FIR2021-0141+Fire_Alarm_Batter_and_Voltage_Calculations+12.7.2021_11.14.45_AM+2557574KWpps Dayton St Dayton St Y Y Fine Alum s Automation W a 13330 SE 30th St Bellevue WA 98005 THE ATRIUM V) D (425) 223-3164 Fax: (425) 223-3165 < Lic. #: KLEPPI*938C6 229 3RD AVE S. EDMOND5, WA 98020 Fire Alarm Device Numbering (5LC) ADDRESSABLE DEVICES NOTIFICATION DEVICES SPEAKERS * SPEAKER/ STROBES CIRCUIT CIRCUIT DEVICE # CIRCUIT DEVICE ADDKE55 DEVICE # CANDELA WATT SETTING @ (70VKM) CANDELA • S LC ### NAC # • ### ## CD NAC # • ### ## CD #.## W CIRCUIT LINE TYPE Circuit Legend Abbreviation Type Name _0 _C'_tZ A 5 B Z # I G/2 FPLP CONVENTIONAL U # I G/2 FPLP 5LC-51GNAL LINE CIRCUIT A # 1412 FPLP NAC-NOTIFICATION CIRCUIT 5 # I G/2 FPLP 5HElLDED AUDIO / SPEAKER CIRCUIT 5 # 1814 FPLP 551-15 V # 1812 FPLP VOICE BUS RISER ROOM LAYOUT (E) (N) r FAC BPS #1 f (E) ZN-02 ZN-0 EXISTING RISER ROOM - DEVICE NOMENCLATURE DEVICE INSTALLATION REQUIREMENTS HVAC SUPPLY DIFFUU5EF NOT PERMITTED I HERE s' MIN j FINISHED CEILING f4" — AUDIO E VISUAL DEVICES 17-77-77 G" MIN FROM CEILING 1// � 3' MIN SMOKE/HEAT DETECTOR SMOKE/HEAT DETECTOR PERMITTED HERE r' MAx SMOKE/F1EAT DETECTOR NOT PERMITTED HERE i 1 SMOKE/HEAT DETECTOR PERMITTED HERE Fig FACP FIRE FIRE FIGHTER FIGHTER MANUAL PULL STATION " coo PHONE HANDSET 6"H CABINET iso W w 801,MIN ass sus e J e. Zos oes Zs o 9G" MAX o 3. PULL O Q GG" AFF 72" AFF 72" AFF 72" AFF O 0 w = FIRE 48" AFF PHONE JACK FINISHED FLOOR PROJECT NOTES - REMOVE THE G UNSUPERVISED NAC CIRCUITS OFF OF THE EX15TING 51LENT KNIGHT 5K-5207 CONVENTIONAL FIRE ALARM CONTROL PANEL AND RELOCATE THEM TO A NEW 51LENT KNIGHT 5K-P5 10 NAC POWER SUPPLY. THE NEW POWER SUPPLY WILL HAVE 7 NAC CIKCUIT5 AVAILABLE FOR USE. - ADD A SYSTEM 5EN50K 2W-13 SMOKE DETECTOR OVER THE FACP * POWER SUPPLY, 51NCE NO SMOKE DETECTOR 15 CURRENTLY INSTALLED ABOVE THE EX15TING FACP. Approved by Fire 12/13/2021 AFM fCF�tterer Bill Of Material Report QTY MANUFACTURER PART NO DESCRIPTION Mounting 1 SILENT KNIGHT SK-5207 EXISTING FIRE ALARM CONTROL PANEL SURFACE 1 SILENT KNIGHT SK-PS10 NEW NAC APPLIANCE POWER SUPPLY SURFACE 1 SILENT KNIGHT PS -SA EXISTING CONVENTIONAL MANUAL PULL STATION 4S BOX 1 SYSTEM SENSOR 2W-B NEW PHOTOELECTRIC SMOKE DETECTOR WITH BASE 4S BOX DEVICE DESCRIPTION SYMBOL BPS NEW NOTIFICATION POWER EXPANDER FACP EXISTING CONVENTIONAL FIRE ALARM CONTROL PANEL L(I EXISTING CONVENTIONAL PULL STATION ONEW PHOTOELECTRIC SMOKE DETECTOR WITH BASE Q- Alder St D U) VICINITY MAP 229 3 rd Ave S, Edmonds, WA 98020 A D M GENERAL NOTES / SCOPE OF WORK 1. FACTORY RECOMMENDED MINIMUM WIRING 51ZE5, TYPE AND CONSTRUCTION A5 NOTED ON THE DRAWINGS MUST BE STRICTLY FOLLOWED. ANYONE WILLING TO MAKE CHANGES WILL DO 50 AT THEIR OWN RISK!! 2. WHEN POWERING UP THE FACP OR REMOTE POWER 5UFFLIF-5 BE SURE TO APPLY AC VOLTAGE BEFORE DC VOLTAGE. WHEN POWERING DOWN REMOVE DC SUPPLY BEFORE AC DISCONNECT. 3. THE CIRCUIT ROUTING AND WIRING COUNTS ON THE FLOOR PLAN DRAWINGS ARE SHOWN DIAGRAMMATIC BASED ON CONTINUOUS AND SHORTEST P055113LE ROUTING FROM THE CONTROL PANEL AND BETWEEN CONNECTED FIELD DEVICES WITH NO FHY51CAL 0135TKUCTION5. THE WIRING OR CIRCUIT COUNTS (IF SHOWN) ARE PROVIDED A5 A CONVENIENCE ONLY AND A5 MEANS TO HASTEN INSTALLATION OR TO DETERMINE WIRING ROUTES. 4. WIRE SHOWN IN TH15 DRAWING SET 15 PERMITTED IN RACEWAYS LEADING TO FIRE PROTECTION EQUIPMENT. OTHER WIRE SHALL NOT BE PERMITTED. 5. ALL WORK SHALL BE DONE IN ACCORDANCE WITH CURRENT EDITION OF U.B.C., TITLE 19, TITLE 24, NFPA AND AMEKICAN5 WITH DISABILITIES ACT (ADA) A5 REQUIRED BY THE GOVERNING AGENCIES. G. PER NFPA 72-201 3 SECTION 5-3.G. 1 .3, DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES 15 COMPLETE AND FINALED. 7. ALL WIRING, CABLE, AND EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 70,NATIONAL ELECTRICAL CODE, ARTICLE 7GO, 770, 780, AND NFPA 72, 4.4. 1 .2 FIRE PROTECTIVE 51GNALING SYSTEMS. 8. SMOKE DETECTORS SHALL NOT BE LOCATED WITHIN A 3'0" KADIU5 OF SUPPLY -AIR DUCTS. NFPA 72-201 3, SECTION 2-3.5.1. 9. FIRE ALARM SYSTEM INSTALLATION SHALL CONFORM WITH THE LATEST U.L., N.E.C., N.F.P.A., W.A.C., AND OTHER 5TANDAKD5 A5 APPLICABLE TO THE CITY 5TANDAKD5. F I R2021-0141 � � A o LEVEL IV so EXPIRES: 11/01/21 PROJECT NAME O N � Q LLJ IC) O I) LU JOB # DATE: 1 2/G/202 1 = m In m CD CD CDm CID U >- U U U U U U U U m o 0 0 0 0 0 0 0 O SHEET L15T I COVER SHEET I SHEET DESCRIPTION COVER SHEET (E) = EX15TING DEVICE (N) = NEW DEVICE RECEIVED Dec 07 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT SHEET NUMBER