FIR2022-0008+Fire_Sprinkler_Equipment_Specification_Sheets+1.26.2022_3.38.28_PM+2643797RECEIVED Jan 27 2022 FIR2022-0008 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT .••���•. .•00,00�. cosco •�' Fire Protection FIRE PROTECTION MATERIAL SUBMITTAL SMC 704-705-706 21601 76TH AVE W EDMONDS WA 98026 Fire Protection Contractor Cosco Fire Protection 4308 South 131s' PI. REVIEWED BY CITY OF EDMONDS Tukwila, Washington 98168 (206) 438-3360 Fax: (206) 438-3356 JOB # 25SS8835 . 0 • •• • • . .go* 0*0. COSCO Fire Protection TABLE OF CONTENTS SECTIONS 1. PIPE AND FITTINGS a. Schedule 40 Pipe b. Mechanical Tee c. Threaded Fittings d. VicFlex 2. SPRINKLER HEADS a. VK3021 3. HANGERS a. All Thread Rod b. Ring Hangers c. Beam Clamp d. Retaining Strap ••••••COSCO ' • is •• • • Fire Protection SECTION 1. PIPE AND FITTINGS FM Approved and Fully Listed SprinklerPipe SCHEDULE 10 SPECIFICATIONS Wheatland's Schedule 10 and Schedule 40 steel fire sprinkler pipe is FM Approvedand UL, NOMINAL NOMINAL C-UL and FM Listed. NPS NOMOD NOMID WALL WEIGHT UL PIECES Approvals and Specifications - in. mm in. mm in. mm lbs./ ft. kg/ m CRR* Lift Both products meetorexceed the following standards: 1 Y* 1.660 42.2 1.442 36.6 .109 2.77 1.81 2.69 7.3 61 • ASTM A135, Type E, Grade A (Schedule 10) 1 y 1.900 48.3 1.682 42.7 .109 2.77 2.09 3.11 5.8 61 • ASTM A795, Type E, Grade A (Schedule 40) 2 2.375 60.3 2.157 54.8 .109 2.77 2.64 3.93 4.7 37 • NFPA 13 ___2V2_ 2.875 73.0 2.635 66.9 .120 3.05 3.53 5.26 3.5 30 Manufacturing Protocols 3 3.500 88.9 3.260 82.8 .120 3.05 4.34 6.46 2.6 19 Schedule 10 and Schedule 40 are subjected to the toughest possible testing protocols to a 4.500 114.3 4.260 108.2 .120 3.05 5.62 8.37 1.6 19 ensure the highest quality and long-lasting 5 5.563 141.3 5.295 134.5 .134 3.40 7.78 11.58 1.5 13 performance. 6 6.625 168.3 6.357 161.5 .134 3.40 9.30 13.85 1.0 10 Finishes and Coatings 8 8.625 219.1 8.249 209.5 .188 4.78 16.96 25.26 2.1 7 All Wheatland black steel fire sprinkler pipe * Calculated using Standard UL CRR formula, UL Fire Protection Directory, Category VIZY. up to 6" receives a mill coating to * The CRR is a ratio value used to measure the ability of a pipe to withstand corrosion. proprietary Threaded Schedule 40 steel pipe is used as the benchmark (value of 1.0). ensure a clean, corrosion -resistant surface that outperforms and outlasts standard lacquer coatings. This coating allows the pipe to be SCHEDULE 40 SPECIFICATIONS easily painted, without special preparation. Schedule 10 and Schedule 40 can be ordered in NOMINAL NOMINAL black, or with hot -dip galvanizing, to meet NPS NOM OD NOM ID WALL WEIGHT UL PIECES FM/UL requirements for dry systems that meet in. mm in. mm in. mm Ibs./ ft. kg/ m CRR* Lift the zinc coating specifications of ASTM A795 or A53. All Wheatland galvanized material is 1 1.315 33.4 1.049 26.6 .133 3.38 1.68 2.50 1.00 70 also UL Listed. 1+/. 1.660 42.2 1.380 35.1 .140 3.56 2.27 3.39 1.00 51 Product Marking 1'/s 1.900 48.3 1.610 40.9 .145 3.68 2.72 4.05 1.00 44 Each length of Wheatland fire sprinkler pipe is continuously stenciled to show 2 2.375 60.3 2.067 52.5 .154 3.91 3.66 5.45 1.00 30 the manufacturer, type ofpipe,grade,size *calculated using Standard ULCRRformula,ULFire Protection Directory. category VIZY. and length. Barcodingisacceptable asa * The CRR is a ratio value used to measure the ability of a pipe to withstand corrosion. supplementary identification method. Threaded Schedule 40 steel pipe is used as the benchmark (value of 1.0). �� C UL F APPROVED ENGINEER: SPECIFICATION REFERENCE: LOCATIONS: COMMENTS: SYSTEM TYPE: ❑ BLACK '•�::�•i Fire protection ❑ HOT -DIP GALVANIZED PROJECT: CONTRACTOR: DATE: WFS-051516 CARBON STEEL PIPE - HOLE CUT PRODUCTS 11.02 Mechanical-T® Bolted Branch Outlets STYLES 920 AND 920N DIMENSIONS GROOVED OUTLET Y<-z� Iv 04 1? w FEMALE THREADED OUTLET Provides a direct branch connection at any location where a hole can be cut in the pipe A pressure responsive gasket provides the seal Request Publication 11.03 for Mechanical-T crossassemblies Pressure rated up to 500 psi/3450 kPa on steel pipe; also available for use with HDPE pipe Sizes from 2 x%"/50x 1 5mm through 8 x 4"/200 x l 00mm IMPORTANT NOTES: Style 920 and Style 920N housings cannot be mated to one another to achieve cross connections. 2 x 1/2(a)N 92ON 500 1.50 2.00 2.53 _ I 1.61 1 5.35 2.75 I 3.1 50 15 3450 38.1 51 64 41 136 70 1.5 3/4 (a) n 500 I 1.50 I 1.97 2.53 1.61 5.35 2.75 3.1 20 920N 3450 38.1 50 64 41 136 70 1.5 1(a) o 500 1.50 1.85 2.53 1.61 5.35 2.75 3.0 25 920N 3450 38.1 47 64 41 136 70 1.4 11/4(a) to 500 1.75 2.05 2.75 3.00 1.61 5.35 3.00 3.5 3.2 32 920N 3450 44.5 52 70 76 41 136 76 1.7 1.5 11/2(a) to 500 1.75 2.03 2.75 3.12 1.61 5.35 3.25 3.6 3.2 40 920N 3450 500 44.5 1.50 52 2.21 70 2.74 79 41 1.82 136 5.64 83 2.75 1.7 3.0 1.5 21/2 1/2 (a) §o x 65 15 920N 3450 38.1 56 70 _ 46 143 70 1.4 3/4 (a) §u 500 1.50 2.18 2.74 1.82 5.64 2.75 3.0 20 920N 3450 38.1 55 70 46 143 70 1.4 1(a) §u 500 1.50 2.06 2.74 1.82 5.64 2.75 2.9 25 y20N 3450 38.1 52 70 46 143 70 1.4 11/4t(a) 500 1.75 2.30 3.00 3.25 1.82 6.29 3.0o 3.5 ' 3.2 32 920N 3450 44.5 58 76 83 46 160 76 1.7 1.5 11/2t(a)r 500 2.00 1 2.28 3.00 3.25 1.82 6.26 3.25 3.6 3.3 40 920N 920N 3450 300 50.8 1.50 58 2.22 76 2.75 83 _ 1 46 2.25 159 6.46 83 3.18 1.7 3.9 1.6 _ 76.1 x 1/2 (a) 15 2065 38.1 56 70 57 164 81 1.8 3/4 (a) 300 1.50 2.19 2.75 2.25 6.46 3.18 3.9 20 920N 2065 38.1 56 70 57 164 81 1.8 1(a) 300 1.50 2.07 2.75 2.25 6.46 3.18 3.8 25 920N 2065 38.1 53 70 57 164 81 1.7 11/4(a)0 500 1.75 2.30 3.00 3.31 1.92 6.29 3.00 3.5 3.2 32 920N 3450 44.5 58 76 84 49 160 76 1.6 1.5 11/2(a)33 500 2.00 2.28 3.00 3.31 1.92 6.29 3.25 3.5 3.3 40 920N 920N 3450 500 50.8 1.50 58 2.52 76 3.05 84 _ 49 2.28 160 6.15 83 2.75 1.6 3.4 1.5 3 x 1/2(a)m 80 15 3450 38.1 64 78 58 156 70 1.6 3/4 (a) u 500 1.50 2.49 3.05 2.28 6.15 2.75 3.4 20 920N 3450 38.1 63 78 58 156 70 1.6 1(a) 500 1.50 2.38 3.06 2.28 6.15 2.75 3.3 25 920N 3450 38.1 61 78 58 156 70 1.6 11/4(a)tu 500 1.75 2.55 3.25 3.56 2.28 6.15 I 3.00 3.8 3.7 32 (b) 920N 3450 44.5 65 83 90 58 156 76 1.8 1.8 11/2(a)tzt 500 2.00 2.78 3.50 3.56 2.28 6.15 3.25 4.1 3.8 40 (b) 920N 3450 50.8 71 89 90 58 156 83 1.9 1 1.8 2 (a) o 500 2.50 2.75 3.50 3.56 2.28 1 6.75 3.88 4.9 4.6 50 920N 920N 3450 500 63.5 2.50 70 3.00 89 _ 90 3.75 58 2.44 172 6.72 99 3.88 2.3 _ 2.1 31/2 x 2 3.8 90 50 3450 63.5 76 95 62 171 99 1.8 TABLE CONTINUED ON PG. 3 ** Center of run to engaged pipe end, female threaded outlet only (dimensions approximate). t Available with grooved or female threaded outlet. Specify choice on order. t Center of run to end of fitting. # Female threaded outlets are available to NPT and BSPT specifications. @ See page 7 for Fire Protection approvals and pressure ratings. (a) British Standard female pipe threaded outlet is available as listed. Specify "BSPr clearly on order (b) For 76.1 mm threaded outlet, specify 21/2" BSPT clearly on order. § Vds approved for fire protection services o LPCB approved for fire protection services 0 Approved for use in China by Tianjin Approvals Company. www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2018 VICTAULIC COMPANY. ALL RIGHTS RESERVED. 11.02_2 ✓ctaulicr REV 0 CARBON STEEL PIPE - HOLE CUT PRODUCTS 11.02 Mechanical -TO Bolted Branch Outlets STYLES 920 AND 920N DIMENSIONS E Y A-Z 0� TABLE CONTINUED FROM PAGE 2 4 x 1/2(a)II 920N 500 1.50 3.03 3.56 _ 2.69 7.01 2.75 3.7 V 100 15 3450 38.1 77 90 68 178 70 1.8 3/4 (a) u 920N 500 1.50 3.00 3.56 _ 2.69 7.01 2.75 3.7 _ 20 3450 38.1 76 90 68 178 70 1.8 W 1(a) o 920N 50° 1.50 2.88 3.56 _ 2.69 7.01 2.75 3.6 _ 25 3450 38.1 73 90 68 178 70 1.8 GROOVED OUTLET 11/4(a)to g20N 500 1.75 3.08 3.78 4.00 2.69 7.01 3.00 4.0 3.6 32(b) 3450 44.5 78 96 102 68 178 76 1.9 1.8 11/2(a) to 920N 500 2.00 3.28 4.00 4.00 2.69 7.01 3.25 4.2 3.9 Y Z 40 (b) 3450 50.8 83 102 102 68 178 83 2.0 1.9 2 (a) to g20N 500 2.50 3.25 4.00 4.00 2.69 7.01 3.88 5.0 4.6 50 3450 1 63.5 83 102 102 68 178 99 2.3 2.1 V 21/2(a)t 500 2.75 2.88 4.00 4.00 2.69 7.34 4.63 5.8 5.0 T 65 920 3450 69.9 73 102 102 68 186 118 2.6 2.3 500 2.75 2.88 _ 4.00 2.69 7.34 4.63 _ 6.4 76.1 mm 920 3450 69.9 73 102 68 186 118 2.9 W 3 (a) t 920 500 3.50 3.31 4.50 4.12 2.69 7.73 5.12 8.4 6.4 FEMALE THREADED OUTLET 80 3450 88.9 84 114 105 68 196 130 3.8 2.9 108.0 x 1 1/4 (a)o g20N 500 1.75 3.08 3.78 _ 2.63 7.64 3.05 5.0 32 3450 44.5 78 96 67 194 78 2.3 Provides a direct branch connection at 11/2 (a)o 920N 500 2.00 3.28 4.00 _ 2.63 7.64 3.25 5.0 _ 40 3450 50.8 83 102 67 194 83 2.3 any location where a hole can be cut 2(a) 500 2.50 3.25 4.00 _ 2.63 7.64 4.00 4.0 _ in the pipe 50 920N 1 3450 63.5 83 102 67 194 102 1.9 76.1 mm 920 500 2.75 2.88 4.00 4.00 2.63 7.64 4.29 8.0 7.8 Apressureresponsivegasketprovides 3450 69.9 73 102 102 67 194 109 3.6 3.5 the seal 3 (a) 500 3.50 3.31 4.50 4.50 2.63 7.63 4.88 6.8 6.5 80 920 3450 88.9 84 114 114 67 194 124 3.1 3.0 Request Publication 11.03 for 5 x11/2(a)t 500 2.00 4.03 4.75 4.75 3.16 9.70 3.69 7.4 7.6 Mechanical-T crossassemblies 125 40 920 3450 50.8 102 121 121 80 246 94 3.4 3.4 2 (a) t 500 2.50 4.00 4.75 4.75 3.16 9.70 4.38 8.2 8.0 Pressure rated up to 500 psi/3450 kPa so 920 3450 63.5 102 121 121 80 246 111 3.7 3.6 on steel pipe; also available for use 21/2(a)t 500 2.75 3.63 4.75 4.75 3.16 9.70 4.63 8.3 7.9 with HDPE pipe 65 920 3450 69.9 92 121 121 80 246 118 3.8 3.6 i 76.1mmu 920 500 2.75 3.75 4.75 3.16 9.70 4.63 8.0 Sizesfrom2xY2"/50x15mm 3450 69.9 95 - 121 80 246 118 - 3.6 through 8 x4"/200 x 1 00mm 3(a)t 500 3.50 3.81 5.00 4.63 3.16 9.70 5.31 8.4 8.8 80 920 3450 88.9 97 127 118 80 246 135 3.8 4.0 133.0 x 52 500 2.50 3.75 4.50 _ 3.17 8.00 3.88 8.0 _ 0 920N 3450 63.5 95 114 81 203 99 3.6 3 500 3.50 3.81 5.00 _ 3.00 9.46 5.31 8.0 _ 80 920 3450 88.9 97 127 76 240 135 3.6 TABLE CONTINUED ON PG. 4 IMPORTANT NOTES: ** Center of run to engaged pipe end, female threaded outlet only (dimensions approximate). Style 920 and Style 920N housings cannot be t Available with grooved or female threaded outlet. Specify choice on order. mated to one another t Center of run to end of fitting. to achieve cross connections. # Female threaded outlets are available to NPT and BSPT specifications. @ See page 7 for Fire Protection approvals and pressure ratings. (a) British Standard female pipe threaded outlet is available as listed. Specify "BSPT clearly on order. (b)For 76.1 mm threaded outlet, specify 21/2" BSPT clearly on order. § Vds approved for fire protection services o LPCB approved for fire protection services 0 Approved for use in China by Tianjin Approvals Company. www.victaulic.com �CtSIl,11iC" VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. @ 2018 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV-0 11.023 CARBON STEEL PIPE - HOLE CUT PRODUCTS 11.02 Mechanical-T® Bolted Branch Outlets STYLES 920 AND 920N DIMENSIONS y _ �Z fiL71■�1i TABLE CONTINUED FROM PAGE 3 139.7 x 1 1/2 t 920N 500 2.00 3.78 4.50 3.30 8.23 3.25 7.0 V 40 3450 50.8 96 114 84 209 83 3.2 1 2 t 500 2.50 3.75 4.50 _ 3.30 8.23 3.88 9.0 50 920N 3450 63.5 95 114 84 209 99 4.1 6 11/4(a) g20N 500 1.75 4.43 5.13 5.13 3.79 9.15 3.25 5.1 y 150 x 32(b) 3450 44.5 112 130 130 96 232 83 2.3 GROOVED OUTLET 11/2(a) ttt 920N 500 2.00 4.40 5.13 5.13 3.79 9.15 3.25 5.4 40(b) 3450 50.8 112 130 130 96 232 83 2.4 2 (a) to g20N 500 2.50 4.38 5.13 5.13 3.79 9.15 3.88 6.0 E y Z _� 50 3450 63.5 ill 130 130 96 232 99 2.7 21/2 920 500 2.75 4.01 5.13 5.12 3.69 10.51 4.63 8.3 65 3450 69.9 110 130 130 94 267 118 3.8 V 500 2.75 4.15 _ 5.21 3.69 10.51 4.63 _ T 76.1 m mtt 920 3450 69.9 105 132 94 267 118 -- 3 (a) t 920 500 3.50 4.31 I 5.50 5.13 3.69 10.51 5.31 9.9 W 80 3450 88.9 110 140 130 94 267 135 4.5 0, Iq 4 (a) to 500 4.50 3.81 5.75 5.38 3.69 10.51 6.25 10.1 FEMALE THREADED OUTLET 100 920 3450 114.3 97 146 137 94 267 159 4.6 1 1/2 (a) 500 2.00 4.41 5.13 I _ 3.63 9.40 3.25 7.8 159.0 x 40 920N 3450 50.8 112 130 92 239 83 3.5 2 (a) 920N 500 2.50 4.38 5.13 _ 3.63 9.40 3.88 8.0 Provides a direct branch connection at 50 3450 63.5 ill 130 92 239 99 3.6 any location where a hole can be cut 500 2.75 4.38 5.50 5.13 3.63 9.40 4.63 9.5 in the pipe 76.1 mm 920 3450 69.9 ill 140 130 92 239 118 4.3 3 500 3.50 4.31 5.50 5.13 3.63 9.40 5.31 8.1 Apressure responsive gasket provides 80 920 3450 88.9 110 140 130 92 239 135 3.7 the seal 500 4.50 4.45 _ 5.38 3.63 9.40 6.12 _ 108.Omm 920 3450 114.3 113 137 92 239 155 Request Publication 11.03 for 4 920 500 4.50 3.81 5.75 _ 3.63 9.40 6.25 18.0 Mechanical-T crossassemblies 100 3450 114.3 96.80 146 92 239 159 8.2 TABLE CONTINUED ON PG. 5 Pressure rated up to 500 psi/3450 kPa ** Center of run to engaged pipe end, female threaded outlet only (dimensions approximate). on steel pipe; also available for use t Available with grooved or female threaded outlet. Specify choice on order. with HDPE pipe t Center of run to end of fitting. Sizes from 2 x%2"/50x 1 5mm # Female threaded outlets are available to NPT and BSPT specifications. through 8 x 4"/200 x 100mm @ See page 7 for Fire Protection approvals and pressure ratings. (a) British Standard female pipe threaded outlet is available as listed. Specify "BSPT" clearly on order. (b) For 76.1 mm threaded outlet, specify 21/2" BSPT clearly on order. § Vds approved for fire protection services u LPCB approved for fire protection services IMPORTANT NOTES: 0 Approved for use in China by Tianjin Approvals Company. Style 920 and Style 920N housings cannot be mated to one another to achieve cross connections. www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2018 VICTAULIC COMPANY. ALL RIGHTS RESERVED. 11.02_4 4.8 2.2 5.1 2.3 5.6 2.5 7.6 3.4 8.4 3.8 8.4 3.8 10.1 4.6 9.5 4.3 14.0 6.4 10.0 4.5 ✓ctoulier REV 0 CARBON STEEL PIPE - HOLE CUT PRODUCTS 11.02 Mechanical -TO Bolted Branch Outlets STYLES 920 AND 920N DIMENSIONS E Y - `Z V 01T 4W y GROOVED OUTLET a Y _Z_ W FEMALE THREADED OUTLET Provides a direct branch connection at any location where a hole can be cut in the pipe A pressure responsive gasket provides the seal Request Publication 11.03 for Mechanical-T crossassemblies Pressure rated up to 500 psi/3450 kPa on steel pipe; also available for use with HDPE pipe Sizesfrom2x%"/50x 1 5mm through 8x4"/200x 100mm IMPORTANT NOTES: Style 920 and Style 920N housings cannot be mated to each other to achieve cross connections. 