FIR2021-0141+Fire_Alarm_Batter_and_Voltage_Calculations+12.7.2021_11.14.45_AM+2557574KWpps
Dayton St Dayton St
Y Y
Fine Alum s Automation
W
a 13330 SE 30th St
Bellevue WA 98005
THE ATRIUM V)
D (425) 223-3164 Fax: (425) 223-3165
< Lic. #: KLEPPI*938C6
229 3RD AVE S.
EDMOND5, WA 98020
Fire Alarm Device Numbering
(5LC) ADDRESSABLE DEVICES
NOTIFICATION DEVICES
SPEAKERS * SPEAKER/ STROBES
CIRCUIT
CIRCUIT
DEVICE #
CIRCUIT
DEVICE ADDKE55
DEVICE #
CANDELA
WATT SETTING @ (70VKM)
CANDELA
•
S LC ###
NAC # • ### ## CD
NAC # • ### ## CD #.## W
CIRCUIT LINE TYPE
Circuit Legend
Abbreviation
Type
Name
_0
_C'_tZ
A
5
B
Z
# I G/2 FPLP
CONVENTIONAL
U
# I G/2 FPLP
5LC-51GNAL LINE CIRCUIT
A
# 1412 FPLP
NAC-NOTIFICATION CIRCUIT
5
# I G/2 FPLP 5HElLDED
AUDIO / SPEAKER CIRCUIT
5
# 1814 FPLP
551-15
V
# 1812 FPLP
VOICE BUS
RISER ROOM LAYOUT
(E) (N)
r FAC BPS #1 f (E)
ZN-02
ZN-0
EXISTING
RISER
ROOM
- DEVICE NOMENCLATURE
DEVICE INSTALLATION
REQUIREMENTS
HVAC SUPPLY
DIFFUU5EF
NOT
PERMITTED
I HERE
s'
MIN j FINISHED CEILING
f4" —
AUDIO E VISUAL DEVICES
17-77-77
G" MIN FROM CEILING
1// �
3' MIN
SMOKE/HEAT
DETECTOR
SMOKE/HEAT DETECTOR
PERMITTED HERE
r'
MAx
SMOKE/F1EAT DETECTOR
NOT PERMITTED HERE
i
1
SMOKE/HEAT DETECTOR
PERMITTED HERE
Fig
FACP FIRE FIRE
FIGHTER FIGHTER
MANUAL
PULL
STATION
" coo
PHONE HANDSET
6"H
CABINET
iso
W w
801,MIN ass sus
e
J
e. Zos oes Zs o
9G" MAX o 3.
PULL
O
Q
GG" AFF
72" AFF 72" AFF 72" AFF
O
0
w
=
FIRE 48" AFF
PHONE
JACK
FINISHED
FLOOR
PROJECT NOTES
- REMOVE THE G UNSUPERVISED NAC CIRCUITS OFF OF THE
EX15TING 51LENT KNIGHT 5K-5207 CONVENTIONAL FIRE ALARM
CONTROL PANEL AND RELOCATE THEM TO A NEW 51LENT KNIGHT
5K-P5 10 NAC POWER SUPPLY. THE NEW POWER SUPPLY WILL
HAVE 7 NAC CIKCUIT5 AVAILABLE FOR USE.
- ADD A SYSTEM 5EN50K 2W-13 SMOKE DETECTOR OVER THE
FACP * POWER SUPPLY, 51NCE NO SMOKE DETECTOR 15
CURRENTLY INSTALLED ABOVE THE EX15TING FACP.
