FIR2021-0080+Fire_Sprinkler_Equipment_Specification_Sheets+7.28.2021_8.29.21_AM+2325452Viking Plastics
Features
• Sizes Available (Nominal): 3/4" (DN20) through 3" (DN80) pipe diameters,
with a Standard Dimension Ratio (SDR) of 13.5 as specified in ASTM F442.
• Environmental Specifications: Indoor use only.
Maximum Ambient Temperature: 150°F (65°C)
• Hazen -Williams C Value: 150
BIazeMaste,-'11" CPVC Pipe
• Pressure Data: Working Pressure: 175 PSI (12.1 bar) at 150°F (65°C)
• Specifications: • Meets NFPA 13R and 13D standards for residential occupancies as well as
NFPA 13 standards for light hazard occupancies.
• Pipe meets or exceeds ASTM F442.
• Certified by NSF International for potable water services.
• CPVC pipe from Viking Plastics use compound cell class 23547
(demonstrated highest structural properties).
• cULus Listed, FM Approved, New York City (MEA) Approved, LPCB Approved.
CPVC PIPE PHYSICAL DATA
FM
SF
pPPCB
Nominal Pipe
Size
Actual Outside
Diameter
Average Inside
Diameter
*Weight per 15'
(4,6 m) length
Length
Approvals
Part Number
Inch
DN
Inch
mm
Inch
mm
Lb.
Kg.
Feet
M
3/4"
DN20
1.050
26,670
0.874
22,199
2.52
1,14
15
4.6
cU NSFFM
34PIPE
1"
DN25
1.315
33,401
1.101
27,965
3.93
1,78
15
4.6
1PIPE
1 1/4"
DN32
1.660
42,164
1.394
35,408
6.27
2,84
15
4.6
114PIPE
1 1/2"
DN40
1.900
48,260
1.598
40,589
8.22
3,73
15
4.6
112PIPE
2"
DN50
2.375
60,325
2.003
50,876
12.89
5,85
15
4.6
2PIPE
21/2"
DN65
2.875
73,000
2.423
61,500
18.86
8,55
15
4.6
212PIPE
3"
DN80
3.500
88,900
2.950
74,900
28.01
12,71
15
4.6
3PIPE
Nominal Pipe
Size
Actual Outside
Diameter
Average Inside
Diameter
*Weight per 10'
(3,05 m) length
Length
Approvals
Part Number
Inch
DN
Inch
mm
Inch
mm
Lb.
Kg.
Feet
M
3/4"
DN20
1.050
26,670
0.874
22,199
1.68
0,76
10
3,05
cU NSFFM
34PIPE10
1"
DN25
1.315
33,401
1.101
27,965
2.62
1,19
10
3,05
1PIPE10
1 1/4"
DN32
1.660
42,164
1.394
35,408
4.18
1,90
10
3,05
114PIPE10
1 1/2"
DN40
1.900
48,260
1.598
40,589
5.48
2,49
10
3,05
112PIPE10
2"
DN50
2.375
60,325
2.003
50,876
8.59
3,90
10
3,05
2PIPE10
21/2"
DN65
2.875
73,000
2.423
61,500
12.57
5,70
10
3,05
212PIPE10
3"
DN80
3.500
88,900
2.950
74,900
18.67
8,47
10
3,05
3PIPE10
NOTE: CPVC Pipe is produced in SDR 13.5 Dimensions in accordance with ASTM F442. Standard Dimension Ratio is the ratio of the outside pipe diameter to the wall thickness of the pipe.
Blazemaster® is a registered trademark of Lubrizol.
Specifications subject to change without notice
*Empty pipe weights
IMPORTANT. Installers should receive thorough hands-on training in the proper methods of assembly and installation of CPVC products
Trusted above all TM NIKJW*i(R)
Viking Plastid
CPVC Pipe Product Specifications
BIazeMastei-'11" CPVC Pipe
Corrosion resistant CPVC fire sprinkler pipe, when installed in strict accordance with the manufacturer's design and instal-
lation instructions, is UL and c-UL Listed by Underwriters Laboratories for use in the following:
• Meets NFPA 13R and 13D standards for residential occupancies as well as NFPA 13 standards for light hazard occupancies.
• Residential occupancies up to and including four stories in height as defined by NFPA 13R.
• Residential occupancies as defined in the Standard for Sprinkler Systems in One and Two Family Dwellings, NFPA 13D.
• Installation of private fire service mains and their appurtenances, NFPA 24.
CPVC fire sprinkler pipe from Viking Plastics shall be employed in wet pipe systems only and are not listed for outdoor use.
CPVC pipe must never be used in a system using compressed air or other gases.
CPVC pipe from Viking Plastics also carries the following
enhanced listings and approvals:
• According to UL Listing
• Can be flush at return air plenums
• Exposed system risers NFPA 13D, 13R
• Exposed basement NFPA 13D (solid wood joist)
• Extended coverage (exposed)
• 20' spacing on pendent in lieu of 15'
• 18' spacing on sidewall in lieu of 14'
• Use with combustible concealed sprinklers
• UL Listed attic sprinkler head (to protect the floor
below)
• UL Listed attic sprinkler head with wet system piping
(feed main and ridge installation)
New and enhanced listings and approvals are being pursued. Always
check with the appropriate Listing and Approval agency for details on
current listing parameters.
CPVC pipe meets all applicable standards for pressure rated applica-
tion as required in ANSI -NSF Standard 14 and complies with ANSI -NSF
Standard 61 for health effects and are marked with the NSF-pw end use
marking.
All CPVC fire sprinkler pipe shall be Listed by Underwriters Laboratories
for wet pipe systems, and shall carry a rated working pressure of 175 psi
@ 150°F (12 bar @ 65.5°C). *The FM Approval is limited to use in wet
pipe fire protection sprinkler systems for light hazard occupancies in both
concealed and exposed applications with certain restrictions.