1 500 1.50 3.88 4.56 _ 3.79 9.34 2.75 8.0 _ 165.1 x 25 920N 1 3450 38.1 99 116 96 237 1 70 3.6 1 1/4 0 920N 500 1.75 4.43 5.13 _ 3.79 9.34 I 3.25 I 8.4 32 3450 44.5 113 130 96 237 83 3.8 11/2(a)ttt 920N 500 2.00 4.41 5.13 5.13 3.79 9.34 3.25 8.4 5.4 40 3450 50.8 112 130 130 96 237 83 3.8 2.4 2 (a) t 920N 500 2.50 4.38 5.13 5.13 I 3.79 9.34 3.88 8.5 6.0 50 3450 63.5 111 130 130 96 237 99 3.9 2.7 76.1 mm 92p 500 2.75 4.01 5.13 5.21 3.63 10.51 4.63 8.6 7.6 3450 69.9 110 130 132 92 267 118 3.9 3.4 3 (a) t 0 500 3.50 4.31 5.50 5.13 3.63 10.51 5.31 10.2 8.4 80 920 3450 88.9 110 140 130 92 267 135 4.6 3.8 4 (a) to 500 4.50 3.81 5.75 5.38 3.63 10.51 6.25 10.5 8.4 100 920 3450 114.3 97 146 137 92 267 159 4.8 3.8 8 x 2 (a) t 500 2.75 5.44 6.19 6.25 4.81 12.42 4.50 11.6 11.6 200 50 920 3450 69.9 138 157 159 122 316 114 5.3 5.3 21/2(a)t 500 2.75 5.07 6.19 6.19 4.81 12.42 4.50 11.6 11.6 65 920 3450 69.9 129 157 157 122 316 114 5.3 5.3 76.1mmtt 920 500 2.75 5.25 _ 6.25 4.81 12.42 4.56 _ 11.6 3450 69.9 133 159 122 316 116 1 5.3 3 (a) to 500 3.50 5.31 6.50 6.50 4.81 12.42 5.31 12.6 1 11.6 80 920 3450 88.9 135 165 165 122 316 135 5.7 5.3 4 (a) to 500 4.50 4.81 6.75 6.38 4.81 12.42 6.25 15.3 12.5 100 920 3450 114.3 122 171 162 122 316 159 6.9 5.7 t Available with grooved or female threaded outlet. Specify choice on order. t Center of run to end of fitting. # Female threaded outlets are available to NPT and BSPT specifications. @ See page 7 for Fire Protection approvals and pressure ratings.' (a) British Standard female pipe threaded outlet is available as listed. Specify "BSPT" clearly on order. (b)For 76.1 mm threaded outlet, specify 21/2" BSPT clearly on order. § Vds approved for fire protection services 9 LPCB approved for fire protection services 0 Approved for use in China by Tianjin Approvals Company. www.victaulic.com �CtalUli@P VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. @ 2018 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV-0 11.025 CARBON STEEL PIPE - HOLE CUT PRODUCTS Mechanical-T® Bolted Branch Outlets STYLES 920 AND 920N FLOW DATA U Exaggerated for clarity 11.02 Flow test data has shown that the total head loss between point (1)and (2) forthe Style 920, 920N and 929Mechanical-T®fittingscan bestbeexpressed in terms of the pressured ifferenceacrossthe inletand branch. The pressure difference can be obtained from the relationship below. Cv and Kv Values Values for flow of water at+60`F/+16`C are shown in the table below. Formulas for Cv/Kv Values: AP = Qz Where: AP = Q! Where: C z Q= Flow (GPM) 1 Q =Flow (m3/hr) AP =Pressure Drop (psi) 6P = Pressure Drop (Bar) Q = C x AP Cv= Flow Coeflcient Q = K•, x ../aP K„ =Flow Coefficient OUTLET NOMIN I ffHREADED 1/2 0.840 GROOVEDIn/mrREADIED 11 1s 21.3 1.050 2 9.4 16 3/4 20 26.7 4 13.7 21 1 1.315 25 33.7 3" 8 50 1.8 48 11/4 1.660 51/2 6 32 42.7 42.9 53 41.1 53 11/2 1.900 40 48.3 11 11 45.4 112 45.4 104 2 2.375 9 101/2 50 60.3 96 119 891 150 21/2 2.875 20 12 1/2 65 73.0 102 161 128.5 3.000 76.1 mm 16* 76.1 3.500 138.1 249 237 3 14 15 1/2 80 88.9 4.500 213.4 421 203.1 401 4 100 114.3 20 22 1 360.8 343.6 t Hazen -Williams coefficient of friction is 120. * Pipe with a wall thickness of 0.165in./4.2mm. ** 1" Firel-ock'" Innovative Groove System (IGS) outlet www.victaulic.com �c-t die" VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2018 VICTAULIC COMPANY. ALL RIGHTS RESERVED. 11.026 REV-0 CARBON STEEL PIPE - HOLE CUT PRODUCTS 11.02 Mechanical -TO Bolted Branch Outlets STYLES 920 AND 920N FIRE PROTECTION APPROVALS AND PRESSURE RATINGS The information provided below is based on the latest listing and approval data atthe time of publication. Listings/Approvals are subject to change and/oradditions bythe approvals agencies. Contact Victaulic for performance on other pipe and the latest listings and approvals. 21/2 - 6 2.875- 6.625 400 400 400 290 232 All 10, 40 65-150 73.0-168.3 2755 2755 2755 1999 1599 21/2 - 4 2.875 - 4.500 300 300 300 290 232 65-100 73.0-114.3 All OF 2065 2065 1 2065 1999 1599 21/2 - 4 2.875 - 4.500 300 300 300 290 232 65 - 100 73.0 - 114.3 All SF 2065 2065 2065 1999 1599 6 6.625 300 300 250 290 232 3,4 10 150 168.3 2065 2065 1724 1999 1599 6 6.625 300 300 300 290 232 3,4 30, 40 150 168.3 2065 2065 2065 1999 1599 8 8.625 21/2 10, 40 400 _ _ _ 145 200 219.1 2755 1000 8 8.625 300 250 145 3,4 10 _ _ 200 219.1 2065 1724 1000 8 8.625 300 300 145 200 219.1 3,4 30, 40 2065 _ 2065 _ 1000 NOTES: 10 refers to Listed/Approved Schedule 10 steel sprinkler pipe. 40 refers to Listed/Approved Schedule 40 steel sprinkler pipe. DF refers to Listed/Approved Dyna-Flow steel sprinkler pipe manufactured by American Tube Company. SF refers to Listed/Approved Super -Flo steel sprinkler pipe manufactured by Allied Tube and Conduit Corporation VIC-TAP II HOLE CUTTING TOOL FOR 4 - 8' /100 - 200MM CARBON STEEL PIPE 362 2496 362 2496 362 2496 362 2496 362 2496 The Vic -Tap II hole cutting tool is designed for use with the Style 931 Vic -Tap II Mechanical-T unit, which is acombination of the Style 920 Mechanical-T and Series 726 Vic -Ball Valve. The Vic -Tap II is capable of tapping into carbon steel pipe systems under pressures up to 500psi/3450kPa. TheStyle931 Vic-TapllMechanical-TunitisafuIIport ballvalvewhichcan bemountedon4"/100mm, 5"/125mm,6"/150mmand8"/200mmdiameter pipe. The Style 931 comeswitha2%2"/65mm grooved outlet. The drill motor is an electric motor with ground fault circuit interrupter (GFCI) in accordance with safety codes. For more information, refer to publication 24.01. www.victaulic.com �CtalUli@P VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.© 2018 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV-0 11.027 �i EDdMZTJLrmdl20N THREADED FITTINGS FIG. WWI 900 Elbow A FIGURE • 900 ELBOW Nominal Size Maximum Dimension A Approx. Wt. Each Working Pressure In. (mm) PSI (kPa) In. (mm) Lbs. (kg) 1 500 1.50 0.62 20 3450 38.10 0.28 1'A 500 1.75 0.90 32 3450 44.45 0.41 1'12 500 1.94 1.20 40 3450 49.276 0.54 2 Wo do Press re latest UL/band �M 500 atin sa f referen pressure sversu e only a�tb1ledon Sc h!/ Pipe sc edule, ldSe h. 40 pip the isit anvi om or 51E0 APPROVED (Approval Details and Limitations, website at www.anvilintl.com or in Anvil'Sales Representative. Dimensions: ASME B16.3 Material: ASTM A536 Grade 65-45-12 Finish: Black Threads: NPT per ASME B1.20.1 Agency Approvals: All ductile iron threaded fittings are UL/ULC Listed and FM Approved. NOTICE: Ductile iron fittings have higher tensile strength than that of steel pipe. Therefore, overtightening can cause damage to pipe threads which may cause leakage. Ductile ironfittings should betightened approximatelythreeturns beyond hand tight, but no more than four turns. PROJECT•' •APPROVAL Project: Approved Address: Approved as noted Contractor: Not approved Engineer: marks: ❑ ❑ Submittal Date: Notes 1: Notes 2: SPF/MI-1.15 Class 150 (Standard) FIG. 3105R Reducing Tee 2 3 FIGURE 3105R - REDUCING TEE Nominal Size Dimensions Approx. 1 2 3 A B C Wt. Each In. (mm) In. (mm) In. (mm) In. (mm) Lbs. (kg) '14 0.97 0.97 0.98 0.24 8 24.64 24.64 24.89 0.11 3/8 1.04 1.04 1.03 0.27 ' z 'lt 10 26.42 26.42 i 26.16 i 0.12 15 3/4 1.22 1.22 1.20 0.37 20 30.99 i 30.99 30.48 0.17 1 1.36 1.36 1.26 0.49 25 34.54 34.54 32.00 0.22 '/t 1.20 1.12 1.22 0.38 1l2 15 30.48 26.16 28.45 0.17 15 3/4 1.31 1.22 1.31 0.45 20 33.27 28.45 33.27 0.20 'A 1.05 1.05 1.08 0.36 8 26.67 26.67 27.43 0.16 3/8 1.12 1.12 1.13 0.39 3/4 10 28.45 28.45 28.70 0.18 20 1/2 1.20 1.20 1.22 0.43 15 30.48 30.48 30.99 0.20 1 1.45 1.45 1.37 0.62 25 36.83 36.83 28.45 0.28 '/4 1 1.50 1.18 1.50 0.63 8 25 38.10 29.97 38.10 0.29 1/2 1.26 1.12 1.36 0.48 1 15 32.00 I 28.45 I 34.54 0.22 '/2 3/4 1.37 1.22 1.45 0.56 15 20 34.80 28.45 34.54 0.25 1 1.50 1.36 1.50 0.67 25 38.10 34.54 38.10 0.30 PROJECT INFORMATION I I C �L II$ FM LISTED APPROVED For Li tings/Approval Details and Limitations, visi our website at -.anvilintl.com or contact an Anvil -Sales Representative. Dimensions: Fittings: ASME B16.3 Unions: ASME B16.39 Bushings/Plugs: ASME B16.14 Material: ASTM A-197 Finish: Black or Hot Dip Galvanized per ASTM A153 Class A Threads*: NPT per ASME B1.20.1 Pressure Ratings: Fittings: ASMEB16.3 Unions: ASME B16.39 Bushings/Plugs: ASME B16.14 Pressure Testing: All malleable iron fittings are tested for through wall porosity using an air underwater process. Agency Approvals: All malleable iron fittings and unions are UL/ULC Listed and FM Approved. . British Standard threading per BS 21 available upon request. SPF/DI-1.15 <s R�Nv'L MALLEABLE 1RONMRWAMMERUMMM &AWIL Class 150 (Standard) FIG. 3105R Reducing Tee 1 x 2 x 3 FIGURE 310SR - REDUCING TEE Nominal Size Dimensions Approx. 1 2 3 A B C Wt. Each In. (mm) in. (mm) in. (mm) In. (mm) Lbs. (kg) 1/2 1.26 1.20 1.36 0.53 15 32.00 30.48 34.54 0.24 3 14 3 /4 1.37 1.31 1.45 0.61 20 20 34.80 33.27 36.83 0.28 1 1.50 1.45 1.50 0.71 25 38.10 36.83 38.10 0.32 3 /8 1.18 1.18 1.27 0.57 10 29.97 29.97 32.26 0.26 1 1/2 1.26 1.26 1.36 0.62 15 32.00 32.00 34.54 0.28 3 /4 1.37 1.37 1.45 0.69 1 20 28.45 28.45 36.83 0.31 1 '/4 1.67 1.67 1.58 0.94 32 42.42 42.42 40.13 0.43 1 '/2 1.80 1.80 1.65 1.07 40 45.72 45.72 41.91 0.49 2 2.02 2.02 1 1.73 1.45 50 51.31 51.31 43.94 0.66 1 1.58 1.36 1.67 0.82 25 40.13 34.54 42.42 0.37 1 '/4 1.75 1.53 1.75 0.95 32 44.45 38.86 44.45 0.43 '/4 1.45 1.31 1.62 0.75 20 36.83 33.27 41.15 0.34 '/4 1 1.58 1.45 1.67 0.87 20 25 40.13 36.83 42.42 0.39 1 '/4 1.75 1.62 1.75 1.00 32 44.45 41.15 44.45 0.45 1/2 1.34 1.26 1.53 0.74 15 34.04 32.00 38.86 0.34 '/4 1.45 1.37 1.62 0.82 20 36.83 28.45 41.15 0.37 1 1.58 1.50 1.67 0.94 25 40.13 38.10 42.42 0.43 1 '/4 1.75 1.67 1.75 108 32 1 44.45 1 42.42 44.45 0*49 FIGURE 3105R - REDUCING TEE Nominal Size Dimensions Approx. 1 2 -F 3 A B C Wt. Each In. (mm) In. (mm) In. (mm) In. (mm) Lbs. (kg) 1/8 1.26 1.26 1.44 0.78 10 32.00 32.00 36.58 0.35 1/2 1.34 1.34 1.53 0.84 15 34.04 34.04 38.86 0.38 3 /4 1.45 1.45 1.62 0.92 V/4 1 '/4 20 36.83 36.83 41.15 0.42 1 1.58 1.58 1.67 1 1.04 32 32 25 40.13 40.13 42.42 0.47 1.88 1.88 1.82 1.34 47.75 47.75 46.23 0.61 IS 2.10 1.90 1.65 53.34 53.34 48.26 0.75 '/2 11/2 1.94 1.66 1.94 1.24 15 40 49.28 42.16 49.28 0.56 'A 1.50 1.26 1.69 0.86 3 /4 20 38.10 32.00 42.93 0.39 11/2 1.94 1.75 1.94 1.29 20 40 49.28 44.45 49.28 0.59 1 1.65 1.50 1.80 1.08 25 41.91 38.10 45.72 0.49 1! 1.82 1.67 1.88 1 1.23 32 46.23 42.42 47.75 0.56 11/2 1.94 1.80 1.94 1.35 40 49.28 45.72 49.28 0.61 3 /4 1.52 1.45 1.75 to 20 38.61 36.83 44.45 0.47 1 1.65 1.58 1.80 1.17 1 '/2 25 41.91 40.13 45.72 0.53 1! 1.82 1.75 1.88 1.32 40 1! 32 32 46.23 44.45 47.75 0.60 11/2 1.94 1.88 1.94 1.45 40 49.28 47.75 49.28 0.66 2 IS 2.10 1.90 is 50 53.34 53.34 48.26 0.83 1/2 1.41 1.41 1.66 to 15 35.81 35.81 42.16 0.47 3 /4 1.52 1.52 1.75 1.14 20 38.61 38.61 44.45 0.52 11/2 1 1.65 1.65 1.80 1.27 40 25 41.91 41.91 45.72 0.58 11/4 1.82 1.82 to 1.43 32 46.23 46.23 47.75 0.65 F2.16 U 2.16 2.02 1.89 54.86 54.86 51.31 0.86 SPF/M 1-1. 15 Class 150 (Standard) FIG. 3105R Reducing Tee 1x2x3 FIGURE 310SR - REDUCING TEE Nominal Size Dimensions Approx. 1 2 3 A B C Wt. Each In. (mm) In. (mm) In. (mm) In. (mm) Lbs. (kg) 1/2 2 2.25 1.88 2.25 1.89 15 50 57.15 47.75 57.15 0.86 3/4 2 2.25 1.97 2.25 1.93 20 50 57.15 50.04 57.15 0.88 1 1.81 1.75 1.87 1.39 1 25 45.97 44.45 47.50 0.63 2 2.25 2.02 2.25 2.00 25 50 57.15 51.31 57.15 0.91 11/4 1.90 1.75 2.10 1.64 32 48.26 44.45 53.34 0.74 11'4 11h 2.02 1.88 2.16 1.80 40 51.31 47.75 54.86 0.82 2 2.25 2.10 2.25 2.09 50 57.15 53.34 57.15 0.95 1 1.73 1.65 2.02 1.57 25 43.94 41.91 51.31 0.71 2 11/4 1.90 1.82 2.10 1.71 50 11/2 32 48.26 46.23 53.34 0.78 40 11h 2.02 1.94 2.16 1.88 40 51.31 49.28 54.86 0.85 2 2.25 2.16 2.25 2.21 50 57.15 54.86 57.15 1.00 1/2 1.49 1.49 1.88 1.53 15 37.85 37.85 47.75 0.69 3/4 1.60 1.60 1.97 1.63 20 40.64 40.64 50.04 0.74 1 1.73 1.73 2.02 1.78 2 25 43.94 43.94 51.31 0.81 11/4 1.90 1.90 2.10 1.97 50 32 48.26 48.26 53.34 0.89 11h 2.02 2.02 2.16 2.12 40 51.31 51.31 54.86 0.96 21h 2.60 2.60 2.39 3.15 65 66.04 66.04 60.71 1.43 FIGURE 3105R - REDUCING TEE Nominal Size Dimensions Approx. 1 2 3 A B C Wt. Each In. (mm) In. (mm) In. (mm) In. (mm) Lbs. (kg) 3/4 1.74 1.74 2.32 2.67 20 44.20 44.20 58.93 1.21 1 1.87 1.87 2.37 2.84 25 47.50 47.50 60.20 1.29 2z 21/2 11/4 2.04 2.04 2.45 3.09 32 51.82 51.82 62.23 1.40 11/2 2.16 2.16 2.51 3.29 40 54.86 54.86 63.75 1.49 2 2.39 2.39 2.60 3.65 50 60.71 60.71 66.04 1.66 2 2 2.52 2.25 2.89 3.88 50 50 64.01 57.15 73.41 1.76 3/4 1.87 1.87 2.61 3.72 20 47.50 47.50 66.29 1.69 1 2.00 2.00 2.66 3.96 25 50.80 50.80 67.56 1.80 3 11/4 2.17 2.17 2.74 4.23 3 32 55.12 55.12 69.60 1.92 11/1 2.29 2.29 2.80 4.45 80 40 58.17 58.17 71.12 2.02 2 2.52 2.52 2.89 4.90 50 64.01 64.01 73.41 2.22 21/2 2.83 2.83 2.99 5.69 65 71.88 71.88 75.95 2.58 2 2.74 2.74 3.41 7.52 50 69.60 69.60 86.61 3.41 4 4 21/2 3.05 3.05 3.51 8.51 100 100 65 77.47 77.47 89.15 3.86 3 3.30 3.30 3.60 9.25 80 83.82 83.82 91.44 4.20 SPF/MI-1.15 SP �RNvL:gt&C.LMEAEBRB IIJMMEPtO E DM ID i RI USN G S &ALWIL FIG. 3ftft 1 R Reducing Coupling Nominal Size Maximum Dimension A Approx. Wt. Each Working Pressure1 In. (mm) PSI (kPa) In. (mm) Lbs. (kg) 1 x'/z 500 1.69 0.39 25x15 3450 42.92 0.18 1 x 3/4 500 1.69 0.53 25x20 3450 42.92 0.24 ♦ —Working Pressure Ratings are for reference only and based on Sch. 40 pipe. For the latest UL/ULC, and FM pressure ratings versus pipe schedule, please visit anvilintl.com or contact your local Anvil Representative. C UL OS FM LISTED APPROVED For Listings/Approval Details and Limitations, visit our website at—anvilintl.com or contact an Anvils Sales Representative. Dimensions: ASME B16.3 Material: ASTM A536 Grade 65-45-12 Finish: Black Threads: NPT per ASME B1.20.1 Agency Approvals: All ductile iron threaded fittings are UL/ULC Listed and FM Approved. NOTICE: Ductile iron fittings have higher tensile strength than that of steel pipe. Therefore, over tightening can cause damage to pipe threads which may cause leakage. Ductile iron fittings should be tightened approximately three turns beyond hand tight, but no more than four turns. PROJECT•' •APPROVALSTAMP Project: Approved Address: Approved as noted Contractor: Not approved Engineer: Remarks: ❑ ❑ ❑ Submittal Date: Notes 1: Notes 2: SPF/MI-1.15 Class 150 (Standard) FIG. 31 M Cap FIGURE Nominal Size 31ff4 - CAP Dimension A Approx. Wt. Each In. (mm) In. (mm) Lbs. (kg) 'la♦ 0.53 0.03 6 13.46 0.01 n♦ 0.63 0.05 8 16.00 0.02 3/8A 0.74 0.07 10 18.80 0.03 'Iz 0.87 0.11 15 22.10 0.05 314 0.97 0.18 20 24.64 0.08 1 1.16 0.30 25 29.46 0.14 1'l4 1.28 0.44 32 32.51 0.20 1'h 1.33 0.55 40 33.78 0.25 2 1.45 0.85 50 36.83 0.39 21I2 1.70 1.49 65 43.18 0.68 3 1.80 2.20 80 45.72 1.00 31h 1.90 3.02 90 48.26 1.37 4 2.08 3.79 100 52.83 1.72 6 2.55 8.77 150 64.77 3.98 ♦-Supplied in Steel only (Black and Galvanized). g&g FM USTEU APPROVED For Listings/Approval Details and Limitations, visit our website at w .anvilintl.00m or contact an AnvP Sales Representative. Dimensions: Fittings: ASME B16.3 Unions: ASME B16.39 Bushings/Plugs: ASME B16.14 Material: ASTM A-197 Finish: Black or Hot Dip Galvanized per ASTM A153 Class A Threads*: NPT per ASME B1.20.1 Pressure Ratings: Fittings: ASMEB16.3 Unions: ASME B16.39 Bushings/Plugs: ASME B16.14 Pressure Testing: All malleable iron fittings are tested for through wall porosity using an air under water process. Agency Approvals: All malleable iron fittings and unions are UL/ULC Listed and FM Approved. * British Standard threading per BS 21 available upon request u Project: LJ Approved Address: LJ Approved as noted Contractor: Not approved Engineer: Remarks: Submittal Date: Notes 1: SPF/DI-1.15 SPF/FINVIL" MALLEABLE IRON THREADED FITTINGS &AWIL Notes 2: SPFIMI-1.15 Victaulic® VicFlexTM Sprinkler Fittings Series AH2 and AH2-CC Braided Flexible Hoses mop — Vic - L 7 SeriesAH2 Series AH2-CC 1.0 PRODUCT DESCRIPTION ✓ctaullc° 10.85 Available Sizes by Component • Series AH21"/DN25 Nominal ID Braided Hose: 31, 36, 48, 60, 72"/790, 91 5, 1 220, 1 525, 1 830 mm. Note: length includes adapter nipple and 5.75"/140 mm straight reducer. • SeriesAH2-CC 1"/DN25 Nominal ID Braided Hose: 31, 36, 48, 60, 72"/790, 91 5, 1 220, 1 525, 1 830mm. Note: length includes captured coupling and 5.75"/l40 mm straight reducer. • Sprinkler Reducers: • Sprinkler Connections: % and 3/"/1 5 and 20 mm • Straight Lengths: 5.75, 9, 1 3"/140, 230, 330mm • 900 Elbows: Short (typically used with concealed sprinklers) Long (typically used with recessed pendent sprinklers) Low Profile Short (for use with Style AB5, AB1 1, AB12, ABBA and ABMM Bracket) Low Profile Long (for use with Style AB5, AB1 1, AB12, ABBA and ABMM Bracket) • Inlet Connections: 1 "/25 mm Grooved IGS 1725mm NPT or BSPT adapter nipples for attaching to pipe and fittings outlined in NFPA standards. %"/20 mm NPT or BSPT adapter nipples available for VdS. 1 %"/ 32 mm BSPT adapter nipples available for LPCB. ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT. System No. Location Spec Section Paragraph Submitted Byl Date Approved Date victaulic.com 10.85 5839 Rev AG Updated 0712019 © 2019 Victaulic Company. All rights reserved. 1 /maullic° victaulic.com 1.0 PRODUCT DESCRIPTION (Continued) Brackets: StyleABI forsuspendedand hard -lid ceilings and sidewalls, allows installation before mostceilingtilesinplace Style AB2 for suspended and hard -lid ceilings and sidewalls, allows for vertical sprinkler adjustment, and installation before most ceiling tiles in place Style AB3 for surface mount applications, wood, metal and block walls, or ceilings StyleAB4 for hard -lid ceilings with hat furring channel grid systems, allows for vertical sprinkler adjustment Style A135 for hard -lid ceilings and sidewalls, allows for vertical sprinkler adjustment Style A137 for suspended and hard-lidceilings Style AB7 Adjustable for suspended and hard -lid ceilings Style A138 for hard -lid ceilings with CD 60/27 profile metal studs (regionally available) Style A139 for hard -lid ceilings with hat furring channel grid systems Style AB10 for Armstrong® TechZonel"ceilings Style AB1 1 for lay -in panel suspended t-grid ceilings or drywall suspended t-grid ceilings, allows for low profile installations (use only with 90' low profile elbows) Style AB12 for suspended and hard -lid ceilings, allows forvertical sprinkler adjustment, and allows for low profile installation down to4"/100mm. Style ABBA bracket for suspended, exposed, and hard -lid ceilings Style ABMM bracket for surface mount and stand off -mount applications, wood, metal and block walls, or ceilings and hard -lid ceilings Maximum Working Temperature • 225-F/107`C Maximum Working Pressure 200 psi/1375 kPa (FMApproval) 175 psi/1206 kPa (cULus Listed) 1600 kPa/232 psi (VdS/LPCB Approved) 1.4 MPa (CCCf Approved) Connections To adapter nipple (inlet) via 1 "/25.4 mm Grooved IGS 1 /25.4 mm NPT or BSPT male thread %"/20 mm BSPT male thread (VdS only) 1 %"/32 mm BSPT male thread (LPCB only) • To sprinkler head (outlet) via %" or 3/"/1 5 mm or 20 mm Minimum Bend Radius 7/178 mm (FM/CCCfApproval) 2"/51 mm (cULus Listed) 3"/76.2mm (VdS/LPCB Approved) Maximum Allowable Sprinkler K-Factors FM (%Z"/15mm reducer) K5.6/8,1 (S.I.), (3/"/20mm reducer) K14.0/20,2 (S.I.) cULus (%2"/1 5 mm reducer) K8.0/1 1,5 (S.I.), (%"/20mm reducer) K14.0/20,2 (S.I.) VdS/LPCB (%2"/15 mm reducer) K5.6/8,1 (S.I.), (%"/20 mm reducer) K8.0/11,5 (S.I.) 10.85 5839Rev AG Updated07/2019©2019VictauIicCompany.AlIrights reserved. victaulic.com X/Ctaullc° victaulic.com 2.0 CERTIFICATION/ LISTINGS FM C UL US vdS LPCB ((( v two NOTE The VicFlexSeries AH2 Hose has been tested and evaluated by Spears® for acceptable use with Spears® CPVC Products and is therefore covered under the Spears® FlameGaurd® Installer Protection Plan. 3.0 SPECIFICATIONS —MATERIAL Series AH2 • Flexible Hose: 300-series Stainless Steel • Collar/Weld Fitting: 300-series Stainless Steel • Gasket Seal: Victaulic EPDM • Isolation Ring: Nylon • Nut and Nipple: Carbon Steel, Zinc Plated • Reducer (1/2"/15mm or 3/4"/20mm): Carbon Steel, Zinc -Plated • Low Profile Elbows: Ductile Iron, Zinc -Plated Brackets: Carbon Steel, Zinc -Plated Series AH2-CC • Flexible Hose: 300-series Stainless Steel • Collar/Weld Fitting: 300-series Stainless Steel • Gasket Seal: Victaulic EPDM • Isolation Ring: Nylon • Coupling Retainer Ring: Polyethelene • Nut and Nipple: Carbon Steel, Zinc Plated • Reducer (1/2"/15mm or 3/4"/20mm): Carbon Steel, Zinc -Plated • Housing: Ductile iron conforming toASTM A 536, Grade 65-45-12. Ductile iron conforming toASTM A 395, Grade 65-45-1 5, is available upon special request. Coupling Housing Coating: Orange enamel (North America, Asia Pacific). Red enamel (Europe). Hot dipped galvanized. Gasket:l Grade "E" EPDM (Type A) FireLock EZ products have been Listed by Underwriters Laboratories Inc., Underwriters Laboratories of Canada Limited, and Approved by Factory Mutual Research for wet and dry (oil free air) sprinkler services within the rated working pressure. Services listed are General Service Guidelines only. Itshould be noted that there are services forwhich these gaskets are not compatible. Reference shouldalways be madetothe latest Victaulic Gasket Selection Guide for specific gasket service guidelines and fora listing ofserviceswhich are not compatible. • Bolts/Nut: Zinc electroplated carbon steel, trackhead meeting the physical and chemical requirements of ASTM A 449 and physical requirements of ASTM A 183. • Linkage: CrMo Alloy Steel zinc electroplated per ASTM B633 Zn/Fe 5, Type III Finish 10.85 5839Rev AG Updated07/2019©2019VictaulicCompany.All rightsreserved. victaulic.com 3 ✓etall victaulic.com 4.0 DIMENSIONS Product Details - Series AH2 Braided Hose H Hose Length Dimensions Hose Length inches mm A inches mm B inches mm 31/790 25.3/641 31/790 36/915 31.3/794 36/915 48/1219 42.3/1073 48/1220 60/1525 54.3/1378 60/1525 72/1830 66.3/1683 72/1830 Series AH2-CC Braided Hose • A of 01 �I • OI'' i�r�uumummm�uuuwgnp� I 1 -I � II ��uuuwunulliiiuuuiilliiii' HowMngth mm inc'Aes MM inAes MM 31/790 24.5/622 29.8/757 36/915 29.5/749 34.8/884 48/1219 41.5/1054 46.8/1189 60/1525 53.5/1359 58.8/1494 72/1830 65.5/1664 70.8/1798 Item Description 1 Flexible Hose isolation King 4 Nut 5 Adapter Nipple Braid 7 Collar/Weld FittingCollar/We Sleeve Item Description exi a Hose Iso ation Ring Gasket 4 Nut 5 Captured Coupling Braid 7Collar/Weld FittingCollar/We Sleeve 10.85 5839Rev AG Updated07/2019©2019VictauIicCompany.AIIrights reserved. victaulic.com 4 ✓ctsulicr victaulic.com 4.0 DIMENSIONS (Continued) Standard Reducer 5.75"/140 mm straight reducer Optional Reducers Lz=z� 9.0"/229 mm straight reducer 13.0"/330 mm straight reducer 2.62"/ 66.5 mm 1 4.83"/ 127mm Short 90°elbowreducer 2.62"/ 66.5 mm T � I- 6.57"/ 166.9 mm Long 90' elbow reducer NOTE The Short90°elbow reducer is typically usedwith concealed sprinklerswhilethe longer90 elbow istypically used inthe installation ofrecessed pendent sprinklers. FM/VdS Approved only. Low Profile 2.84"/ 72 mm 1.4"/ 1.3 mm Short 90°elbowreducer 4.59"/ 116 mm 36 mm Long 90° elbow reducer NOTE Style ABll: When low profileselbowsare used with the Style ABl1 bracket, the Low Profile Short Elbow is typically usedwith concealed sprinklers while the Low Profile Long Elbow is typically used in the installation of recessed pendent sprinklers. 10.85 5839Rev AG Updated07/2019©2019VictaulicCompany. All rights reserved. victaulic.com ✓ctaulicr victaulic.com 4.1 DIMENSIONS VicFlex Brackets Style AB1 • Suspended Ceilings • Hard -Lid Ceilings (FM Only) Item Description 1 24"/610 mm or 48"/1219 mm Square Bar 2 Patented Center Bracket 3 End Bracket NOTE • Both sizes FM/VdS/LPCB Approved, cULus listed Style AB2 • Suspended Ceilings • Hard -Lid Ceilings Item Description 1 24"/610 mm or48"/1219 mm Square Bar 2 Patented Vertically Adjustable Center Bracket 3 End Bracket NOTE • Both sizes FM/VdS/LPCB Approved, cULus listed Style AB3 • Surface Mount Applications • FM/LPCB Approved 10.85 5839Rev AG Updated07/2019©2019VictaulicCompany.All rightsreserved. victaulic.com A ✓ctaullc� victaulic.com 4.2 DIMENSIONS VicFlex Brackets Style AB4 • Hard -Lid Ceilings with Hat furring channel grid system Item Description 1 1 247610 mm or 48"/1219 mm Square Bar 2 Patented Vertically Adjustable Center Bracket 3 End Bracket for Hat Furring Channel NOTE • Both sizes FM/VdS/LPCB Approved, cULus listed. Style AB5 • Hard -Lid Ceilings Item Description 1 24"/610 mm or 48"/1219 mm Square Bar 2 Patented Vertically Adjustable Center Bracket 3 1 End Bracket NOTE • Both sizes FM/VdS/LPCB Approved, cULus listed. Style AB7 • Suspended Ceilings • Hard -Lid Ceilings Item Description 1 24"/610 mm or 48"/1219 mm Square Bar 2 Patented 1-Bee2® Center Bracket 3 End Bracket NOTE • Both sizes FM/VdS/LPCB Approved. Style AB7 Adjustable • Suspended Ceilings • Hard -Lid Ceilings Item Description 1 700 mm or 1400 mm Square Bar 2 Patented 1-Bee2® Center Bracket 3 End Bracket (adjustable) NOTE • Both sizes FM/VdS/LPCB Approved. 10.85 5839Rev AG Updated07/2019©2019VictaulicCompany. All rights reserved. victaulic.com 7 ✓otoulicr victaulic.com 4.3 DIMENSIONS vicFlex Brackets Style AB8 • Hard -Lid Ceilings Item Description 1 700 mm or 1400 mm Square Bar 2 Patented Vertically Adjustable Center Bracket 3 End Bracket NOTE • Both sizes FM/VdS/LPCB Approved. Style AB10 • Suspended ceilings Armstrong' TechZone'" Item Description 1 6"/152 mm Square Bar 2 Patented 1-Bee2® Center Bracket 3 End Bracket NOTE • FM/VdS/LPCB Approved, cULus listed Style AB11 • Suspended ceilings • Hard -Lid ceilings Item Description 1 247610 mm or 48"/1219 mm Square Bar 2 Patented 1-Bee2® Center Bracket 3 End Bracket NOTE • FM/VdS Approved, cULus listed. Style AB12 • Suspended ceilings • Hard -Lid ceilings Item Description 1 Style AB12 Bracket Body 2 #2 Square Drive Set Screw NOTE • FM/Vd5 Approved. 10.85 5839Rev AG Updated07/2019©2019VictaulicCompany. All rights reserved. victaulic.com 0 ✓ctsulicr victaulic.com 4.3 DIMENSIONS (CONTINUED) vicFlex Brackets Style ABBA Floor -above mount Cantilever mount Temporary mount in exposed ceilings Item Description 1 Style ABBA Mounting Plate 2 Style ABBA Square Bar 3 Cap Screw, Serated Flange, M6 x 1 x 20, T25 Torx Drive Recessed 4 Style ABMM Bracket Body 5 Cap Screw, Serated Flange, M6 x 1 x 15,24, T25 Torx Drive Recessed Style ABMM Surface mount Stand-off mount Item Description 1 Style ABMM Bracket Body Cap Screw, Serated Flange, M6 x 1 x 15,24, T25 Torx Drive Recessed 10.85 5839Rev AG Updated07/2019©2019VictauIicCompany.AlIrights reserved. victaulic.com 4 ✓ctaullc� victaulic.com 4.4 DIMENSIONS Clearances Series AH2 Braided Hose and Style AB1 Bracket R A Bracket See Chart Assembly 2'V'/60 mm 2"� a"/68 mm Style AB1 max. hole max. hole 2"/51 mm 23da"/60 mm 44„/ min. hole min. hole 15.9 mm 113 mm Typical 1.7'/43 mm ceiling tile Typical ceiling grid RL Finished See note ceiling face 24"/610 mm or V27 V38 48"/1219 mm on Pendent Center Hose Clearance Chart Straight Reducer V2707 V3802 V2707 V3802 3/4" '/z " 3/4" '/z " V2707 V3802 Max Recess Max Recess Max Recess Max Recess 3/4"Max Recess '/2"Max Rec inches inches inches inches inches inches mm mm mm mm mm mm Elbow I Short Elbow V2707 V31802 3/4" Max Recess '/z"Max Rec inches inches mm mm "R" Minimum 2.0 3.0 7.0 Bend Radius 50 80 175 "A" Minimum Required 8.6 10.1 9.6 11.1 13.6 15.1 5.8 5.8 Installation 218 269 244 281 345 383 147 147 Space NOTE • Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance differences from thefigures above. 10.85 5839Rev AG Updated07/2019©2019VictaulicCompany. All rights reserved. victaulic.com 10 ✓Ctsulicr victaulic.com 4.5 DIMENSIONS Clearances Series AH2 Braided Hose and Style AB2 Bracket A See Chart Bracket 18"/ #10 Assembly 45 mm 2"11a"/68 mm 2'@"/60 mm 2'8"/60 mm *x4"Scre w Style AB2 max. hole max. hole max. hole FU 2@"/60 mm2"/51 mm 2"/51 mm min. hole min. hole min. hole 389I II I 16"/406mm Finished Stud C/C ceiling Hose Clearance Chart Straight Reducer V2707 V3802 V2709 V2707 V3802 V2709 V2707 V3802 V2709 3/4" 120mm 1/2" 113mm 3/4" 120mm 3/4" 120mm 1/2" 1 13mm 3/4" 120mm 3/4" 120mm 1/2" 113mm 3/4" 120mm MakiRlwess" Wjill t oess Siddwall MalaQtilmess 10116R9timess SiftWall Maingil Bess MeiR9timess Side all mm mm mm mm mm mm mm mm mm "R" Minimum 2.0 3. 7.0 Bend Radius 50 80 175 "A" Minimum Required 6.2 7.6 6.1 7.2 8.6 7.1 11.2 12.6 11.1 Installation 158 193 155 183 218 180 285 320 282 Space Hose Clearance Chart Long Elbow Short Elbow V2707 V2709 V3802 3/4" 120mm 3/4" 120mm 1/2" 113mm Max Recess Sidewall Max Recess inches inches inches HIM mm mm "R" Minimum Bend Radius "A" Minimum Required 3.3 3.6 3.3 Installation 84 91 84 Space NOTE • Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance differences from the figures above. 10.85 5839Rev AG Updated07/2019©2019VictauIicCompany.AIIrights reserved. victaulic.com ✓ctsulicr victaulic.com 4.6 DIMENSIONS Clearances Series AH2 Braided Hose and Style AB4 Bracket ceiling tile ceiling race See note '/b"/23 mm Typical 16"/406 mm— Typical 24"/610 mm on Center ceiling grid 2'Ib"/60 mm 2"!la"/68 mm Irt max. hole max. hole 2"/51mm 2'Y/60mm min. hole min. hole 4 MAI V27 V38 Pendent Hose Clearance Chart aht Reducer Lona Elbow I Short El 3/4" 1/2" 3/4" t/z" V2707 V3802 V2707 V3802 Max Recess Max Recess Max Recess Max Recess 3/4"Max Recess 1/z"Max Recess 3/4"Max Recess 1/z"Max Recess inches inches inches inches inches inches inches inches mm mm mm mm mm mm mm mm n Iviinimum Z.0 Z.0 j.0 J.0 i.0 i.0 Bend Radius 50 50 80 80 175 175 "A" Minimum Required 8.8 10.2 9.8 11.2 13.8 15.2 8.0 59 Installation 224 259 249 285 351 386 203 150 Space NOTE Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance differences from the figures above 10.85 5839Rev AG Updated07/2019©2019VictaulicCompany. All rights reserved. victaulic.com 12 ✓Ctsuliicr victaulic.com 4.7 DIMENSIONS Clearances Series AH2 Braided Hose and Style ABS Bracket M Drywall 16"/406 mm Stud C/C Mr. 2'h"/60 mm 2"Aa"/68 mm 2'8"/60 mm max.hole max.hole max.hole 2"/51mm 28760 mm 2"/51 mm min.hole min. hole min.hole 4 1 im Hose Clearance Chart Straight Reducer W2707 V3802 V2709 V2707 V3802 V2709 V2707 V3802 V2709 3/4" 1 20 mm 1/2" 113mm 3/4" 120mm 3/4" 120mm 1/2" 1 13mm 3/4" 120mm 3/4" 1 20mm 1/2" 113mm 3/4" 120mm Ma*,Wi ss" Mailal Sid all MAn timess Min tlwess Sid all Will Mara4t> cress Sit1vh"ll mm mm mm mm mm mm mm mm mm "R" Minimum 2.0 3.0 7.0 Bend Radius 50 80 175 "A" Minimum Required 6.0 7.7 6.1 7.0 8.7 7.1 11.0 12.7 11.1 Installation 158 196 155 178 221 180 279 323 282 Space Hose Clearance Chart Low -Profile Long Elbow Long Elbow ShortElbow V2707 V3802 V2709 V3802 V3802 3/4" 120mm 1/2" 113mm 3/4" 120mm 1/2" 113mm 1/2" 113mm Max Recess Max Recess Sidewall Max Recess Max Recess inches inches inches inches inches HIM mm mm mm mm "R" Minimum Bend Radius "A" Minimum Required 3.5 4.9 3.6 2.9 3.3 Installation 89 124 91 74 84 Space NOTE • Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance differences from the figures above. 10.85 5839Rev AG Updated07/2019©2019VictauIicCompany.AIIrights reserved. victaulic.com 13 ✓otoulic victaulic.com 4.8 DIMENSIONS Clearances Series AH2 Braided Hose and Style AB1 1 Bracket (LOW PROFILE SOLUTION) 2'Y/60 mm 2" Ila"/68 mm Bracket max. hole max. hole Assembly 2"/51 mm 2'�"/60 mm A Style AB11 min. hole min. hole See Chart 3.0"/ I ILL I`` 76 m m �i 17 II II 1.7"/43 mm Finished .4 Typical '/b"/15.9mm ceilingface ceiling grid Typical ceiling tile See Note 24"/610 mm or V27 V38 48"/1219 mm on center Pendent Hose Clearance Chart Low -Profile Low -Profile Long Elbow Short Elbow V2707 V3802 3/4" 120mm 1/2" 113mm Max Recess" Max Recess inches inches MITI mm "A" Minimum 4.0 3.9 102 99 NOTE • Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance differences from the figures above. 