REVIEWED BLD BLD2021-0143+Interior_Lighting_Summary+3.22.2021_12.32.29_PM+21047892015 Washinaton State Fnerov Code Compliance Forms for Commercial Buildinas inrludina R2. R3_ R4 over 3 stories and all R1 Revised Nov 2017
Project Info
Project Title: 1- Thistitlewillcopyontootherforms
Date 3/18/2021
Compliance
forms do not
Applicant Information. Provide contact information for individual who can
respond to inquiries about compliance form information provided.
For Building Department Use
Company Name: Strobl Design
require a
password to
Company Address: 3923 N 31stSt, Tacoma, WA98407
use. Instructional
and calculating
Applicant Name: Jacob Strobl
cells are write-
protected.
Applicant Phone: 206-661-3622
Applicant Email: jacob@strobldesign.com
Project Description
0 New Building 0 Addition 0 Alteration 0 No Lighting Scope
Include PROJ-SUM form (included in envelope forms workbook) with lighting compliance forms.
Interior Lighting System
(4) Recessed LED Can lights for new mailroom at existnig apartment building clubhouse.
Description
0 Interior Lighting Plans Included
Interior Lighting Power
0 Building Area Method 0 Space -by -space Method
Allowance Method
Select method used in project.
Interior Lighting Controls
0 All C405.2.1- C405.2.8 Lighting Controls 0 C405.2 Exception 5 Luminaire Level
Lighting Controls (LLLC)
0 Additional Efficiency Package Option
C406.4 Enhanced Digital Lighting
To comply with C406.4, no less than 90% of the total installed interior lighting power shall comply with
required controls per C406.4.
Dwelling Unit Interior
Permanently installed interior lighting fixtures in dwelling units comply with: a No Dwelling
Lighting
0 C405.2 thru C405.5 Commercial Lighting Controls and LPA Units
0 C406.3 High Efficacy Lighting
0 R404.1 Residential High Efficacy Lighting. Dwelling unit lighting complies with WSEC Residential
provisions in lieu of WSEC Commercial provisions.
Exterior Lighting System
No Exterior Lighting Included in the Project Scope
Description
0 Exterior Lighting Plans Included
Building Additions
Compliance Method
Interior lighting
Exterior lighting
Lighting systems in addition area comply with all applicable
provisions as a stand alone new construction project
o
Refer to Section C502.2.6 for additional
requirements.
0
0
Lighting systems in addition are combined with existing
building lighting systems to demonstrate compliance
o
Addition is combined with existing:
For interior lighting projects, include new + existing -to -remain interior lighting fixture wattage in
Proposed Lighting Wattage table in LTG-INT-BLD or L TG-INT-SPA CE form.
For exterior lighting projects, include new + existing -to -remain exterior lighting fixture wattage in
Proposed Tradable and Proposed Non -Tradable Lighting Wattage tables in LTG-EXT form.
2015 Washington State Energv Code Compliance Forms for Commercial Buildings including R2, R3, R4 over 3 stories and all R1 Revised Nov 2017
Project Title: Fill this line out at top ofLGT-SUM
Date 3/18/2021
Change of Space Use
0 Existing interior lighting systems in areas under -going a change in space use are upgraded to
comply with LPAs for the new space types per Tables C405.4.2(1) or C405.4.2(2).
Identify interior spaces requiring LPD upgrade to the current Code in Proposed Lighting Wattage
table in LTG-INT-BLD or LTG-INT-SPACE form.