Piping must always be installed in strict accordance to the manufacturer's
DESIGN AND INSTALLATION GUIDE, including product storage and
handling, joining methods, supporting and bracing, expansion and con-
traction allowance and testing, etc. National Fire Protection Association
(NFPA) Standards 13, 13D, and 13R must be referenced for design and
installation requirements in conjunction with the installation instructions.
• Exposed sidewall sprinkler listing for exposed pipe & fittings
• 24' extended coverage sidewall sprinkler, 12" drop, 155T
sprinkler head
• 18' extended coverage sidewall sprinkler, 12" drop, 165T
sprinkler head
• 16' extended coverage sidewall sprinkler, 12" drop, 175T
sprinkler head
• 14' standard coverage sidewall sprinkler, 12" drop, 200T
sprinkler head
Factory Mutual Approved*
• Factory Mutual Approval exposed
• Factory Mutual Approval above drop -in ceilings
• Factory Mutual Approval exposed w/Soffi-Steel soffiting
covering system
All CPVC fire sprinkler pipe from Viking Plastics is manufactured in the
USA. All CPVC pipe shall be packaged immediately after its manufacture
to prevent damage and shall be stored indoors after production, at the
manufacturing site, until shipped from the factory. The pipe shall bear the
logo of the listing agencies, and shall carry the National Sanitation Foun-
dation (NSF) seal of approval for potable water applications.
CPVC products are intended for use in areas where the maximum ambi-
ent temperature does not exceed 150°F (65.5°C). If the ambient tempera-
ture is expected to exceed this limitation, refer to the manufacturer's DE-
SIGN AND INSTALLATION GUIDE for additional information on methods
to reduce the pipe exposure temperatures. CPVC pipe is not intended to
be installed in outdoor applications. CPVC pipe is intended to be used in
wet pipe systems only and have not been investigated for use in dry pipe
systems. Special installation and design criteria relative to pipe hanger
spacings, piping and sprinkler restraint, sprinkler temperature rating,
piping locations, testing procedures and friction loss characteristics are
specified in the manufacturer's installation instructions provided with the
pipe. The manufacturer's installation instructions should be reviewed and
the Authority Having Jurisdiction consulted before installation.
Trusted above all TM NIKJW*iCR)
Sprinkler Head Adapters
BRASTICTm Adapter
Straight
Tee
Size (inches)
Part Number
Box Qty
with metal thread insert
3/4x1/2
V5003SBT-101
100
1 x 1/2
V50035BT-130
50
1 x 3/4
V50035BT-131
50
900 Elbow
3/4x1/2
V50073SBT-101
100
1 x 1/2
V50073SBT-130
50
1 x 3/4
V50073SBT-131
50
Tee
1 x 1 x 1 V50073SBT-101
1 x 1 x 1/2 V50073SBT-130
1 x 1 x 3/4 V50073SBT-131
* Brass starter thread molded into plastic,
virtually eliminating cross -threading.
50
50
50
Female Adapter
3/4 x 1/2
V5003SBI-101
100
with metal thread insert
1 x 1/2
V5003SBI-130
50
1 x 3/4
V5003SBI-131
10
Spigot Female Adapter
3/4x 1/2
V50032SBI-101
100
with metal thread insert
1 x 1/2
V50032SBI-130
50
Sprinkler Head 90
1 3/4x 1/2
I V50073SBI-101
100
with metal thread insert
1 x 1/2
1 x 3/4
I V50073561-130
I V50073SBI-131
50
10
1-1/4x1/2
I V50073SBI-166
5
do
Size (inches)
1x1x1
3/4 x 3/4 x 1/2
1x1x1/2
1-1/4x 1-1/4x 1/2
1-1/2 x 1-1/2 x 1/2
2x2x1/2
1 x 3/4 x 1/2
1-1/4x 1 x 1/2
1-1/2x 1-1/4x 1/2
2x1-1/2x1/2
Part Number
V5012SBI-010
V5012SBI-101
V5012SBI-130
V5012SBI-166
V5012SBI-209
V5012SBI-247
V5012RSBI-124
V5012RSBI-156
V5012RSBI-199
V5012RSBI-237
Back to Back Cross 1xlx1/2x1/2(1-1/8) V50353SBIS-130
with metal thread insert
1x1x12x1/2(t-5n6) V50353SBIL-130
in
Box Qty
50
10
50
5
5
2
10
5
5
2
20
1
Back to Back Tee 1 /2 x i/2 x 1 (t-va)V501133SBIS-075 30
with metal thread insert
1/2x1/2x1 (1-sne) V501133561L-075 30
4W
Trusted above aII.T" V�KING�
CPVC Standard Fittings
Tee
Size (inches)
Part Number Box Qty
Reducing Tee
Size (inches)
Part Number
Box Qty
3/4
V5011-007
250
I 3/4 x 3/4 x 1
_ V5011 R-102
10
4%
1
V5011-010
100
1 x 3/4 x 3/4
V5011 R-125
100
1-1/4
V5011-012
25
1 x 3/4 x 1 I