10.85 5839Rev AG Updated07/2019©2019VictauIicCompany.AIIrights reserved. victaulic.com 14 ✓otoulilcr victaulic.com 4.9 DIMENSIONS Clearances Style AB12 and ABBA Bracket Suspended Ceiling Grid with Recessed Sprinkler with Low Profile Short Elbow M Finished Face of '/b-inch/16-mm Typical Ceiling V2707 W/12.7 mMAX. RECESS Suspended Ceiling Grid with Recessed Sprinkler and Straight 5.75"/140 mm Reducer Square k Nominal le 14"/355.6 a KT; Finished Face of '/b-inch/16-mm Typical Ceiling V2707'/."/19 mm MA%.RECESS Low Profile Low Profile Standard Standard Standard Dimension Short Elbow Long Elbow Short Elbow Long Elbow Straight Reducer 3/4"/19 mm 3/4"/19 mm 3/4"/19 mm 3/4"/19 MM 3/4"/19 mm Recessed* Concealed Recessed Concealed Recessed Concealed Recessed Concealed Recessed Concealed inches inches inches inches inches inches inches inches inches inches mm mm mm mm mm mm mm mm mm mm A Minimum Required Distance from Top of 0.5 2.0 1.5 1.5 1.5 1.5 3.0 3.0 3.0 3.0 B Typical Ceiling Tile to Bottom of Gate 12.7 50.8 38.1 38.1 38.1 38.1 76.2 76.2 76.2 76.2 *Adjustabilitywill be limited Style ABMM Bracket Stand-off Dimensions 3.93 2.94"/ 56 mm "4r, 8"/ 100mm 7mm, 10.85 5839Rev AG Updated07/2019©2019VictauIicCompany.AIIrights reserved. victaulic.com 15 ✓otoulilcr victaulic.com 4.10 DIMENSIONS Clearances Style AB3 and ABMM Bracket Surface Mount Application with Recessed Sprinkler 2"/51 mm min. hole Hose Clearances inches inches inches inches inches inches inches inches inches inches Dimension mm mm mm mm mm mm mm mm mm mm Wall Thickness 2 4 6 8 10 2 4 6 8 10 °A" 50 100 150 200 250 50 100 150 200 250 Outlet Length 5.751 5.75 5.75 5.75 16.14 228.E 330.2 146.1 228.E 330.2 228.6 330.2 330.2 330.2 146.1 228.E 330.2146.1 228.E 330.2 228.E 330.2 330.2 330.2 Hose Clearance 11.6 14.8 18.8 9.6 112.8 116.8 1 10.8 14.8 12.8 10.8 12.6 15.8 19.8 10.6 13.8 17.8 11.8 15.8 13.8 11.8 °c" 21 376 478 243 1325 1427 1 275 376 325 275 319 2 503 268 351 452 300 402 351 300 Bend Radius 7 8 "R" 175 200 NOTE Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance differences from thefigures above. 10.85 5839Rev AG Updated07/2019©2019VictauIicCompany.AIIrights reserved. victaulic.com m ictsuliiic victaulic.com 5.0 PERFORMANCE — FRICTION LOSS DATA Series AH2 and AH2-CC Braided Hoses with Straight 5.75"/140 mm Reducers GLIDED°S Style AB1, AB2, AB4, ABS and AB10 Brackets Maximum Equivalent Length Number of of 1" 133.7 mm 900 Bends at 2"/51mm Sch. 40 Pipe (C=120) Bend Radius inches/mm inches/mm/type feet/meters '/2"/15/Straight 16/4.9 4 31 /790 4 3/4"/20/Straight 17/5.2 '�'715/Straight 21 /6.4 5 36/915 5 3/4"/20/Straight 23/7.0 '�"/15/Straight 32/9.8 8 48/1220 3/4'720/Straight 37/11.3 8 '�"/15/Straight 46/14.0 10 60/1525 3/4'720/Straight 46/14.0 10 '�"/15/Straight 55/16.8 12 72/1830 3/4"/20/Straight 53/16.2 12 D uL us Series AH2 and AH2-CC Braided Hose with 900 Low Profile Elbows LISTED Style AB11 VkFlexBracket Maximum Equivalent Length Number of of 1" 133.7 mm 900 Bends at 2"/51mm Sch. 40 Pipe Bend Radius inches/mm inches/mm feet/meters '/2 "/15 24/7.3 4 31 /790 4 %V20 24/7.3 /2"/15 26/7.9 5 36/915 3/4"/20 28/8.5 5 '/2"/15 43/13.1 8 48/1220 3/4"/20 42/12.8 8 A V15 49/14.9 10 60/1525 3/4"/20 50/ 15.2 10 '/2"/15 65/19.8 12 72/1830 3/4"/20 63/19.2 12 10.85 5839Rev AG Updated07/2019©2019VictauIicCompany.AIIrights reserved. victaulic.com 17 ✓Otou1icr victaulic.com 5.0 PERFORMANCE — FRICTION LOSS DATA(CONTINUED) Series AH2 and AH2-CC Braided Hoses Equivalent Length Design Guide Equivalent length values at various numbers of 90 degree bends at 2"/51 mm center line bend radius Length of Stainless Steel Flexible Outlet 1 2 3 4 5 6 7 8 9 10 11 12 Hose Size Bend Bends Bends Bends Bends Bends Bends Bends Bends Bends Bends Bends inches/ inches/ feet/ feet/ feet/ feet/ feet/ feet/ feet/ feet/ feet/ feet/ feet/ feet/ mm mm meters meters meters meters meters meters meters meters meters meters meters meters 'h'%15 8.5/2.6 11.0/3.4 13.014.0 16.()14.9 N.A ir N.A. N.A. N.A N.A N.A N.A 1/4%20 10.0/3.0 12.5/3.8 14.0/4.3 17.0/5.2 N.A N.A. N.A. N.A. N.A N.A N.A 36/915 1/2 15 13.5/4.1 16.0/4.9 18.015.5 19.0/5.8 21.0/6.4 N.A N.A N.A N.A N.A N.A N.A 3/4%20 14.0/4.3 17.0/5.2 19.5/5.9 20.0/6.1 23.0/7.0 N.A N.A N.A N.A N.A N.A N.A lh715 15.5/4.7 17.015.2 19.515.9 20.0/6.1 21.0/6.4 22.0/6.7 28.0/8.5 320/9.8 N.A N.A N.A N.A 3/4%20 17.015.2 19.0/5.8 21.5/6.6 24.5/7.5 26.0/7.9 27.0/8.2 30.019.1 37.0/11.3 N.A N.A N.A N.A '/2 /15 21.5/6.6 24.0/7.3 27.0/8.2 28.5/8.7 30.0/9.1 31.0/9.4 37.0/11.3 42.0/12.8 44.0/13.4 46.0/14.0 N.A N.A (50/1525 3/4%20 23.0/7.0 24.0/7.3 28.0/8.5 29.5/9.0 30.5/9.3 31.0/9.4 38.0/11.6 42.0/12.8 44.0/13.4 46.0/14.0 N.A N.A 'h'%15 30.019.1 32.0/9.8 36.5/11.1 37.5/11.4 40.5/12.5 41.0/12.8 42.0/12.8 46.0/14.0 49.0/14.9 52.0/15.8 54.0116.5 55.0/16.8 3/4720 L12,019.8 32.5/9.9 35.0/10.7 35.5/10.8 40.0/12.3 40.5/123 41.0/125 46.0/14.0 j /16.2 NOTES: • Values for use with 5.75"/140mm straight reducers. How to use this Design Guide: For some systems, it maybe advantageous forth eclesigner to calculate the system hydrau I ics us in g shorter equivalent I engths associated with fewer th ant he maximum allowable number of bends. In this case, the designer may select a design number of bends forthejob and use the associated equivalent length from the design guide to determine the system hydraulics. Itis possible that the actual installed condition ofsome oftheflexible drops may have more bends thanthe designer selected. Whenthishappens, the design guide may be used tofindequivalent lengths based ontheactual installed number of bends for particular sprinkler installations. The system hydraulicscan be recalculated using actual equivalent lengths to verify the performance of the system. 10.85 5839Rev AG Updated0712019©2019VictaulicCompany. All rights reserved. victaulic.com m ✓ctaulicr victaulic.com 5.1 PERFORMANCE — FRICTION LOSS DATA FM Series AH2 and AH2-CC Braided Hoses Style AB1, AB2, AB3, AB4, ABS, AB7, AB7 Adj., AB8, AB10, AB12, ABBA and ABMM vicFlex Brackets Maximum Equivalent Number Length of Length of of90°Bends Stainless Steel Outlet 1" 133.7 mm at 7"/178mm Flexible Hose K-Factor Size Sch. 40Pipe Bend Radius inches/mm Imperial/5.l. inches/mm/type feet/meters 13.$/4.2 31 /790 5.6/8.1 23.5/7.1 2 /z'%15/Straight 16.6/5.1 36/915 5.6/8.1 /z"/15/90° Elbow 25.6/7.8 2 23.4/7.1 48/1220 5.6/8.1 30.7/9.3 3 1/2715/Straight 30.2/9.2 60/1525 5.6/8.1 /z'%15/90° Elbow 35.9/10.9 4 37.0/17.3 72/1830 5.6/8.1 41.1/12.5 4 3/a "/20/Straight 16.8/5.1 31 /79Q 8.0/1 1.5 3/a%20/9D" Elbow 16.8/5.1 2 20/6.0 36/915 8.0/11.5 AL 19.7/6.0 2 3/a "/20/Straight 27.8/8.4 4$/1220 8.0/1 1.5 3/a%20/90° Elbow 26.6/8.1 3 35.7/10.9 60/1525 8.01.5 h 33.6/10.2 4 3/a "/20/Straight 43.5/13 2 72/1830 8.0/11.5 3/a'%20/90" Elbow 40.6/122 4 31 /79D 11.2/16.116.5/5.0 17.8/5.4 2 3/a "/20/Straight 19.5/5.9 36/915 11.2/16.1 3/a'%20/90° Flbow 20.7/6.3 2 48/1220 11.2/16.126.7/8.1 27.9/8.5 3 3/a"/20/Straight 33.9/10.3 60/1525 11.2/16.1 3/a'720/90° Elbow 35hOJ 4 41.3/12.5 72/1830 11.2/16.1 42.2/12.8 4 3/a "/20/Straight 14.9/4.5 31/790 14.0/202 a/4'720/90° Elbow 15.5/4.72 2 19.4/5.9 361915 14.0/20.2 19.6/5.9 2 3/a "/20/Straight 30.3/9.2 4$/1220 14.0/202 3/a'720/90° Elbow 29.5/$.9 3 33.9/10.3 60/1525 14.0/20.2 34.1 /10.4 4 3/a "/20/Straight 37.5/11.4 72/1830 14.0/201 3/a'%20/90° Elbow 38.6/11.7 4 FM NOTES: TheSeriesAH2 hose has been tested and Approved byFMGlobal foruseinwet, dry and preactionsystems per NFPA13,13R,and l 3DandFMdatasheets 2-0, 2-5,and2-8. FM 1637standardforsafetyinclude, butarenotlimitedto, pressure cycling, corrosion resistance, flowcharacterisitics,vibration resistance, leakage, mechanical and hydrostatic strength. EXAMPLE: A 48-inch hose installed with two 30' bends and two 90' bends is permitted and considered equivalent tothe data in the table shown above. In this example, the total number of degrees is 240% which is less than the allowable 270% 10.85 5839Rev AG Updated07/2019©2019VictaulicCompany. All rights reserved. victaulic.com ✓ctauli;cr victaulic.com 5.2 PERFORMANCE —FRICTION LOSS DATA Series AH2 Braided Hose with 900 Low Profile Elbows FM Style AB5, AB11, AB12, ABBA and ABM M vicFlex Bracket Length of Stainless Steel Flexible Hose K-Factor inches/mm Imperial/S.I. Outlet Size inches/mm Equivalent Length of 1" 133.7mm Sch. 40Pipe feet/meters Maximum Number of 901 Bends at 7"/178mm Bend Radius 31 /790 5.6/8.1 13.7/4.2 2 36/915 5.6/8.1 Yz %15 17.0/5.2 2 48/1220 5.6/8.1 25.0/7.6 3 60/1525 5.6/8.1 /� j15 33.0/10.1 4 72/1830 5.6/8.1 41.1 / 12.5 4 31 /790 S0/1 1.5 3/4'%20 13.6/4A 4 2 36/915 8.0/11.5 16.9/5.2 2 48/1220 80/11.5 N, 20 27.8/8.5 3 60/1525 8.0/11.5 32.6/9.9 4 72/1830 80/1 1.5 3/4'%20 40.6/12.4 4 31 /790 11.2/16.1 13.7/4.2 2 36/915 11.2/16.1 3/4'%20 17.015.2 2 48/1220 11.2/16.1 " 24.9/7.6 3 60/1525 11.2/16.1 3/4720 32.9/10.0 4 72/1830 11.2/16.1 40.9/12.5 4 31 /790 14.0/20.2 3/4 720 13.5/4.1 2 36/915 14.0/202 16.8/5.1 2 48/1220 14.0/202 3/4'%20 24.717.5 3 60/1525 14.0/202 " 32.7/9.9 4 72/1830 14.0/20.2 3/4'%20 40.7112.4 4 FM NOTES: TheSeriesAH2 hose has been tested and Approved by FM Global foruseinwet,dry and preactionsystems perNFPAI 3,1 3R,and 1 313andFMdatasheets 2-0, 2-5, and 2-8. FM 1637 standard for safety include, butare not limitedto, pressure cycling, corrosion resistance, flowcharacterisitics, vibration resistance, leakage, mechanical and hydrostatic strength. EXAMPLE: A 48-inch hose installed with two 30' bends and two 90' bends is permitted and considered equivalent tothe data in the table shown above. In this example, the total number of degrees is 240', which is less than the allowable 270% 10.85 5839Rev AG Updated0712019©2019VictaulicCompany. All rights reserved. victaulic.com 20 ✓ctaulicr victaulic.com 5.3 PERFORMANCE - FRICTION LOSS DATA Series AH2 and AH2-CC Braided Hose S Style AB1, AB2, AB4, ABS, AB7, AB7 Adj., AB8, AB10, AB11 and AB12 Brackets Length of Stainless Steel Flexible Hose m m/inches Outlet Size m m/inches Equivalent Length of steel pipe accordingto EN 10255 DN25 (33,7 x 3,25) m ete rs/feet Maximum Number of 900 Bends at 3"176.2 mm Bend Radius meters/feet 31/790 5.5/18.0 3 36/915 6.4/21.0 3 48/1220 8.5/27.9 3 60/1525 10.7/35.1 12.$/42.0 4 72/1830 4 VDS CEILING MANUFACTURERS LIST AB1,AB2,AB7,AB10,AB11 AB4 1. AMF 2. Armstrong 3. Chicago Metallic 4. Dipling S. Durlum 6. Geipel 7. Gema-Armstrong 8. Hilti 9. Knauf 10. Lafarge 11. Linder 12. Odenwald 13. Richter 14. Rigips 15. Rockfon Pagos 16. Suckow&Fischer 17. USG Donn Nospecificapproval ABS, AB8 1. Hilti 2. Knauf 3. Lafarge 4. Lindner 5. Rigips Series AH2 and AH2-CC Braided Hose LPC B Style AB1, AB2, AB3, AB4, ABS, AB7, AB8, and AB10 Brackets Length of Equivalent Length Maximum Stainless of steel pipe Number of Steel according to 90oBendsat Flexible Outlet EN 10255 DN 25 Y/76.2 mm Hose Size (33,7 x 3,25) Bend Radius mm/inches mm/inches/type 15 mm//z /Straight meters/feet 790/31 1.8/6.0 2 15 mm/1h'%Straight 915/36 20 mm/l/4'YStraight 3.6/11.9 3 15 mm/1h'%Straight 1220/48 20 mm/1/4'%Straight 4.3/14.0 3 15 mm/l/z'%Straight 1525/60 4.1/13.6 3 20 mm/Y4'%Straight 15 mm/'h'%Straight 1830/72 5.5/18.1 3 20 mm/%'%Straight Series AH2 Braided Hose Style AB1, AB2, AB3, AB4, ABS, AB7, AB8, AB10 and AB12 Brackets Length of Flexible Equivalent Length of Haim 1'y33.7 mm Sch. 40 Pipe inches Straight Configuration Bend Configuration 790 0.87 2.70 31 2.9 8.9 915 1.00 2.80 36 3.3 9.2 1220 2.23 4.66 48 7.3 15.3 1525 2.90 6.5 60 9.5 21.3 1830 3.31 7.16 72 10.9 23.5 CCCF NOTE Friction loss data is in accordancewith GB51 35.1 6tested ataflowrate of 114liters per minute (30 gallons per minute). 10.85 5839Rev AG Updated07/2019©2019VictaulicCompany. All rights reserved. victaulic.com 21 ✓ctsulicr victaulic.com 6.0 NOTIFICATIONS 0 WARNING e Read and understand all instructionsbeforeattemptingto install, remove, adjust, or maintainanyVictaulicpiping products. e Alwaysverifythatthepipingsystemhasbeencompletelydepressurizedanddrainedimmediatelypriortoinstalla- tion, removal, adjustment, or maintenance of any Victaulicproducts. e Wear safety glasses, hardhat, and foot protection. Failure to follow these instructions could result in death or serious personal injury and property damage. SWARNING It is the responsibi lityof the system designer to verifysu itabilityof3OO-seriesstainlesssteelflexible hose for use with the intended fluid media within the piping system and external environments. » The effect of chemical composition, pH level, operating temperature, chloride level,oxygen level, and flow rate on 300-series stainless steel flexible hose mustbeevaluated bythe material specifiertoconfirm system lifewill be acceptable for the intended service. Fail uretofoIlowthoeeinsDuctionsoeuIdcauseproductfaiIure, roeulunginseriouspersonalinjuryand/orpropertydamage. 10.85 5839Rev AG Updated0712019©2019VictauIicCompany.AlIrights reserved. victaulic.com 22 victaulic.com 7:0 REFERENCE MATERIALS -CHARACTERISTICS vicFlex Maximum Load Values SeriesAH2 Hose with 24" Bracket Model Size 31/790 36/915 48/1220 60/1525 72/1830 Actual Length Total Load Max. Uniform Load ft m Ib N Ib/linearft N/linearm 2.6 0.8 5.2 23 2.6 38 3 09 5.5 25 2.8 40 46 4 6.3 28 3A 1.2 51 5 1.5 7.0 31 3.5 6 1.8 7.7 34 39 57 SeriesAH2 Hose with 48" Bracket Actual Length Total Load Max. Uniform Load ft Model Size m Ib N Ib/linearft N/linearm 31 /790 2.6 6.1 27 1.5 22 36/915 9 6.4 29 1.6 23 48/1220 1 2 7.2 32 1.8 26 60/1525 1 5 7.9 35 2.0 29 72/1830 1 $.7 39 2.2 32 Total Load is defined as the sum of the weights of the following: water -filled flexible sprinkler hose with threaded end fittings, including atypical fire sprinkler bracket assembly (any applicable Victaulic bracket model of the relevant associated size) ASTM C 635: Suspension System Load -Carrying Capabilities (excerpted) Suspension System Actual Length ft/m Min. Allowable Uniform Load Ib/linearft N/linearm Direct Hung Light 5.0 75.7 Intermediate 12.0 181.0 Heavy 16.0 241.7 SUMMARY: All direct -hung suspension system dutyclassificationsperASTMC63Sare able towithstand the maximum water -filled weight of the vicFlex sprinkler hose and bracket. 10.85 5839Rev AG Updated07/2019©2019VictauIicCompany.AlIrights reserved. victaulic.com 23 ✓ctaullc� victaulic.com 7.0 REFERENCE MATERIALS — CHARACTERISTICS (CONTINUED) Flexible Hose In -Plane Bend Characteristics One Bend I I I Minimum I bend radius I I 90" I I \y I Minii bends Two Bends OR inimum nd radius Minin bend r Three Bends VM mum id radius NOTE For out -of -plane (three-dimensional) bends, care must be taken to avoid imparting torque on the hose. I-VicFlex-AB1-AB2-AB10 I-VicFlex-AB3 I-VicFlex-AB4 I-VicFlex-AB7 I-VicFlex-AB8 I-VicFlex-AB12 I-VicFlex-ABBA I-VicFlex-ABMM User Responsibility for Product Selection and Suitability Each userbears final responsibilityformakingadeterminationastothesuitabiliryof Victaulic products foraparticularend-use application, in accordance with industry standards and project specifications, and theapplicable building codes and related regulations as well as Victaulic performance, maintenance, safety, and warning instructions. Nothing inthisc ranyotherdocument, noranyverbal recommendation, advice, oropinionfrom anyVictaulicemployee, shall be deemed to alter, vary, supersede, orwaive any provision of Victaulic Company's standard conditions of sale, installation guide, or this disclaimer. Intellectual Property Rights No statement contained herein concerning a possible orsuggested use ofany material, product, service, ordesign is intended, orshould beconstructed,tograntanylicense underany patent orother intellectual property right of Victaulicoranyof its subsidaries oraffiliates covering such useordesign,oras arecommendation forthe useofsuch material, product, service, ordesign intheinfringementofanypatentorotherintellectual property right. The terms "Patented" or"Patent Pending' referto design or util ity patents orpatentapplicationsforarticlesand/or methods ofuseintheUnitedStatesand/orother countries. Note This productshall be manufactured byVictaulicortoVictaulicspecifications. All products tobe installed in accordance with current Victaulicinstallation/assembly instructions. Victaulicreservesthe righttochange product specifications, designs and standard equipment without notice and without incurring obligations. Installation Reference should always be made to I-VICFLEX-AB1 -AB2-AB1 0, I-VICFLEX-AB4, I-vi CFLEX-AB7, or I-VICFLEX-AB8 forthe productyou are installing. Handbooks are includedwith each shipmentofVictaulic productsforcomplete installation and assembly data, and are available in PDF format on ourwebsite at www.victaulic.com. Warranty Refer to the Warranty section of the current Price List or contact Victaulic for details. Trademarks VictaulicandalIotherVictauIicmarks arethetrademarks orregi stered trademarks of Victaulic Company, and/orits affiliated entities, inthe U.S. and/orothercountries. 