APPROVED FIR FIR2021-0124+Fire_Sprinkler_Plan+11.9.2021_7.07.37_PM+2512075GENERAL NOTES AND DETAILS NOT TO SCALE SCOPE OF WORK FIRE PROTECTION DESIGN AND INSTALL A COMPLETE FIRE PROTECTION SYSTEM BASED ON NFPA 13D ED.2013. DESIGN CRITERIA PROVIDE A WET SYSTEM WITH A MINIMUM DENSITY OF 0.05 GPM/SQ.FT. IN THE TWO MOST HYDRAULIC REMOTE SPRINKLERS USING STANDARD RESPONSE SPRINKLERS 155-F & 1757F TEMP.1/2- NPT, K-4.9 FACTOR, RESIDENTIAL CONCEALED STYLE. 16' SPACING MAXIMUM, 256 FT' MAXIMUM PER HEAD, HEADS AREA TO BE LOCATED NO FURTHER THAN 8 FT FROM ANY WALL AND NO CLOSER THAN 8 FT BETWEEN SPRINKLERS. WATER SUPPLY PRIMARY: CITY WATER SUPPLY STATIC PSI 70 RESIDUAL: 35 GPM AT 70 PSI DESIGN NOTES 1. SPRINKLER DEFLECTOR AND LOCATIONS SHALL BE DESIGNED IN ACCORDANCE TO NFPA 13D-2013 AND MANUFACTURERS LISTING. 2. ALL HANGER ASSEMBLIES TO BE INSTALLED IN ACCORDANCE WITH NFPA 13D-2013 AND MANUFACTURERS LISTING. 3. CPVC PIPE AND FITTINGS FOR ALL AREAS, SHALL BE INSTALLED PER THE MANUFACTURERS LISTING. THIS INCLUDES HANGING, METHONDS OF RESTRAINT, BRACING, VERTICAL RESTRAINT, THERMAL EXPANSION, CONCEALMENT. 4. EACH SYSTEM SHALL BE INSTALL WITH A WATERFLOW AND AUTIBLE LOCAL ALARM. 5. EACH SPRINKLER SYSTEM SHALL HAVE A MINIMUM V DRAIN ON THE SYSTEM SIDE OF THE CONTROL VALVE. 6. TEST CONNECTIONS SHALL BE INSTALLED AT LOCATIONS THAT ALLOW FLOW TESTING OF WATER, SHALL CONTAIN A K-FACTOR EQUAL TO OR SMALLER THAN THE SMALLEST SPRINKLER K-FACTOR INSTALLED IN THE SYSTEM. 7. OBSTRUCTIONS TO RESIDENTIAL SPRINKLERS SHALL BE ACCORDANCE WITH NFPA 13D-2013 SECTION 8.2.5. 8. UNDERGROUND PIPE, ANY TYPE OF PIPE OR TUBE ACCEPTABLE UNDER THE APPLICABLE PLUMBING CODE FOR UNDERGROUND SUPPLY PIPE SHALL BE ACCEPTABLE AS AN UNDERGROUND SUPPLY FOR A FIRE SPRINKLER SYSTEM. 9. ALL MATERIALS TO BE INSTALLED SHALL BE UL LISTED. 10. IT IS THE OWNER'S RESPONSIBILITY TO ENSURE THAT THE STRUCTURE SHOWN ON THE CONTRACT DRAWINGS CAN ADEQUATELY SUPPORT ALL FIRE SPRINKLER PIPE AND SEISMIC LOADS. 11. IS THE OWNER'S RESPONSIBILITY FOR MAINTAINING TEMPERATURES ABOVE 40 DEGREES TO PROTECT THE WET FIRE SPRINKLER SYSTEM FROM FREEZING. 12. ALL WIRING OF FIRE PROTECTION SYSTEM COMPONENTES TO BE DONDE BY OTHERS. 