE REQUIRED IN ATTICS, CONCEALED SPACES DEDICATED EXCLUSIVELY TO AND
CONTAINING ONLY DWELLING UNIT VENTILATION EQUIPMENT, FLOOR/CEILING SPACES, CRAWL SPACES,
AND OTHER CONCEALED SPACES THAT ARE NOT USED OR INTENDED FOR LIVING PURPOSES.
2. MECHANICAL CLOSETS SMALLER THAN 400FT' , PENDENT, UPRIGHT AND SIDEWALL RESIDENTIAL
SPRINKLER SHALL BE PERMITTED TO BE INSTALLED IN EITHER OF THE FOLLOWING SITUATIONS:
- WITHIN 18 IN OF THE CEILING TO AVOID OBSTRUCTIONS NEAR THE CEILING WHERE THE COMPARTMENT
IS ENCLOSED BY WALL AND A DOOR.
- AT THE HIGHEST CEILING LEVEL WITHOUT REGARD TO OBSTRUCTIONS OR MINIMUM DISTANCES TO
WALL.
3. PENDENT SPRINKLERS NO CLOSER THAN 3 FEET OF THE CENTER OF A CEILING FAN.
4. UNDERGROUND PIPE COVER MINIMUM OF 24 INCHES.
HYDRAULIC INFORMATION
AREA PER SPRINKLER 256 SO. FT. MAX 1
CALCULATED AREA
512
SQ.FT.
DENSITY
0.054
GPM/SQ.FT.
SPRINKLERS CALCULATED
2
SPRINKLER FLOW
27.8
GPM
WATER REQUIRED
27.8
GPM
RQ'D PRESSURE
22.6
PSI
AVL PRESSURE AND FLOW
40.4 ® 28
PSI ® GPM
CUSHION PRESSURE 1 17.7
WATER SUPPLY
PRIMARY: CITY WATER SUPPLY
STATIC PSI 70
RESIDUAL: 35 GPM AT 70 PSI
SYMBOLOGY
SPRINKLER
PIPE CPVC
e
CPVC RISER
ASSEMBLY
9=
10" ALARM BELL
®
RESIDENTIAL SPRINKLER
CONCEALED K-4.9 155'F
QOHYDRAULICS
S C'
NODES
Q WATER METER
X DIAMETER [INCHES]
X-X DISTANCE [FEET] -[INCHES]
FIRE SPRINKLER LEGEND
PSI
RECEIVED
Nov 10 2021
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
SYMBOL MANUFACTURER
1_
SIN
TYPE
1.
NPT
1
ORIFICE
_1
K—FACTOR
_
TEMP FINISH
1_ 1
QUANTITY
-
® 1 VIKING
VK494
CONCEALED
PENDENT
1/2"
-
K-4.9
155F WHITE
015
0)
NORTH
7615 201 ST ST SW,
EDMONDS, WA 98026
REVISIONS
TOTAL SPRINKLERS IN THIS PLAN 015
SPRINKLER DISTRIBUTION
DRAWN UY IOC
SCALE INDICATED
DATE NOVIDO12021
SHEET NO. FPSOI