Swedish – Birthing Center- Med Gas Special Inspection Report 3.31.2022 (2)Medical Gas Services 918 S Horton St, Suite 917 Seattle, WA 98134 medgasservices.io (425) 894 5918 Medical Gas Line Verification Report Date: March 29th, 2022 Job Number: 3626 Contractor: UMC, Inc. Date(s) / Time(s) of Testing: March 29th, 2022 - 0900 hrs. Facility: Swedish - Edmonds Campus 2160176th Ave W Edmonds, WA 98026 Scope of Work: Addition of new outlets/inlets to existing distribution systems Our firm certifies that the verifier named in the report is properly trained and certified to perform the activities required. All testing and measurement equipment are properly calibrated and maintained. As a representative of Medical Gas Services, LLC, the verifier named in this report has conducted testing and verification of medical gas piping systems and related equipment to certify the following on the above date. General Findings: A. Medical gases and vacuum are in compliance with NFPA 99 (2012ed): Category 1 B. No crossed lines were found in medical gas or vacuum systems in the tested areas on the day of testing. C. Medical gases meet minimum concentration. D. Medical gases meet minimum flow and are at normal pressure. E. Medical vacuum meets minimum flow and is at normal vacuum pressure. F. Medical gas system components in the area tested are in compliance with NFPA 99 (2012ed). G. Medical Gas Line Purity Test: PASS H. Permit #: BLD2022-0106 / City of Edmonds I. Attachments: Worksheets Note: Existing Equipment and Systems NFPA 99(2012ed)115114 - An existing system that is not in strict compliance with the provisions of this standard shall be permitted to be continued in use as long as the authority havingiurisdiction has determined that such use does not constitute a distinct hazard to life. 3626-3.29.22-VR Pg 1 of 3 Medical Gas Services 918 S Horton St, Suite 917 Seattle, WA 98134 medgasservices.io (425) 894 5918 II. Medical Gases: A. Oxygen: 1. Static Line Pressure: 53.5 psi 2. Dynamic Outlet Free Flow: >3.5 scfm 3. Dynamic Outlet Free Flow: >6.0 scfm (for 3 seconds in 'Critical Care Area') 4. Oxygen Concentration: 97.5 % 5. Delta Flow: PASS B. Medical Air: 1. Static Line Pressure: 51.6 psi 2. Dynamic Outlet Free Flow: >3.5 scfm 3. Dynamic Outlet Free Flow: >6.0 scfm (for 3 seconds in 'Critical Care Area') 4. Oxygen Concentration: 20.3 % 5. Delta Flow: PASS 6. Carbon Monoxide: Non -Detectable 7. Carbon Dioxide: 442 ppm 8. THC's: Non -Detectable 9. Dew Point: 13.5° F III. Vacuum: A. Medical -Surgical Vacuum 1. Static Line Vacuum: 20.51" HqV 2. Dynamic Inlet Free Flow: >3.0 scfm 3. Delta Flow: PASS IV. Particulate Test: PASS V. Odor: None VI. Outlets / Inlets: A. Brand: BeaconMedaes B. Quick Connect Style: Chemetron VII. Zone Valves: A. Brand: Chemetron B. Down line gauges: Yes C. Labeled for Area Controlled: Yes VIII. Alarms: A. Area Alarms: 1. Brand: Chemetron 2. Labeled for Area Monitored: Yes 3626-3.29.22-VR Pq 2 of 3 Medical Gas Services 918 S Horton St, Suite 917 Seattle. WA 98134 medsasservices.io (425) 894 5918 IX. Brazier: Chase Headrick A. Brazier Number: HEADRC"913LH B. Contractor: UMC, Inc. X. Comments: A. None XI. Recommendations: A. None Tested By: Alexander Christensen - Medical Gas Technician Reviewed By: Matthew Waa�chhsmuth - ASSE 6030 Verifier 3626-3.29.22-VR PS 3 of 3 Medical Gas Services 918 S Horton St, Suite 917 Seattle. WA 98134 medsasservices.io (425) 894 5918 Medical Gas Outlet / Inlets Evaluation Worksheet Facility: Swedish - Edmonds Campus Job #: 3626 IDate: 3.29.22 Area Tested: Th Floor - Birthing Center I Verifier: AC Zone halve - r-1 None r-1 Not Reauired r-1 New 171 Existino Labeled As: 704, 705, 706 6 707 ZV Brand: Chemetron Gas 3 Part Valve DL Gauge Ga. PSI Act PSI Comments: OX ® Yes ❑ No ® Yes ❑ No 52 53.5 MA ® Yes ❑ No ® Yes ❑ No 48 51.6 VAC ® Yes ❑ No ® Yes ❑ No 20 20.51 Area Alarm - F1 None F1 Not Reauired F1 New N Existino Labeled As: Patient Rooms 704-707 Brand: Chemetron Gas PSI Set HI Set LO Sensor Comments: OX 52.4 60 40 DL MA 51.3 60 40 DL VAC 20.5 -- 12 DL UUtletS & Inlets - M New rA Existino Outlet / Inlets Brand: BeaconMedaes Location: Wall Quick Connect: Chemetron Area Room Door Gas Flow SCFM Delta Flow Conc. % Part.Comments: 704 VAC 4.5 >12 -- -- All New OX >8 <5 97.5 .000 OX I >8 <5 97.5 1 .000 VAC 4.5 >12 -- -- MA >8 <5 20.3 .000 DP: 13.5°F CO:Oppm CO2:442ppm 705 VAC 4.5 >12 -- -- All New OX >8 <5 97.5 .000 OX >8 <5 97.5 .000 VAC 4.5 >12 -- -- MA >8 <5 20.3 .000 706 VAC 4.5 >12 -- -- Existing OX >8 <5 97.5 .000 Existing OX >8 <5 97.5 .000 New VAC 4.5 >12 -- -- New MA >8 <5 20.3 .000 New 3626-3.29.22 Page 1 & 2 Medical Gas Services 918 S Horton St, Suite 917 Seattle, WA 98134 medgasserViceSJO (425) 894 5918 Supplemental Outlet / Inlets Evaluation Worksheet Facility: Swedish - Edmonds Campus Job #: 3626 Date: 3.29.22 Area Tested: Birthing Center Verifier: AC Outlets & Inlets - ® New ® Existing Outlet / Inlets Brand: BeaconMedaes Location: Wall Quick Connect: Chemetron Area Room Door Gas Flow SCFM Delta Flow Conc. Part. Comments: 707 OX >8 <5 97.5 .000 All existing VAC 4.5 >12 -- -- MA >8 <5 20.3 .000 OX >8 <5 97.5 .000 VAC 4.5 >12 -- -- 3626-3.29.22 Page 2 of 2