FIR2021-0130+Fire_Alarm_Battery_Calculations+11.17.2021_3.09.13_PM+2525806Approved by Fire 11/30/2021 AFM /<_/F�tterer ------------------- Approved, subject to contractor pretest and field inspection BANK OF AMERICA FIRE ALARM SYSTEM EDMONDS WASHINGTON SHEET # DESCRIPTION FA— 01 SYSTEM INFORMATION FA-02 TYPICAL WIRING AND MOUNTING DETAILS FA 03 CALCULATION & RISER DIAGRAM FA-04 GROUND FLOOR PLAN - FIRE ALARM PLAN SHEET LIST ADD SMOKE DETECTORS AND HORN STROBES, STROBES TO NEW BOOSTER POWER SUPPLY. SCOPE OF WORK WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE — ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPLP S STROBE CIRCUIT TWO #14 FPLP T POWER SUPPLY TRIGGER TWO #16 FPLP I INITIATION CIRCUIT TWO #18 FPLP CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1 /2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1 /2" .82 SQUARE INCH 2" 1.34 SQUARE INCH 1. ALL WALL -MOUNTED AUDIBLE & VISUAL SIGNALING APPLIANCES SHALL HAVE THEIR HEIGHTS ABOVE THE FINISHED FLOOR AT 80" TO BOTTOM, NFPA 72, 2013 EDITI❑N, ALLOWS 80"-96" FOR VISUAL DEVICES (CH, 4-4,4) AND REQUIRES A MINIMUM OF 90" TO TOP FOR AUDIBLE DEVICES OR 6" FROM CEILING, WHICHEVER IS LOWER (CH, 4-3.5). FOR SLEEPING AREAS GREATER THAN 16' (LINEAR) VISIBLE N❑TIFICATI❑N SHALL BE WITHIN 16' OF PILL❑W AND GREATER THAN OR EQUAL TO 24" FROM CEILING TO TOP OF LENS FOR 110cd (CH. 4-4.4.3.2) 2. ALL EQUIPMENT SHALL BE U.L. LISTED. 3. ELECTRICAL CONTRACTOR SHALL FURNISH ACCESS PANELS TO AREAS THAT REQUIRE SERVICING, TROUBLE SH❑❑TING, ETC, 4. D❑ NOT DEVIATE FROM C❑NDUIT RUNS AS SHOWN ON FLOOR PLANS WITH❑UT PRI❑R APPROVAL FROM SYSTEM SUPPLIER (GUARDIAN SECURITY SYSTEMS, INC,, TEL (206)622-6545). FACTORS SUCH AS EXCESSIVE VOLTAGE DROP, ADDITI❑NAL PARTS, ENGINEERING, ETC,, THAT ARE A RESULT ❑F C❑NDUIT RUN DEVIATI❑NS SHALL BE THE SOLE RESP❑NSIBILITY OF THE ELECTRICAL CONTRACTOR, 5. DETECTORS SHALL NOT BE LOCATED IN A DIRECT AIR-FL❑W, NOR CLOSER THAN 3 FEET (900mm) FROM AN AIR SUPPLY DIFFUSER, 6. ALL 120VAC POWER REQUIREMENTS FOR THE FIRE ALARM SYSTEM SHALL BE FURNISHED BY THE ELECTRICAL CONTRACTOR AND SHALL MEET ALL REQUIREMENTS OF THE AUTH❑RITIES HAVING JURISDICTI❑N, 7. ALL FIRE ALARM DEVICE BACKB❑XES, FIRE ALARM TERMINAL CABINETS, GUTTERS, JUNCTI❑N BOXES, AND ASS❑CIATED C❑NDUITS SHALL BE FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR UNLESS ❑THERWISE NOTED, REFER TO FIRE ALARM SYMBOL LIST AND/OR M❑UNTING DETAILS FOR ADDITI❑NAL INF❑RMATI❑N. SYSTEM SUPPLIER PR❑VIDED BACKB❑XES SHALL BE