Approved by Fire
12/13/2021 AFM fCF�tterer
Bill Of Material Report
QTY
MANUFACTURER
PART NO
DESCRIPTION
Mounting
1
SILENT KNIGHT
SK-5207
EXISTING FIRE ALARM CONTROL PANEL
SURFACE
1
SILENT KNIGHT
SK-PS10
NEW NAC APPLIANCE POWER SUPPLY
SURFACE
1
SILENT KNIGHT
PS -SA
EXISTING CONVENTIONAL MANUAL PULL STATION
4S BOX
1
SYSTEM SENSOR
2W-B
NEW PHOTOELECTRIC SMOKE DETECTOR WITH BASE
4S BOX
DEVICE
DESCRIPTION
SYMBOL
BPS
NEW NOTIFICATION POWER EXPANDER
FACP
EXISTING CONVENTIONAL FIRE ALARM CONTROL PANEL
L(I
EXISTING CONVENTIONAL PULL STATION
ONEW
PHOTOELECTRIC SMOKE DETECTOR WITH BASE
Q-
Alder St D
U)
VICINITY MAP
229 3 rd Ave S,
Edmonds, WA 98020
A
D
M
GENERAL NOTES / SCOPE OF WORK
1. FACTORY RECOMMENDED MINIMUM WIRING 51ZE5, TYPE AND
CONSTRUCTION A5 NOTED ON THE DRAWINGS MUST BE
STRICTLY FOLLOWED. ANYONE WILLING TO MAKE CHANGES WILL
DO 50 AT THEIR OWN RISK!!
2. WHEN POWERING UP THE FACP OR REMOTE POWER 5UFFLIF-5
BE SURE TO APPLY AC VOLTAGE BEFORE DC VOLTAGE. WHEN
POWERING DOWN REMOVE DC SUPPLY BEFORE AC
DISCONNECT.
3. THE CIRCUIT ROUTING AND WIRING COUNTS ON THE FLOOR
PLAN DRAWINGS ARE SHOWN DIAGRAMMATIC BASED ON
CONTINUOUS AND SHORTEST P055113LE ROUTING FROM THE
CONTROL PANEL AND BETWEEN CONNECTED FIELD DEVICES WITH
NO FHY51CAL 0135TKUCTION5. THE WIRING OR CIRCUIT COUNTS
(IF SHOWN) ARE PROVIDED A5 A CONVENIENCE ONLY AND A5
MEANS TO HASTEN INSTALLATION OR TO DETERMINE WIRING
ROUTES.
4. WIRE SHOWN IN TH15 DRAWING SET 15 PERMITTED IN
RACEWAYS LEADING TO FIRE PROTECTION EQUIPMENT. OTHER
WIRE SHALL NOT BE PERMITTED.
5. ALL WORK SHALL BE DONE IN ACCORDANCE WITH CURRENT
EDITION OF U.B.C., TITLE 19, TITLE 24, NFPA AND AMEKICAN5
WITH DISABILITIES ACT (ADA) A5 REQUIRED BY THE GOVERNING
AGENCIES.
G. PER NFPA 72-201 3 SECTION 5-3.G. 1 .3, DETECTORS SHALL
NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP
OF ALL TRADES 15 COMPLETE AND FINALED.
7. ALL WIRING, CABLE, AND EQUIPMENT SHALL BE INSTALLED IN
ACCORDANCE WITH NFPA 70,NATIONAL ELECTRICAL CODE,
ARTICLE 7GO, 770, 780, AND NFPA 72, 4.4. 1 .2 FIRE
PROTECTIVE 51GNALING SYSTEMS.
8. SMOKE DETECTORS SHALL NOT BE LOCATED WITHIN A 3'0"
KADIU5 OF SUPPLY -AIR DUCTS. NFPA 72-201 3, SECTION
2-3.5.1.
9. FIRE ALARM SYSTEM INSTALLATION SHALL CONFORM WITH
THE LATEST U.L., N.E.C., N.F.P.A., W.A.C., AND OTHER
5TANDAKD5 A5 APPLICABLE TO THE CITY 5TANDAKD5.
F I R2021-0141
� � A
o LEVEL IV so
EXPIRES: 11/01/21
PROJECT NAME
O
N
�
Q
LLJ
IC)
O
I)
LU
JOB #
DATE: 1 2/G/202 1
= m In m CD CD CDm CID
U
>- U U U U U U U U
m o 0 0 0 0 0 0 0
O
SHEET L15T
I COVER SHEET I
SHEET DESCRIPTION
COVER SHEET
(E) = EX15TING DEVICE
(N) = NEW DEVICE
RECEIVED
Dec 07 2021
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
SHEET NUMBER