10.85 5839Rev AG Updated07/2019©2019Victaulic: Company. All rights reserved. victaulic.com 24 ✓ctauli;cr victaulic.com 10.85 5839Rev AG Updated07/2019©2019VictauIicCompany.AIIrights reserved. victaulic.com 25 ✓ctoulicr victaulic.com .••••••. COSCO • • •• • • Fire Protection SECTION 2. SPRINKLER HEADS 10.85 5839Rev AG Updated07/2019©2019VictauIicCompany.AlIrights reserved. victaulic.com Page 1 of 5 j VK3021 QUICK RESPONSE �J PENDENT SPRINKLER (K5.6) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com 1. DESCRIPTION The Viking VK3021 Quick Response Pendent Sprinkler is a small thermosensitive glass bulb spray sprinkler available with various finishes and temperature ratings to meet design requirements. The special Polyester and Electroless Nickel PTFE (ENT) coatings can be used in decorative applications where colors are desired. In addition, these coatings have been investigated for installation in corrosive environments and are Listed and Approved as indicated in the Approval Chart. 2. LISTINGS AND APPROVALS C UL us UL Listed: Category VNIV .�o FM Approved: Classes 2017, 2015, 2043 Also approved for use in FM Approved vacuum dry sprinkler systems with a maximum supervisory vacuum pressure of -3 PSI (-207 mbar) CE CE: Standard EN12259-1, DOP_XT1A_1-3-21 Refer to the Approval Chart and Design Criteria for requirements that must be followed. 3. TECHNICAL DATA Specifications: Minimum Operating Pressure: 7 PSI (0.5 bar) Rated to: UL - 250 PSI (24 bar) WWP FM - 175 PSI (12 bar) WWP Factory tested hydrostatically to 500 PSI (34.5 bar) Thread size: 1/2" NPT (15 mm BSPT) WARNING Gnncerand ReproductiveHarm- NominalK-factor: 5.6 U.S. (80.6 metric*) www.P65Warnings.ca.gov Glass -bulb fluid temperature rated to -65 °F (-55 °C) * Metric K-factor measurement shown is in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. Material Standards: Sprinkler Body: Brass CW602N, UNS-C84400 or QM Brass Deflector: Stainless Steel UNS S30400 Pip Cap Shell - Stainless Steel UNS-S44400 Pip Cap Disc - Stainless Steel UNS-S30100 Belleville Spring - Nickel Alloy Pip Cap Seal - Polytetrafluoroethylene (PTFE) Compression Screw: Brass CW612N, CW508L, UNS-C36000 or UNS-C26000 Shipping Cap: Polyethylene Bulb: Glass, nominal 3 mm diameter Ordering Information: (Refer to Table 1 and the current Viking List Price Book.) 4. INSTALLATION Refer to appropriate NFPA, FM Global, and/or any other applicable installation standards. ` •211111111111 Risk of permanent damage. Overthe sprinkler can cause permanent damage. > Tighten the sprinkler to a MAXIMUM torque of 14 ft-lbs (19 N-m). 5. OPERATION During fire conditions, when the temperature around the sprinkler reaches its operating temperature, the heat -sensitive liquid in the glass bulb expands, causing the bulb to shatter, releasing the pip cap assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY Viking Sprinklers are available through a network of domestic and international distributors. See the Viking website for the closest distributor or contact Viking. 8. GUARANTEE For details of warranty, refer to Viking's current list price schedule or contact Viking directly. Form No. F_110720 21.04.19 Rev 21.2 Replaces Form No. F_110720 Rev 21.1 (Added Models E-1, E-2 and E-3 Escutcheons) Page 2 of 5 n VK3021 QUICK RESPONSE 4 I Ki PENDENT SPRINKLER (K5.6) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com TABLE 1: ORDERING INFORMATION Instructions: Using the sprinkler base part number, .. the suffix for the desired Finish Size .. the suffix for the desired Temperature Rating. 1: Finishes 2: Temperature Ratings Sprinkler Base Part NPT Number BSPT Description Suffix , Nominal Rating Bulb Color Max. Ambient Ceiling Suffix Inch mm Temperature 238707 1/2 Brass A 135 °F (57 °C) Orange 100 °F (38 °C) A 238827 15 Chrome F 155 °F (68 °C) Red 100 °F (38 °C) B White Polyester 4,6 M-AN 175 °F (79 °C) Yellow 150 °F (65 °C) D Black Polyester 4,6 M-/B 200 °F (93 °C) Green 150 °F (65 °C) E ENT 4,5,5 JN 286 °F (141 °C) Blue 225 °F (107 °C) G OPEN -- -- Z Example: 23870MB/W = VK3021 with white polyester finish and 155 °F (68 °C) nominal temperature rating. This sprinkler is to be installed into an area with a maximum ambient temperature of 100 °F (38 °C) meaning if the area will experience temperatures above the maximum ambient rating, you shall use a higher temperature -rated sprinkler. Accessories Sprinkler Wrenches (see Figure 1): A. Standard Wrench: Part number 23559MB B. Recessed Socket Wrench: Part number 23560MB2 Sprinkler Cabinet: A. Up to 6 sprinklers: Part number 01724A B. 6-12 sprinklers: Part number 01725A Footnotes Where a dash (-) is shown in the Finish suffix designation, insert the desired Temperature Rating suffix. See example above. 2. Requires a 1/2" ratchet which is not available from Viking. 3. Based on NFPA 13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 4. UL Listed as corrosion resistant. 5. FM Approved as corrosion resistant. 6. The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Chan. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end -user that the coatings are compatible with or suitable for the proposed environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway. 7 UL Listed for 250 PSI (17 bar) WWP. Figure 1: Sprinkler Wrenches 7/16" (11 mm) Nominal Pipe Engagement 1/2" NPT 15 mm BSPT 1-15/16" (49 mm) Figure 2: Sprinkler Dimensions Form No. F_110720 21.04.19 Rev 21.2 Page 3 of 5 n VK3021 QUICK RESPONSE 4 I Kj PENDENT SPRINKLER (K5.6) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com APPROVAL CHART in lsh(es)� Viking Quick Response Pendent Sprinkler Temperature(s) lA1X KEY VK3021 K5.6 (80.6 metric) Escutcheon(s), If applicable Thread Size Listings and Approvals2,6 Sprinkler Base Part Number' NPT BSPT cULus FM CE6 Inch mm Approval Listings Maximum WWP Approval Listings Maximum WWP Approval Listings 23870 1/2 -- A1, B2X, B3Y 250 PSI (17 bar) A1, B2X, B3Y 175 PSI (12 bar) C1, D2X, D3Y 23882 -- 15 A1, B2X, B3Y 250 PSI (17 bar) A1, B2X, B3Y 175 PSI (12 bar) C1, D2X, D3Y Approved Temperature Ratings: A = 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C) and 286 °F (141 °C) B = 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C) C = 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C) and 286 °F (141 °C) D = 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C) Approved Finishes: 1 = Brass, Chrome, White Polyester 3,4, Black Polyester 3,4, and ENT 45 2 = Brass, Chrome, White Polyester 3.4, and Black Polyester 3.4 3 = ENT 4.5 Approved Escutcheon Code: X = Installed with Viking Recessed Escutcheons Models E-1, E-2, E-3, NP-1, NP-2, and NP-3, or Viking Standard Surface Mounted Escutcheons Y = Installed with Viking Recessed Escutcheons Models E-1 and NP-1, or Viking Standard Surface Mounted Escutcheons Footnotes 1 Base Part number is shown. For complete part number, refer to Viking's current price schedule. I This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals. 3 Other colors are available upon request with the same Listings and Approvals as the standard colors. I cULus Listed as corrosion resistant. 5 FM Approved as corrosion resistant. ICE: Standard EN12259-1, Declaration of Performance DOP XT1A 1-3-21. DESIGN CRITERIA - UL cULus Listing Requirements: The Viking VK3021 Quick Response Pendent Sprinkler is cLILus Listed as indicated in Approval Chart for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers. • Designed for use in Light and Ordinary Hazard occupancies. • The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers shall be followed. IMPORTANT: Always refer to Form Number F 091699 - Care and Handling of Sprinklers. Also refer to Form Number F 080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance With the latest edition of Viking Technical Data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. DESIGN CRITERIA - FM FM Approval Requirements: The Viking VK3021 Quick Response Pendent Sprinkler is FM Approved as quick response Non -Storage Pendent sprinkler as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling. NOTE: The FM Installation guidelines may differ from UL and/or NFPA criteria. IMPORTANT: Always refer to Form Number F 091699 - Care and Handling of Sprinklers. Also refer to Form Number F 080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance With the latest edition of Viking Technical Data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Form No. F_110720 21.04.19 Rev 21.2 Page 4 of 5 n VK3021 QUICK RESPONSE PENDENT SPRINKLER (K5.6) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com 1. Install the escutcheon inner ring onto the sprinkler threads. 2. Carefully slide the wrench** sideways around the protective cap then push upwards to engage with the sprinkler wrench flats. / t 3. Install the sprinkler and escutcheon assembly into the pipe fitting. Be sure the escutcheon outer ring contacts the surface of the finished ceiling. Figure 3: Recessed Installation (with Recessed Socket Wrench) **A 1/2" ratchet is required (not available from Viking). 1. Install the escutcheon onto the sprinkler threads. 2. Carefully slide the wrench onto the sprinkler wrench flats. Figure 4: Installation (with Standard Wrench) 3. Install the sprinkler and escutcheon assembly into the pipe fitting. Be sure the escutcheon contacts the surface of the finished ceiling. Form No. F_110720 21.04.19 Rev 21.2 Page 5 of 5 n VK3021 QUICK RESPONSE 4 I Ki PENDENT SPRINKLER (K5.6) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com Models E-1 or NP-1 Recessed Escutcheon 2-1/8" (54 mm) Ceiling opening size: > Minimum: 2-5/16" (59 mm) Maximum: 2-1/2" (64 mm) Min. 13/16" Max. 1-7/16" (21 mm) (37 mm) e �` Ceiling opening size: Minimum: 2-5/16" (59 mm) Maximum: 2-1/2" (64 Max. 1-3/4" (44 mm) I 6" Im) Standard Surface -Mounted Escutcheon 2-1/8" (54 mm) Figure 5: Installation Dimensions with Viking Escutcheons Models E-2, E-3, NP-2 or NP-3 Thread- Recessed Escutcheon (E-3 and NP-3 Outer rings have larger diameters) Min. 15/16" (24 mm) Form No. F_110720 21.04.19 Rev 21.2 Replaces Form No. F_110720 Rev 21.1 (Added Models E-1, E-2 and E-3 Escutcheons) Page 1 of 4 CARE AND HANDLING OF SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com SPRINKLERS ARE FRAGILE - HANDLE WITH CARE! General Handling and Storage: • Store sprinklers in a cool, dry place. • Protect sprinklers during storage, transport, handling, and after installation. • Use the original shipping containers. DO NOT place sprinklers loose in boxes, bins, or buckets. • Keep sprinklers separated at all times. DO NOT allow metal parts to contact sprinkler operating elements. For Pre -Assembled Drops: • Protect sprinklers during handling and after installation. • For recessed assemblies, use the protective sprinkler cap (Viking Part Number 10364). Sprinklers with Protective Shields or Caps: • DO NOT remove shields or caps until after sprinkler installation and there no longer is potential for mechanical damage to the sprinkler operating elements. • Sprinkler shields or caps MUST be removed BEFORE placing the system in service! • Remove the sprinkler shield by carefully pulling it apart where it is snapped together. • Remove the cap by turning it slightly and pulling it off the sprinkler. Sprinkler Installation: • DO NOT use the sprinkler deflector or operating element to start or thread the sprinkler into a fitting. • Use only the designated sprinkler head wrench! Refer to the current sprinkler tech- nical data page to determine the correct wrench for the model of sprinkler used. • DO NOT install sprinklers onto piping at the floor level. • Install sprinklers after the piping is in place to prevent mechanical damage. • DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings, pipe, or couplings in close proximity to sprinklers. Sprinklers can be damaged from direct or indirect impacts. • DO NOT attempt to remove drywall, paint, etc., from sprinklers. • Take care not to over -tighten the sprinkler and/or damage its operating parts! Maximum Torque: 1/2" NPT: 14 ft-Ibs. (19.0 N-m) 3/4" NPT: 20 ft-Ibs. (27.1 N-m) 1" NPT: 30 ft-Ibs. (40.7 N-m) (Original container used) (Placed loose in box) (Protected with caps) (Protective caps not used) (Piping is in place at the (Sprinkler at floor level) ceiling) (Special installation (Designated wrench not wrenches) used) /,\ WARNING: Cancer and Reproductive Harm - (I w P65Warnmgs,ca.gov A WARNING Any sprinkler with a loss of liquid from the glass bulb or damage to the fusible element should be destroyed. Never install sprinklers that have been dropped, damaged, or exposed to temperatures exceeding the maximum ambient temperature allowed. Sprinklers that have been painted in the field must be replaced per NFPA 13. Protect sprinklers from paint and paint overspray in accordance with the installation standards. Do not clean sprinklers with soap and water, ammonia, or any other cleaning fluid. Do not use adhesives or solvents on sprinklers or their operating elements. Refer to the appropriate technical data page and NFPA standards for complete care, handling, installation, and maintenance instructions. For additional product and system information Viking data pages and installation instructions are available on the Viking Web site at www.vikinggroupinc.com. Form No. F_091699 18.10.11 Rev 16.1.P65 Replaces Form No. F_091699 Rev 16.1 (Added P65 Warning) Page 2 of 4 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com PROTECTIVE SPRINKLER SHIELDS AND CAPS General Handling and Storage: Many Viking sprinklers are available with a plastic protective cap or shield temporarily covering the operating elements. The snap - on shields and caps are factory installed and are intended to help protect the operating elements from mechanical damage during shipping, storage, and installation. NOTE: It is still necessary to follow the care and handling instructions on the appropriate sprin- kler technical data sheets* when installing sprinklers with bulb shields or caps. WHEN TO REMOVE THE SHIELDS AND CAPS: NOTE: SHIELDS AND CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE! Remove the shield or cap from the sprinkler only after checking all of the following: • The sprinkler has been installed*. The wall or ceiling finish work is completed where the sprinkler is installed and there no longer is a potential for mechanical damage to the sprinkler operating elements. SHIELDS AND CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE! Figure 1: Sprinkler shield being removed from a pendent sprinkler. Figure 2: Sprinkler cap being removed from a pendent sprinkler. Figure 3: Sprinkler cap being re- moved from and upright sprinkler. HOW TO REMOVE SHIELDS AND CAPS: No tools are necessary to remove the shields or caps from sprinklers. DO NOT use any sharp objects to remove them! Take care not to cause mechanical damage to sprinklers when removing the shields or caps. When removing caps from fusible ele- ment sprinklers, use care to prevent dislodging ejector springs or damaging fusible elements. NOTE: Squeezing the sprinkler cap excessively could damage sprinkler fusible elements. To remove the shield, simply pull the ends of the shield apart where it is snapped together. Refer to Figure 1. To remove the cap, turn it slightly and pull it off the sprinkler. Refer to Figures 2 and 3. IsmRefer to the current sprinkler technical data page to determine the correct sprinkler wrench for the model of sprinkler used. AWARNIIIG Never install sprinklers that have been dropped, damaged, or exposed to temperatures in excess of the maximum ambient temperature allowed. * Refer to the appropriate current technical data pages for complete care, handling, and installation instructions. Data pages are included with each shipment from Viking or Viking distributors. They can also be found on the Web site at www. vikinggroupinc.com. Form No. F_091699 18.10.11 Rev 16.1.P65 Page 3 of 4 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com ©CAUTION CONCEALED COVER ASSEMBLIES ARE FRAGILE! TO ASSURE SATISFACTORY PERFORMANCE OF THE PRODUCT, HANDLE WITH CARE. Concealed Sprinkler and Adapter Assembly with Protective Cap Concealed Sprinkler and Adapter Assembly (Protective Cap Removed) Cover Plate Assembly (Pendent Cover 12381 shown) GENERAL HANDLING AND STORAGE INSTRUCTIONS: • Do not store in temperatures exceeding 100 °F (38 °C). Avoid direct sunlight and confined areas subject to heat. • Protect sprinklers and cover assemblies during storage, transport, handling, and after installation. Use original shipping containers. Do not place sprinklers or cover assemblies loose in boxes, bins, or buckets. • Keep the sprinkler bodies covered with the protective sprinkler cap any time the sprinklers are shipped or handled, during testing of the system, and while ceiling finish work is being completed. • Use only the designated Viking recessed sprinkler wrench (refer to the appropriate sprinkler data page) to install these sprinklers. NOTE: The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed. • Do not over -tighten the sprinklers into fittings during installation. • Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation. • Do not attempt to remove drywall, paint, etc., from the sprinklers. • Remove the plastic protective cap from the sprinkler before attaching the cover plate assembly. PROTECTIVE CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE! Refer to the appropriate current technical data pages for complete care, handling, and installation instructions. Data pages are included with each shipment from Viking or Viking distributors. They can also be found on the Web site at www. vikinggroupinc.com. Form No. F_091699 18.10.11 Rev 16.1.P65 Page 4 of 4 CARE AND HANDLING OF SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com USE THE FOLLOWING PRECAUTIONS WHEN HANDLING WAX -COATED SPRINKLERS Many of Viking's sprinklers are available with factory -applied wax coating for corrosion resistance. These sprinklers MUST receive appropriate care and handling to avoid damaging the wax coating and to assure satisfactory performance of the product. General Handling and Storage of Wax -Coated Sprinklers: • Store the sprinklers in a cool, dry place (in temperatures below the maximum ambient temperature allowed for the sprinkler temperature rating. Refer to Table 1 below.) • Store containers of wax -coated sprinklers separate from other sprinklers. • Protect the sprinklers during storage, transport, handling, and after installation. • Use original shipping containers. • Do not place sprinklers in loose boxes, bins, or buckets. Installation of Wax -Coated Sprinklers: Use only the special sprinkler head wrench designed for installing wax -coated Viking sprinklers (any other wrench may damage the unit). • Take care not to crack the wax coating on the units. • For touching up the wax coating after installation, wax is available from Viking in bar form. Refer to Table 1 below. The coating MUST be repaired after sprinkler installation to protect the corrosion -resistant properties of the sprinkler. • Use care when locating sprinklers near fixtures that can generate heat. Do not install sprinklers where they would be exposed to temperatures exceed- ing the maximum recommended ambient temperature for the temperature rating used. • Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant coating. Thereafter, inspect representative samples of the coated sprinklers in accordance with NFPA 25. Close up visual inspections are necessary to determine whether the sprinklers are being affected by corrosive conditions. Sprinkler Temperature Rating (Fusing Point) Wax Part Number Wax Melting Point Maximum Ambient Ceiling Temperature Wax Color 155 °F (68 °C) / 165 °F (74 °C) 02568A 148 °F (64 °C) 100 °F (38 °C) Light Brown 175 °F (79 °C) 04146A 161 °F (71 °C) 150 °F (65 °C) Brown 200 °F (93 °C) 04146A 161 °F (71 °C) 150 °F (65 °C) Brown 220 °F (104 °C) 02569A 170 °F (76 °C) 150 °F (65 °C) Dark Brown 286 °F (141 °C) 02569A 170 °F (76 °C) 150 °F (65 °C) Dark Brown Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. ©WARNING Never install sprinklers that have been dropped, damaged, or exposed to temperatures in excess of the maximum ambi- ent temperature allowed. Refer to the appropriate current technical data pages for complete care, handling, and installation instructions. Data pages are included with each shipment from Viking or Viking distributors. They can also be found on the Web site at www. vikinggroupinc.com. Form No. F_091699 18.10.11 Rev 16.1.P65 Replaces Form No. F_091699 Rev 16.1 (Added P65 Warning) Page 1 of 3 N411UNG4 SPRINKLER OVERVIEW The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com 1. DESCRIPTION Viking fire sprinklers consist of a threaded frame with a specific waterway or orifice size and a deflector for distributing water in a specified pattern. A closed or sealed sprinkler refers to a complete assembly, including the thermosensitive operating element. An open sprinkler does not use an operating element and is open at all times. The distribution of water is intended to extinguish a fire or to control its spread. Viking sprinklers are available in several models and styles. Refer to specific sprinkler technical data pages for available styles, finishes, temperature ratings, thread sizes, and nominal K-Factors for the particular model selected. 2. LISTINGS AND APPROVALS Refer to the Approval Charts on the appropriate sprinkler technical data page(s) and/or /,� WARNING cancer and Reproauctive Harm - approval agency listings. U wWW P65Warnings,ca.gov 3. TECHNICAL DATA Pressure Ratings: Maximum allowable water working pressure is 175 psig (12 Bar) unless rated and specified for high water working pressure [250 psig (17.2 bar)]. Sprinkler Identification: Viking sprinklers are identified and marked with the word "Viking", the sprinkler identification number (SIN) consisting of "VK" plus a three digit number*, the model letter, and the year of manufacture. Available Finishes: Viking sprinklers are available in several decorative finishes. Some models are available with corrosion -resistant coatings or are fabricated from non -corrosive material. Refer to the sprinkler technical data page for additional information. Available Temperature Ratings: Viking sprinklers are available in several temperature ratings that relate to a specific temperature classification. Applicable installa- tion rules mandate the use and limitations of each temperature classification. In selecting the appropriate temperature classifica- tion, the maximum expected ceiling temperature must be known. When there is doubt as to the maximum temperature at the sprinkler location, a maximum -reading thermometer should be used to determine the temperature under conditions that would show the highest readings to be expected. In addition, recognized installation rules may require a higher temperature classifica- tion, depending upon sprinkler location, occupancy classification, commodity classification, storage height, and other hazards. In all cases, the maximum expected ceiling temperature dictates the lowest allowable temperature classification. Sprinklers located immediately adjacent to a heat source may require a higher temperature rating. K-Factors: Viking sprinklers are available in several orifice sizes with related K-Factors. The orifice is a tapered waterway and, therefore, the K-Factor given is nominal. Nominal U.S. K-Factors are provided in accordance with the 1999 edition of NFPA 13, Section 3-2.3. Refer to the specific data page for appropriate K-Factor information. Available Styles: Viking sprinklers are available for installation in several positions as indicated by a stamping on the deflector. The deflector style dictates the appropriate installation position of the sprinkler; it breaks the solid stream of water issuing from the sprinkler orifice to form a specific spray pattern. The following list indicates the various styles and identification of Viking sprinklers. UPRIGHT SPRINKLER: A sprinkler intended to be installed with the deflector above the frame so water flows upward through the orifice, striking the deflector and forming an umbrella -shaped spray pat- tern downward. Marked "SSU" (Standard Sprinkler Upright) or "UPRIGHT" Viking Technical Data may be found on on the deflector. PENDENT SPRINKLER: A sprinkler intended to be oriented with the deflec- The Viking Corporation's Web site at for below the frame so water flows downward through the orifice, striking http://www.vikinggroupinc.com. the deflector and forming an umbrella -shaped spray pattern downward. The Web site may include a more recent Marked "SSP" (Standard Sprinkler Pendent) or "PENDENT" on the de- edition of this Technical Data Page. flector. CONVENTIONAL SPRINKLER: An `old style" sprinkler intended to be installed with the deflector in either the upright or pendent position. The deflector provides a spherical type pattern with 40 to 60 percent of the water initially directed downward and a proportion directed upward. Must be installed in accordance with installation rules for conventional or old style sprinklers. DO NOT USE AS A REPLACEMENT FOR STANDARD SPRAY SPRINKLERS. Marked "C U/P" (Conventional Upright/Pendent) on the deflector. Form No. F_080814 18.12.06 Rev 14.1.P65 Replaces Form No. F_080814 Rev 14.1 (Added P65 Warning.) Page 2of3 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com VERTICAL SIDEWALL (VSW) SPRINKLER: A sprinkler intended for installation near the wall and ceiling. The deflector provides a water spray pattern outward in a quarter -spherical pattern and can be installed in the upright or pendent position with the flow arrow in the direction of discharge. Marked "SIDEWALL" on the deflector with an arrow and the word "FLOW". (Note: Some vertical sidewall sprinklers can only be installed in the upright or pendent position —in this case, the sprinkler will also be marked "UPRIGHT" or "PENDENT'.) HORIZONTAL SIDEWALL (HSW) SPRINKLER: A sprinkler intended for installation near the wall and ceiling. The special deflector provides a water spray pattern outward in a quarter -spherical pattern. Most of the water is directed away from the nearby wall with a small portion directed at the wall behind the sprinkler. The top of the deflector is oriented parallel with the ceiling or roof. The flow arrows point in the direction of discharge. Marked "SIDEWALL" and "TOP" with an arrow and the word "FLOW". EXTENDED COVERAGE (EC) SPRINKLER: A spray sprinkler designed to discharge water over an area having the maximum dimensions indicated in the individual listings. Maximum area of coverage, minimum flow rate, orifice size, and nominal K-Factor are specified in the individual listings. EC sprinklers are intended for Light -Hazard occupancies with smooth, flat, horizontal ceil- ings unless otherwise specified. In addition to the above markings, the sprinkler is marked "EC". QUICK RESPONSE (QR) SPRINKLER: A spray sprinkler with a fast- actuating operating element. The use of quick response sprinklers may be limited due to occupancy and hazard. Refer to the Authority Having Jurisdiction (AHJ) prior to installing. QUICK RESPONSE EXTENDED COVERAGE (QREC) SPRINKLER: A spray sprinkler designed to discharge water over an area having the maximum dimensions indicated in the individual listing. This is a sprinkler with an operating element that meets the criteria for quick response. QREC sprinklers are only intended for Light Hazard occupancies. The sprinkler is marked "QREC'. FLUSH SPRINKLER: A decorative spray sprinkler intended for installation with a concealed piping system. The unit is mounted flush with the ceiling or wall, with the fusible link exposed. Upon actuation, the deflector extends beyond the ceiling or wall to distribute water discharge. The sprinkler is marked "SSP", "PEND", or "SIDEWALL" and "TOP". CONCEALED SPRINKLER: A decorative spray sprinkler intended for installation with a concealed piping system. The sprinkler is hidden from view by a cover plate installed flush with the ceiling or wall. During fire conditions, the cover plate detaches, and upon sprinkler actuation, the deflector extends beyond the ceiling or wall to distribute water discharge. The sprinkler is marked "SSP", "PEND", or "SIDEWALL" and "TOP". RECESSED SPRINKLER: A spray sprinkler assembly intended for installation with a concealed piping system. The assembly con- sists of a sprinkler installed in a decorative adjustable recessed escutcheon that minimizes the protrusion of the sprinkler beyond the ceiling or wall without adversely affecting the sprinkler distribution or sensitivity. Refer to the appropriate technical data page for allowable sprinkler models, temperature ratings, and occupancy classifications. DO NOT RECESS ANY SPRINKLER NOT LISTED FOR USE WITH THE ESCUTCHEON. CORROSION -RESISTANT SPRINKLER: A special service sprinkler with non -corrosive protective coatings, or that is fabricated from non -corrosive material, for use in atmospheres that would normally corrode sprinklers. DRY SPRINKLER: A special -service sprinkler intended for installation on dry pipe systems or wet pipe systems where the sprinkler is subject to freezing temperatures. The unit consists of a sprinkler permanently secured to an extension nipple with a sealed inlet end to prevent water from entering the nipple until the