Interior and Exterior
Lighting Power
Interior lighting
Parking garage
Exterior lighting
Lighting Alterations
50% or more of existing are replaced
o
0
0
Select all Lighting Povver and Lighting
Control elements that apply to the scope
Less than 50% of existing are replaced
o
0
0
of the retrofit project. If project includes a
Lamp and/or ballast replacement only
o
0
0
combination of spaces Mere less than
50% of the existing fixtures are replaced
—existing total wattage not increased
50% or more replaced - Total lighting povtier of new + existing -to -remain fixtures shall comply with
in some spaces, and 50% or more of the
fixtures are replaced in others, then
total LPA per Sections C405.4.2 and C405.5.2. Include new+ existing -to -remain fixtures in
provide separate lighting pouter
Proposed Lighting Wattage table in LTG-INT-BLD, L TG-INT-SPA CE or LTG-EXT form.
compliance forms for the tvc retrofit
conditions. Spaces undergoing the same
Less than 50% replaced - Total lighting power of new + existing -to -remain fixtures shall not exceed
type of retrofit may be combined into one
the total lighting poorer prior to alteration. Include new + existing -to -remain fixtures in the Proposed
lighting pouter compliance form.
Lighting Wattage table in LTG-INT-BLD, L TG-INT-SPA CE or LTG-EXT form.
50% threshold applies to number of luminaires for interior spaces and parking garages, and total
Refer to Section C503.6 for additional
installed wattage for exterior luminaires.
requirements.
Lighting Controls
Interior lighting
Parking garage
Exterior lighting
New wiring installed to serve added
All alteration lighting controls shall be
fixtures and/or fixtures relocated to
0
0
0
new circuit(s)
New or moved lighting panel
o
0
0
Interior space is reconfigured
0
luminaires unchanged or relocated
New wiring or circuit - For interior lighting, provide required manual controls per C405.2.3,
occupancy sensor controls per C405.2.1, daylight responsive controls per C405.2.4 and application
o No changes are being made to
specific lighting controls per C405.2.5. For exterior lighting, provide required controls per C405.2.7.
the interior or exterior lighting
New or moved panel - Provide all applicable lighting controls as noted for New Wiring and
systems and existing space
automatic time svdtch controls per C405.2.2.
uses and configuration are not
Reconfigured interior space - Provide all required lighting controls that apply to a newinterior
changed.
space. Application specific lighting control provisions per C405.2.5 do not apply to reconfigured
9n95 %A/achinnfnn Cfafo Fnom\/ rnrfo Cmmnllanra Fnrmc fnr r.nmmarrial Riiilrlinnc inrliirlinn R9 R3 Rd nvor 9 cfnrioc anf all R9 RaxAcad Nrri9n97
Project Title: Fill this line out onLGT-SUM
Date 3/18/2021
Calculation
Area NOTE
Q New Construction 10 Addition- 10 Addition
0 Spaces where < 50% of ■ Spaces where >_ 50% of * Spaces where the Use
For Building Department Use
LPA
Calculation
Type
■ Standard Q Additional Efficiency Package Option
C406.3 Reduced Interior Lighting
To comply idth C406.3, the Proposed LPD shall be 25% lomer than the Target LPA.
Refer to C406.3 for additional requirements.
User Note
Maximum Allowed Lighting Wattage NOTE'
Location (plan #,
room #)
Space Type
Ceiling
Height NOTE
2
GrossInterior
Area in ft2
Allowed
Watts per ft2
Watts Allowed
(watts/if x area)
Mailroom
Lobby: all other
9
262
0.720
189
Total Area 262
Retail Display Allowance from LTG-INT-DISPLAY
Lobby Art/Exhibit Display Allowance from LTG-INT-DISPLAY NOTE 8� Allowed Watts 189
Proposed Lighting Wattage NOTE
Location (plan #,
room #)
Fixture Description NOTE 4, 5, 6
Number of
Fixtures
Watts/
Fixture NOTE 7
Watts
Proposed
Mail Room
6" LED Recessed Can Light
4
21
84
Proposed Retail Display Lighting from LTG-INT-DISPLAY
Total Proposed Watts maynot exceed Total Allomed Watts for Interior Lighting Total Proposed Watts
1 84
Interior Lighting Power Allowance COMPLIES
Note 1 - Listall unique space types per Table C405.4.2(2) that occur in the project scope. Selectspace type category from drop domn menu.
