FIR2021-0044+Fire_Sprinkler_Equipment_Specification_Sheets+4.30.2021_9.38.24_AM+2172833
"THE INCH" GL6) RESIDENTIAL AUTOMATIC SPRINKLERS FIRE SPRINKLER C®RP®RUI®N MODEL GL4906 ONE INCH ADJUSTABLE FLAT PLATE CONCEALED PENDENT DESCRIPTION AND OPERATION The Globe Model GL4906 Residential One Inch Adjustable Concealed Pendent Sprinkler has a flat plate profile that utilizes a 3mm frangible glass ampule as the thermosensitive element. Itfeatures economy, aesthetics and the lowest allowable water flow with a nominal 1"of adjustment for easier installation. The combination of the 3mm frangible glass ampule and specially designed deflector make the Model GL4906 the ultimate in life safety and fire control. It has met the strict requirements of Underwriters Laboratories Inc. as described in UL Standard,1626, for Residential Sprinklers for Fire Protection Service, and should be used accordingly. This sprinkler should also be installed in accordance with the appropriate NFPA Standard 13, 13D or 13R and under the direction of the approving authorities having jurisdiction. All that is seen at the ceiling is the 3 5116" diameter flat ceiling plate color finished to match the specifier's exact requirements. The ceiling plate is soldered to the sprinkler's special upper support assembly in three places. Upon the application of sufficient heat, the plate falls to the floor exposing the residential pendent spray sprinkler. Atthe prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass bulb to shatter. This results in water discharge which is distributed in an approved pattern. TECHNICAL DATA 9 See reverse side for Approvals and Specifications. • Temperature Rating: 155°F (68°C) • Water Working Pressure Rating- 175 psi (12 Bars) • Factory tested hydrostatically to 500 psi (34 Bars) • Maximum lowtemperature glass bulb rating: -67F (-55°C) • Frame bronze • Deflector - brass • Screw - brass • Bulb seat - copper • Spring - nickel alloy • Seal - teflon • Bulb - glass with alcohol based solution, 3mm size • Cover Plate - brass • Upper Escutcheon Assembly -steel RESIDENTIAL FLAT PLATE CONCEALED PENDENT • SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING AVAILABLE SPRINKLER N.F.P.A. MAXIMUM CLASSIFICATION TEMPERATURES 6201 BULB COLOR CEILING TEMPERATURE ORDINARY RED 4077AIRPARK DRIVE, STANDISH, MICHIGAN 48658 SEPTEMBER 2011 A-10 989-846-4583 • FAX 989-846-9231 BULLETIN GL4906, REV. #1 RESIDENTIAL AUTOMATIC SPRINKLERS MODEL GL4906 ONE INCH ADJUSTABLE FLAT PLATE CONCEALED PENDENT SPECIFICATIONS AND APPROVALS SIN NOMINAL 155°F (68"C) MODEL "PCFACTOR THREAD SIZE LENGTH FINISHES SPRINKLER WITH cULus 135*F 57°C PLATE Bright Chrome White Painted GL4906 4.9 (68 metric) 1/2" NPT 3" (7.6 cm) Bright Brass* X X Satin Chrome" Other Painted Finishes* NOTE: METRIC CONVERSIONS ARE APPROXIMATE. 'FINISHES AVAILABLE ON SPECIAL ORDER. FOR PAINTED PLATES OTHER THAN WHITE, CONTACT GLOBE FOR ORDERING SPECIFICATIONS. INSTALLATION DATA FOR FLAT AND SLOPED CEILINGS" ONE INCH ADJUSTABLE FLAT PLATE CONCEALED PENDENT MODEL MAXIMUM AREA OF COVERAGE MINIMUM WATER DISCHARGE & PRESSURES NEEDED PER SPRINKLER* GL4906 12'x12' 13G.P.M.-7P.S.1. 14'x14' 13G.P.M.-7P.S.I. 16' x 16' 13 G.P.M. - 7 P.S.I. 18, z 18' 17 G.P.M. - 12 P..S.I. 20' x 20' 20 G.P.M. - 16.7 P.S_I. NOTE: MINIMUM 9' SPRINKLER SPACING. 'WHEN THESE SPRINKLERS ARE USED IN NFPA 13 SYSTEMS, A 0.1 DESIGN DENSITY MINIMUM SHALL BE UTILIZED. **REFER TO PAGE 2 OF THE GLOBE RESIDENTIAL SPRINKLER INSTALLATION GUIDE FOR NFPA 13D and 13R REQUIREMENTS. ORDERING INFORMATION CROSS SECTION SPECIFY 2 3I4' DIA. MIN......_... HOLE IN CEILING 2 3/8" OIA... j REDUCER DEFLECTOR �? DROP PIN b —' y - 2 3/4° MAX. Gi ti 1 7/8' MIN. SUPPORTSHELL� 511V CEILING COVER PLATE' FLAT PLATE CONCEALEDPENDENT GL&13E FIRE SPRINKLER CORPORATION SEPTEMBER2011 • Quantity • Model Number • Style Orifice • Temperature • Finishes desired • Quantity - Concealed Wrenches - PIN 332765 • Quantity - Protective Caps - PIN 332868 COVER PLATE SIZE WHITE 136OF PART # CHROME 136DF PART # 3 5/16" 332892 332891 GLOBE® PRODUCT WARRANTY Globe agrees to repair or replace any of its own manu- factured products found to be defective in material or workmanship for a period of one year from date of ship- ment. For specific details of our warranty please refer to Price List Terms and Conditions of Sale (Our Price List). 