13. ALL PIPE AND COMPONENTES TO BE TESTED, INSPECTED AND MAINTENANCE IN ACCORDANCE WITH NFPA 13D, 13 OR 25. POSITIONING OF SPRINKLER TO AVOID OBSTRUCTION AGAINST WALLS RESIDENTIAL UPRIGHT AND PENDENT SPRINKLERS POSITIONING OF SPRINKLER TO AVOID OBSTRUCTION DISCHARGE RESIDENTIAL UPRIGHT AND PENDENT SPRINKLERS Celing on A See Table 8.2.5.3.2 NFPA 13D - 2019 HANGER NOTES HANGERS AND STRAPS SHALL NOT COMPRESS, DISTORT, CUT OR ABRADE THE PIPING AND SHALL ALLOW FOR FREE MOVEMENT OF THE PIPE TO COMPENSATE THERMAL EXPANSION AND CONTRACTION OF CPVC PIPE AND FITTINGS. INSTALLATION SHALL BE IN ACCORDANCE WITH MANUFACTURER LISTING THAT INCLUDES DISTANCE BETWEEN HANGERS AND LOADS. HANGER DETAILS angerNo.1— Olhet Pipe Herger rrrri rrrr rrrr rrrrr rrrrrrrrr HANGER TYPICAL INSTALLATION DETAILS HeHp 11 & .1aW stomp 9PwwA i(�) wae.0 O Hunorn.mnln.r sple.r as Horpar and Raatraint Application STANDARD SUPPORT SPACING MAXIMUM DISTANCE BETWEEN HANGER (Fr -IN IA11eNY 792E 1 1 1 4 1 I P rn1c 5- e I a -o 1 e - a T-p a -o TABLE A - MAXIMUM SUPPORT SPACING TABLE B - MAXIMUM SUPPORT SPACING DISTANCE IN LINE SPRINKLER HEAD DROP DISTANCE END SPRINKLER HEAD DROP TEE OR TWO POINTS OF RESTRAINT (R) ELBOW OR ONE POINT OF RESTRAINT (R) 12P4-1101W1 am WE N Lee 7"'00 PA LM TW1100 P9 0/4 4' r 1 r e 1 1/4 r r 1 1/2 - e r Y VIKING RESIDENTIAL CONCEALED PENDENT SPRINKLER K-4.9 R 1�MAX. ANY DISTANCE OPVC - Whi != PPE (N) LOS itetl 100 Pel TINE TIVI 100 PSI y4 r r 1 tr r 1 1/4 1r tr 1 1/2 -J x' tr �Itttt��tttt� �IIII�Itttta 11-23-2021 PLAN REVIEW NOTES: Approved with condition 1. Valve at riser to shut off both fire and domestic water supply. DFM Burt INSULATION RECOMENDATIONS FOR MORE OPTIONS SEE NFPA 13D SECTIONS A9.1.1 (a) - (f) Caution-: It is importante that the insulation be installed tight against the joist. In unheated areas, any spaces or voids between the insulation and the joist causes the water in the fire sprinkler piping to freeze NFPA 13D - FIGURE A.9.1.1 (a) INSULATION RECOMMENDATIOS RISER CPVC ASSEMBLY CPVC RISER SHALL NOT BE EXPOSED 1 TO SPRINKLER SYSTEM STAND ALONE TYPE INSPECTOR, TEST AND DRAIN VALVE Unheated FLOW SWITCH Blown -in attic insulatlo space 1" BACK FLOW PREVENTER � l Tenting material Tent' spacqq keeping_ insulation dbove piping DOMWTIC WATER FI• / SYSTEM TEED 22MjwnC WATER SHUT Heated OFF VALVE space TO WATER METER AND CITY CONNECTION NFPA 13D - FIGURE A.9.1.1 (f) INSULATION RECOMMENDATIOS , I , I I I I , ALL RISER ASSEMBLIES SHALL BE ENCLOSED IN A WALL / BUILD UP WITH EASY ACCESS AND WITH AND APPROVED ACCESS DOOR, UNLESS OTHERWISE APPROVED BY THE FIRE DEPARTMENT. CPVC RISER SUPPORT NOTES RISERS SHALL BE SUPPORTED BY PIPE CLAMPS OR BY HANGERS LOCATED ON THE HORIZONTAL CONNECTION