INSTALLED BY ELECTRICAL CONTRACTOR UNLESS ❑THERWISE NOTED, 8, SMOKE DETECTOR TESTING SHALL BE ACC❑MPLISHED WITH APPROVED SMOKE, 9. ALL WIRING, INITIATING DEVICES AND ANNUNCIAT❑R PANEL SHALL BE SUPERVISED TO THE PRINCIPAL P❑INT OF ANNUNCIATI❑N, THE FIRE ALARM CONTROL PANEL TO SUPERVISE THE ANNUNCIAT❑R PANEL, ALL INITIATING AND INDICATING DEVICE CIRCUITS, 10, ALL WIRING SHALL BE CUT FOR IN AND OUT, WIRING SHALL NOT BE LOOPED THROUGH DEVICES, ALL SPLICED WIRE P❑SSESING SHIELDS SHALL HAVE SHIELDS SPLICED AND TAPED TO PREVENT GROUND FAULTS. 11. THE ALARM SYSTEM SHALL HAVE AN AUDIBILITY OF NOT LESS THAN 15olB ABOVE AMBIENT N❑ISE LEVELS, TESTING SHALL BE ACC❑MPLISHED WITH A cIB METER, 12. ALL DEVICES IN THE ALARM SYSTEM SHALL BE C❑MPATIBLE AND INSTALLED PER MANUFACTURER'S SPECIFICATI❑NS, 13. FIRE ALARM SYSTEM INSTALLATI❑N COMPANY SHALL BE UL LISTED (UUJS), 14. INSTALLATI❑N SHALL BE IN STRICT C❑MPLIANCE WITH NFPA, LOCAL AND STATE, NEC AND CONTRACT DRAWINGS 15. ALL C❑NDUIT SIZING AND R❑UTING BY ELECTRICAL CONTRACTOR PER NEC AND AHJ 16. THE FACP SHALL NOT BE ENERGIZED WITH❑UT THE PRESENCE ❑F G,S,S, TECHNICIANS 17, A SET OF INSTALLATI❑N AS -BUILT DRAWINGS SH❑WING ACTUAL C❑NDUIT AND CONDUCTOR ROUTES SHALL BE KEPT BY PROJECT FOREMAN FOR USE BY G.S.S. FIELD TECHNICIANS 18. A SET ❑F AS BUILT DRAWINGS TO BE TURNED INT❑ GSSINC WITH APPR❑PRIATE COLOR CODED MARKUP DRAWINGS (SEE SYMBOL LEGEND FOR COLOR C❑DING), QUANTITY SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT E FACP CONTROL PANEL 66" A.F.F. E (EXISTING) SFP-1024 NOTIFIER EXISTING TO TOP 1 BPS REff0_PLAFWSTER PSN-106 POTTER PROVIDED 66" A.F.F. POWER SUPPLY TO TOP 5 ® SMOKE DETECTOR 2WB SYSTEM SENSOR 4S DEEP W/ CEILING (CONVENTIONAL) 1-1/2" EXTN y FIRE ALARM PC2WL SYSTEM SENSOR 4S BOX CEILING 5 U HORN STROBE 1 MVP FIRE ALARM HORN STROBE P2RK SYSTEM SENSOR WPBB WALL MOUNT LOCATION & HEIGHT WEATHERPROOF AHJ APPROVED FIRE ALARM SCWL SYSTEM SENSOR 4S BOX CEILING 2 STROBE E ❑F E MANUAL PULL STATION NBG-12LX NOTIFIER EXISTING 48" A.F.F. TO CENTER ANN REMOTE EXISTING EXISTING EXISTING 60" A.F.F. E ANNUNCIATOR TO CENTER END —OF —LINE VERIFY LOCATION RESISTOR IN FIELD EXISTING N/A N/A N/A N/A E DEVICE A.F.F. ABOVE FINISHED N/A N/A N/A N/A FLOOR F.B.O. FURNISHED BY N/A N/A N/A N/A OTHERS N/A NOT N/A N/A N/A N/A APPLICABLE — — — RED AS BUILT N/A N/A N/A ADD OR CHANGE — — — GREEN AS BUILT N/A N/A N/A REMOVE BLUE AS BUILT N/A N/A N/A NOTES TO CAD F I R2021-0130 RONALD MANSFIELD JR. NICET LEVEL IV CERT. #111878 EXP. 