sprinkler operates. The unit MUST be installed in a tee fitting. Dry upright sprinklers are marked with the "B" dimension [distance from the face of the fitting (tee) to the top of the deflector]. Dry pendent and sidewall sprinklers are marked with the "A" dimension [the distance from the face of fitting (tee) to the finished surface of the ceiling or wall]. LARGE DROP SPRINKLER: A type of special application sprinkler used to provide fire control of specific high -challenge fire haz- ards. Large drop sprinklers are designed to produce an umbrella -shaped spray pattern downward with a higher percentage of "large" water droplets than standard spray sprinklers. The sprinkler has an extra -large orifice with a nominal K-Factor of 11.2. Marked "HIGH CHALLENGE" and "UPRIGHT'. EARLY SUPPRESSION FAST -RESPONSE (ESFR) SPRINKLER: A sprinkler intended to provide fire suppression of specific high - challenge fire hazards through the use of a fast response fusible link, 14.0, 16.8, or 25.2 nominal K-Factor, and special deflector. ESFR sprinklers are designed to produce high -momentum water droplets in a hemispherical pattern below the deflector. This permits penetration of the fire plume and direct wetting of the burning fuel surface while cooling the atmosphere early in the development of a high -challenge fire. Marked "ESFR" and "UPRIGHT' or "PEND". INTERMEDIATE LEVEL/RACK STORAGE SPRINKLER: A standard spray sprinkler assembly designed to protect its operating element from the spray of sprinklers installed at higher elevations. The assembly consists of a standard or large orifice upright or pendent sprinkler with an integral upright or pendent water shield and guard assembly. Use only those sprinklers that have been tested and listed for use with the assembly. Refer to the technical data page for allowable sprinkler models. RESIDENTIAL SPRINKLER: A sprinkler intended for use in the following occupancies: one- and two-family dwellings with the fire protection sprinkler system installed in accordance with NFPA 13D; residential occupancies up to four stories in height with the fire protection system installed in accordance with NFPA 13R; and where allowed by the Authority Having Jurisdiction in resi- dential portions of any occupancy with the fire protection system installed in accordance with NFPA 13. Form No. F_080814 18.12.06 Rev 14.1.P65 Page 3 of 3 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Residential sprinklers have a unique distribution pattern and utilize a "fast response" heat sensitive operating element. They en- hance survivability in the room of fire origin and are designed to provide a life safety environment for a minimum of ten minutes. For this reason, residential sprinklers must not be used to replace standard sprinklers unless tested for and approved by the Authority Having Jurisdiction. In addition to standard markings, the unit is identified as "RESIDENTIAL SPRINKLER" or "RES". 4. INSTALLATION Refer to appropriate NFPA Installation Standards. 5. OPERATION Refer to the appropriate sprinkler technical data page(s). 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking's current list price schedule or contact Viking directly. IM PORTANT:Always referto Bulletin Form No. F_091699 -Care and Handling of Sprinklers and the appropriate sprin- klergeneralcare, instal lation,andmaintenanceguide.Vikingsprinklersaretobeinstalled inaccordancewiththelatest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organizations,andalsowiththeprovisionsofgovernmentalcodes,ordinances,andstandards,wheneverapplicable. The sprinkler technical data page may contain installation requirements specific for the sprinkler model selected. The use of certain types of sprinklers may be limited due to occupancy and hazard. Refer to the Authority Having Jurisdiction prior to installation. Form No. F_080814 18.12.06 Rev 14.1.P65 Replaces Form No. F_080814 Rev 14.1 (Added P65 Warning.) Page 4 of 4 SPRINKLER GENERAL CARE, INSTALLATION, AND MAINTENANCE GUIDE The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page. 1. DESCRIPTION - STANDARD RESPONSE, QUICK RESPONSE, EXTENDED COVERAGE, AND DRYSPRINKLERS Viking thermosensitive spray sprinklers consist of a small frame and either a glass bulb or a fusible operating element. Available styles include pendent, flush pendent, concealed pendent, upright, horizontal sidewall, vertical sidewall, or conventional, depending on the particular sprinkler model selected. Viking sprinklers are available with various finishes, temperature ratings, responses, and K-Factors to meet design requirementst. Used in conjunction with one of the corrosion -resistant coatings (for frame style sprinklers), the units provide protection against many corrosive environments. In addition, the special Polyester or PTFE coatings can be used in decorative applications where colors are desired. t Refer to the sprinkler technical data page for available styles, finishes, temperature ratings, responses, and nominal K-Factors for specific sprinkler models. 2. LISTINGS AND APPROVALS Refer to the Approval Charts on the appropriate sprinkler technical data page(s) and/or approval agency listings. 3. TECHNICAL DATA Specifications: WARNING: Cancer and Reproductive Harm - Refer to the appropriate sprinkler technical data sheet. www.P55Wamingsca.gov Material Standards: Refer to the appropriate sprinkler technical data sheet. 4. INSTALLATION NOTE: Take care not to over -tighten the sprinkler and/or damage its operating parts! Maximum Torque: 1/2" NPT: 14 ft-Ibs. (19.0 N-m) 3/4" NPT: 20 ft-Ibs. (27.1 N-m) 1" NPT: 30 ft-Ibs. (40.7 N-m) A. Care and Handling (also refer to Bulletin - Care and Handling of Sprinklers, Form No. F_091699.) Sprinklers must be handled with care. They must be stored in a cool, dry place in their original shipping container. Never install sprinklers that have been dropped, damaged, or exposed to temperatures exceeding the maximum ambient temperature al- lowed (refer to the temperature chart on the sprinkler technical data page). Never install any glass -bulb sprinkler if the bulb is cracked or if there is a loss of liquid from the bulb. A small air bubble should be present in the glass bulb. Any sprinkler with a loss of liquid from the glass bulb or damage to the fusible element should be destroyed immediately. (Note: Installing glass bulb sprinklers in direct sunlight (ultraviolet light) may affect the color of the dye used to color code the bulb. This color change does not affect the integrity of the bulb.) Sprinklers must be protected from mechanical damage during storage, transport, handling, and after installation. Sprinklers subject to mechanical damage must be protected with an approved sprinkler guard. Use only sprinklers listed as corrosion resistant when subject to corrosive environments. When installing corrosion -resistant sprin- klers, take care not to damage the corrosion -resistant coating. Use only the special wrench designed for installing coated or recessed Viking sprinklers (any other wrench may damage the unit). Concealed sprinklers must be installed in neutral or negative pressure plenums only! Use care when locating sprinklers near fixtures that can generate heat. Do not install sprinklers where they could be exposed to temperatures exceeding the maximum recommended ambient temperature for the temperature rating used. Wet pipe systems must be provided with adequate heat. Sprinklers supplied from dry systems in areas subject to freezing must be listed dry sprinklers, upright, or horizontal sidewall sprinklers installed so that water is not trapped. For dry systems, pendent sprinklers and sidewall sprinklers installed on return bends are permitted, where the sprinklers, return bend, and branch line piping are in an area maintained at or above 40 °F (4 °C). B. Installation Instructions - Standard Spray Sprinklers Viking sprinklers are manufactured and tested to meet the rigid requirements of approving agencies. They are designed to be installed in accordance with recognized installation standards. Deviation from the standards or any alteration to sprinklers or cover plate assemblies after they leave the factory including, but not limited to: painting, plating, coating, or modification, may render them inoperative and will automatically nullify the approvals and any guarantee made by The Viking Corporation. Form No. F_080614 18.10.11 Rev 16.1.P65 Replaces Form No. F_080614 Rev 16.1 (Added P65 Warning.) Page 2 of 4 SPRINKLER GENERAL CARE, INSTALLATION, AND MAINTENANCE GUIDE The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page. Before installation, be sure to have the appropriate sprinkler model and style, with the correct K-Factor, temperature rating, and response characteristics. Sprinklers must be installed after the piping is in place to prevent mechanical damage. Keep sprinklers with protective caps or bulb shields contained within the caps or shields during installation and testing, and any time the sprinkler is shipped or handled. 1 a. For frame -style sprinklers, install escutcheon (if used), which is designed to thread onto the external threads of the sprinkler. Refer to the appropriate sprinkler data page to determine approved escutcheons for use with specific sprinkler models. 1 b. For flush and concealed style sprinklers: Cut the sprinkler nipple so that the or 3/4" (15 mm or 20 mm)* NPT outlet of the reducing coupling is at the desired location, and centered in the opening* in the ceiling or wall. *Size depends on the sprinkler model used. Refer to the sprinkler technical data page. 2. Apply a small amount of pipe -joint compound or tape to the external threads of the sprinkler only, taking care not to allow a build- up of compound in the sprinkler inlet. NOTE: Sprinklers with protective caps or bulb shields must have the caps or shields kept on them when applying pipe -joint compound or tape. Exception: For domed concealed sprinklers, remove the protective cap for installation, and then place it back on the sprinkler temporarily.. 3. Refer to the appropriate sprinkler technical data page to determine the correct sprinkler wrench for the model of sprinkler used. DO NOT use the deflector or fusible element to start or thread the sprinkler into a fitting. a. Install the sprinkler onto the piping using the special sprinkler wrench only, taking care not to over -tighten or damage the sprinkler. b. For flush and concealed style sprinklers: the internal diameter of the special sprinkler installation wrench is designed for use with the sprinkler contained in the protective cap. Exception: For domed concealed sprinklers, remove the protective cap for installation, and then place it back on the sprinkler temporarily. Thread the flush or concealed sprinkler into the or 3/4" (15 mm or 20 mm)* NPT outlet of the coupling by turning it clockwise with the special sprinkler wrench. *Thread size depends on the particular sprinkler model used. Refer to the sprinkler technical data page. C. Installation Instructions - Dry Sprinklers WARNING: Viking dry sprinklers are to be installed in the 1" outlet (for dry and preaction systems), or run of malleable, ductile iron, or Nibco CPVC* threaded tee fittings (for wet systems) that meet the dimensional requirements of ANSI 1316.3 (Class 150), or cast iron threaded tee fittings that meet the dimensional requirements of ANSI B16.4 (Class 125), even at branch line ends. The threaded end of the dry sprinkler is designed to allow the seal to penetrate and extend into the fitting to a predetermined depth. This prevents condensation from accumulating and freezing over the sprinkler seal. *NOTE: When using CPVC fittings with Viking dry sprinklers, use only new Nibco Model 5012-S-13I. When selecting other CPVC fittings, contact Viking Technical Services. 1. DO NOT install the dry sprinkler into a threaded elbow, coupling, or any other fitting that could interfere with thread penetration. Such installation would damage the brass seal. 2. DO NOT install dry sprinklers into couplings or fittings that would allow condensation to accumulate above the seal when the sprinkler is located in an area subject to freezing. 3. NEVER try to modify dry sprinklers. They are manufactured for specific "A" or "B" dimensions and cannot be modified. The dry sprinkler must be installed after the piping is in place to prevent mechanical damage. Before installation, be sure to have the correct sprinkler model and style, with the appropriate "A" or "B" dimension(s), temperature rating, orifice size, and response characteristics. Keep sprinklers with protective caps or bulb shields contained within the caps or shields during installation and testing, and any time the sprinkler is shipped or handled. Exception: For concealed and adjustable recessed dry sprinklers, the protective caps and shields are removed for installation. To install the dry sprinkler, refer to the instructions below and the appropriate sprinkler technical data page for illustrated instruc- tions. Dry upright sprinklers must be installed above the piping, in the upright position only. When installing dry upright or plain barrel style vertical sidewall sprinklers on piping located close to the ceiling, it may be necessary to lower the sprinkler into the fitting from above the ceiling. When installing dry upright or plain barrel vertical sidewall sprinklers from below the ceiling, verify that the opening in the ceiling is a minimum 1-112" (38.1 mm) in diameter. For dry upright or plain barrel vertical sidewall sprinklers in the upright position: First, install the escutcheon (if used) over the threaded end of the sprinkler barrel. Slide the escutcheon past the external threads. NOTE: When installing the dry upright or plain barrel vertical sidewall sprinkler from above the ceiling, it will be necessary to install the escutcheon after lowering the threaded end of the sprinkler through the ceiling penetration. A. For all dry sprinklers: Apply a small amount of pipe -joint compound or tape to the external threads of the sprinkler barrel only, taking care not to allow a build-up of compound or tape over the brass inlet and seal. NOTE: Sprinklers with protective caps or bulb shields must be contained within the caps or shields before applying pipe -joint compound ortape. Form No. F_080614 18.10.11 Rev 16.1.P65 Page 3 of 4 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page. B. Refer to the appropriate sprinkler technical data page to determine the correct sprinkler wrench for the model of sprinkler used. C. Install the dry sprinkler on the piping using the special dry sprinkler wrench only, while taking care not to damage the sprinkler. NOTE: Thread the sprinkler into the fitting hand tight, plus 1/2 turn with the dry sprinkler wrench. D. For adjustable standard and adjustable recessed dry pendent and sidewall sprinklers: Escutcheons can be installed after the sprinklers have been installed onto the piping. Refer to the appropriate sprinkler technical data page for escutcheon installation instructions and illustrations. D. Installation Instructions -Testing 4. After installation, the entire sprinkler system must be tested. The test must be conducted to comply with the installation stand- ards. Viking high pressure sprinklers may be hydrostatically tested at a maximum of 300 psi (20.7 bar) for limited periods of time (two hours), for the purpose of acceptance by the Authority Having Jurisdiction. a. Make sure the sprinkler is properly tightened. If a thread leak occurs, normally the sprinkler must be removed, new pipe -joint compound or tape applied, and then reinstalled. This is due to the fact that when the joint seal is damaged, the sealing compound or tape is washed out of the joint. Air testing [do not exceed 40 psi (2.76 bar)] the sprinkler piping prior to testing with water may be considered in areas where leakage during testing must be prevented. Refer to the Installation Standards and the Authority Having Jurisdiction. b. Remove plastic protective sprinkler caps or bulb shields AFTER the wall or ceiling finish work is completed where the sprinkler is installed and there no longer is a potential for mechanical damage to the sprinkler operating ele- ments. To remove the bulb shields, simply pull the ends of the shields apart where they are snapped together. To remove caps from frame style sprinklers, turn the caps slightly and pull them off the sprinklers. SPRINKLER CAPS OR BULB SHIELDS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE! Retain a protective cap or shield in the spare sprinkler cabinet. 