V5011 R-126
10
1-1/2
V5011-015
25
1 x 1 x 3/4 I
V5011 R-131
100
2
V5011-020
2
1-1 /4 x 1 x 3/4 I
V5011 R-157
5
2-1/2
V5011-025
1
1-1 /4 x 1 x 1 I
V5011 R-158
25
3
V5011-030
1
1-1Ax1x1-1A
V5011R-159
5
_
1-1/4 x 1-1/4 x 3/4
V5011R-167
25
900Elbow
1-1/4 x 1-1/4 x 1
V5011R-168
25
3/4
V5007-007
250
1-1/4x1-1/4x1-1/2
V5011R-169
5
1
V5007-010
100
11-1/2x1-1/4x3/4
V5011R-201
5
1-1/4
V5007-012
25
I 1-1/2 x 1-1/4 x 1
V5011R-202
5
1-1/2
V5007-015
25
1-1/2 x 1-1/2 x 3/4
V5011 R-210
25
2
V5007-020
2
1-1/2 x 1-1/2 x 1
V5011R-211
25
1/2
V5007-025
1
1-1/2x1-1/2x1-1/4
V5011R-212
5
3
E12
V5007-030
1
1-1/2 x 1-1/2 x 2
V5011 R-213
5
x 3/4
V5007R-131
100
2 x 2 x 3/4
V5011 R-248
2
2 x 2 x 1
V5011 R-249
10
450 Elbow
3/4
_
V5006-007
250
2 x 2 x 1-1/4
V5011 R-250
2
1
V5006-010
100
2 x 2 x 1-1/2
V5011 R-251
2
1-1/4
V5006-012
5
2-1/2 x 2-1/2 x 1
V5011 R-289
1
1-1/2
V5006-015 5
2-1/2x2-1/2x1-1/4
V5011R-290
1
2
V5006-020
2
2-1/2 x2-1/2 x 1-1/2
V5011R-291
1
2-1/2
V5006-025
1
2-1/2 x 2-1/2 x 2
V5011 R-292
1
3
V5006-030
1
3 x 3 x 1-1/2
V5011 R-337
1
3 x 2
V5011 R-338
1
Cross
3/4
V5035-007
10
3 x 2-1/2
V5011 R-339
1
1
V5035-010
100
1-1/4
V5035-012
5
Bushing
1 x3/4
V5018-131
100
1-1/2
V5035-015
20
1-1 /4 x 3/4
V5018-167
25
2
V5035-020
1
1-1Ax1
V5018-168
25
2-1/2
V5035-025
1
1-1/2 x 3/4
V5018-210
5
1 x 1 x 3/4 x 3/4
V5035R-131J_
10
1-1/2 x 1
V5018-211
25
1-1/2x1-1/4
V5018-212
25
Coupling
3/4
V5001-007
250
2 x 3/4
V5018-248
2
1
V5001-01
100
2 x 1
V5018249
2
1-1/4
V5001-012
25
2 x 1-1/4
V5018-250
2
1-1/2
V5001-015
25
2 x 1-1/2
V5018 251
2
2
V5001-020
10
2-1/2x1
V5018-289
15
2-1/2
V5001-025
1
2-1/2 x 1-1/4
V5018-290
1
3
V5001-030
1
2-1/2 x 1-1 /2
V5018-291
1
2-1/2 x 2
V5018-292
1
Reduced Coupling
3 x 1-1/2
V5018-337
15
1 x3/4
V5001R-131
10
3 x 2
V5018-338
1
i 1-1 /4 x 1
V5001 R-168
5
3 x 2-1/2
V5018-339
1
#'
1-1/2 x 3/4
V5001 R-210
5
1-1/2x1
V5001R-211
5
1-1/2x1-1A
V5001R-212
5
Cap
3/4
V5017-007
250
2 x 1
V5001 R-249
2
1
V5017-010
100
2x1-1/2
V5001R-251
2
1-1/4
V5017-012�
5
1-1/2
V5017-015
5
2
V5017-020
2
2-1/2
V5017-025
1
3
V5017-030
1
May 2014
CPVC Pipe
Size(inches) 11 Part Number 11 Box Qty
3/4
34PIPE
240
1 1
1PIPE
180
1-1/4
114PIPE
105
*l� 1-1/2
112PIPE
75
y 2
_
2PIPE _
60
2-1/2
212PIPE _
30
1 3
3PIPE
15
CPVC Transition Fittings
Female Adapter N Size (inches) �I Part Number Box Qty Grooved Coupling Size (inches) Part Number Box Qty
with metal thread insert Adapter
3/4 V5003BI-007 10 1-1/4 _V5001G-012 30 J
1 V5003B1-010 50 1-1/2 _V5001G-015 25 J
1-1/4 V5003B1-012 5 2 _V5001G-020 15 J
1-1/2 V5003BI-015 5 2-1/2 V5001G-025 4
2 V5003BI-020 2 3 V5001G-030 2
Spigot Female Adapter 3/4 V50032BI-007 250 Standard Union 3/4 _I V5033E-007 I 1
with metal thread insert
1 V5003261-010 100 � 1 _I V5033E-010 I 1
Male Adapter 3/4 V5004BI-007 10
with metal thread insert
1 V5004BI-010 10
1-1/4 V5004BI-012 5
1-1/2 V5004BI-015 5
2 V5004BI-020 2
Accessories
Solvent Cement Size (inches) Part Number Box Qty Dauber Size (inches) Part Number Box Qty
Quart V5097Q 12 � Small V5093-5 100
Pint V5097P 12 Large V5093-L 100
Test Plug 1/2 V450-005 50 Roller N/A V5097 24
Brush N/A V5096 12
May 2014
Recommended Installation Practices and Precautions for Freedom® CPVC Systems
E
Dos MRW
• Install product according to the manufacturer's instructions.
• Follow recommended safe work practices.
• Make certain that thread sealants, gasket lubricants, or fire stop materials are
compatible with BlazeMaster® CPVC.
• Use only latex -based paints if painting is desired.
• Keep pipe and fittings in original packaging until needed.
• Cover pipe and fittings with an opaque tarp if stored outdoors.
• Follow proper handling procedures.
• Use tools designed for use with plastic pipe and fittings.
• Use proper solvent cement and follow application instructions.
• Use a drop cloth to protect interior finishes.
• Cut the pipe ends square.
• Deburr and bevel the pipe end before solvent cementing.
• When solvent cementing, rotate the pipe 1/4 turn when bottoming pipe in
fitting socket.
• Always apply solvent cement to the pipe first then fitting.