CLOSE TO THE RISER. ONLY LISTED HANGERS AND CLAMPS SHALL BE USED. VERTICAL LINES MUST BE SUPPORTED AT INTERVALS TO AVOID PLACING EXCESSIVE LOAD ON ANY FITTING AT THE LOWER END OF THE RISER. VERTICAL PIPING SHALL BE SUPPORTED AT EACH FLOOR OR AT 10 FT INTERVALS, WHICHEVER IS LESS, SUPPORT CAN BE ACHIEVED BY USING RISER CLAMPS OR DOUBLE BOLT PIPE CLAMPS LISTED FOR THIS SERVICE. DO NOT USE RISER CLAMPS WHICH SQUEEZE THE PIPE OR DEPEND ON COMPRESSION FOR SUPPORT. 1.Approved set of plans must be on site at the time of inspection. Failure to provide the approved set may result in a re -inspection fee. System drain(s) required at riser and must drain to the exterior. If riser is above lowest grade, 2nd drain required and signage at riser indicating location. Systems require signage IAW NFPA 13D. 2.Coverage required to the following areas: Clothes closets, linen closets and pantries exceeding 24 square feet in area, with the smallest dimension greater the 3' and having wall and ceiling surfaces of gypsum board. Bathrooms more than 55 square feet in area. When fuel fired equipment is present on covered decks or porches, or if living space above, at least one quick -response intermediate temperature sprinkler shall be installed above the equipment or area under living space. All fuel fired appliances, except attics if above all living areas. 3.Residential 13R add: Vertical back flow preventer must be tested annually. Strongly recommend system be monitored by fire alarm FI R2021-0124 CONDITION: Install shut off valve so that both systems are shut off simultaneous. RECEIVE' Nov 10 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT DESIGNER LOGO Q,_..SPACE FOR SEAL/STAMP REVISIONS �... 1 M FIRE PROTECTION LCC SPRINKLER DISTRIBUTION ............... . . . . . . N0. DESCRIPTION DATE A 1007G FOR REVISION 11 OB 21 6O20607 94TH AVE EAST a.`:. E'o:aP`�K�E:a.a=a 7615 201 ST ST SW CONTRACT GRAHAM, WA 98338 ; Byron Ranfferi Morales -Mora NC , CONROVAL NO 40M Fire 209-AG Level, _ EDMONDS, WA 98026 APPROVAL /IAA � '/ K 7�6 ' M Fire Protection System, LLC DRAWN 8Y IOC MFIREFP810B 11-8-21 sm=n iaeu, singe sdunaa � "' SCALE INDICTED 253-315-9266 ' sie. .• DATE NOV/08/2021 M.E. FRANCISCO GUZMAN FIRE PROTECTION SYSTEMS LLC r �$ SHEET No.1 FPS02 SPRINKLER DISTRIBUTION - FIRTS FOOR PLAN 1 /4" = 1 r—Orr NORTH DESIGNER LOGO . eo sm,n is �, s-mpisowno: M.E. FRANCISCO GUZMAN FIRE PROTECTION SYSTEMS LLC M FIRE PROTECTION LCC 20607 94TH AVE EAST GRAHAM, WA 98338 r r� 253-315-9266 PEX M PEX �I ll 6" CITY WATER MAIN Z UNDERGROUND PIPE DISTRIBUTION 1 /8" = 1 r-0" SPACE FOR SEAL/STAMP Byron Ranlferi Morales -Mora . 