APPROVED Structural PlansI GENERAL STRUCTURAL NOTES (THE FOLLOWING APPLY UNLESS SHOWN OTHERWISE ON THE PLANS.) A. GENERAL 1. ALL MATERIALS, WORKMANSHIP, DESIGN, AND CONSTRUCTION SHALL CONFORM TO THE DRAWINGS, SPECIFICATIONS, AND THE INTERNATIONAL BUILDING CODE {IBC}, 2018 EDITION, AS AMENDED BY LOCAL JURISDICTION. 2. STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH ARCHITECTURAL DRAWINGS FOR BIDDING AND CONSTRUCTION. CONTRACTOR SHALL VERIFY DIMENSIONS AND CONDITIONS FOR COMPATIBILITY AND SHALL NOTIFY ARCHITECT OF ANY DISCREPANCIES PRIOR TO CONSTRUCTION. SEE ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS AND DIMENSIONS OF DOOR AND WINDOW OPENINGS. SEE MECHANICAL DRAWINGS FOR SIZE AND LOCATION OF MISCELLANEOUS MECHANICAL OPENINGS. 3. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SAFETY PRECAUTIONS AND THE METHODS, TECHNIQUES, SEQUENCES OR PROCEDURES REQUIRED TO PERFORM HIS WORK. STRUCTURAL DESIGN OF THE BUILDING IS BASED ON RESISTANCE TO DEAD LOADS, CODE SPECIFIED LATERAL LOADS, AND MAXIMUM EXPECTED SERVICE LOADS. NO CONSIDERATION HAS BEEN GIVEN TO LOADS WHICH WILL BE INDUCED BY ERECTION PROCEDURES. THE CONTRACTOR SHALL VERIFY, TO THE SATISFACTION OF HIMSELF AND THE OWNER, THE ABILITY OF THE STRUCTURE TO RESIST ALL ERECTION LOADS WITHOUT EXCEEDING THE ALLOWABLE STRESSES OF THE MATERIALS USED. WHERE ERECTION LOADS WOULD OVERSTRESS THE STRUCTURE, THE CONTRACTOR SHALL SUBMIT DESIGN DOCUMENTS FOR TEMPORARY BRACING AND STRENGTHENING, INCLUDING FABRICATION AND ERECTION DRAWINGS, TO THE ARCHITECT FOR REVIEW. THESE DOCUMENTS SHALL BEAR THE SEAL AND SIGNATURE OF A REGISTERED ENGINEER IN THE STATE OF WASHINGTON. THE CONTRACTOR SHALL PROVIDE, INSTALL AND IF NECESSARY REMOVE SUCH TEMPORARY WORK AS REQUIRED. 4. CONTRACTOR -INITIATED CHANGES SHALL BE SUBMITTED IN WRITING TO THE ARCHITECT AND ENGINEER FOR APPROVAL PRIOR TO FABRICATION OR CONSTRUCTION. CHANGES SHOWN ON SHOP DRAWINGS ONLY WILL NOT SATISFY THIS REQUIREMENT. 5. DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRUCTION. WHERE CONDITIONS ARE NOT SPECIFICALLY INDICATED, BUT ARE OF SIMILAR CHARACTER TO DETAILS SHOWN, SIMILAR DETAILS OF CONSTRUCTION SHALL BE USED, SUBJECT TO REVIEW AND APPROVAL BY THE ARCHITECT AND THE ENGINEER. 6. ALL STRUCTURAL SYSTEMS WHICH ARE TO BE COMPOSED OF COMPONENTS TO BE FIELD ERECTED SHALL BE SUPERVISED BY THE SUPPLIER DURING MANUFACTURING, DELIVERY, HANDLING, STORAGE AND ERECTION IN ACCORDANCE WITH INSTRUCTIONS PREPARED BY THE SUPPLIER. 7. INSPECTIONS: INSPECTIONS OF THE WOOD FRAMING, THE STEEL REBAR AND WOOD FORMS FOR CONCRETE FOOTINGS & FOUNDATIONS, AND CONCRETE SLABS ARE REQUIRED PER IBC SECTION 109.3. 