09/01/2022 cn z 0 U) w w cn Q w J w t_fD ON 0 Or- ao z N o � z C) N Q yw I- Z~ w LO o LO ��� N L:> CV Q I— (D C/) N � w m w � o_ z 0 IZ U cn w 0 N c� z a o- 0 o_ 0 V) W Q o N \ 0 \ C)aaaaa z O Q N o 00 U_ Er W ^Z O W 0 zz �_1 LL LL Q Cn O Qo W (y)o Z O rn Q v♦ 1120 0 LU RECEIV 10 Nov 18 20 1 CITY E DEVELOPMENT SER _-ES DEPARTMENT SCALE: NOT TO SCALE DRAWN BY: P.GUPTA DESIGNED BY: T. QUAALE DATE: 1 1 /04/21 BACKROUND PLAN PROVIDED BY: JOB NUMBER:62901-1 WIRE DESIGNATION GENERAL NOTES SYMBOLS / LEGEND Copvriaht 2014 by Guardian Securitv Svstems. Inc. All Riahts Reserved SHEET FA- 01 TILE CEILII HARD LID - CEILING s HORN/STROBE MOUNTING (DROP CEILING 00 p� ®®® 000 4S BOX CEILING HORN/STROBE HORN/STROBE MOUNTING (HARD LID POTTER PSN-106 REMOTE BOOSTER POWER SUPPLY WIRING DETAIL NAC CKT S1 TO PSN S HORN STROBE + + EOL HORN HORN HORN WEATHERPROOF STROBE HORN STROBE TYPICAL NAC CIRCUIT WIRING DIAGRAM HORN STROBE/STROBE — R � 4S BOX ------ E _ �J 80" A.F.F. TO BOTTOM MANUAL PULL STATION 48" A.F.F. TO CENT[ 4" SQUARE DEEP BACK BOX WITH 1 G TRIM RING STROBE & MANUAL STATION MOUNTING DETAILS TYPICAL WIRING AND MOUNTING DETAILS II 1K1r TTfIAI nnV NEXT DEVICE -NDED 1INATED CEILING SMOKE DETECTOR MOUNTING DETAILS BELOW ROOF (FIELD VERIFY —TO BE APPROVED BY FIF WEATHERPROOF HORN STROBE WPBB WEATHERPROOF BACKBOX 4S DEEP BOX W/ 2 GANG RING OUTDOOR HORN STROBE MOUNTING DETAILS F I R2021-0130 RONALD MANSFIELD JR. NICET LEVEL IV CERT. #111878 EXP. 09/01/2022 U) z O w o- w Q W J W � �'D O a0 coy-, oft 0, 00 z N o � z C) N Q yw I- Z~ w cn L) 0 o cn Ln Q N L:> CV Q I- \0 (D C/) N � � J W m0 w IL z O n U W 0 U) C5 Z Q Of 0 O- O N w o N \ \ C)aaaaa J Q W 0 0 Z O Q N O Z U_ � w � w U) O � Cn zZ ry- Q Cn ILL Q 0 O Qo� Z LU c �' o Q z O C'3 m o Z W J Q RECEI EL) Nov 18 20 1 n CITY OF EDMON DEVELOPMENT SER -ES DEPARTMENT SCALE: NOT TO SCALE DRAWN BY: P.GUPTA DESIGNED BY: T. QUAALE DATE: 1 1 /04/21 BACKROUND PLAN PROVIDED BY: JOB NUMBER:62901-1 SHEET FA- 0 2 Capvriaht 2014 Guardian Securitv Svstems. Inc. All Riahts Reserved FIRE ALARM BOOSTER POWER SUPPLY BATTERY CALCULATION Project: COCHRAN ELECTRIC Panel: NEW POTTER PSN-106 BOOSTER POWER SUPPLY Date: November 4, 2021 Module/Device Qty Standby Total Standby Alarm Total Alarm mA mA mA mA Power Module 1 60 60 0 200 200 0 A TOTAL FIRE ALARM POWER SUPPLY 60 200 B Auxiliary Device Current 0 0 C Notification Appliance Load (Max. Total / mA) 0 820 Total(A)= 60 Total(B)= 1020 CALCULATION D Total current ratings of all devices in system (line A + line B + line C) 60 1020 E Total current ratings converted to amperes (line D x .001) 0.06 1.02 F Number of standby hours (24 or 60 per NFPA 72, Chapter 1, 1-5.2.5). 