2901-0209-AG Level ' M Fire Protection System, LLC MFFII�R,E,F��P810B 11 88AL 0 -21 DESIGN CRITERIA PROVIDE A WET SYSTEM WITH A MINIMUM DENSITY OF 0.05 GPM/SQ.FT. IN THE TWO MOST HYDRAULIC REMOTE SPRINKLERS USING STANDARD RESPONSE SPRINKLERS 155-F & 175-F TEMP.1/2" NPT, K-4.9 FACTOR, RESIDENTIAL, CONCEALED AND RECESSED STYLE. 16' SPACING MAXIMUM, 256 FT' MAXIMUM PER HEAD, HEADS AREA TO BE LOCATED NO FURTHER THAN 8 FT FROM ANY WALL AND NO CLOSER THAN 8 FT BETWEEN SPRINKLERS. HYDRAULICALLY DESIGNED WITH TWO HEADS FLOWING. 1. SPRINKLER SHALL NOT BE REQUIRED IN ATTICS, CONCEALED SPACES DEDICATED EXCLUSIVELY TO AND CONTAINING ONLY DWELLING UNIT VENTILATION EQUIPMENT, FLOOR/CEILING SPACES, CRAWL SPACES, AND OTHER CONCEALED SPACES THAT ARE NOT USED OR INTENDED FOR LIVING PURPOSES. 2. MECHANICAL CLOSETS SMALLER THAN 400FT' , PENDENT, UPRIGHT AND SIDEWALL RESIDENTIAL SPRINKLER SHALL BE PERMITTED TO BE INSTALLED IN EITHER OF THE FOLLOWING SITUATIONS: - WITHIN 18 IN OF THE CEILING TO AVOID OBSTRUCTIONS NEAR THE CEILING WHERE THE COMPARTMENT IS ENCLOSED BY WALL AND A DOOR. - AT THE HIGHEST CEILING LEVEL WITHOUT REGARD TO OBSTRUCTIONS OR MINIMUM DISTANCES TO WALL. 3. PENDENT SPRINKLERS NO CLOSER THAN 3 FEET OF THE CENTER OF A CEILING FAN. 4. UNDERGROUND PIPE COVER MINIMUM OF 24 INCHES. HYDRAULIC INFORMATION AREA PER SPRINKLER 256 SO. FT. MAX 1 CALCULATED AREA 512 SQ.FT. DENSITY 0.054 GPM/SQ.FT. SPRINKLERS CALCULATED 2 SPRINKLER FLOW 27.8 GPM WATER REQUIRED 27.8 GPM RQ'D PRESSURE 22.6 PSI AVL PRESSURE AND FLOW 40.4 ® 28 PSI ® GPM CUSHION PRESSURE 1 17.7 WATER SUPPLY PRIMARY: CITY WATER SUPPLY STATIC PSI 70 RESIDUAL: 35 GPM AT 70 PSI SYMBOLOGY SPRINKLER PIPE CPVC e CPVC RISER ASSEMBLY 9= 10" ALARM BELL ® RESIDENTIAL SPRINKLER CONCEALED K-4.9 155'F QOHYDRAULICS S C' NODES Q WATER METER X DIAMETER [INCHES] X-X DISTANCE [FEET] -[INCHES] FIRE SPRINKLER LEGEND PSI RECEIVED Nov 10 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT SYMBOL MANUFACTURER 1_ SIN TYPE 1. NPT 1 ORIFICE _1 K—FACTOR _ TEMP FINISH 1_ 1 QUANTITY - ® 1 VIKING VK494 CONCEALED PENDENT 1/2" - K-4.9 155F WHITE 015 0) NORTH 7615 201 ST ST SW, EDMONDS, WA 98026 REVISIONS TOTAL SPRINKLERS IN THIS PLAN 015 SPRINKLER DISTRIBUTION DRAWN UY IOC SCALE INDICATED DATE NOVIDO12021 SHEET NO. FPSOI