8. PRE -MANUFACTURED, PRE-ENGINEERED STRUCTURAL COMPONENTS SHALL BE DESIGNED BASED ON THE CRITERIA PRESENTED IN THE CONTRACT DOCUMENTS. THE COMPONENT DESIGNER IS RESPONSIBLE FOR CODE CONFORMANCE, TEMPORARY AND PERMANENT BRACING AND ALL NECESSARY CONNECTIONS, INCLUDING CONNECTIONS TO THE PRIMARY STRUCTURE, NOT SPECIFICALLY CALLED OUT ON THE ARCHITECTURAL OR STRUCTURAL DRAWINGS. SHOP DRAWINGS SHALL INDICATE THE MAGNITUDE AND DIRECTION OF ALL LOADS IMPOSED ON THE PRIMARY STRUCTURE. SHOP DRAWINGS AND CALCULATIONS SHALL BE SUBMITTED AS NOTED PREVIOUSLY. B. DESIGN CRITERIA 1. DESIGN LOADS ROOF LIVE LOAD 25 PSF (SNOW) RESIDENTIAL LIVE LOAD 40 PSF ALLOWABLE SOIL PRESSURE 1,500 PSF AT 1'-6" DEPTH LATERAL EARTH PRESSURE 50 PCF PASSIVE PRESSURE 300 PCF COEFFICIENT OF FRICTION 0.4 2. LATERAL RESISTANCE SYSTEM: SHEATHED BEARING WALLS, ASCE 7-10 C. RENOVATION DEMOLITION: CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS BEFORE COMMENCING ANY DEMOLITION. SHORING SHALL BE INSTALLED TO SUPPORT EXISTING CONSTRUCTION AS REQUIRED AND IN A MANNER SUITABLE TO THE WORK SEQUENCES. DEMOLITION DEBRIS SHALL NOT BE ALLOWED TO DAMAGE OR OVERLOAD THE EXISTING STRUCTURE. LIMIT CONSTRUCTION LOADING (INCLUDING DEMOLITION DEBRIS) ON EXISTING FLOOR SYSTEMS TO 40 PSF. CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS, MEMBER SIZES, AND CONDITIONS PRIOR TO COMMENCING ANY WORK. ALL DIMENSIONS OF EXISTING CONSTRUCTION SHOWN ON THE DRAWINGS ARE INTENDED AS GUIDELINES ONLY AND MUST BE VERIFIED. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT AND ENGINEER IS EXISTING CONDITIONS DETERMINED DURING WORK VARY FROM THE EXISTING CONSTRUCTION SHOWN ON THE DRAWINGS. EXISTING REINFORCING SHALL BE SAVED WHERE AND AS NOTED ON THE PLANS. SAW CUTTING, IF AND WHERE USED, SHALL NO CUT EXISTING REINFORCING THAT IS TO BE SAVED. A. ALL NEW OPENINGS THROUGH EXISTING WALLS, SLABS, AND BEAMS SHALL BE ACCOMPLISHED BY SAW CUTTING WHEREVER POSSIBLE. CORNERS SHALL NOT BE OVER CUT. B. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS AND LOCATION OF MEMBERS PRIOR TO CUTTING ANY OPENINGS. C. SMALL ROUND OPENINGS SHALL E ACCOMPLISHED BY CORE DRILLING. D. WHERE NEW REINFORCING TERMINATES AT EXISTING CONCRETE, DRILL AND EPDXY CONTRACTOR SHALL CHECK FOR DRY ROT AT ALL AREAS OF NEW WORK. ALL ROT SHALL BE REMOVED AND DAMAGED MEMBERS SHALL BE REPLACED OR REPAIRED AS DIRECTED BY THE ENGINEER OR ARCHITECT. D. FOUNDATION 1. FOUNDATION EXCAVATION, BACKFILLAND COMPACTION SHALL CONFORM TO SPECIFICATION REQUIREMENTS. THIS CONSTRUCTION WORK, INCLUDING DRAINAGE, SHORING AND SUCH OTHER RELATED WORK AS REQUIRED, SHALL BE CONDUCTED BY THE CONTRACTOR UNDER THE OBSERVATION AND DIRECTION OF THE GEOTECHNICAL ENGINEER. 2. FOOTINGS SHALL BEAR ON SOLID UNDISTURBED EARTH (CONTROLLED, COMPACTED STRUCTURAL FILL OR BOTH) AT LEAST 18" BELOW LOWEST ADJACENT FINISHED GRADE. MATERIAL TO BE COMPACTED TO 95% MINIMUM OF MAXIMUM DRY DENSITY AS DETERMINED BYASTM ❑1557. 3. FOOTINGS MAY BE POURED IN NEAT EXCAVATIONS PROVIDED SIZE IS INCREASED 3" AT EACH INTERFACE WITH SOIL. 4. ALL FOOTING EXCAVATIONS SHALL BE HAND CLEANED PRIOR TO PLACING CONCRETE. 