Note 2 - Indicate ceiling height for atriums and spaces utilizing the ceiling height adjustment per Table C405.4.2(2), Footnotes d thru f.
Note 3 - List all proposed lighting fixtures including exempt lighting equipment and existing -to -remain fixtures.
Note 4 - For proposed Fixture Description, indicate fixture type, lamp type (e.g. T-8), numberof lamps in the fixture, and ballasttype (if included). For
track lighting, list the length of the track (in feet) in addition to the fixture, lamp, and ballast information.
Note 5 - For lighting equipment eligible forexemption per C405.4.1, note exception numberand leave Watts/Fixture blank.
Note 6 - Existing -to -remain fixtures shall be included in the Proposed Lighting Wattage table in the same manneras new fixtures. Identify as existing
in fixture description.
Note 7 - For proposed Watts/Fixture enter the luminaire mettage for installed lamp and ballast using manufacturer or other approved source. For
luminaires mith screw -in lamps, enter the manufacturer's listed maximum inputmettage of the fixture (not the lamp mattage). Forlow voltage
lighting, enter the mettage of the transformer. Forline voltage track/busmey systems, enter the larger of the attached luminaire mettage or 50
mettsdineal foot, or enter the menage limit of permanent current limiting device.
Note 8 - LobbyArt/ExhibitDisplayAllomence is independent of the MaximumAllomed Lighting Wattage. Enter all proposed lobby art(exhibit display
fixtures in LTG-INT-DISPLAYform only.
Note 9 - Calculation Area Details:
.I inhfinn fivf — in hnilriinn orirlifinn mov—hi men cf—I mInna nmiarf nr fhat mov ha rnmhinar! uifh fho n—m11 avicfinn hnilriinn
PermitLighting, Motor, and Electrical •
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 R3 R4 over 3 stories and all R1 Revised Nov 2017
Project Title: Fill this line out on LGT-SUM
Date 3/18/2021
The following information is necessary to check a permit application for compliance with the lighting, motor, and electrical requirements in the
Applicability
Location in
building Liepartment
(yes,no,na)
Code Section
Component
Compliance information required in permit documents
Documents
Notes
LIGHTING CONTROLS
Yes
C405.2
Lighting controls,
For all lighting fixtures, indicate lighting control method on plans
1�A2
general
for spaces and lighting zone(s) served, or exception taken
Luminaire level
Indicate on plans all fixtures provided with LLLC in lieu of
C405.2
lighting controls
C405.2 lighting controls; provide description of control
LLLC
capabilities and performance parameters
For permanently installed lighting fixtures in dwelling units,
C405.1
Lighting in dwelling
indicate lighting control method on plans for spaces and
units
lighting zone(s) served, or demonstrate compliance with high
efficacy exceiption
C405.2.3
Indicate on plans the method of manual lighting control
C405.2.1.1
(whether combined with occupancy sensor, automatic light
Yes
C405.2.2.2
Manual controls
reduction, daylight responsive or specific application controls),
1/A2
C405.2.4
location of manual control device and area or specific
C405.2.5
application it serves
C405.2.2.1
Manual interior light
Indicate on plans which method of manual 50% lighting load
C405.2.2.2
reduction controls
reduction is provided, or whether lighting load is reduced via
C405.2.3
occupancy sensors or daylight res onsive controls
Indicate on plans the method of automatic shut-off control
during unoccupied periods (occupancy sensor, time switch or
C405.2.2
Method of automatic
diqital timer switch) for all liqhtinq zones;
Indicate locations where automatic shutoff is provided by other
shut-off control
methods (occupancy sensor or digital timer switch) or which
time switch control exception applies
Indicate on plans the spaces served by occupancy sensors;
Indicate whether occupancy sensor controls are configured to
C405.2.1
Occupancy sensor
C405.2.1.1
controls
be manual -on, automatic 50%-on, or serve a space eligible for
automatic 100%-on per exception
Occupancy sensor
Indicate aisleways and open areas in warehouse spaces
C405.2.1.2
controls -
provided with occupancy sensor controls that reduce lighting
warehouses
Power by 50%
C405.2.2.1
Automatic time
Indicate locations of override switches on plans and the lighting
switch controls
zones served include areas . ft.