• Avoid puddling of solvent cement in fittings and pipe.
• Make certain that solvent cement does not run and plug the sprinkler
head orifice.
• Follow the manufacturer's recommended cure times prior to pressure testing.
• Fill lines slowly and bleed the air from the system prior to pressure testing.
• Support sprinkler head properly to prevent lift up of the head through the
ceiling when activated.
• Keep threaded rod within 1/16"of the pipe.
• Install BlazeMaster CPVC pipe and fittings in wet systems only or specially
listed dry systems.
• Follow manufacturer'hs recommendations for freeze protection.
• Allow for movement due to expansion and contraction.
• Renew your BlazeMaster CPVC pipe and fittings installation training every
two years.
• Follow manufacturer's recommendations on pressure testing.
• Follow current NFPA standards for use of antifreeze solutions.
Blazemaster® is a registered trademark of Lubrizol
Teflon® is a registered trademark of E. I. du Pont de Nemours and Company
Crisco® is a registered trademark of the J.M. Smucker Company
Regional Headquarters
Don'ts Iff
Do not use petroleum or solvent -based paints, sealants, lubricants or fire
stop materials.
• Do not use any glycol -based solutions as an anti -freeze.
• Do not use both Teflon® tape and thread sealants simultaneously.
• Do not use solvent cement that exceeds its shelf life or has become
discolored or gelled.
• Do not allow solvent cement to plug the sprinkler head orifice.
• Do not connect rigid metal couplers to BlazeMaster® CPVC grooved adapters.
• Do not thread BlazeMaster CPVC pipe.
• Do not use solvent cement near sources of heat, open flame, or
when smoking.
• Do not pressure test until recommended cure times are met.
• Do not use dull or broken cutting tool blades when cutting pipe.
• Do not use BlazeMaster CPVC pipe that has been stored outdoors
unprotected and is faded in color.
• Do not allow threaded rod to come in contact with the pipe.
• Do not install BlazeMaster CPVC pipe in cold weather without allowing
for expansion.
• Do not install BlazeMaster CPVC pipe and fittings in dry systems, unless
specifically Listed for such use.
• Do not use ratchet cutters below 50•F.
• Do not use edible oils such as Crisco® as a gasket lubricant.
• Do not install tape, insulated wire, or cable in direct contact with BlazeMaster
CPVC pipe.
Note:This list does not constitute as a complete installation guide.
Viking SupplyNet - U.S. East Viking SupplyNet - U.S. Midwest Viking SupplyNet - U.S. West
4B Cranberry Rd 2353 International St 9101 Sorensen Ave.
Parsippany, NJ 07054 Columbus, OH 43228 Santa Fe Springs, CA 90670
Phone: 800-845-4645 Phone: 800-926-7757 Phone: 800-366-1727
Fax: 269-818-1639 Fax: 614-527-5818 Fax: 562-944-1058
Viking SupplyNet - U.S. South Viking SupplyNet - Latin America Viking SupplyNet - Canada
100 Piedmont Court, Suite A 2840 SW 42nd St, Port 95 Ind Ctr Blg IV 325 Vaughan Valley Blvd.
Doraville, GA 30340 Hollywood, FL 33312 Woodbridge, Ontario L4H 3135
Phone:800-234-2443 Phone:954-791-1756 Phone:905-856-3557
Fax: 770-446-3713 Fax: 954-791-1614 Fax: 905-856-3558
WARNING: Cancer and Reproductive Harm-
www.P65 Warnings.ca.gov
May 2014
Viking 1 210 N Industrial Park Drive, Hastings, MI 49058,Telephone: (269) 945-9501, Facsimile: (269) 945-9599 1 www.vikinggroupinc.com MKT-1089
Page 1 of 5
FREEDOM° RESIDENTIAL
CONCEALED PENDENT
SPRINKLER VK494 (K4.9)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
1. DESCRIPTION
Viking Freedom") Residential Concealed Pendent Sprinkler VK494 is a small
thermosensitive, glass -bulb residential sprinkler designed for installation on concealed
pipe systems where the appearance of a smooth ceiling is desired. The orifice design,
with a K-Factor of 4.9 (70.6 metric*), allows the sprinkler's efficient use of available
water supplies for the hydraulically designed fire -protection system. The fast
response glass bulb operating element and special deflector characteristics meet
the challenges of residential sprinkler standards.
The sprinkler is pre -assembled with a threaded adapter for installation with a
low -profile small -diameter cover assembly installed flush to the ceiling. The two-
piece design allows installation and testing of the sprinkler prior to installation
of the cover plate. The "push -on", "thread -off' design of the concealed cover
plate assembly allows easy installation of the cover plate after the system has
been tested and the ceiling finish has been applied, while also providing up to
1/2" (13 mm) of vertical adjustment. The cover assembly can be removed and
reinstalled, allowing temporary removal of ceiling panels without taking the sprinkler
system out of service or removing the sprinkler. The Electroless Nickel PTFE (ENT)
coating has been investigated for installation in corrosive atmospheres and is C-UL-
US-EU Listed as corrosion resistant as indicated in the Approval Charts. The ENT
finish is only available for the sprinkler assembly, the cover plate is not plated.
2. LISTINGS AND APPROVALS
e@us UL Listed (C-UL-US-EU): Category VKKW
eu Refer to the Approval Charts and Design Criteria on for C-UL-US-EU Listing
requirements that must be followed.
TECHNICAL DATA
Specifications:
Minimum Operating Pressure: Refer to the Approval Chart.
Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to 500
psi (34.5 bar).
Thread size: 1/2" (15 mm) NPT
Nominal K-Factor: 4.9 U.S. (70.6 metric*)
Glass -bulb fluid temperature rated to -65 °F (-55 °C)
* Metric K-factor measurement shown is in Bar. When pressure is measured in kPa, divide the metric
K-factor shown by 10.0.