5. ALL ABANDONED FOOTINGS, UTILITIES, ETC. THAT INTERFERE WITH NEW CONSTRUCTION SHALL BE REMOVED. 6. CONTRACTOR SHALL PROVIDE FOR DESIGN AND INSTALLATION OF ALL CRIBBING, SHEATHING, AND SHORING REQUIRED TO SAFELY RETAIN EXCAVATIONS. 7. BACKFILL BEHIND ALL WALLS WITH WELL DRAINING, GRANULAR FILL MATERIAL, AND PROVIDE PERFORATED PIPE DRAINS AS DESCRIBED IN THE SOILS REPORT. BACKFILL BEHIND WALLS SHALL NOT BE PLACED BEFORE THE WALL IS PROPERLY SUPPORTED BY THE FLOOR SLAB, OR TEMPORARY BRACING. ALL FOOTINGS SHALL BE CENTERED BELOW CENTERLINE OF COLUMNS OR WALLS ABOVE, UNLESS NOTED OTHERWISE. E. CONCRETE 1. ULTIMATE STRENGTH DESIGN PER INTERNATIONAL BUILDING CODE AND ACI 318-14 2. CONCRETE FOR FOOTINGS AND SLABS -ON -GRADE SHALL CONFORM TO A 28- DAY STRENGTH OF fc = 2500 PSI, SHALL CONTAIN NOT LESS THAN 5-1/2 SACKS OF CEMENT PER CUBIC YARD, AND SHALL BE PROPORTIONED TO PRODUCE A SLUMP OF 5" OR LESS. CONCRETE EXPOSED TO EARTH OR WEATHER SHALL HAVE A 28-DAY STRENGTH OF fc= 3000 psi. THE MINIMUM AMOUNTS OF CEMENT AND MAXIMUM AMOUNTS OF WATER MAY BE CHANGED IF A CONCRETE DESIGN MIX IS SUBMITTED TO THE ENGINEER AND THE BUILDING OFFICIAL FOR APPROVAL TWO WEEKS PRIOR TO PLACEMENT OF CONCRETE. THE CONCRETE PERFORMANCE MIX SHALL INCLUDE THE AMOUNTS OF CEMENT, FINE AND COARSE AGGREGATES, WATER AND ADMIXTURES AS WEI THE WATER - CEMENT RATIO, SLUMP, CONCRETE YIELD AND SUBSTANTIATING STRENGTH DATA IN ACCORDANCE WITH ACI 318, SECTION 5.3. CONTRACTOR MAINTAINS RESPONSIBILITY FC SPECIFIED PERFORMANCE OF CONCRETE PRODUCTS. ALL CONCRETE EXPOSED TO FREEZING TEMPERATURES WHILE CURING AND ALL CONCRETE PERMANENTLY EXPOSED TO WEATHER SHALL BE AIR -ENTRAINED WITH AN AIR -ENTRAINING AGENT CONFORMING TO IBC SECTION 1904.2. TOTAL AIR CONTENT SHALL BE IN ACCORDANCE WITH TABLE 1904.2.1 OF THE INTERNATIONAL BUILDING CODE. NO ADMIXTURES, OTHER THAN FOR AIR-ENTRAINMENTAS NOTED ABOVE, SHALL BE USED WITHOUT PRIOR REVIEW BY THE ENGINEER. ALL CONCRETE IN ELEVATED STRUCTURAL SLABS AND BEAMS SHALL BE POURED MONOLITHICALLY UNLESS SHOWN OTHERWISE OR APPROVED BY THE ENGINEER PRIOR TO PLACEMENT. 3. REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM A615 (INCLUDING SUPPLEMENT S1), GRADE 60, fy = 60,000 PSI. EXCEPTIONS: ANY BARS SPECIFICALLY NOTED ON THE DRAWINGS AS GRADE 40, fy = 40,000 PSI. WELDED WIRE FABRIC: ASTM A82 AND ASTM Al85, SPLICE WITH AT LEAST ONE FULL MESH. PLACE AT MID -DEPTH, OR SLIGHTLY ABOVE, OF SLAB. MATERIAL TO BE SUPPLIED IN FLAT SHEETS. 4. REINFORCING STEEL SHALL BE DETAILED (INCLUDING HOOKS AND BENDS) IN ACCORDANCE WITH ACI 315-02. LAP ALL CONTINUOUS REINFORCEMENT PER NOTE D.5. PROVIDE CORNER BARS AT ALL WALL INTERSECTIONS. LAP CORNER BARS PER NOTE D.5. LAP ADJACENT MATS OF WELDED WIRE FABRIC A MINIMUM OF 8" AT SIDES AND ENDS. 5. REINFORCING STEEL LAPS AND EMBEDMENT SHALL BE AS NOTED BELOW, UNLESS NOTED OTHERWISE: DEVELOPMENT LENGTH 48 BAR DIAM. DEVELOPMENT LENGTH, top bar' 64 BAR DIAM. LAP SPLICE LENGTH 64 BAR DIAM. LAP SPLICE LENGTH, top bar" 80 BAR DIAM. *TOP BARS ARE HORIZONTAL REINFORCEMENT SO PLACED THAT MORE THAN 12" OF CONCRETE IS CAST IN THE MEMBER BELOW THE BAR. ALL HOOKS SHALL BE "STANDARD" IN ACCORDANCE WITH ACI 318. REINFORCING SHALL NOT BE TACK WELDED. 