4077AIRPARK DRIVE, STANDISH, MICHIGAN 48658 989-846-4583 1-800-248-0278 PRINTED U.S.A. FAX 989-846-9231 www.globesprinkler.com BULLETIN GL4906, REV. #1 GLOBE RESIDENTIAL SPRINKLER GUIDE NFPA 13 REQUIREMENTS: When sprinklers are used in NFPA 13 Systems, A 0.1 Design Density minumum shall be utilized. NFPA 13D REQUIREMENTS: For each of the following situations, the number of sprinklers in the design area shall be all of the sprinklers within a compartment, up to a maximum of two sprinklers, that require the greatest hydraulic demand: (1). A flat smooth, horizontal ceiling with no beams up to a maximum of 24 ft. above the floor. (2). A smooth flat, sloped ceiling with no beams up to a maximum slope of 8 in 12. The highest portion of the ceiling shall not be more than 24 ft. above the floor. The highest sprinkler in the sloped portion of the ceiling shall be above all openings from that compartment containing the sloped ceiling into any communicating spaces. (3). A sloped ceiling with beams up to 14 in. deep with pendent sprinklers under the beams. The compartment containing the sloped, beam ceiling shall be a maximum of 600 ft2 in area_ The slope of the ceiling shall be between 2 in 12 and 8 in 12. The highest portion of the ceiling shall not be more than 24 ft. above the floor. The highest sprinkler in the sloped portion of the ceiling shall be above all openings from the compartment containing the sloped ceiling into any communicating spaces. (4). A sloped ceiling with beams of any depth with sidewall or pendent sprinklers in each pocket formed by the beams. The compartment containing the sloped, beamed ceiling shall be a maximum of 600 ft2 in area. The slope of the ceiling shall be between 2 in 12 and 8 in 12. The highest portion of the ceiling shall not be more than 24 ft above the floor. For situations not meeting one of the conditions above, residential sprinklers listed for use in specific ceiling configurations shall be permitted to be used in accordance with their listings. For situations not meeting one of the conditions above, the number of sprinklers in the design area shall be determined in consultation with the authority having jurisdiction as appropriateforthe conditions. Sprinklers shall be installed in accordance with their listing where a type of ceiling configuration is referenced in the listing. NFPA 13R REQUIREMENTS: Horizontal Ceiling criteria may be used for sloped ceiling configurations up to 8:12 pitch when accept- able to the Local Authority having Jurisdiction. The following pages contain illustrations for customers reference. If conflicting data is found, NFPA 13, 13D, or 13R requirements take presedence. SEPTEMBER 2011 Page 2 BULLETIN R.S.I.G., REV. ##15 .... &OEM rnow 1ER FIRE SPRINKLER CORPORATION RESIDENTIAL AUTOMATIC SPRINKLERS MODEL GL4231 HORIZONTAL SIDEWALL RECESSED HORIZONTAL SIDEWALL DESCRIPTION AND OPERATION The Globe Model GL4231 Residential Horizontal Sidewall Sprinklers have a durable design which utilizes a 3mm frangible glass ampule as the thermosensitive element. They feature econ- omy, aesthetics and low flow. The combination of the 3mm frangible glass ampule and specially designed deflector make the Model GL4231 Sprinklers the ultimate in life safety and fire control. These Globe Horizontal Sidewall and Recessed Horizontal Sidewall Residential Sprinklers have met the strict requirements of Underwriters Laboratories Inc. as described in the UL Standard for Residential Sprinklers for Fire Protection Service, UL 1626, and should be used accordingly. These sprin- klers should also be installed in accordance with the appropriate NFPA Standard 13, 13D or 13R and under the direction of the ap- proving authorities having jurisdiction. The heart of Globe's Model GL4231 sprinklers proven actuating assembly is a hermetically sealed frangible glass