5. For flush style sprinklers: the ceiling ring can now be installed onto the sprinkler body. Align the ceiling ring with the sprinkler body and thread or push it on (depends on sprinkler model) until the outer flange touches the surface of the ceiling. Note the maximum adjustment is 1/4" (6.35 mm). DO NOT MODIFY THE UNIT. If necessary, re -cut the sprinkler drop nipple as required. 6. For concealed sprinklers: the cover assembly can now be attached. a. Remove the cover from the protective box, taking care not to damage the cover plate assembly. b. Gently place the base of the cover plate assembly over the sprinkler protruding through the opening in the ceiling. c. Push the cover plate assembly onto the sprinkler until the unfinished brass flange of the cover plate base (or the cover adapter, if used) touches the surface of the ceiling. d. Refer to the applicable technical data sheet to determin the maximum adjustment available for concealed sprinklers. DO NOT MODIFY THE UNIT. If necessary, re -cut the sprinkler drop nipple. NOTE: If it is necessary to remove the entire sprinkler unit, the system must be taken out of service. See section 6. INSPECTIONS, TESTS AND MAINTENANCE and follow all warnings and instructions. 5. OPERATION Refer to the appropriate sprinkler technical data page(s). During fire conditions, the operating element fuses or shatters (depending on the type of sprinkler), releasing the pip cap and sealing assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appro- priate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. The sprinkler technical data page may contain installation requirements specific for the sprinkler model selected. The use of certain types of sprinklers may be limited due to occupancy and hazard. Refer to the Authority Having Jurisdiction prior to installation. Form No. F_080614 18.10.11 Rev 16.1.P65 Page 4 of 4 SPRINKLER GENERAL CARE, INSTALLATION, AND MAINTENANCE GUIDE The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page. 6. INSPECTIONS, TESTS AND MAINTENANCE NOTICE: Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. NOTICE: The owner is responsible for having the fire -protection system and devices inspected, tested, and maintained in proper operating condition in accordance with this guide, and applicable NFPA standards. In addition, the Authority Having Jurisdiction may have additional maintenance, testing, and inspection requirements that must be followed. A. Sprinklers must be inspected on a regular basis for corrosion, mechanical damage, obstructions, paint, etc. Frequency of inspec- tions may vary due to corrosive atmospheres, water supplies, and activity around the sprinkler unit. B. Sprinklers or cover plate assemblies that have been field painted, caulked, or mechanically damaged must be replaced im- mediately. Sprinklers showing signs of corrosion shall be tested and/or replaced immediately as required. Installation standards require sprinklers to be tested and, if necessary, replaced after a specified term of service. Refer to NFPA 25 and the Authority Having Jurisdiction for the specified period of time after which testing and/or replacement is required. Never attempt to repair or reassemble a sprinkler. Sprinklers and cover assemblies that have operated cannot be reassembled or re -used, but must be replaced. When replacement is necessary, use only new sprinklers and cover assemblies with identical performance char- acteristics. C. The sprinkler discharge pattern is critical for proper fire protection. Therefore, nothing should be hung from, attached to, or otherwise obstruct the discharge pattern. All obstructions must be immediately removed or, if necessary, additional sprinklers installed. D. When replacing existing sprinklers, the system must be removed from service. Refer to the appropriate system description and/ or valve instructions. Prior to removing the system from service, notify all Authorities Having Jurisdiction. Consideration should be given to employment of a fire patrol in the affected area. 1. Remove the system from service, drain all water, and relieve all pressure on the piping. 2a. For frame -style sprinklers, use the special sprinkler wrench to remove the old sprinkler by turning it counterclockwise to unthread it from the piping. 2b. For flush and concealed style sprinklers: Remove the ceiling ring or cover plate assem- bly before unthreading the sprinkler body from the piping. Ceiling rings and cover plates can be removed ei- ther by gently unthreading them or pulling them off the sprinkler body (depends on the sprinkler model used). After the ceiling ring or cover plate assembly has been removed from the sprinkler body, place the plastic protective cap (from the spare sprinkler cabinet) over the sprinkler to be removed and then fit the sprinkler wrench over the cap. Then use the wrench to unthread the sprinkler from the piping. Exception: Domed concealed sprinklers are removed without the plastic cap. 3. Install the new sprinkler unit by following the instructions in section 4. INSTALLATION. Care must be taken to ensure that the replacement sprinkler is the proper model and style, with the correct K-Factor, temperature rating, and response character- istics. A fully stocked spare sprinkler cabinet should be provided for this purpose. For flush or concealed sprinklers: stock of spare ceiling rings or cover plates should also be available in the spare sprinkler cabinet. E. Place the system back in service and secure all valves. Check for and repair all leaks. Sprinkler systems that have been sub- jected to a fire must be returned to service as soon as possible. The entire system must be inspected for damage, and repaired or replaced as necessary. Sprinklers that have been exposed to corrosive products of combustion or high ambient temperatures, but have not operated, should be replaced. Refer to the Authority Having Jurisdiction for minimum replacement requirements. 7. AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking's current list price schedule or contact Viking directly. Form No. F_080614 18.10.11 Rev 16.1.P65 Replaces Form No. F_080614 Rev 16.1 (Added P65 Warning.) Page 1 of 4 REGULATORY AND HEALTH WARNINGS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com 1. DESCRIPTION Regulatory and Health Warnings applying to materials used in the manufacture and construction of fire protection products are provided herin as they relate to legally mandated jurisdictional regions. A WARNING STATE OF CALIFORNIA, USA Installing or servicing fire protection products such as sprinklers, valves, piping etc. can expose you to chemicals including, but not li- mited to, lead, nickel, butadiene, titaninum dioxide, chromium, carbon black, and acrylonitrile which are known to the State of California to cause cancer or birth defects or other reproductive harm. For more information, go to www.P65Warnings.ca.gov 2. WARRANTY TERMS AND CONDITIONS For details of warranty, refer to Viking's current list price schedule at www.vikinggroupinc.com or contact Viking directly. Page 1 of 1 t••••••. COSCO ' • • •• • • ' Fire Protection SECTION 3. HANGERS Threaded Accessories B3205 - Threaded Rod (right-hand threads - both ends) JOLCO Fig.103) B3205L - Threaded Rod (right & left hand threads) Size Range: 3/8"-16 thru 3"-4 rod Material: Steel Function: Recommended for use as a hanger support in hanger assemblies. Rod is threaded on both ends with right hand threads of the length shown. Also available with left and right hand threads - specify Fig. B3205L when ordering. Maximum Temperature: 750OF (399°C) Finish: Plain or Electro-Galvanized. Contact B-Linefor alternative finishes and materials. Order By: Figure number, rod size, length and finish Standard Design Load Thread Size Thread Length TL 650°F (343°C) 750OF (399°C) Part No. A in. (MM) Lbs. (M) Lbs. (M) B3205.3/8 X V 3/8"-16 21/2" (63.5) 730 (3.25) 572 (2.54) B3205-1/2 X V 1/2"-13 21/2" (63.5) 1350 (6.00) 1057 (4.70) B3205-5/8 X V 5/8"-11 21/2" (63.5) 2160 (9.61) 1692 (7.52) B3205-3/4 X V 3/4"-10 3" (76.2) 3230 (14.37) 2530 (11.25) B3205-7/8 X V 7/8"-9 31/2" (88.9) 4480 (19.93) 3508 (15.60) For larger sizes consult full line pipe hanger catalog. ATR - All Threaded Rod - 120" (3.05m) Lengths (TOLCO Fig. 100) Fig. 99 - All Threaded Rod Cut To Length Size Range: 3/8"-16 thru 11/2"-6 rod in 120" lengths or cut to length Material: Steel Maximum Temperature: 750OF (399°C) Finish: Plain or Electro-Galvanized. Contact B-Line for alternative finishes and materials. Order By: Figure number, rod size, length and finish '0 _�0000 Part No. - Size x Length Threads Recommended Load Approx. Wt.1100 Ft. ATR Fig. 99 Per Inch Lbs. (kN) Lbs. (kg) ATR 1/4" x 120 99-1/4" x length 20 240 (1.07) 12 (5.44) ATR 3/8" x 120 99-318" x length 16 730 (3.24) 29 (13.15) ATR 1/2" x 120 99.1/2" x length 13 1350 (6.00) 53 (24.04) ATR 5/8" x 120 99-518" x length 11 2160 (9.60) 89 (40.37) ATR 3/4" x 120 99-314" x length 10 3230 (14.37) 123 (55.79) ATR 718" x 120 99-7/8" x length 9 4480 (19.93) 170 (77.11) For larger sizes consult full line pipe hanger catalog. Page 8of7 OTOLCO All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified. 18.19.11 Rev TVJ by E:t•N Revised412812014 94 Fire Protection Solutions Fig. 2 — Adjustable Band Hanger Size Range — Size 21/2" thru 6" pipe. Material — Carbon Steel, Pre -Galvanized Function — Recommended for the suspension of non -insulated pipe or insulated pipe with Fig. 220 shield. Fig. 2NFPA accommodates the reduced rod schedule of the National Fire Protection Association Pamphlet 13. Approvals — Factory Mutual Engineering approved. Underwriters Laboratories Listed. Conforms to Federal Specification WW-H-171 E, Type 10 and Manufacturers Standardization Society SP-69, Type 10. Finish — Pre -Galvanized Note — Available in Stainless Steel materials. Order By — Figure number, pipe size and material Dimensions • Weights Pipe Max. Rec. Approx. Size Rod Size A B C Load Lbs. wt./100 21/2 1/2* 53/4 4'/4 15/8 600 41 3 1/2* 6 41/8 11/4 600 45 31/2 1/2* 73/8 51/4 21/8 600 52 4 5/8* 8 5 Ss 1000 59 5 5/8** 9 61/8 21/4 1250 97 6 3/4** 93/8 6'/2 17/8 1250 139 con UMD FM OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330 CUSTOMER SERVICE • 800.786.5266 www.tolco.com Beam Clamps Fig. 65 - Reversible Steel C-Type Beam Clamp 3/4" (19.omm) Throat Opening Fig. 65XT - Reversible Steel C-Type Beam Clamp 3/4" (19.omm) Throat Opening (bottom of page Size Range: Fig. 65 - 1/2"-13 rod sizes, and 5/8"-11 rod sizes Fig. 65XT - 3/8"-16 rod size (see below) Material: Steel with hardened cup point set screw and jam nut Function: Recommended for hanging from steel beam where flange thickness does not exceed 3/4" (19.Omm). Features: All steel construction eliminates structural deficiencies associated with casting type beam clamps. May be used on top or bottom flange of beam. (Beveled lip allows hanging from top flange where clearance is limited.) May be installed with set screw in up or down position. Offset design permits unlimited rod adjustment by allowing the rod to be threaded completely through the clamp. Open design permits inspection of thread engagement. Approvals: Underwriters Laboratories Listed in the USA (UL) and Canada (cUL). Exceeds requirements of the National Fire Protection Association (NFPA), pamphlet 13, 3/8"-16 rod will support 1/2" (15mm) thru 4" (loomm) pipe 1/2"-13 rod will support thru 8" (200mm) pipe Finish: Plain. Contact B-Line for alternative finishes and materials. Order By: Figure number and finish Fig. 65 Patent #4,570,885 Part Rod Size B C D E No. A in. (mm) in. (mm) in. (mm) in. (mm) 65-1/2 1/2"-13 11/2" (38.1) 3/4" (19.0) 1" (25.4) 9/16" (14.3) 65-5/8 5/8"-11 11/2" (38.1) 3/4" (19.0) 1" (25.4) 9/16" (14.3) Set Screw and Locknut Included Part F Approx. Wt./100 No. in. (mm) Lbs. (kg) 65-1/2 11/4" (31.7) 55 (24.9) 65-5/8 11/4" (31.7) 55 (24.9) Fig. 65XT-3/8 - Beam Clamp Feature: Extruded holes allows for more thread engagement of threaded rod and set screw. Weight: Approx. Wt./l00 - 28.0 Lbs. (12.7kg) Finish: Plain or Electro-Galvanized 3/4., Order By: Figure number and finish (19.0) '( Approvals: Underwriters Laboratories Listed (cULus) and FM Approved (FM) for up to 4" (1oomm) pipe. Set Screw and Designed to meet or exceed requirements of Locknut Included FM DS 2-0. 1" t (25.4) 19/ i (39.739.7) 7/," 1'/s" (22.2) (34.9) {� TCILCO- ) C &us LISTED WOW C &us LISTED pFMEo All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified. Fire Protection Solutions 13 B-Line by EJ-N dMI Fig. 69 - Beam Clamp Retaining Strap Size Range — 3/8" thru 7/8" rod by 4" thru 16" length.* Material — Pre -Galvanized Steel Function — To offer more secure fastening of various types of beam clamps to beam where danger of movement might be expected. NFPA 13 requires the use of retaining straps with all beam clamps installed in earthquake areas. Satisfies requirements of NFPA 13 (2010) 9.3.7.1. Important Note — Good installation practice of a retaining strap requires that the strap be held tightly and securely to all component parts of the assembly. Therefore a locking mech- anism of some kind such as a hex nut or the beveled locking slot on the TOLCO® Fig. 69R will provide a more secure reliable installation. Approvals — Underwriters' Laboratories listed in the USA (UL) and Canada (WL). Approved for use with any listed beam clamp. Included in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and Development (OSHPD). For additional load, spacing and placement information relat- ing to OSHPD protects, please refer to the TOLCO Seismic Restraint Systems Guidelines. Finish — Pre -Galvanized Order By — Figure number, type, length "B" and rod size being used with beam clamp Note — Minimum return on Strap: 1". Dimensions Type Rod Size A Hole Size B 1 3/8 7/16 1/2 9/16 Specify Specify 2 5/8 11/16 3/4 13/16 Specify Specify 3 3/8-7/8 Specify Specify Longer lengths are available, consult factory. Component of State of California OSHPD Approved C V� llS LISTED Seismic Restraints System OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330 CUSTOMER SERVICE • 800.786.5266 www.tolco.com