6. CONCRETE PROTECTION (COVER) FOR REINFORCING STEEL SHALL BE AS FOLLOWS: FOOTINGS AND OTHER UNFORMED SURFACES, EARTH FACE 3" FORMED SURFACES EXPOSED TO EARTH (i.e. WALLS BELOW GROUND) OR WEATHER 2" SLABS AND WALLS (INTERIOR FACE) 1 112" 7. CONCRETE WALL REINFORCING - PROVIDE THE FOLLOWING UNLESS DETAILED OTHERWISE: 6" WALLS #4 @ 16" HORIZ. #4 @ 18" VERTICAL 1 CURTAIN @ CENTER 8" WALLS #5 @ 18" HORIZ. #5 @ 18" VERTICAL 1 CURTAIN @ CENTER 8. EPDXY GROUTED ITEMS SPECIFIED ON THE DRAWINGS SHALL BE GROUTED WITH SIMPSON SET ADHESIVE BY SIMPSON STRONG TIE, PER ER-5729, FOLLOWING MANUFACTURER'S INSTALLATION INSTRUCTIONS ABBREVIATIONS (THIS IS A COMPREHENSIVE LIST OF ABBREVIATIONS, SOME OF WHICH MAY NOTAPPEAR ON THESE DRAWINGS.) F. CARPENTRY 1. GLUED LAMINATED MEMBERS SHALL BE FABRICATED IN CONFORMANCE WITH ANSI STANDARD A190.1. EACH MEMBER SHALL BEAR AN AITC OR APA EWS IDENTIFICATION MARK AND SHALL BE ACCOMPANIED BYAN AITC OR APA EWS CERTIFICATE OF CONFORMANCE. ALL SIMPLE SPAN BEAMS SHALL BE DOUGLAS FIR COMBINATION 24F-V4, Fb = 2,400 PSI, Fv = 240 PSI. ALL CANTILEVERED BEAMS SHALL BE DOUGLAS FIR COMBINATION 24F-V8, Fb = 2400 PSI, Fv = 240 PSI. CAMBER ALL GLULAM BEAMS TO 2,000' RADIUS, UNLESS SHOWN OTHERWISE ON THE PLANS. 2. FRAMING LUMBER SHALL BE GRADED AND MARKED IN CONFORMANCE WITH WCLIB STANDARD GRADING RULES FOR WEST COAST LUMBER, LATEST EDITION. FURNISH TO THE FOLLOWING MINIMUM STANDARDS: MEMBER SIZE SPECIES GRADE MIN. BASIC DESIC STRESS JOISTS AND RAFTERS: 2x-3x DF #2 Fb = 875 PSI JOISTS AND RAFTERS: 4x ❑F #1 Fb = 1000 PSI BEAMS AND STRINGERS: 6x-LRGR. ❑F #1 Fb = 1350 PSI POSTS AND TIMBERS 6x-LRGR. DF #1 Fc = 1000 PSI TOP AND BOTTOM PLATE AT SHEARWALLS & BEARING WALLS: DF #2 Fb = 1000 PSI STUDS, PLATES,& MISC. LIGHT FRAMING: ❑F #2 Fb = 875 PSI ALL LUMBER WITH A LEAST DIMENSION OF 2" (NOMINAL) SHALL BE STAMPED SURFACE -DRY AND SHALL HAVE A MOISTURE CONTENT WHEN SURFACED AND WHEN INSTALLED OF NOT MORE THAN 19 PERCENT. LUMBER WITH A LEAST DIMENSION OF 4" (NOMINAL) OR GREATER SHALL BE STAMPED SURFACE -GREEN AND AIR-DRIED TO A MOISTURE CONTENT OF NOT MORE THAN 19 PERCENT PRIOR TO ITS USE IN FRAMING THE STRUCTURE. 