Material Standards:
Sprinkler Body: Brass UNS-C84400 or QM Brass
Deflector: Phosphor Bronze UNS-051000
Deflector Pins: Stainless Steel UNS-S30200
Button: Brass UNS-C36000
Pip Cap and Insert Assembly: Copper UNS-C11000 and SS UNS-S30400
Compression Screw: 18-8 Stainless Steel
Yoke: UNS-S43000 Stainless Steel or Phosphor Bronze UNS-051000
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Cover Adapter: Cold Rolled Steel UNS-G10080, Finish: Clear Chromate over Zinc Plating
Shipping Cap: Polyethylene
Cover Plate Materials:
Cover Plate Assembly: Copper UNS-C11000 and Brass UNS-C26800
Spring: Beryllium Nickel
Solder: Eutectic
Ordering Information: (Also refer to the current Viking price list.)
Viking Freedom° Residential Concealed Pendent Sprinkler VK494 and Cover Plate Assembly must be ordered separately:
Sprinkler: Order Sprinkler VK494 by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the
temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A and ENT = JN
Temperature Suffix: 155 °F (68 °C) = B, 200 °F (93 °C) = E
For example, sprinkler VK494 with a Brass finish and a 200 °F (93 °C) temperature rating = Part No. 20759AE.
Cover Plate Assembly: Base Part No. 13504 (2-3/4" diameter), Base Part No. 13642 (3-5/16" diameter), or Base Part No. 15394
(square cover plate, 3-5/16" diameter)
Form No. F_012116 17.04.20 Rev 17.2 Replaces Form No. F_012116 Rev 17.1
(added alt. material for yoke)
Page 2 of 5
FREEDOM° RESIDENTIAL
CONCEALED PENDENT
SPRINKLER VK494 (K4.9)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Specify finish and temperature rating of the cover plate assembly by adding the appropriate suffixes for the finish and the cover
temperature rating to the base part number:
Finish Suffix: Polished Chrome = F, Brushed Chrome = F-/B, Bright Brass = B, Antique Brass = B-/A, Brushed Brass = B-/B, Brushed
Copper = E-/B, Painted White = M-/W, Painted Ivory = MA, Painted Black = M-/B
Temperature Suffix: 135 °F/57 °C = A
For example, cover 13504 with a Polished Chrome finish and a 135 °F/57 °C temperature rating = 13504FA.
Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the Viking website.)
Sprinkler Wrenches":
A. Heavy Duty Part No. 14047W/B** (available since 2006), or
B. Head Cabinet Wrench Part No. 14031 *** (available since 2006)
C. Optional Concealed Cover Plate Installer Tool Part No. 14412 (available since 2007)
D. Optional Large Concealed Cover Plate Installer Tool Part No. 14867 (available since 2007)
**Requires a ''/2' ratchet (not available from Viking). ***Also optional for removal of the protective cap. Ideal for sprinkler cabinets.
Sprinkler Cabinet: Part No. 01731A (available since 1971)
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches,
releasing the deflector. Continued heating of the exposed sprinkler causes the heat -sensitive liquid in the glass bulb to expand,
causing the glass to shatter, releasing the yoke and pip cap and sealing spring assembly.. Water flowing through the sprinkler
orifice strikes the deflector, forming a uniform spray pattern over a specific area of coverage determined by the water supply pres-
sure at the sprinkler to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
Viking Sprinkler Model VK494 is available through a network of domestic and international distributors. See The Viking Corporation
web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
TABLE
1: AVAILABLE SPRINKLER
TEMPERATURE
RATINGS
AND FINISHES
Sprinkler
Sprinkler
Maximum
Temperature Rating
Cover
Large Square
Temperature
Nominal
Ambient
of the Cover
Plate
Cover Plate Cover Plate
Bulb Color
Classification
Temperature
Ceiling
Assembly
Base Part
Base Part Base Part
Rating'
Temperature2
(Required)'
Number°
Number° Number°
Ordinary
155 °F (68 °C)
100 °F (38 °C)
135 °F (57 °C)
13504
13642
15394
Red
Intermediate
200 °F (93 °C)
150 °F (65 °C)
135 °F (57 °C)
13504
13642
15394
Green
Sprinkler Finishes:
Brass and
ENT
Cover Plate Finishes: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted
White, Painted Ivory, or Painted Black
Corrosion Resistant Coatings5: ENT
Footnotes
The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
Jurisdiction. Refer to specific installation standards.
Maximum ambient temperature for cover assembly is 100 °F (38 °C).
° Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These tests cannot and
do not represent all possible corrosive environments. Prior to installation, verify through the end -user that the coatings are compatible with or suitable for the proposed
environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway. For ENT coated sprinklers, the Belleville spring
is exposed.
Form No. F_012116 17.04.20 Rev 17.2
Page 3 of 5
FREEDOM° RESIDENTIAL
CONCEALED PENDENT
SPRINKLER VK494 (K4.9)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Approval Chart
Viking VK494, 4.9 K-Factor Residential Concealed Pendent Sprinkler
For systems designed to NFPA 13D or NFPA 13R. For systems designed to NFPA 13, refer to the design criteria. For Ceiling types refer to
current editions of NFPA 13, 13R or 13D
Sprinkler Base
NPT Thread Size
Nominal K-Factor
Maximum Water Wor-
Part Number 1
SIN
king Pressure
Inches
mm
U.S.
metric 2
20759
VK494
1/2
15
4.9
70.6
175 psi (12 bar)
Max. Coverage
6
Flow
GPM
Pressure
Listings and
Minimum
Area
(LPM)
PSI(bar)
Deflector to
Installation
Approvals3,s
Spacing
Ceiling
Type
Ft.
155 °F (68 °C), 200 °F (93 °C) Temperature
` p °S
Ft. X Ft.