ampule that con- tains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern. The sprinkler and escutcheon are not factory assembled. Assembly is done in the field. TECHNICAL DATA • See reverse side for Approvals and Specifications. • Temperature Rating - 155°F (68°C), 175°F (79°C) • Water Working Pressure Rating - 175 psi (12 Bars) • Factory tested hydrostatically to 500 psi (34 Bars) • Maximum low temperature glass bulb rating is -67°F (-55°C) • Frame - bronze • Deflector - brass • Screw - brass • Lodgement Wire - stainless steel • Bulb seat - copper • Spring - nickel alloy • Seal - teflon • Bulb - glass with alcohol based solution, 3mm size • Escutcheon Assembly - steel x RESIDENTIAL HORIZONTAL SIDEWALL RESIDENTIAL RECESSED HORIZONTAL SIDEWALL • SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING CLASSIFICATIONJ AVAILABLE SPRINKLER BUnCOLORN.F.P.A. MAXIMUM CEILING TEMPERATURES TEMPERATURE ORDINARY INTERMEDIATE 150T 66°C DEC 2016 GFS-330 (FormerlyA-4) RESIDENTIAL AUTOMATIC SPRINKLERS MODEL GL4231 HORIZONTAL SIDEWALL RECESSED HORIZONTAL SIDEWALL SPECIFICATIONS AND APPROVALS SIN MODEL NOMINAL "K" FACTOR THREAD SIZE LENGTH FINISHES cULus CE NYC - DOB MEA 101-92-E Factory Bronze 1/2"NPT 2 1/2" Chrome GL4231 4.2 ( 60 metric) X X (15mm) (6.4cm) White Polyester2 Black Polyester' 2 NOTE: METRIC CONVERSIONS ARE APPROXIMATE. 'FINISHES AVAILABLE ON SPECIAL ORDER. 2AVAILABLE AS cULus LISTED CORROSION RESISTANT WHEN SPECIFIED ON ORDER. INSTALLATION DATA FOR FLAT AND SLOPED CEILINGS** TEMPERATURE • *MIN. SIN MODEL STYLE MAX. AREA OF COVERAGE' Feet (Meters) PRES- SURE P.S.I. (bars) *MIN. FLOW G.P.M. (L/min.) DEFLECTOR TO CEILING DISTANCE Inches (mm) MIN. DISTANCE BETWEEN SPRINKLERS Feet (Meters) 155°F (68°C) 1757 (79°C) 12 (3.7) x 12 (3.7) 9.6 (.66) 13 (49) 14 (4.3) x 14 (4.3) 12.8 (.88) 15 (57) HORIZONTAL SIDEWALL 4(101.6) 16 (4.9) x 16 (4.9) 14.5 (1.00) 16 (61) GL4231 RECESSED X X to 8(2.4) HORIZONTAL SIDEWALL 6(152.4) 16 (4.9) x 18 (5.5) 20.5 (1.41) 19 (72) 16 (4.9) x 20 (6.1) 1 30.0 (2.07) 23 (87) NOTE: METRIC CONVERSIONS ARE APPROXIMATE. *WHEN THESE SPRINKLERS ARE USED IN NFPA 13 SYSTEMS, A 0.1 DESIGN DENSITY MINIMUM SHALL BE UTILIZED. **REFER TO PAGE 2 OF GLOBE'S RESIDENTIAL SPRINKLER INSTALLATION GUIDE (BULLETIN R.S.I.G.) FOR NFPA 13D AND 13R REQUIREMENTS. 'FOR COVERAGE AREA DIMENSIONS LESS THAN OR BETWEEN THOSE INDICATED, USE THE MINIMUM REQUIRED FLOW FOR THE NEXT HIGHEST COVERAGE AREA FOR WHICH HYDRAULIC DESIGN CRITERIAARE STATED. THE LENGTH x WIDTH REFERS TO THE BACKWALL WHERE THE SPRINKLER IS LOCATED (WIDTH) x HORIZONTAL THROW OF THE SPRINKLER (LENGTH). CROSS SECTION DIA, 1 29/32" DIA.I I 2" MIN. DIA. HOLE IN CEILING I_J-} 1/8" MIN. 5/8" MAX. - 112 AD3. 7/8" MAX. - 3/4" AD]. ORDERING INFORMATION SPECIFY • Quantity • Model Number • Style 4„MIN. • Orifice • Temperature • Finishes desired 6" MAX. • Quantity - Wrenches - P/N 325390 I1 • Quantity - Recessed Wrenches - P/N 327102 • Quantity - Protective Caps - P/N 327109-CAP (Friction Fit Recessed) [I 1" MIN. 3/4" MAX. 1/2" OR 3/4" ADJUSTMENT RECESSED HORIZONTAL SIDEWALL CLtSE FIRE SPRINKLER CORPORATION GLOBE° PRODUCT WARRANTY Globe agrees to repair or replace any of its own manufactured products found to be defective in material or workmanship for a period of one year from date of shipment. For specific details of our warranty please refer to Price List Terms and Conditions of Sale (Our Price List). 4077AIRPARK DRIVE, STANDISH, MICHIGAN 48658 989-846-4583 FAX 989-846-9231 1-800-248-0278 www.globesprinkler.com DEC 2016 PRINTED U.S.A. GFS-330 (FormerlyA-4) zoo P.O. Box 3365 South E! Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 515 DOUBLE OFFSET C.P.V.C. HANGER SIZE - 3/4" and 1" pipe. MATERIAL - Carbon Steel. FINISH - Mil. Galvanized. LISTINGS - � ct�us EX 4231 PATENT - No. 6,702,236 FUNCTION - Hanger/restrainer on CPVC pipe. INSTALLATION - PerN.P.EA 13, 13R and 13D on side of beam. FASTENERS - UL Listed per N1{PA 13. in WOOD: #904 screw - no pre -drill. in STEEL: 1 /4" or # 14 'Tek Screw. FEATURES * Double 1 1/2" offset. * Center line matches AFCON #514. * 3/4" and 1" pipe size have common center -line. * Offset edge eliminates abrasion. * Required AFCON #904 screw has 3/8" hex head - included. ORDERING - Part # and pipe size. 1 /04 16011 INCORPORATED CORONA, CA • (714) 737-5599 32 FIG. 22 HANGER FOR C.P.V.C. PLASTIC PIPE SINGLE FASTENER STRAP TYPE Size Range - 3/4" thni 2" C.P.V.C, Pipe. Mate riot - Carbon Steel wills galvanizecl 16i�i, (3,90 govt, sp~c. Function - Figure 22 is intended to perform as a hanger to support only C.P.V.C. piping used in automatic fire sprinkler systems. The product acts as a hanger when tab is upward and the fastener screw is in the horizontal position. Figure 22 can be installed on the top of a beam, bu[ hi this situation acts as a guide to the pipiog which is supported by the beam itself. Figure 22 is not interacled to support C.P.V.C. pipe from under a flat horizontal surface, such as a ceiling. For this type of installation use the Tolco Figure 23, Double Fastener Strap Hanger for C.P.V.C. Piping. Figure 22, when inverted, with the hanger tab downward, does not act as a hanger, but can function as a restrainer to prevent the upward movement of the sprinkler head during activation. Approvals - Underwriters' Laboratories listed to support fire sprinkler piping. Meets and exceeds the requirements of N.F-P.A. 13, 13R, and 13D. Features - Figure 22 incorporates features which protect the pipe and ease installation. The flared edge design" protects C.P.V.C. pipe from any rough surface. Figure 22 is easily attached to the building structure using the special hex head self threading screw" furnished with the product. It is recommended that rechargeable electric drills fitted with a hex socket attachment be used as installation tools. No impact tools (such as a hammer) or impact fasteners (such as drive screws or nails) are allowed. Damage has been known to result from installations using impact type tools. No pre drilling of a pilot hole in wood is required. Order By - Figure number and C.P.V.C. pipe size. Patent Pending Minimum fastener size acceptable, #12 x 1-1/4" hardened hex head self threading screw. A MAX. HANGER FASTENER APPROX. C.P.V..C, SPACING HEX HEAD WEIGHT PIPE SIZE A B C (FT.) SIZE LENGTH PER 100 3/4 2 - 7/16 1 - 5/16 1 - .3,/16 5-1/2 5/16 1 - 1/4 9 1/166 5 1& 1 1/4 3 - 1/16 1-5/8 1 - 3/16 6-1/2 5/lEi 1 1/4 11 vj 1tlf� 7" 51Ci 1'- 1/4 12 2 3 3/4 2- 1/8 1 - 3/16 8 5/16 1 1/4 15 Fig. 29 - Double offset Hanger & Restrainer for CPVC Plastic Pipe Size Range — Available in 3/4" and 1" pipe sizes Material — Pre -Galvanized Steel Function — intended to perform as a hanger and restrainer for CPVC, plastic fire sprinkler pipe. Provides double offset 1 '/2" x 1 1/2" from mounting surface. This design will ease installation by eliminating the need for wood block extension and allow retro-fit attachment of hanger to sprinkler pipe. Features — • Thumb tab provides protection to restrain pipe in rough job site conditions. Tab is not required to be bent for listed installation. • Offset edge eliminates abrasion. • Attaches easily to wood structure with two special #10 x 1 hex head self -threading screws furnished with product. • Can be used as a single offset hanger by aligning "dimples" with top of mounting surface and utilizing two fasteners in two of the three holes provided. Approvals — Underwriters' Laboratories Listed in the USA (UL) and Canada (cUL) as a hanger and restrainer to support fire sprinkler systems. Meets and exceeds requirements of NFPA 13, 13R and 13D. Finish — Pre -Galvanized Order By -- Figure number and pipe size. PATENT PENDING Install using a rechargeable electric drill fitted with a 5f16" socket attachment with the special hex head self -tapping screws provided. Install screws until they bottom out. Pipe can be "snapped" into hanger before or after installation of the screws to the mounting surface. "Thumb tab" may be bent up to provide additional protection to the pipe, but is not required for performance of the hanger I restrainer function. C @1s USTED OFRCEJMANUFACTURING FACILITY • 1375 SAMPSON AVE_ • CORONA, CA 92879 • PH: 951.737.5599 - FAX: 951.737.0330 CUSTOMER SERVICE • 00@785 5265 www.tolco.com Fig. 28 "Stand -Off" Hanger & Restrainer for CPVC Plastic Pipe Size Range — 3/4" through 2" Material --- Carbon Steel, Pre -Galvanized Function — Designed to be used as a hanger and restrainer for CPVC piping where the "stand-off' design will ease installation by eliminating the need for wood blocking. Features: • Flared edge design protects CPVC pipe from any rough or abrasive surfaces. • Unique twist and lock design holds pipe firmly in place and allows retrofit type of installation. • The "Stand -Offs design eliminates the need for wood block extension. • Can be installed on horizontal or vertical piping regardless of mounting surface orientation. • Attaches easily to wood structure with two hex head self -threading screws furnished with product. • Installs easily using rechargeable electrical driver with 5/16" extension socket eliminating impact tool damage to pipe. • Attaches easily to steel, minimum 18 gauge with (2) 1/4" x 1 " tek type self drilling tapping screws. • UL Listed as a hanger and a restrainer for fire sprinkler piping. Approvals — Underwriters' Laboratory Listed in the USA (UL) and Canada (cUL) to support automatic fire sprinkler systems. May be installed into wood using fasteners supplied with product, or into minimum 18 gauge steel using (2) 1/4" x 1" tek type screws. Meets and exceeds the requirements of NFPA 13, 13R and 13D. Fig. 28 satis- fies the UL vertical restraint requirement where needed. UL Listed as a hanger and ver- tical restraint when installed on 3/8" composite wood material. Use two Fig. 27B Speed Nuts when used as a hanger and restraint. Use one Fig. 27B Speed Nut on the upper installed screw when used as a hanger only. Order by — Figure number and pipe size. PATENT # 7,455,268 HANGER A RESTRAW APPUCAPON z C Div us IIS» A B C y Dimensions • Wei hts Pipe Approx. Size A B C Wt. 3/4 TA2 2 31h .180 1 35/e 23/1e Th .210 11/4 35A 23/s 31h .225 11h 4 21h 31h .310 2 41h 211/16 35A .340 OFF[CFJNIANUFACTURING FACILrTY • 1375 SAMPSON AVE. + CORONA, CA 92979 • PH: 951.737-5599 • FAX: %1.737.0330 CUSTOMER SERVICE • 800.786.5266 WWW'WICa.aam FIG. 23 HANGER FOR C.P.V.C. PLASTIC PIPE DOUBLE FASTENER STRAP TYPE I � I -0 - BCE-13�I 1=-i A Do Size Range - 3/4" thru 2" C.P.V.C. pipe. Material - Carbon Steel with galvanized finish G-90 govt. Spec. Function - The Fig. 23 and Fig. 24 are intended to perform as a hanger / restrainer to support only C.P.V.C. piping used in automatic fire sprinkler systems. Fig. 23 and Fig. 24 can be installed on the top or on the bottom of a beam. The Fig. 23 can also be installed on the side of a beam. The Fig. 23 and Fig. 24 can also function as a restrainer to prevent the upward movement of the sprinkler head during activation. Approvals - Underwriters' Laboratories listed to support fire sprinkler piping. Meets and exceeds the requirements of N.F.P.A. 13, 13R, and 13D. A B I C C.P.V.C. PIPE SIZE FIG. 23 FIG. 24 FIG, 23 FIG. 24 ;FIG. 23 FIG. 24 3/41 3-1/8 2-5/16 1-9/16 1-5/32 1-3/16 1-3/16 FIG. 24 HANGER FOR C.P.V.C. PLASTIC PIPE DOUBLE FASTENER STRAP TYPE - SIDE MOUNT A �1-k Features - The Fig. 23 and Fig. 24 incorporate features which protect the pipe and ease installation. The flared edge design` protects the C.RV.C. pipe from any rough surface. The Fig. 23 and Fig. 24 are easily attached to the building structure using the two hex head self threading screws` furnished with the product, It is recommended that rechargeable electric drills fitted with a hex socket attachment be used as installation tools. No impact tools (such as a hammer) or impact fasteners (such as drive screws or nails) are allowed. Damage has been known to result from installations using impact type tools. No pre drilling of a pilot hole in wood is required. . Order By - Figure number and C.P.V.C. pipe size. Patents Pending " - Minimum fastener size acceptable, #12 x 1-I14" hardened hex head self threading screw. MAX. HANGER FASTENER APPROX. SPACING HEX HEAD WEIGHT (FT.) SIZE + LENGTH PER 100 5-1/2 5/16 1-1/4 9 1-1/4 4-3/16 3 2-3/32 