24 G Multiply lines E and F Total Standby AH 1.44 H Alarm sounding period in hours (5 mins+ .0833 hours) 0.0833 1 Multiply lines E and H Total Alarm AH 0.084966 J Add lines G and I Total Standby and Alarm AH 1.524966 K Multiply line J by 1.2 (20% extra insurance to meet desired performance) 1.8299592 12-V DC BATTERY SIZE RECOMMENDED AMPERE -HOUR 7 F IFI Notification Appliance Circuit Detail PROJECT: COCHRAN ELECTRIC Panel: BPS REMOTE POWER SUPPLY Wire Resistance 2.58 Date: November 5, 2021 CURRENT TOTAL= 820.00 2 PC2W @ @15Cd 71' 142 1 PC2W @ @30Cd 90 2 PC2W @ @95Cd 165 330 P2RK@75Cd 176 176 , 2 SCW @15cd 41 82 AM ML-66 0 DEVICES 8 TOTAL mA= 820 14 ■ Total Wire Resistance ( R ) Total Device Load, Amps (1) Voltage Drop ( E ) EOL Voltage CALACULATION_ S S S S S WP S S1-1 S1-2 S1-3 S1-4 S1-5 95d 95Cd 15Cd 15Cd 75Cd BPS 120 VAC, DEDICATED (BY OTHERS) RISER DIAGRAM 163 23.31 820 (WL*2)*(R/ft) 0.84 ■ (Total Cct Load) 0.82 (E= I * R) 0.69 24 - E) 23.31 9 S S1-6 S1-7 S1-8 15Cd 15Cd 30Cd EOL S1 F I R2021-0130 RONALD MANSFIELD JR. NICET LEVEL IV CERT. #111878 EXP. 09/01/2022 z 0 U) W w a W W --I O r'(D_ 0, ao Z N O z N X yw J Q Q U N LJ_J N Q _ ,�D CD C/) N � w m 0 IL W z 0 m U Lu 0 0 0 Z a Of 0 D- O W Q o N \ O \ C)aaaaa Q C� Q 0 Q o U � W Er w z L LJ U) cn 0zz Q �Q� L.L Q 06 O Qo� LU `) 0 z z� o Q 0 0o o — w � U RECEIV HU Nov 18 20 1 CITY E DEVELOPMENT SE SER CES DEPARTMENT SCALE: NOT TO SCALE DRAWN BY: P.GUPTA DESIGNED BY: T. QUAALE DATE: 1 1 /04/21 BACKROUND PLAN PROVIDED BY: JOB NUMBER:62901-1 SHEET FA- 0 3 Copvriaht 2014 by Guardian Securitv Svstems. Inc. All Riahts Reserved L � o ❑ ❑0- 0 o L GROUND FLOOR FIRE ALARM PLAN_ 3/1611= 1 loll F I R2021-0130 RONALD MANSFIELD JR. NICET LEVEL IV CERT. #111878 EXP. 09/01/2022 U) z 0 w o' w Q W J W � r� O O-, ao � oft 0 ao z N o � z � N Q yw I- Z~ w �LC) o� N LJJ N Q I— � o C/') N � � J W m w 0 z 0 IZ U U) W 0 N 0 Z Q Of 0 O- O N W Q 0 N \ O \ C)aaaaa z g 2 oc 1� Q 0 w U_ cr) Ir z— CC w 0 LL LLJ c) z Q � zQ czn z LL Q O Qo� In w C)o Z� o rr Q O om O H n z RECEIV le Nov 18 20 1 rr CITY OF EDMON DEVELOPMENT SER CES ' R DEPARTMENT U SCALE: 3/1 6'=1'-O" DRAWN BY: P.GUPTA DESIGNED BY: T. QUAALE DATE: 1 1 /04/21 BACKROUND PLAN PROVIDED BY: JOB NUMBER:62901-1 SHEET FA- 0 2 Capvriaht 2014 Guardian Securitv Svstems. Inc. All Riahts Reserved