(m)
(m X m)
Rated Sprinklers
Eo
12 X 12
13
7.0
(3.7 X 3.7)
(49.2)
(0.48)
14 X 14
13
7.0
(4.3 X 4.3)
(49.2)
(0.48)
Refer to Figure 2
Concealed with
Cover Plate
See Footnotes 7,10, & 11
8
16 X 16
13
7.0
(4.9 X 4.9)
(49.2)
(0.48)
Assembly.
See Footnote 9.
(2.4)
18 X 18
17
12.0
(5.5 X 5.5)
(64.4)
(0.83)
20 X 20
20
16.7
(6.1 X 6.1)
(75.7)
(1.15)
Footnotes
Part number shown is the base part number. For complete part number, refer to current Viking price schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals.
Refer also to Design Criteria.
4 Listed by Underwriter's Laboratories, Inc. for use in the U.S., Canada, and European Union.
5 Meets New York City requirements, effective July 1, 2008.
6 For areas of coverage smaller than shown, use the "Flow' and "Pressure" for the next larger area listed. Flows and pressures listed are per sprinkler. The distance from
sprinklers to walls shall not exceed one-half the sprinkler spacing indicated for the minimum "Flow' and "Pressure" used.
Cover Temperature Rating is 135 °F (57 °C). Cover Part No. 135041, 136421 (large diameter), or 15394' (square cover plate).
9 Other paint colors are available on request with the same listings as the standard finish colors. Listings and approvals apply for any paint manufacturer. Contact Viking
for additional information. Custom colors are indicated on a label inside the cover assembly. Refer to Figure 3.
0 Accepted Cover Plate Finishes are: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted Ivory, or
Painted Black 1.
" C-UL-US-EU Listed as corrosion resistant - Electroless Nickel PTFE (ENT)
Form No. F_012116 17.04.20 Rev 17.2
Page 4 of 5
FREEDOM° RESIDENTIAL
CONCEALED PENDENT
SPRINKLER VK494 (K4.9)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
DESIGN CRITERIA
(Also refer to the Approval Chart on page 3.)
UL Listing Reguirements (C-UL-US-EU):
When using Viking Residential Concealed Pendent Sprinkler VK494 for systems designed to NFPA 13D or NFPA 13R, apply the listed areas of cover-
age and minimum water supply requirements shown in the Approval Chart.
For systems designed to NFPA 13: The number of design sprinklers is to be the four contiguous most hydraulically demanding sprinklers. The minimum
required discharge from each of the four sprinklers is to be the greater of the following:
• The flow rates given in the Approval Chart for NFPA 13D and NFPA 13R applications for each listed area of coverage, or
• Calculated based on a minimum discharge of 0.1 gpm/sq. ft. over the "design area" in accordance with sections 8.5.2.1 or 8.6.2.1.2 of NFPA 13.
• Minimum distance between residential sprinklers: 8 ft. (2.4 m).
NOTE: Concealed sprinklers must be installed in neutral or negative pressure plenums only.
IMPORTANT. Always refer to Bulletin Form No. F 080415 - Best Practices for Residential Sprinkler Handling and Installation.
Also refer to Form No. F 080614 for general care, installation, and maintenance information. Viking sprinklers are to be in-
stalled in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA and any other similar
Authorities Having Jurisdiction, and also with the provisions of governmental codes, ordinances, and standards, whenever
applicable. Final approval and acceptance of all residential sprinkler installations must be obtained from the Authorities
Having Jurisdiction.
Sprinkler and Adapter Assembly
• Protective cap removed
• Use wrench 14047W/B**
Sprinkler Wrench
Part No. 14047W/B**
Step 1:
Carefully slide the
wrench sideways around
the deflector and pins
NEVER install the sprinkler by applying the installation
wrench across the frame arms. DO NOT overtighten.
Use only the designated sprinkler wrenches, Viking
Part Numbers 14047W/B** or 14031**. A leak tight seal
should be achieved by turning the sprinkler clockwise
1 to 1-1/2 turns beyond finger tight.
2-1/4" (57 mm)
diameter opening
required in the
ceiling.
Step 2: 1 1
Carefully press the wrench upward and
turn slightly to ensure engagement with
the sprinkler wrench flats.
Sprinkler
wrench flat
Figure 1: Sprinkler Installation and Proper Wrench Usage
** A 1/2" ratchet is required (Not available from Viking)
Sprinkler
frame arms
Form No. F_012116 17.04.20 Rev 17.2
Page 5 of 5
FREEDOM° RESIDENTIAL
CONCEALED PENDENT
SPRINKLER VK494 (K4.9)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
1/2" (15 mm) NPT
E
N co
S
2-9/16" (65 mm)
Maximum
NOTE: Upon sprinkler activation, the deflector descends
to approximately 13116" (21 mm) below the sprinkler body.
2-1/16" (52 mm)
Minimum
Figure 2: Sprinkler Dimensions and Cover Installation
QQ�\�--p C USTO�A
a �2
O C)
v� O
VIKING0.
All custom color painted cover plates will have an
identifying label affixed to the inside of the cover that
indicates the custom color and will have a representative
sample (a paint dot) of the paint on the label.
Figure 3: Identification of Custom Paint for Concealed Covers
2-3/4" (70 mm) or
3-5/16" (84 mm)
- -1 - \- . .... .,
Figure 4: Square Cover Assembly 15394
Form No. F_012116 17.04.20 Rev 17.2
Replaces Form No. F_012116 Rev 17.1
(added alt. material for yoke)
Page 1 of 8
® QUICK RESPONSE
DRY HORIZONTAL
N4 I KJ SIDEWALL SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
1. DESCRIPTION
Viking Quick Response Dry Horizontal Sidewall Sprinklers are thermosensitive
spray sprinklers suitable for use in areas subject to freezing. The sprinklers are
designed for dry systems and preaction systems where it is necessary to prevent
water or condensation from entering the drop nipple before sprinkler operation.