C405.2.6
Digital timer switch
Indicate digital timer switch control includes: manual on/off,
time delaV, audible and visual indication of impending time-out
Indicate primary and secondary sidelight daylight zone areas on
plans, include sq. ft.;
Indicate toplight daylight zone areas on plans, include sq. ft.;
C405.2.4.2
Daylight zones -
For small vertical fenestration assemblies (rough opening less
C405.2.4.3
Sidelight and toplight
than 10 percent of primary daylight zone) where daylight
responsive controls are not required, provide fenestration area
to da li ht zone calculation(s)
Indicate on plans lighting zone(s) served by daylight responsive
controls;
Identify sidelight and toplight daylight zones that are not
provided with daylight sensing controls and the exception(s)
C405.2.4
Daylight responsive
that apply;
Indicate on plans the lighting load reduction method -
controls
continuous dimming, or stepped dimming that provides at least
two even steps between 0%-100% of rated power;
Indicate that daylight sensing controls are configured to
completely shut off all controlled lights in the lighting zone
Additional controls -
Identify spaces and lighting fixtures on plans that require
C405.2.5
Specific application
specific application lighting controls per this section
lighting controls
Indicate on plans that display and accent lighting, and display
C405.2.5 -
Display and accent
case lighting are controlled independently from both general
Items 1 &2
lighting
area lighting and other lighting applications within the same
space;
Indicate manual and automatic lighting control method
PermitLighting, Motor, and Electrical •
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 R3 R4 over 3 stories and all R1 Revised Nov 2017
Project Title: Fill this line out on LGT-SUM
Date 3/18/2021
The following information is necessary to check a permit application for compliance with the lighting, motor, and electrical requirements in the
Applicability
Location in
Building Department
(yes,no,na)
Code Section
Component
Compliance information required in permit documents
Documents
Notes
C405.2.5 -
Hotel/motel guest
Indicate method of automatic control - vacancy or captive key
Item 3
rooms
control of all installed luminaires and switched receptacles in
guest room
C405.2.5 -
Supplemental task
Indicate method and location of automatic shut-off vacancy
Item 4
lighting
control for supplemental task lighting, including under -shelf or
under -cabinet lighting
Indicate on plans eligible non -visual lighting applications,
include sq. ft. area of each lightinq control zone;
Indicate on plans that non -visual lighting are controlled
C405.2.5 -
Lighting for non-
Item 5
visual applications
independently from both general area lighting and other lighting
applications within the same space;
Indicate method of manual lighting control and applicable
automatic lighting control
Indicate on plans that lighting equipment for sale or
Lighting equipment
demonstration are controlled independently from both general
C405.2.5 -
for sale or
area lighting and other lighting applications within the same
Item 6
demonstration
space;
Indicate method of manual lighting control and applicable
automatic lighting control
Identify on plans egress fixtures that function as both normal
and emerqency means of egress illumination;
Provide calculation of lighting power density of total egress
C405.2.5 -
Means of egress
lighting;
If total egress lighting power density is greater than 0.02 W/sq.