3. MANUFACTURED LUMBER SHALL BE AS MANUFACTURED BY TRUS JOIST MacMILLAN OR APPROVED EQUAL. REQUESTS FOR APPROVAL AS EQUAL WILL REQUIRE SUBMITTAL OF NER "NATIONAL EVALUATION REPORTS" EQUIVALENT TO NER 292 FOR PARALLEL STRAND LUMBER (PSL), OR NERA81 FOR LAMINATED STRAND LUMBER (LSL). THE MINIMUM ALLOWABLE DESIGN VALUES ARE AS FOLLOWS PSL - Fb = 2,900; Fv = 290 PSI; E = 2,000,000 PSI LSL - Fb = 2,250; Fv = 400 PSI; E = 1,500,000 PSI 4. SHEATHING SHALL BE APA PERFORMANCE RATED PANELS PER APA "PLYWOOD DESIGN SPECIFICATION, "INCLUDING APPLICABLE SUPPLEMENTS, UNLESS NOTED OTHERWISE. PLYWOOD PANELS SHALL BE GRADE CD AND ALSO CONFORM TO DOC PS-1 & PS-2. ALL PANELS SHALL BE IDENTIFIED AS EXPOSURE 1 UNLESS NOTED OTHERWISE. PANEL RATING TO BE AS FOLLOWS UNLESS NOTED OTHERWISE: ROOF: 19132" THICK, 32116, (OR 518" THICK, 32116) WALLS: 15/32" THICK, 32116, (OR 112" THICK, 2410) FLOORS: 23132" (OR 3/4") THICK, TONGUE & GROOVE, 48124 UNLESS NOTED OTHERWISE ON THE PLANS, ROOF AND FLOOR SHEATHING SHALL BE LAID UP WITH GRAIN PERPENDICULAR TO SUPPORTS AND NAILED WITH 10d NAILS @ 6" oc TO FRAMED PANEL EDGES AND OVER STUD WALLS SHOWN ON PLANS AND @ 12"oc (10"oc AT FLOORS) TO INTERMEDIATE SUPPORTS. PROVIDE APPROVED SHEATHING EDGE CLIPS @ 16" oc AT UNBLOCKED ROOF SHEATHING EDGES. ALL FLOOR SHEATHING EDGES SHALL HAVE APPROVED TONGUE -AND -GROOVE JOINTS AND SHALL BE SUPPORTED WITH SOLID BLOCKING. TOENAIL BLOCKING TO SUPPORTS WITH 16d NAILS, UNLESS NOTED OTHERWISE. UNLESS NOTED OTHERWISE ON THE PLANS, WALL SHEATHING MAY BE LAID UP HORIZONTALLY OR VERTICALLY, UNSUPPORTED EDGES SHALL BE BLOCKED AND ALL EDGES SHALL BE NAILED WITH 10d @ 6"oc, NAIL WITH 10d @ 12"oc AT INTERMEDIATE SUPPORTS. NAIL SHEAR WALL SHEATHING TO ALL HOLDOWN STUDS USING EDGE NAIL SPACING WHEN HOLDOWN STUD DOES NOT OCCUR AT PANEL EDGES. SHEATHING NAILS SHALL BE DRIVEN FLUSH BUT SHALL NOT FRACTURE THE SURFACE OF THE SHEATHING. 5. ALL WOOD PLATES IN DIRECT CONTACT WITH CONCRETE OR MASONRY SHALL BE PRESSURE -TREATED WITH AN APPROVED PRESERVATIVE. PROVIDE TWO LAYERS OF ASPHALT IMPREGNATED BUILDING PAPER BETWEEN UNTREATED LEDGERS, BLOCKING, ETC., AND CONCRETE OR MASONRY. ALL METAL CONNECTORS TO PRESSURE TREATED LUMBER SHALL BE HOT DIP GALVANIZED, INCLUDING WASHERS, NAILS, SCREWS, AND SIMPSON STRONG -TIE HANGERS, STRAPS, AND PLATES, AND BOLTS LESS THAN 1/2" DIAMETER. 6. NOTATIONS ON DRAWINGS RELATING TO FRAMING CLIPS, JOIST HANGERS AND OTHER CONNECTING DEVICES REFER TO CATALOG NUMBERS OF CONNECTORS MANUFACTURED BY THE SIMPSON STRONG -TIE COMPANY, SAN LEANDRO, CALIFORNIA. EQUIVALENT DEVICES BY OTHER MANUFACTURERS MAY BE SUBSTITUTED, PROVIDED THEY HAVE ICC APPROVAL FOR EQUAL OR GREATER LOAD CAPACITIES. SUBMIT MANUFACTURER'S CATALOG AND ICC REPORTS TO ARCHITECT AND ENGINEER FOR REVIEW WHEN REQUESTING SUBSTITUTIONS. ALL SPECIFIED FASTENERS MUST BE USED AND PROPER INSTALLATION PROCEDURES MUST BE OBSERVED IN ORDER TO OBTAIN ICC APPROVED LOAD CAPACITIES. VERIFY THAT THE DIMENSIONS OF THE SUPPORTING MEMBER ARE SUFFICIENT TO RECEIVE THE SPECIFIED FASTENERS. STRUCTURAL CONNECTORS ALL STRUCTURAL CONNECTORS TO BE BY SIMPSON STRONG TIE OR EQUAL. USE ZMAXIHDG HOT DIPPED GALVANIZED OR STAINLESS STEEL CONNECTORS AS A MINIMUM. USE FASTENERS GALVANIZED PER ASTM A153. ALL PRESSURE TRATE❑ LUMBER USED SHALL BE COMPATIBLE WITH ZMAX GALV. CONNECTORES, RE: SIMPSON STRONG -TIE CORROSION INFORMATION. 