They may also be installed in spaces subject to freezing and supplied from a wet
system in an adjacent heated area.
Viking Quick Response Dry HSW Sprinklers are available in various finishes
and temperature ratings to meet design requirements. The special Polyester and AL
Electroless Nickel PTFE (ENT) coatings have been investigated for installation
in corrosive atmospheres and are listed/approved as corrosion resistant as indi-
cated in the Approval Charts. (Note: FM Global has no approval classification for
Polyester coatings as corrosion resistant.)
2. LISTINGS AND APPROVALS
cULus Listed: Category VNIV
FM Approved: Classes 2013 and 2015 For Light Hazard Occupancies Only
M, NYC Approved: MEA 89-92-E, Volume 15
Refer to Approval Charts and Design Criteria for Listing and Approval that must be followed.
3. TECHNICAL DATA
Specifications:
Available since 1993. WARNING: Cancer and Reproductive Harm -
Minimum Operating Pressure: 7 psi (0.5 bar) Zt www.P65Warnings.ca.gov
Maximum Working Pressure: 175 psi (12 bar).
Factory tested hydrostatically to 500 psi (34.5 bar)
Thread size: 1" NPT or 25 mm BSPT
Nominal K-Factor: 5.6 U.S. (80.6 metric') for all listed and approved lengths.
Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
Glass -bulb fluid temperature rated to -65 °F (-55 °C)
Covered by the following U.S. Patent numbers: 8,636,075 and 8,376,060 and 10,220,231
Material Standards:
Frame Casting: Brass UNS-C84400
Deflector: Phosphor Bronze UNS-051000
Bulb: Glass, nominal 3 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Compression Screw: Brass UNS-C36000
Pip Cap: Brass UNS-C31400 or UNS-C31600
Pip Cap Adapter: Brass UNS-C36000
Orifice: Copper UNS-C22000 or UNS-C11000
Tube: ERW Hydraulic Steel Tube
Support (Internal): Stainless Steel UNS-S30400
Barrel: Steel Pipe UNS-G10260, Electrodeposited Epoxy Base finish
Barrel End and Threads: QM Brass
Sleeve (for Adjustable Standard style only): Brass UNS-C26000 or UNS-C26800
Escutcheon Materials:
Adjustable Standard Dry Escutcheons: Brass UNS-C26000 or UNS-C26800
Recessed Dry Escutcheons: Cold Rolled Steel UNS-G10080
ENT Coated Adjustable and Recessed Escutcheons: Stainless Steel UNS-S30400
Ordering Information: (Also refer to the current Viking price list.)
Order QR Dry HSW Sprinklers by first adding the appropriate suffix for the sprinkler finish, the appropriate suffix for the temperature rating,
and then the suffix for the length ("A" dimension) to sprinkler base part number. Order in a specific length noted as the "A" dimension. The
"A" dimension is the distance from the face of the fitting (tee) to the desired finished surface of the wall in which it is to be installed.
These sprinklers are listed and approved in lengths from 1-1/2" to 45-1/2" (38.1 mm to 1,156 mm) for the adjustable standard style, 3" to
47" (76.2 mm to 1,194 mm) for the plain barrel style, and 3-1/4" to 47-1/2" (82.5 mm to 1,207 mm) for the adjustable recessed style.
Lengths exceeding the standard lengths are available, with no approvals, on a "made -to -order" basis: Recessed Dry HSW up to 65-
1/2" (1,664 mm). Adjustable Standard Dry HSW up to 63-1/2" (1,613 mm). Plain Barrel Dry HSW up to 65" (1,651 mm). Contact
the manufacturer for more information.
Finish Suffix: Brass = A, Chrome = F, White Polyester = M-NV, and ENT = JN
Form No. F_031993 20.04.16 Rev 20.1
Replaces Form No. F_031993 Rev 19.2
(Removed cover 15610.)
Page 2 of 8
® QUICK RESPONSE
DRY HORIZONTAL
N4 I KJ SIDEWALL SPRINKLERS
4
P
6
7
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
Temperature Suffix: 155 °F (68 °C) = B, 175 °F (79 °C) = D, 200 °F (93 °C) = E, 286 °F (141 °C) = G
Escutcheon Suffix = Y for the adj. recessed sprinkler with the Model G-1 Escutcheon (no suffix needed for the Model E-1 Escutcheon).
For example, sprinkler VK182 with 1" NPT Threads, a Chrome finish, a 155
°F (68 °C) temperature rating, the Model G-1 Escutcheon, and "A" length
of 10" = Part No. 08386UFBY10.
Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the "Sprinkler Accessories" section.)
Sprinkler Wrenches:
A. Standard Wrench: Part No. 07297W/B (available since 1991)
B. Wrench for recessed sprinklers: Part No. 07565W/B** (available since 1991)
**A'/i' ratchet is required (not available from Viking).
Replacement Escutcheons:
A. Adjustable Standard Dry Escutcheon: Base Part No. 08086F
B. Model E-1 Recessed Dry Escutcheon Cup: Base Part No. 05459A
C. Model G-1 Recessed Dry Escutcheon Cup: Base Part No. 20133
INSTALLATION
Refer to appropriate NFPA Installation Standards.
OPERATION
During fire conditions, the heat -sensitive liquid in the glass bulb expands,
causing the glass to shatter, releasing the internal parts to open the water-
way. Water flowing through the sprinkler orifice strikes the sprinkler deflector,
forming a uniform spray pattern to extinguish or control the fire.