Item 7
lighting
ft., indicate on plans egress fixtures requiring automatic shut-off
during unoccupied periods;
Indicate method of automatic shut-off control
Indicate on exterior lighting plans and fixture schedules the
automatic lighting control method, control sequence, and
locations served;
For building facade and landscape lighting, indicate automatic
Exterior lighting
controls shut off lighting as a function of dawn/dusk and fixed
C405.2.7
controls
opening/closinq time;
For all other exterior lighting,
g g, indicate automatic controls shut
off lighting as a function of available daylight; include control
sequence that also reduces lighting power by at least 30%
between 12am-6am, or from 1 hour after closing to 1 hour
before openina. or based upon motion sensor
Exterior building
For building grounds fixtures greater than 100 watts, indicate on
C405.5.1
grounds lighting
plans whether fixtures have efficacy greater than 80 lumens or;
controls
are controlled by motion sensor, or are exempt lighting per
C405.5.2
Area controls -
Indicate location(s) of master control switch(es) intended to
C405.2.5
Master control
control multiple independent switches; circuit breaker may not
(listed after
switches and circuit
be used as a master control switch;
Verify that no 20 amp circuit controlled by a single switch or
C405.2.7)
power limit
automatic control is loaded beyond 80%
ADDITIONAL
EFFICIENCY
PACKAGE OPTION - ENHANCED DIGITAL LIGHTING CONTROLS
To comply with additional efficiency package option, indicate on
plans all interior lighting fixtures that are individually addressed
Enhanced digital
and provided with continuous dimming, or exception taken;
C406.4
lighting controls
Include calculation of percent total installed interior lighting
power that is configured with required enhanced lighting control
functions (min 90% to comply with additional efficiency package
option)
PermitLighting, Motor, and Electrical •
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 R3 R4 over 3 stories and all R1 Revised Nov 2017
Project Title: Fill this line out on LGT-SUM
Date 3/18/2021
The following information is necessary to check a permit application for compliance with the lighting, motor, and electrical requirements in the
Applicability
Location in
Building Department
(yes,no,na)
Code Section
Component
Compliance information required in permit documents
Documents
Notes
INTERIOR LIGHTING POWER & EFFICACY
Include all luminaires in lighting fixture schedule; indicate fixture
types, lamps, ballasts, and manufacturer's rated watts per
fixture;
Identify spaces eligible for lighting power exemption on plans
C405.4.1
Total connected
and in compliance forms; indicate the exception applied;
Identify lighting equipment eligible for lighting power exemption
C405.4.2
interior lighting power
in fixture schedule and in compliance forms; indicate the
exception applied;
Indicate that exempt lighting equipment is in addition to general
area lighting and is controlled independently
C405.3
Exit signs
Indicate location of exit signs on plans and rated watts per
fixture in lighting fixture schedule maximum 5 watts per side
If high efficacy exception is applied to permanently installed
Lighting in dwelling
lighting fixtures in dwelling units, indicate in lighting fixture
C405.1
units lamp efficacy
schedule if lamps in fixtures are high efficacy per R404.1.
Calculate percentage of fixtures with high efficacy lamps in
promecto to comply with exception),
Interior Li h !no Power Calculation - Indicate com liance path taken
Building Area
Complete required compliance forms — proposed wattage per
C405.4.2.1
Method
building area does not exceed maximum allowed wattage per
building area; identify locations of building areas on plans
Complete required compliance forms — total proposed wattage
C405.4.2.2
Space -By -Space
does not exceed maximum allowed wattage; identify locations
Method
of space types on plans, including retail display areas, lobby art
& exhibit display areas, and ceiling heights as applicable
ADDITIONAL
EFFICIENCY
PACKAGE OPTION - REDUCED INTERIOR LIGHTING POWER
DENSITY
To comply with additional efficiency package option,
Reduced lighting
demonstrate in compliance forms that total connected interior
C406.3
power density
lighting wattage is 25 /o less than the total maximum allowed
lighting wattage via Building Area Method or Space -By -Space
Method
Reduced lighting
For project with dwelling units, to comply with additional
power density -
efficiency package option indicate in lighting fixture schedule if
C406.3
dwelling unit lamp
lamps in interior fixtures have efficacy rating of 60 lumens per
efficacy
watt or more. Calculate percentage of fixtures with lamps that
have this efficacv ratina (min 95% to comDly with option)
EXTERIOR LIGHTING POWER & EFFICACY
Include all luminaires in lighting fixture schedule; indicate fixture
types, lamps, ballasts, and manufacturer's rated watts per
fixture;
Identify exterior applications eligible for lighting power
Total connected
C405.5.2
exterior lighting
exemption on plans and in compliance forms; indicate
exception applied;
power
Indicate that exempt exterior lighting is controlled independently
from non-exempt exterior lighting; include exception claimed for
each fixture or group of fixtures under exception category
Table
Exterior lighting zone
Indicate building exterior lighting zone as defined by the AHJ
C405.5.2 1
Exterior building
For building grounds fixtures rated at greater than 100 watts
C405.5.1
grounds lighting
that are complying based on efficacy, indicate rated lamp
efficacy in lumens per watt in fixture schedule
Exterior lighting
Complete required compliance form — proposed wattage for
C405.5.2
power calculations
exterior lighting plus base site allowed does not exceed
maximum allowed
PermitLighting, Motor, and Electrical .
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 R3 R4 over 3 stories and all R1 Revised Nov 2017
Fill this line out on LGT-SUM
Date 3/18/2021
The following information is necessary to check a permit application for compliance with the lighting, motor, and electrical requirements in the
Applicability
Location in
building Department
(yes,no,na)
Code Section
Component
Compliance information required in permit documents
Documents
Notes
LIGHTING ALTERATIONS
Where >_ 50% of existing luminaires in interior space(s) or
parking garage are replaced; indicate compliance path (building
area or space -by -space method); include all new and existing -
to -remain luminaires in compliance form (LTG-INT-BLD or LTG-
INT-SPACE); indicate proposed lighting wattage does not
Interior and parking
exceed maximum allowed oer compliance oath
Where < 50% of existing luminaires in interior space(s) or
C503.6
garage lighting
fixture alterations
parking garage are replaced; indicate total existing lighting
wattage in each space prior to alteration; include all new and
existing -to -remain luminaires in LTG-INT-SPACE form; indicate
proposed total lighting wattage in alteration area does not
exceed total existing lighting wattage prior to alteration
Where >_ 50% of existing exterior lighting wattage is replaced;
include all new and existing -to -remain luminaires in LTG-EXT
form; indicate proposed total exterior lighting wattage does not
Exterior lighting
exceed maximum allowed
/o Where < 50 of existing exterior lighting wattage is replaced;
C503.6
fixture alterations
indicate total existing lighting wattage prior to alteration; include
all new and existing -to -remain luminaires in LTG-EXT form;
indicate proposed total exterior lighting wattage does not
exceedI existina wattace prior to alteration
Where new wiring is installed to serve new interior luminaires
Interior lighting wiring
and /or luminaires are relocated to a new circuit; indicate
C503.6
alterations
lighting controls are provided (as applicable) - manual
(C405.2.3); occupancy sensor (C405.2.1); daylight responsive
(C405.2.4); specific application (C405.2.5); exit signs (C405.3)
Exterior lighting
Where new wiring is installed to serve new exterior luminaires
C503.6
wiring alterations
and /or luminaires are relocated to new circuit; indicate exterior
lighting controls are provided C405.2.7
Where a new lighting panel is installed or an existing panel is
Lighting panel
moved (all new raceway and conductor wiring); indicate lighting
C503.6
alterations
controls are provided (as applicable) - same provisions as
wiring alterations; time switch controls and manual light
reduction controls (C405.2.2)
Where interior space(s) is reconfigured (permanently installed
C503.6
Interior space
walls or ceiling -height partitions); indicate lighting controls are
reconfiguration
provided (as applicable) - same provisions as lighting panel
alterations
Identify existing luminaires being upgraded with bulb and / or
C504.2
Lighting repairs
ballast replacement; indicate fixture alteration does not
increase existing fixture wattage
Identify spaces on plans where the building area type or space
use type is being changed from one type to another per Tables
C405.4.20) or (2)
Indicate compliance path (building area or space -by -space
C505.1
Change of space use
method); include all new and existing -to -remain luminaires in
compliance form (LTG-INT-BLD or LTG-INT-SPACE); indicate
proposed lighting wattage does not exceed maximum allowed
r compliance path
RECEPTACLES
Identify all controlled and uncontrolled receptacles on electrical
plans in each space in which they are required; include
Controlled
receptacle configuration such as spacing between controlled
C405.10
receptacles
and uncontrolled, duplex devices, etc;
Indicate on plans whether the method of automatic control for
each controlled receptacle zone is by occupant sensor or
Programmable time -of -day control