7. WOOD TRUSSES TRUSSES ARE TO BE METAL PLATED CONNECTED WOOD TRUSSES FABRICATED IN ACCORDANCE WITH THE IBC. TRUSS FABRICATORTO PROVIDE ALL REQUIRED BRIDGING AND BLOCKING, BOTH FOR ERECTION AND PERMANENT LOADING. SHOP DRAWINGS STAMPED BYA WASHINGTON STATE LICENSED PROFESSIONAL ENGINEER SHALL BE SUBMITTED TO THE ARCHITECT FOR APPROVAL PRIOR TO FABRICATION. DESIGN CRITERIA SHALL MEET OF EXCEED THE FOLLOWING: ROOF TRUSSES: TOP CHORD 25 PSF LL, 23 PSF DL BOTTOM CHORD 5 PSF DL DEFLECTION LIMIT TOTAL LOAD L1240, LIVE LOAD 1_1360 OTHER LOADS SPECIFIED ON DRAWINGS. TRUSS SUPPLIERS NOTE: THE TRUSS CONFIGURATIONS, INCLUDING DEPTHS AND MEMBER SIZES, SHOWN ON THE DRAWINGS INDICATE THE DESIRED TRUSS CONFIGURATIONS AND ARE TO BE COMPLIED WITH WHERE POSSIBLE. IF A TRUSS MANUFCTURER IS UNABLE TO MEET THE LOAD REQUIREMENTS SPECIFIED WITH THE TRUSS CONFIGURATION INDICATED, HE IS TO SUBMIT WRITTEN NOTICE TO THAT EFFECT TO THE ARCHITECT. IT IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR AND TRUSS MANUFACTURER TO VERIFY THE WEIGHT AND LOCATIONS OF ALL MECHANICAL EQUIPMENT PRIOR TO SUBMITTING SHOP DRAWINGS TO THE ARCHITECT AND ENGINEER OF RECORD FOR REVIEW. THE DESIGN LOADS LISTED ABOVE SHALL BE APPLIED SIMULTANEOUSLY. 8. WOOD FRAMING NOTES - THE FOLLOWING APPLY UNLESS OTHERWISE SHOWN ON THE PLANS: 8.1 ALL WOOD FRAMING DETAILS NOT SHOWN OTHERWISE SHALL BE CONSTRUCTED TO THE MINIMUM STANDARDS OF THE INTERNATIONAL BUILDING CODE. MINIMUM NAILING, UNLESS OTHERWISE NOTED, SHALL CONFORM TO TABLE 2304.9.1 OF THE INTERNATIONAL BUILDING CODE. COORDINATE THE SIZE AND LOCATION OF ALL OPENINGS WITH MECHANICAL AND ARCHITECTURAL DRAWINGS. 8.2 WALL FRAMING: ALL STUD WALLS SHOWN AND NOT OTHERWISE NOTED SHALL BE 2x4 STUDS @ 16"oc AT INTERIOR WALLS AND 2x6 STUDS @ 16" AT EXTERIOR WALLS. TWO STUDS MINIMUM SHALL BE PROVIDED AT THE END OF ALL WALLS AND AT EACH SIDE OF ALL OPENINGS AND UNDER THE ENDS OF ALL BEAMS. UNLESS NOTED OTHERWISE A (2) 2x8 HEADER SHALL BE PROVIDED OVERALL OPENINGS IN 2x4 STUD WALLS AND A (3) 2x8 HEADER OVER ALL OPENINGS IN 2x6 WALLS. SOLID BLOCKING FOR WOOD COLUMNS SHALL BE PROVIDED THROUGH FLOORS TO SUPPORT BELOW. PROVIDE CONTINUOUS SOLID BLOCKING AT MID -HEIGHT OF ALL STUD WALLS OVER 8' IN HEIGHT. ALL STUD WALLS SHOWN ON STRUCTURAL DRAWINGS SHALL HAVE THEIR LOWER PLATES ATTACHED TO WOOD FRAMING BELOW WITH 16d NAILS AT 12" oc STAGGERED OR BOLTED TO CONCRETE WITH 518" DIAMETER ANCHOR BOLTS AT 4'-0" oc, EMBEDED 7", UNO REFER TO THE STRUCTURAL PLANS AND SHEAR WALL SCHEDULE FOR REQUIRED SHEATHING AND NAILING. 