1-1/2 ',1-3/16 1- 2 4 7/8 3 11/16 2- 7/16 1 27/32� 1 3/16 1 R V RE S/91 6-1/2 i 5/16- i 1-1/4 11 8 --5/16 1-1/4 i15 Fig. 28M - Offset Hanger and Restrainer for CPVC Plastic Pipe and IPS Pipe Size Range — 3/4" thru 1-1/4" pipe Material — Carbon Steel; Electro-Galvanized Function — Designed to be used as a hanger and restrainer for CPVC piping where the "stand-off" design will ease installation by eliminating the need for wood blocking Features — • Flared edge design protects CPVC pipe from any rough or abrasive surfaces • Unique snap -on design holds pipe firmly in place and allows retrofit type of installation • The "Stand -Off" design eliminates the need for wood block extension • Can be installed on horizontal or vertical piping regardless of mounting surface orientation • Attaches easily to wood structure with two hex head self -threading screws furnished with product • Installs easily using rechargeable electrical driver with 5/16" extension socket eliminating impact tool damage to pipe • Attaches easily to steel, minimum 18 gauge with (2) 1/4" x 1" tek type self drilling tapping screws • .cULus Listed as a hanger and a restrainer for fire sprinkler piping Approvals Underwriters' Laboratory Listed in the USA (UL) and Canada (cUL) to support automatic fire sprinkler systems. May be installed into wood using fas- teners screws. Meets and exceeds the requirements of NFPA 13, 13R and 13D. Fig. 28M satisfies the UL vertical restraint requirements where needed. Order By — Figure number and pipe size PATENT PENDING 4 RESTRAINT u Fig. 28M Dimensions • Weights Max. Spacing Pie required per Approx Size A B C NFPA 13 for Wt.1100 CPVC pIEMc pipe 3/4 2 3/16 3-1/2 5'-6" 9 1 2-1/8 3/16 3-1/2 6'-0" 12 1-1/4 2-5/16 3/16 3-1/2 6-6" 13 C &u o RESTRAINT OFACWANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX- 951.737.0333 CUSTOMER SERVICE • 803.786,5266 WWW101Co.Com Friction Loss (PSI per Linear Foot) and Velocity (Feet per second) (Hazen -Williams C Factor = 150) Nnminal Pipe Size. 3/4 inch 1 inch 11/4 inches 11/2 inches 2 inches 21/2 inches 3 inches Avg. LD. (inches) (.884) (1.109) (1.400) (1.602) (2.003) (2.423) (2.951) Friction Friction Friction Friction Friction Friction Friction GPM Loss Velocity Loss Velocity Loss Velocity Loss Velocity Loss Velocity Lass Velocity Lass Velocity 1 .0008 .5 .0003 .3 .0001 .2 .0000 .1 0000 .1 .0000 .0 .0000 .0 2 .0028 1.0 '0009 .6 .0003 .4 .0002 .3 .0001 .2 .0000 .1 .0000 .0 3 .0059 1.5 .0020 .9 .0006 6 0003 .4 .0001 .3 .0000 .2 .0000 .1 4 .0101 2.0 .0033 1.3 .0011 .8 .0006 .6 .0002 .4 .0001 .2 .0000 .1 5 .0152 2.6 .0051 1.6 .0016 1.0 .0008 .7 .0003 .5 .0001 .3 .0000 .2 6 ..0214 3.1 .0071 1.9 .0023 1.2 .0012 .9 .0004 .6 .0002 .4 .0001 .2 7 .0284 3.6 .0094 2.3 .0030 1.4 .0016 1.1 .0005 .7 .0002 .4 .0001 .3 8 .0364 4.1 .0121 2.6 .0039 1.6 .0020 1.2 .0007 .8 .0003 .5 .0001 .3 9 .0452 4.7 .0150 2.9 .0048 1.8 .0025 1.4 .0008 .9 .0003 .6 .0001 .4 10 .0550 5.2 .0182 3.3 .0059 2.0 .0030 1.5 .0010 1.0 .0004 .6 .0002 .4 11 .0656 5.7 .0217 3.6 .0070 2.2 .0036 1.7 .0012 1.1 .0005 .7 .0002 .5 12 .0770 6.2 .0255 3.9 .0082 2.5 .0043 1.9 .0014 1.2 .0006 .8 .0002 .5 13 .0893 6.7 .0296 4.3 .0095 2.7 .0049 2.0 .0017 1.3 .0007 .9 .0003 .6 14 .1024 7.3 .0840 4.6 .0109 2.9 .0057 2.2 .0019 14 .0008 .9 .0003 .6 15 .1164 7.8 .0386 4.9 .0124 3.1 .0064 2.3 D022 1.5 .0009 1.0 .0003 .7 16 .1312 8.3 .0435 5.3 .0140 3.3 .0072 2.5 .0024 1.6 .0010 1.1 .0004 .7 17 .1467 8.8 .0486 5.6 .0156 3.5 0081 2.7 .0027 1.7 .0011 1.1 .0004 .7 18 .1631 9.4 .0541 5.9 .0174 3.7 .0090 2.8 .0030 1.8 .0012 1.2 .0005 .8 19 .1802 9.9 .0597 6.3 .0192 3.9 .0100 3.0 .0034 1.9 .0013 1.3 .0005 .8 20 .1982 10.4 .0657 6.6 .0211 4.1 .0110 3.1 .0037 2.0 .0015 1.3 .0006 .9 21 .2169 10.9 .0719 6.9 .0231 4.3 .0120 3.3 .0040 2.1 .0016 1.4 .0006 .9 22 .2364 11.5 .0783 7.3 .0252 4.5 .0131 3.5 .0044 2.2 .0017 1.5 .0007 1.0 23 .2567 12.0 .0851 7.6 .0273 4.7 .0142 3.6 .0048 2.3 .0019 1.6 .0007 1.0 24 .2777 12.5 .0920 7.9 .0296 5.0 .0153 3.8 .0052 2.4 .0020 1.6 .0008 1.1 25 .2995 13.0 .0993 8.3 .0319 5.2 .0166 3.9 .0056 2.5 .0022 1.7 .0008 1.1 26 .3220 13.5 .1067 8.6 .0343 5.4 .0178 4.1 .0060 2.6 .0024 1.8 .0009 1.2 27 .3453 14.1 .1144 8.9 .0368 5.6 .0191 4.2 .0064 2.7 .0025 1.8 .0010 1.2 28 .3693 14.6 .1224 9.3 .0394 5.8 .0204 4.4 .0069 2.8 .0027 1.9 .0010 1.3 29 .3941 15.1 .1306 9.6 .0420 6.0 .0218 4.6 .0073 2.9 .0029 2.0 .0011 1.3 30 .4196 15.6 .1391 9.9 .0447 6.2 .0232 4.7 .0078 3.0 .0031 2.0 .0012 1.4 31 .4458 16.2 .1478 10.2 .0475 6.4 .0246 4.9 .0083 3.1 .0033 2.1 .0013 1.4 32 .4728 16.7 .1567 10.6 .0504 6.6 .0261 5.0 .0088 3.2 .0035 2.2 .0013 1.5 33 .5005 17.2 .1659 10.9 .0533 6.8 .0277 5.2 .0093 3.3 .0037 2.2 .0014 1.5 34 .5289 17.7 .1753 11.2 .0564 7.0 .0292 5.4 .0098 3.4 .0039 2.3 .0015 1.5 35 .5580 18.2 .1850 11.6 .0595 7.2 .0308 5.5 .0104 3.5 .0041 2.4 .0016 1.6 36 .5879 18.8 .1949 11.9 .0626 7.5 .0325 5.7 .0109 3.6 .0043 2.5 .0017 1.6 37 .6185 19.3 .2050. 12.2 .0659 7.7 .0342 5.8 .0115 3.7 .0046 2.5 .0017 1.7 38 .6498 19.8 .2154 12.6 .0692 7.9 .0359 6.0 .0121 3.8 .0048 2.6 .0018 1.7 39 .6817 20.3 .2260 12.9 .0726 8.1 .0377 6.2 .0127 3.9 .0050 2.7 .0019 1.8 40 .7144 20.9 .2366 13.2 .0761 8.3 .0395 6.3 .0133 4.0 .0053 2.7 .0020 1.8 GPM 41 .2479 13.6 .0797 8.5 .0413 6.5 .0139 4.1 .0055 2.8 .0021 1.9 42 .2592 13.9 .0833 8.7 .0432 6.6 .0146 4.2 .0058 2.9 .0022 1.9 43 .2707 14.2 .0870 8.9 .0451 6.8 .0152 4.3 .0060 2.9 .0023 2.0 44 .2824 14.6 .0908 9.1 .0471 7A .0159 4.4 .0063 3.0 .0024 2.0 45 .2944 14.9 .0947 9.3 .0491 7.1 .0165 4.5 .0065 3.1 .0025 2.1 46 .3067 15.2 .0986 9.5 .0511 7.3 .0172 4.6 .0068 3.2 .0026 2.1 47 .3191 15.6 .1026 9.7 .0532 7.4 .0179 4.7 .0071 3.2 .0027 2.2 48 .3318 15.9 .1067 10.0 .0553 7.6 .0186 4.8 .0074 3.3 .0028 2.2 49 .3447 16.2 ' 1108 10.2 .0575 7.7 .0194 4.9 .0077 3.4 .0029 2.2 50 .3578 16.6 .1150 10.4 .0597 7.9 .0201 5.0 .0080 3.4 .0030 2.3 52 .3847 17.2 .1237 10.8 .0642 8.2 .0216 5.2 .0086 3.6 .0033 2.4 54 .4126 17.9 .1326 11.2 .0688 8.5 .0232 5.4 .0092 3.7 .0035 2.5 56 .4413 18.6 .1419 11.6 .0736 8.9 .0248 5.7 .0098 3.8 .0038 2.6 58 .4709 19.2 .1514 12.0 .0785 9.2 .0265 5.9 .0105 4.0 .0040 2.7 60 .5013 19.9 .1612 12.5 .0836 9.5 .0282 6.1 .0111 4.1 .0043 2.8 62 .5327 20.5 .1713 12.9 .0888 9.8 .0299 6.3 '0118 4.3 .0045 2.9 64 .5649 21.2 .1816 13.3 .0942 10.1 .0317 6.5 .0126 4.4 .0048 3.0 66 .5980 21.9 .1923 13.7 .0997 10.5 .0336 6.7 .0133 4.5 .0051 3.0 68 .6320 22.5 .2032 14.1 .1054 10.8 .0355 6.9 .0141 4.7 .0054 3.1 70 .6668 23.2 .2144 14.5 .1112 11.1 .0375 7.1 .0148 4.8 .0057 3.2 .72 .7025 23.9 .2258 15.0 .1171 11.4 .0395 7.3 .0156 5.0 .0060 3.3 74 .7390 24.5 .2376 15.4 .1232 11.7 .0415 7.5 .0164 5.1 .0063 3.4 76 .7764 25.2 .2496 15.8 .1295 12.0 .0436 7.7 .0173 5.2 .0066 3.5 78 .8146 25.9 .2619 16.2 .1358 12.4 .0458 7.9 .0181 5.4 .0069 3.6 80 .8536 26.5 .2744 16.6 .1424 12.7 .0480 8.1 .0190 5.5 .0073 3.7 Engineering Data Pipe and Fitling Specifications Spears® FlameGuard® CPVC Sprinkler Pipe is produced in SDR 13.5 dimensions, as specified in ASTM F 442. Engineering data on Material Properties and Expansion & Contraction are provided in this manual for (A) Spears" FlameGuard® or Vlctaulic FireLock° and (B) Harvel BlazeMaster° CPVC Fire Sprinkler Pipe. Consult other manufacturers for applicable variations Spears' FlameGuard° CPVC Sprinkler Fittings are produced in Schedule 40 and Schedule 80 dimensions for sizes 314" through 1-114", and in Schedule 80 for sizes 1-112" through 3", in accordance with ASTM F 437, ASTM F 438, and ASTM F 439 as applicable. These products are UL Listed FM/Approved for a rated working pressure of 175 psi (1200kPa)at 150' F (65' C) for sprinkler service and LPCB listed for a rated working pressure of 175 psi (1200kPa) at 120° F (49° C). CPVC Fire Sprinkler Pipe Dimensions SDR 13.5 (Ref. ASTM F442) Weight lbs/ft (kgim) Size Average Average Nominal riches OD inches (mm) ID inches 314 1.050 0.874 0.168 (DN20) (26,7) (22,5) (0,2) 1 1.315 1.101 0.262 (DN25) (33,4) (28,2) (0,4) 1-1i4 1.660 1.394 0.418 (DN32) (42,2) (35,6) (0,6) 1-112 1.900 1.598 0.548 (DN40) (48,3) (40,7) (0,7) 2 2.375 2.003 0.859 (DN50) (60,3) (50,9) (1,2) 2-112 2.875 2.423 1.257 (DN65) (73,0) (61,5) (1,2) 3 3.500 2.950 1.867 (DN80) (88,9) (75,0) (1,2) Hydraulic