PermitLighting, Motor, and Electrical •
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 R3 R4 over 3 stories and all R1 Revised Nov 2017
Fill this line out on LGT-SUM
Date 3/18/2021
The following information is necessary to check a permit application for compliance with the lighting, motor, and electrical requirements in the
Applicability
Location in
building Department
(yes,no,na)
Code Section
Component
Compliance information required in permit documents
Documents
Notes
MOTORS, TRANSFORMERS, ELECTRIC METERS, INTERIOR TRANSPORTATION
C405.6
Electrical
Include electrical transformer schedule on electrical plans;
transformers
indicate transformer size efficiency, or exception taken
Dwelling unit
Indicate on electrical plans that each dwelling unit in Group R-2
C405.7
electrical energy
has a separate electrical energy meter
consumtion
Electric motor
Include all motors, including fractional hp motors, in electric
C405.8
efficiency
motor schedule on electrical plans; indicate hp, rpm, rated
efficiency, or exception applied
For luminaires in each elevator cab, provide calculated average
efficacy of combined fixtures that indicates efficacy is not less
than 35 lumens per watt;
Indicate rated watts per cfm for elevator cab ventilation fans do
C405.9.1
Elevator cabs
not exceed 0.33 watts per cfm;
Indicate automatic controls that de -energize lighting and
ventilation fans when elevator is stopped and unoccupied for a
period of 15 minutes or more
Escalators and
Indicate escalators comply with ASME A17.1/CSA B44;
C405.9.2
moving walks
automatic controls are configured to reduce operational speed
to the minimum ermitted when not in use
C405.9.3
Regenerative drive
Indicate all one-way down or reversible escalators are provided
with a variable frequencV regenerative drive
DOCUMENTATION
AND SYSTEM REQUIREMENTS TO SUPPORT COMMISSIONING (Cx)
Indicate that all electrical systems (receptacles, transformers,
motors, vertical and horizontal transportation) for which the
WSEC requires control functions and / or configuration to
Scope of electrical
perform specific functions are required to be commissioned;
power and lighting
Where total building lighting load is > 20 kW, or where total
C408.3
systems
lighting load of luminaires requiring daylight sensing and / or
commissioning
occupancy control > 10 kW, indicate that all automatic lighting
control systems are required to be commissioned; or provide
I
building lighting power calculation demonstrating eligibility for
exception,
Indicate Cx requirements in plans and specifications for all
applicable electrical and liqhtinq control systems per C408;
Include general summary with at minimum Items 1 thru 4 of the
C405.13
Commissioning
Cx plan per C408.1.2 including: narrative description of
C408.1.1
requirements in
activities, responsibilities of the Cx team, schedule of activities
C408.1.2
construction
including verification of project close out documentation per
C408.1.4.2
documents
C103.6. and conflict of interest clan (if reauired):
Include in general summary that a Cx project report or
C103.6
Compliance Checklist (Figure C408.1.4.2) shall be completed
by the Certified Cx Professional and provided to the owner prior
Ito the final electrical inspection
Functional
Identify in plans and specifications the intended operation of all
C408.3.1
performance testing
equipment and controls during all modes of operation, including
criteria
interfacing between new and existing -to -remain systems
PROJECT CLOSE OUT DOCUMENTATION
Indicate in plans that project close out documentation is
Project close out
required including WSEC lighting compliance forms and
C103.6.3
documentation
calculations that document all interior and exterior lighting area
requirements
and / or surface types, lighting power allowances and installed
densities
If "no" is selected for any question, provide explanation:
End of Lighting, Motor & Transformer Permit Documents Checklist