8.3 FLOOR AND ROOF FRAMING: PROVIDE DOUBLE JOISTS UNDER ALL PARALLEL PARTITIONS AND AROUND ALL OPENINGS IN FLOORS OR ROOFS UNLESS OTHERWISE NOTED. PROVIDE BRIDGING @ 8'-0" oc AND SOLID BLOCKING AT ALL BEARING POINTS. COORDINATE THE SIZE AND LOCATION OF ALL OPENINGS WITH ARCHITECTURAL AND MECHANICAL DRAWINGS. TOENAIL JOISTS TO BEARING SUPPORTS WITH 16d NAILS. UNLESS NOTED OTHERWISE, ATTACH JOISTS TO FLUSH HEADERS OR BEAMS WITH SIMPSON "U" SERIES METAL JOIST HANGERS TO SUIT JOIST SIZE. ALL DOUBLE JOISTS, BEAMS, AND SLOPED AND/OR SKEWED JOISTS SHALL BE CONNECTED TO FLUSH MEMBERS WITH HU-SERIES JOIST HANGERS UNLESS NOTED OTHERWISE. SKEW AND Titl SLOPE ALL CONNECTORS AS REQUIRED. FACE-NAILALL MULTI -JOIST BEAMS TOGETHER WITH 16d SPIKES @ 24"oc STAGGERED. 8.4 NAILS SHALL BE MANUFACTURED IN CANADA OR THE UNITED STATES IN SIZES AND TYPES AS FOLLOWS, UNLESS NOTED OTHERWISE: PNEUMATIC NAILING - PLAIN SHANK, COATED OR GALVANIZED 8d = .131 DIAMETER x 2-1/2" MINIMUM LENGTH 10d = .131 DIAMETER x 3" MINIMUM LENGTHTO 16d = .131 DIAMETER x 3-1/2" MINIMUM LENGTH HAND NAILING - SINKERS, COATED 8d = 11-1/2 GAGE x 2-3/8" 10d = 11 GAGE x 2-7/8" 16d = 9 GAGE x 3-114" SPECIAL CONDITIONS CONTRACTOR TO COORDINATE ALL TRADES AND VERIFY DIMENSIONS IN THE FIELD. OBTAIN OWNERS APPROVAL PRIOR TO ALL FIELD CHANGES. SEE ARCHITECTURAL DRAWINGS FOR ALL FLOOR AND WALL OPENING DIMENSIONS AND LOCATIONS, FLOOR AND WALL FINISHES, ETC. AB ANCHOR BOLT CL CENTERLINE (E) EXISTING GL GLUE -LAMINATED LOC LOCATION OPP OPPOSITE STL STEEL & AND SYMBOLS ACI AMERICAN CONCRETE INSTITUTE CLR CLEAR EA EACH GWB GYPSUM WALL BOARD LONGIT LONGITUDINAL OSB ORIENTED STRAND BOARD STRUCT STRUCTURAL @ AT ADDL ADDITIONAL CMU CONCRETE MASONRY UNIT EF EACH FACE GYP GYPSUM LSL LONG SLOTTED HOLE SYM SYMMETRICAL BEAM CAMBER ADJ ADJACENT COL COLUMN EL ELEVATION LVL LAMINATED VENEER LUMBER PAR PARALLEL fZ CENTERLINE ■ COLUMN CONTINUOUS AFF ABOVE FINISHED FLOOR CONIC CONCRETE ELEC ELECTRICAL HDR HEADER LWC LIGHT WEIGHT CONCRETE PERP PERPENDICULAR T TOP 0 DIAMETER; ROUND AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION CONN CONNECTION, CONNECT ELEV ELEVATOR HNG HANGER PL PLATE T&B TOP AND BOTTOM # NUMBER; POUND 1 SECTIONS ALT ALTERNATE CONSTR CONSTRUCTION EMB EMBED, EMBEDDED, EMBEDMENT HORIZ HORIZONTAL M MISC SHAPE PLWD PLYWOOD T&G TONGUE AND GROOVE 0 SQUARE Il COLUMN BELOW 5100 ANSI AMERICAN NATIONAL STANDARDS INSTITUTE CONT CONTINUOUS ENGR ENGINEER HP HP SHAPE MAS MASONRY PREFAB PREFABRICATED TEMP TEMPERATURE L STRUCTURAL ANGLE APA AMERICAN PLYWOOD ASSOCIATION CONTR CONTRACTOR EQ EQUAL HS HIGH STRENGTH MATL MATERIAL PROP PROPERTY THK THICKNESS JL DOUBLE ANGLE APPROX APPROXIMATE; APPROXIMATELY COORD COORDINATE EQUIP EQUIPMENT HT HEIGHT MAX MAXIMUM PSF POUNDS PER SQUARE FOOT THRU THROUGH PLATE ARCH ARCHITECT; ARCHITECTURAL CID COMPLETE PENETRATION ES EACH SIDE MECH MECHANICAL PSI POUNDS PER SQUARE INCH TOB TOP OF BEAM ASSY CSK COUNTERSINK; COUNTERSUNK EW EACH WAY ID INSIDE DIAMETER MFR MANUFACTURER PSL PARALLEL STRAND LUMBER TOC TOP OF CONCRETE; TOP OF CURB ASTM AMERICAN SOCIETY FOR TESTING &MATERIALS CTR EXP EXPANSION; INSIDEIF FACE MIN MINIMUM; E