Design Hydraulic calculations for the sizing of systems incorporating Spears® FlameGuard° CPVC Fire Sprinkler Products must be calculated using a Hazen -Williams C value of 150. Pipe friction loss calculations must be made according to NFPA Standard 13. The following table shows the allowance for friction loss for fittings, expressed as equivalent length of pipe. For additional information regarding friction loss, contact Spears". FG-3-1010 © 2010 Spears" Manufacturing Company Page 37 Allowance for friction Loss in Fittings Equivalent Feet (meters) of Pipe 314" 26,7 mm 1" 33,7 mm 1-114" 42,4 mm 1-112" 48,3 mm 2" 60,3 mm 2-1/2" 73,0 mm 3" 88,9 mm Tee Run 1(0,3) 1(0,3) 1(0,3) 1(0,3) 1(0,3) 2(0,6) 2(0,6) Tee Branch 3(0,9) 5(1,5) 6(1,8) 8(2,4) 10(3,1) 12(3,7) 15 (4,6) 90' Elbow 4(1,2) 5(1,5) 6(1,8) 7(2,1) 9(2,7) 12(3,7) 13(4,0) 45' Elbow 1(0,3) 1 (0,3) 2(0,6) 2(0,6) 2(0,6) 3 (0,9) 4(1,2) Coupling 1(0,3) 1(0,3) 1(0,3) 1 (0,3) 1(0,3) 2(0,6) 2(0,6) Hangers & Supports Since CPVC Fire Sprinkler pipe is rigid, it requires fewer supports than flexible, plastic systems. Spears® recommends use of hangers that are designed and listed for supporting the CPVC Fire Sprinkler pipe. However, some hangers designed for steel pipe may be used if their suitability is clearly established. These hangers must have a minimum 1f2-inch, load -bearing surface, and they must be selected to accommodate the specific pipe size. In addition, they cannot contain rough or sharp edges that contact the pipe, and they must not bind the pipe from axial movement. Vertical runs must be supported so that the weight of the run is not on a fitting or a joint. Horizontal runs must be braced so that the stress loads (caused by bending or snaking pipe) will not be placed on a fitting or a joint. Support spacing is shown in the following table. See "Snaking/Deflection of Pipe" in this manual for information regarding bending or snaking CPVC Fire Sprinkler Pipe, Pipe Size Nominal inches Maximum Support Spacing feet (meters) Wt. Water Filled Pipe lbslft (kglm) 314 (DN20) 5-112 (1,7) 0.427 (0,6) 1 (DN25) 6(1,8) 0.674 (0,9) 1-114 (DN32) 6-112 (2,0) 1.078 (1,5) 1-1/2 (DN40) 7(2,1) 1.412 (1,9) 2 (DN50) 8(2,4) 2.223 (3,0) 2-112 (DN65) 9(2,7) 3.254 (61,5) 3 (DN80) 10(3,0) 4.831 (75,0) Page 38 0 2010 Spears° Manufacturing Company FG-3-1010 NFPA 13D permits "support methods comparable to those required by focal plumbing codes." The above hanger/support requirements must also be followed on NFPA 13D systems. CAUTION: DO NOT use hanger items such as plumber's tape or "nail -on' devices. Pipe hanger must comply with NFPA 13, 13D and 13R. When a sprinkler head activates, a significant reactive force can be exerted on the pipe. With a pendent head, this reactive force can cause the pipe to lift vertically if it is not secured properly, especially if the sprinkler drop is from small diameter pipe. The pipe must be braced against the vertical lift -up with the closest hanger. Refer to the following illustration and Table A & B. �Ajl- — b Hatf suppad sparing - �J, I r c l upport ? ` sruWsupport i� Finish# Celia dine Table A - Maximum Support Spacing Distance End Line Sprinkler Head Drop Elbow Pipe Size Nominal inches Line Pressure <100 psi (<689kPa) Line Pressure >100 psi (>689kPa) 314 (DN20) 9 inches (228,6 mm) 6 inches (168,3 mm) 1 (DN25) 12 inches (304,8 mm) 9 inches (228,6 mm) 1-1/4 (DN32) 16 inches (406,4 mm) 12 inches (304,8 mm) 1-1/2 - 3 (DN40 - DN80) 24 inches (610,0 mm) 12 inches (304,8 mm) Note: Support spacing can be increased by approximately 50% for lower pressures. Table B - Maximum Support Spacing Distance Inhne Sprinkler Head Drop Tee Pipe Size Nominal inches Line Pressure <100 psi (<689kPa) Line Pressure >100 psi (>689kPa) 3/4 (DN20) 4 feet (1,22 meters) 3 feet* (0,91 meters) 1 (DN25) 5 feet (1,52 meters) 4 feet* (1,22 meters) 1-114 (DN32) 6 feet (1,83 meters) 5 feet* (1,52 meters) 1-112 - 3 (DN40 - DN80) 7 feet (2,13 meters) 7 feet (2,13 meters) Note: *Support spacing can be increased by one foot for lower pressures. FG-3-1010 0 2010 Spears° Manufacturing Company Page 39