Loading...
FIR2021-0080+Calculations+7.28.2021_8.29.03_AM+2325450COLUMBIA FIRE 111 S. FINDLAY ST. SEATTLE, WA. 98108 HYDRAULIC CALCULATIONS FOR 76TH TOWNHOMES 7528 215TH ST. SW EDMONDS, WA. 98026 DRAWING NUMBER: C2106 DATE: 7/9/21 -DESIGN DATA - REMOTE AREA NUMBER: REMOTE AREA LOCATION: 3RD FLOOR BEDROOM OCCUPANCY CLASSIFICATION: NFPAI3D 2016' EDITION DENSITY: gpm/sq. ft. AREA OF APPLICATION: 2 HEADS sq. ft. COVERAGE PER SPRINKLER: 16'X16' sq. ft. TYPE OF SPRINKLERS CALCULATED: RESIDENTIAL PENDENT NUMBER OF SPRINKLERS CALCULATED: 2 HOSE -STREAM DEMAND: 0 gpm TOTAL WATER REQUIRED (INCLUDING HOSE): 26.0 gpm FLOW AND PRESSURE (AT BASE OF RISER): 26.0 gpm @ 28.7 psi TYPE OF SYSTEM: WET WATER SUPPLY Source: CITY MAIN Test Date: 7/7/21 Test By: MODELED BY CITY Location: Static: 74.02 psi Residual: 72.32 psi Flow: 1000 gpm Source Elevation Relative to Finished Flow Level: 0 ft. INSTALLING CONTRACTOR Name: COLUMBIA FIRE Address: 111 S. FINDLAY ST SEATTLE, WA. 98108 Phone: 206-232-8569 Certification number: COLUMFI952MG NAME OF DESIGNER: STEVE ADAMSON AUTHORITY HAVING JURISDICTION: EDMONDS F.M. NOTES: Calculations performed by HASS under license # 64623395 , granted by HRS SYSTEMS, INC. (Notes continue after pipe calculations results.) (Notes continue after pipe calculations results.) SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 7/9/2021 C:\Users\Steve Adamson\Documents\hassdata\C2106.sdf JOB TITLE: 76TH TOWNHOMES WATER SUPPLY ANALYSIS Static: 74.02 psi Resid: 72.32 psi Flow: 1000.0 gpm 1 70.0 60.0 G A U 50.0 G E p 40.0 R 2 E S 30.0 S U R 20.0 E .i ii ii .............. ii ....................... ii ii ............ ii i i .................... 11 111 loll III III Jill III III -14.7 LEGEND Available pressure 74.02 psi @ 26.0 gpm jRequired pressure 37.67 psi @ 26.0 gpm A. Source Supply Curve B. System Demand Curve 200300 400 500 600 700 800 900 1000 FLOW (GPM) Note: (1) Dashed Lines indicate extrapolated values from Test Results SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 7/9/2021 C:\Users\Steve Adamson\Documents\hassdata\C2106.sdf JOB TITLE: 76TH TOWNHOMES NFPA WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) 8 74.0 72.3 1000.0 74.0 26.0 37.7 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 26.0 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM OTHER HOSE STREAM ALLOWANCES 0.0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 26.0 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES (FT) (PSI) (GPM) 1 26.3 K= 4.79 7.4 13.0 2 26.3 K= 4.79 7.4 13.0 3 26.8 - - - - 8.1 - - - 4 26.8 - - - - 14.6 - - - 5 1.0 - - - - 28.7 - - - 6 0.0 - - - - 32.0 - - - 7 0.0 - - - - 35.0 - - - 8 0.0 SOURCE 37.7 26.0 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE: 7/9/2021 C:\Users\Steve Adamson\Documents\hassdata\C2106.sdf JOB TITLE: 76TH TOWNHOMES 141a19=0*am 071 W1 Pipe Tag K-fac Add F1 Add F1 To Fit: L C (Pt) Frm Node E1 (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) To Node E1 (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf) Pipe: 1 4.79 13.0 Disch 10.00 150 0.0 2 26.3 7.4 -11.5 1.000 E: 7.0 7.00 -0.0 1 26.3 7.4 1.5 1.101 17.00 0.001 0.0 Pipe: 2 4.79 13.0 Disch 26.50 150 0.7 3 26.8 8.1 -1.5 1.000 2T:12.0 12.00 -0.2 1 26.3 7.4 11.5 1.101 38.50 0.025 0.9 Pipe: 3 4.79 13.0 Disch 18.00 150 0.7 3 26.8 8.1 1.5 1 1.000 E: 7.0 7.00 -0.2 2 26.3 7.4 14.5 1.101 25.00 0.037 0.9 Pipe: 4 0.0 14.5 2 24.00 150 6.5 4 26.8 14.6 11.5 1 1.000 5E:35.0 35.00 -0.0 3 26.8 8.1 26.0 1.101 59.00 0.111 6.5 Pipe: 5 0.0 0.0 25.80 150 14.1 5 1.0 28.7 26.0 3 1.000 G: 0.4 0.40 11.2 4 26.8 14.6 26.0 1.101 26.20 0.111 2.9 Pipe: 6 0.0 0.0 117.00 150 3.3 6 0.0 32.0 26.0 4 1.250 4E:20.3 20.35 0.4 5 1.0 28.7 26.0 1.554 137.35 0.021 2.8 Pipe: 7 0.0 Fixed Pressure Loss Device 7 0.0 35.0 26.0 5 3.0 psi, 26.0 gpm 6 0.0 32.0 26.0 Pipe: 8 Source 0.0 8.00 150 2.7 8 0.0 37.7 26.0 6 1.000 T: 6.0 7.00 -0.0 7 0.0 35.0 26.0 0.995 G: 1.0 15.00 0.181 2.7 NOTES (HASS): (1) Calculations were performed by the HASS 2020 D computer program in accordance with NFPA13 (2016) under license no. 64623395 granted by HRS Systems, Inc. 208 Southside Square Petersburg, TN 37144 (931) 659-9760 (2) The system has been