PT POST TENSION TOF TOP OF FOOTING AWS AMERICAN WELDING SOCIETY CU FT FOOT CUBICR EXP JT EXPANSION JOINT IN INCH MISC MISCELLANEOUS TOL TOP OF LEDGER 5����� SIMPSON STRONG -TIE HOEDOWN CU IN CUBIC INCH EXT EXTERIOR INCL INCLUDE; INCLUDING; INCLUSIVE MO MASONRY OPENING RD ROOF DRAIN TOM TOP OF MASONRY BD CY CUBIC YARD INFO INFORMATION REF REFERENCE TOS TOP OF STEEL, TOP OF STRUCTURE y�i� i+ BLDG BUILDING F❑ FLOOR DRAIN INT INTERIOR (N) NEW REINF REINFORCE; REINFORCING TOW TOP OF WALL 4 by SIMPSON STRAP BLKG BLOCKING d PENNY (NAILS) FDN FOUNDATION N NORTH REQ'D REQUIRED TS TUBING, STRUCTURAL BM ❑BL DOUBLE FF FAR FACE, FINISHED FLOOR JT JOINT NF NEAR FACE RO ROUGH OPENING TYP TYPICAL BMU BRICK MASONRY UNIT(S) ❑EPT DEPARTMENT FLR FLOOR; FLOOR LINE NFPA NATIONAL FOREST PRODUCTS ASSOC BOF BOTTOM OF SLAB DIET DETAIL FLG FLANGE K KIP = 1000 POUNDS NIC NOT IN CONTRACT SCHE❑ SCHEDULE UBC UNIFORM BUILDING CODE BOS ❑IA DIAMETER (SEE SYMBOLS) FOC FACE OF CONCRETE KO KNOCK -OUT NOM NOMINAL SEC SECTION UL UNDERWRITER'S LABORATORY, INC. RESU B BOT BOTTOM DIAG DIAGONAL FOM FACE OF MASONRY KSI KIPS PER SQUARE INCH NS NEAR SIDE SHT SHEET UNO UNLESS NOTED OTHERWISE BRG BEARING DIAPH DIAPHRAGM FOS FACE OF STUD NTS NOT TO SCALE SHTG SHEATHING; SHEETING URM UNREINFORCED MASONRY Apr 05 2021 BEAM ❑ICA DRILLED -IN CONCRETE ANCHOR FS FULL SIZE; FAR SIDE LAB LABORATORY SIM SIMILAR UT ULTRA -SONIC TEST CITY OF EDMONDS C STANDARD CHANNEL DIM DIMENSION FT FEET; FOOT LB POUND cc ON CENTER SPA SPACING, SPACE, SPACES DEVELOPMENT SERVICES CG CENTER OF GRAVITY ❑N DOWN FTG FOOTING LF LINEAL FOOT O❑ OUTSIDE DIAMETER SPEC SPECIFICATION VERT VERTICAL DEPARTMENT CGS CENTER OF GRAVITY OF STRANDS ❑O DITTO LLBB LONG LEGS BACK-TO-BACK OF OUTSIDE FACE SQ SQUARE CIP CAST -IN -PLACE DWG DRAWING GA GAUGE LLH LONG LEGS HORIZONTAL OH OPPOSITE HAND STD STANDARD W WIDE FLANGE CJ CONSTRUCTION JOINTICONTROL JOINT DWL DOWELS GALV GALVANIZED LLV LONG LEGS VERTICAL OPNG OPENING STIFF STIFFENER WP WORK POINT WWF WELDED WIRE FABRIC STlkUCTURAL ENGINEERING BUILDING CODE CONSULTING [ART ENGINEERING STRUCTURAL ENGINEERING BUILDING CODE CONSULTING PROJECrV M V .lre PROJECTN� r DATE , SUBJECT � SHEET OF T��'[� � gy. cf ACI W —It� 19, coo i & ",� f URT NGINEEILING - -T Pry P(4w my 0 fL `* • # T tp 51�CrraA/ A � 4 t� � r,-g4. STRUCTU A L ENGINEERING BUILDING CODE CONSULTING PROJECT P rid PR01ECTIM 4074 DATE E- ,- SUg{EI If + SHEET OF r3�c44 p* pad y URT ENGINEERING PROJECr T qV M 03.V,41 rr- mv vb 0 u Y/e�UT y t)I PdV�P. 2F e- U T ENGINEERING PROJECT* Z t 0 " DATE SHEET OF BY 'V�qj- ?* vbu) j(v wR' [. G I� c c �� _�P., A44 tv��°fir STRUCYU A L. ENGI N EE RING BUJ f LDFNG CODE CON51ULTENG pwj I �# 99/ PROJECT DATE a, ,(,. x suslFcT r SHEET OF LU Rv c q T- 7V FAT-&� rT M4 REVIEWED BY ' CITY OF EDMONDS, ■ ■ BUILDING DEPARTMENT RESUB Apr 19 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT