REVIEWED BLD-BLD2021-1071+Structural_Analysis_or_Calculations+8.2.2021_7.11.26_AM+2332833BLD2021-1071 RECEIVED ESG DESIGN Eli Grassley, P.E. Aug 03 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT • • • • •REVIEWED Client: Frances Fedoriska = BY € March 12, 2021 CITY OF EDMONDS € Property: 9601 Laurel Lane .BUILDING DEPARTMENT . Edmonds, WA 98020 RE: Structural Analysis of Kitchen Wall Removal Dear Frances, SUMMARY: ESG Design has been retained to assist in the structural analysis of your proposed interior remodel project at the Edmonds area address listed above. A site visit was performed on February 11, 2021 to review and assess the proposed removal of your existing main floor kitchen/pantry interior wall. Original blueprint drawings were not available for review during the site visit, but visual observations and measurements were made of the proposed remodel location while at the home. The following report summarizes the structural requirements which should be observed upon proceeding with the wall removal project. Figure 1. Exterior view of home STRUCTURAL OBSERVATIONS &ANALYSIS: The existing 1-story home is built in a mid-century modern style, with a prominent low -slope roof spanning across the home to a central ridgeline. The roof framing above the entry and living room areas of the home is readily visible as large timber rafter beams. The roof framing above the kitchen, dining and bedroom wings of the home are concealed above a flat ceiling however. In order to observe the kitchen area roof framing, an access hole was cut into the ceiling above the laundry closet. From this access hole a series of photos were taken to record the structural framing layout above the kitchen/dining areas (see Figures 2,3,4). The roof framing observed is different than the exposed living room area timber beams. Instead, the kitchen area is framed with 2x6 rafters spaced at 24", and spanning approximately 12-ft between interior bearing wall lines. One of the bearing wall lines which is present in the home is the east -wall of the laundry closet (see highlighted area in Figure 2). The other 3 walls of the laundry closet were confirmed to be non-structural, and may be freely removed. The remainder of this report will outline two options which you may consider towards removing or modifying the east wall of the laundry closet. ENGINEERED • STRUCTURES • GLOBAL • DESIGN ESG Design, PLLC - 12540 202nd PL SE, Issaquah, WA 98027 engineer@esg-design.com 206-660-2044 EESG DESIGN Figure 2.• Roof framing above laundry east wall OPTION 1 — Leave Existing Structural Bearing Columns: At present, the roof above the kitchen/laundry area is supported c two beams which are flush -framed into the ceiling (see Figure 2). These two ceiling beams are supported on the existing corners of the laundry closet east wall (see Figure 5). The "low cost" option b remodel the laundry closet is to remove all of the closet walls, sav( for the 2 corner support columns. These column locations would need to be upgraded (replaced) with new solid 4x4 wood posts which are installed and secured to be stable as isolated columns. Existing ceiling beam (A) Existing ceiling beam (A) Bearing posts locations Figure 5.• Option 1 bearing columns Eli Grassley, P.E. Figure 3.• roof beam above kitchen Figure 4.• Bearing line at dining room wall New 16' span ceiling girder beam ffRemove laundry closft- 9 et , H Figure 6.Option 2 ceiling girder beam ENGINEERED • STRUCTURES • GLOBAL • DESIGN I Fedoriska Wall Demo EESG DESIGN Eli Grassley, P.E. OPTION 2 — Install New Long -Span Ceiling Girder Beam: If keeping the vertical structural columns at the laundry closet east wall location is too obtrusive, an alternative is to remove the existing ceiling beams in the attic space and replace with a new long -span girder beam. Based on preliminary structural analysis, the required specifications for the new ceiling beam would be as follows: New Ceiling Beam: 3-1/2" x 15" 24F-V4 Glulam (may be recessed above ceiling) New End Supports: Remove drywall to verify minimum (4)2x4 bearing studs, or add new solid 4x4 DF#2 post Post Foundations: Existing exterior wall foundation is structurally acceptable Verify or add new 20"x20"x7" pad footing in crawlspace below interior bearing point. Sample markups describing the Option-2 beam installation layout are provided in Figure 6. It is advised that you discuss the costs of this option with a qualified remodel contractor to assess the scope of the project. I trust that the above report provides you with sufficient detail to proceed with your project. If you have any questions or require further analysis or recommendations please feel free to contact our office. Regards, W�lSpti� Eli S. Grassley, PE ESG Design / B 01810. : ��V� x�Y,.. Al 0 ENGINEERED • STRUCTURES • GLOBAL • DESIGN IFedoriska Wall Demo Page 3 FEDORISKA Engineered Structures Global Design, PLLC www.esg-design.com BeamChek v2020 licensed to: ESG Design Reg # 4151-64740 NEW CEILING BEAM Prepared by: ESG Date: 3/16/21 Selection 3-1/8x 15 GLB 24F-V4 DF/DF Lu = 16.0 Ft Conditions NDS 2015 Min Bearing Area R1= 5.8 in R2= 5.8 in (1.5) DL Defl= 0.27 in Recom Camber= 0.40 in Data Attributes Actual Critical Status Ratio Values Adjustments Beam Span 16.0 ft Reaction 1 LL 2300 # Reaction 2 LL 2300 # Beam Wt per ft 11.39 # Reaction 1 TL 3791 # Reaction 2 TL 3791 # Bm Wt Included 182 # Maximum V 3791 # Max Moment 15165'# Max V (Reduced) 3199 # TL Max Defl L / 240 TL Actual Defl L / 360 LL Max DO L / 360 LL Actual Defl L / 718 Section (in') Shear (inz) TL DO (in) LL Defl 117.19 46.88 0.53 0.27 96.96 17.38 0.80 0.53 OK OK OK OK 83% 37% 67% 50% Fb (psi) Fv (psi) E (psi x mil) Fe-L (psi) Reference Values 2400 240 1.8 650 Adjusted Values 1877 276 1.8 650 Cv Volume 1.000 Cd Duration 1.15 1.15 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1.00 1.00 Cl Stability 0.6800 Rb = 23.45 Le = 29.83 Ft Loads Uniform LL: 288 Uniform TL: 403 = A Par Unif TL Start End H = 60 0 16.0 H Uniform Load A R1 = 3791 R2 = 3791 SPAN =16FT Uniform and partial uniform loads are Ibs per lineal ft.