calculated to provide an average imbalance at each node of 0.001 gpm and a maximum imbalance at any node of 0.009 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 10.7 ft/sec at pipe 8. Notes SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE: 7/9/2021 C:\Users\Steve Adamson\Documents\hassdata\C2106.sdf JOB TITLE: 76TH TOWNHOMES (4) Items listed in bold print on the cover sheet are automatically transferred from the calculation report. (5) Available pressure at source node 8 under full flow conditions is 74.02 psi with a flow of 42.67 gpm. (6) PIPE FITTINGS TABLE HASS Pipe Table Name: standard.pip PAGE: F MATERIAL: CPVC HWC: 150 Diameter Equivalent Fitting Lengths in Feet (in) F E T R K C G F45 Ell Tee RunT Kplg ChkVly Gate 1.101 1.40 7.00 6.00 1.70 1.00 8.00 0.40 PAGE: K MATERIAL: CT-K HWC: 150 Diameter Equivalent Fitting Lengths in Feet (in) E T F R K C G N Ell Tee 45-Ell TeeRun Kouplg ChkVly GatVly NPTee 0.995 2.00 6.00 1.00 2.00 0.00 6.00 0.00 6.00 PAGE: * MATERIAL: S40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell -------------------------------------------------------- Tee LngEll ChkVly BfyVly GatVly A1mChk DPVly NPTee F F45Ell 1.554 3.37 6.73 1.68 7.57 5.05 0.84 8.42 8.42 6.73 1.68 Utility Report: Equivalent K-Factor Calculator Node Sprinkler Pres. Dia. Pipe Ftgs. Total H-W Equivalent Name K-Factor (psi) (in) Len.(ft) Len.(ft) coef. K-factor ----------------------------------------------------------------------- 1 4.90 7.00 1.101 0.50 T 6.83 120.00 4.79 y of I:n,y "� WATER AVAILABILITY CERTIFICATE PERMITTING & DEVELOPMENT ENGINEERING DIVISION 121 5th Avenue N P: 425.771.0220 www.edmondswa.aov ITEMS IN THIS BOX TO BE FILLED IN BY APPLICANT M Building Permit ❑ Preliminary Plat or PUD ® Subdivision ❑ Rezone or Other Applicant's name: Li G. Li Proposed Use: Fire Suppression System (for4-UnitTownhome Building) Location (attach map and legal description if necessary): 7528 215th St. SW Updated on 811412018 Pagel of 2 ITEMS IN THIS BOX TO BE FILLED IN BY EDMONDS DEVELOPMENT SERVICES DEPARTMENT Permit Number Project Name BLD2021-0020 76th Street Townhomes INFORMATION PROVIDED BY WATER AGENCY 1. N a. Water will be provided by service connection only to an existing iz-inch (size) water main that is adjacent to the site. OR ❑ b. Water service will require an improvement to the water system of: ❑ (i). feet of water main to reach the site; and/or ❑ (z). The construction of a distribution system on the site; and/or ❑ W. Other (describe): z. N a. The water system is in conformance with a City approved water comprehensive plan. OR ❑ b. The water system improvement will require a water comprehensive plan amendment. (This will cause a delay in permit issuance and approval.) I N a. The proposed project is within the corporate limits of the City, or has been granted Boundary Review board approval for extension of service outside the City, or is within the City approved service area of a private water purveyor. OR ❑ b. Annexation or Boundary Review Board approval will be necessary to provide service. q. N a. Water is/or will be available at the rate of flow and duration indicated below at no less than zo psi Measured at the nearest fire hydrant ioo feet from the building/property (or as marked on attached map) Rate of Flow Duration ❑ Lessthan 500 gpm. (approximately gpm) ❑ Less than one (i) hour ❑ 500 to 999 gpm ❑ One (1) to two (z) hours ❑ i5oo gpm or more N Two (2) hours or more ❑ Flow test of gpm ❑ Other N Calculation of 5182 gpm (Commercial building permits require flow test or calculation) OR ❑ b. Water will system is not capable of providing fire flow. WATER AGENCY CERTIFICATION COMMENTS/CONDITIONS: Per model Static Pressure is 74.02 Psi at i000 qpm, residual pressure is 72.12 Psi at max flow of 53.82 qpm, residual pressure is jo psi *All values generated usinci water model not to nearest hydrant I hereby certify that the above water purveyor information is true. This certification shall be valid for one year from date of signature. City of Edmonds Russell Lynch (Agency Name) Signatofy Printed Name Associate En ineer (Title) (Signs Kure/Date) Updated on 811412018 Page 2 of2