Sprinkler s eo s Jeways
clarltyCRef�r rjure : r-/
correct defector orlentatlonJ
INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. Figure 1:
AVAILABILITY Standard Sprinkler Wrench 07297W/B
The Viking Quick Response Dry Horizontal Sidewall Sprinkler is available through a network of domestic and international distribu-
tors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE
RATINGS AND FINISHES
Sprinkler Temperature Sprinkler Nominal
Maximum Ambient
Bulb Color
Classification Temperature Rating'
CeilingTemperature2
Ordinary
155 °F (68 °C)
100 °F (38 °C)
Red
Intermediate
175 °F (79 °C)
150 °F (65 °C)
Yellow
Intermediate
200 °F 93 °C
150 °F 65 °C
Green
High
286 °F 141 °C
225 °F 107 °C
Blue
Sprinkler Finishes: Brass, Chrome, White Polyester, and ENT
Corrosion -Resistant Coating3,4: White Polyester and ENT in all temperature ratings
Footnotes
' The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
3 The corrosion -resistant Polyester and ENT coatings have passed the standard corrosion test required by the approving agencies indi-
cated in the Approval Charts. These tests cannot and do not represent all possible corrosive environments. Note: These coatings are
NOT corrosion proof. Prior to installation, verify through the end -user that the coatings are compatible with or suitable for the proposed
environment. Polyester and ENT coatings are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers
with Polyester and ENT coatings.
" When installed in some corrosive environments, the Polyester finish may change color. This natural discoloration over time is not in itself
an indication of corrosion and should not be treated as such. All sprinklers installed in corrosive environments should be replaced or
tested as described in NFPA 25 on a more frequent basis.
Form No. F_031993 20.04.16 Rev 20.1
Page 3 of 8
® QUICK RESPONSE
DRY HORIZONTAL
N4 I KJ SIDEWALL SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
�i
)K*Notei A 1/2" ratchet is required,
Sprinkler Wrench Part (Not available from Viking)
No 07565W/B)K)K for
installing recessed
dry sprinklers.
--------------
(^ i_ ____
_________T_
j I
' 1
Step 1: Carefully slide the
Step 2: Press the wrench onto
wrench sideways around the
J
the sprinkler wrench flats and
deflector and protective
turn slightly to ensure engage -
shield as shown
ment with the wrench flats.
Figure 2: Wrench 07565W/B
for Adjustable Recessed Dry Horizontal Sidewall Sprinklers
For 'A" Dimension:
1. Determine the distance from the face of TFFFT
the tee to the finished face of the wall,
2. Round to the nearest 1/2' (12.7 mm) between
1-1/2' (38.1 mm) and 45-1/2' (1,156 mm).
NOTE: The deflector will extend approximately
4-1/8' (104.8 mm) from the wall with 2' +/-
1' (25.4 mm) horizontal adjustment available.
�A
Minimum wall opening J
diameter: 1-3/4' (44.5 mm).
Maximum wall opening
diameter) 2-1/4' (57 mm),
mummmmmumnaw
Deflector at
Minimum Distance
- Finished Ceiling From Wall
Finished Wall
4' (102 mm) Minimum
6' (152 mm) Maximums
1 (79.4 mm)
17
3-1/16"
l (77,8 mm)
�
/ 5/8' (15,9 `
1 Sleeve diameter)
1-1/2' (38.1 mm).
-13/16' Sleeve finish matches )K
(20.6 mm) finish of escutcheon.
NOTE1
To locate the deflector
at the minimum distance
from the wall, with no
adjustment available,
order the standard dry
horizontal sidewall sprink-
ler 1' (25.4 mm) shorter
than the 'A' Dimension.
Deflector at NOTE
Maximum Distance To locate the deflector
From Wall at the maximum distance
from the wall, with no
adjustment available,
order the standard dry
horizontal sidewall sprink-
ler 1' (25.4 mm) longer
than the 'A' Dimension.
May be allowed up to 18' (457 mm) for certain
FM installations. Refer to the appropriate installation
standards, including NFPA 13 and/or FM Loss
Prevention Data Sheet 2-0.
Figure 3: Adjustable Standard Dry Horizontal Sidewall Sprinkler
Slot
Deflector _ Slot
Push and Rotate
Sleeve
STEP 1: Align the slot in STEP 2: Push the rounded STEP 3: Pull the escutcheon STEP 4: Push and rotate STEP 5: To minimize
the escutcheon with the end of the slot against the away from the near edge the escutcheon onto the visibility of the slot
horizontal surface of near edge of the deflector. of the deflector. Move the sleeve, in the escutcheon,
the deflector as shown. Push the far side of the near side of the escut- position the slot
escutcheon past the deflec- cheon over the deflector, at the top of the
Tor, toward the sleeve, sprinkler sleeve.
Figure 4: Adjustable Standard Escutcheon Installation
Form No. F_031993 20.04.16 Rev 20.1
Page 4 of 8
® QUICK RESPONSE
DRY HORIZONTAL
SIDEWALL SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
Approval Chart 1 (UL)
Temperature KEY
Quick Response Dry Horizontal Sidewall Sprinklers Finish
For Light Hazard Occupancies Only AIX *- Escutcheon (if applicable)
Maximum 175 PSI (12 bar) WWP
Sprinkler Base
Thread Size
Nominal
Order Length
Listings and Approvals'
Part No.'
SIN
Style
K-FactorZ
Increment
(Refer also to Design Criteria on page 106e.)
NPT
BSPT
U.S.
metric'
Inches
mm
cULus'
NYC6
VdS
LPCB
(E
Ci
08384U
VK178
Adjustable
Standard
1"
--
5.6
80.6
1/2"
12.7
A1, A5
Al
--
--
--
-
16458U
--
25 mm
--
80.6
1/2"
12.7
A1, A5
08386U
VK182
Adjustable
Recessed
1"
--
5.6
80.6
1/4"
6.35
B2, B6
B2
--
--
-
16454U
--
25 mm
--
80.6
1/4"
6.35
B2, B6
-
--
--
08388U
VK174
Plain Barrel
ill
--
5.6
80.6
1/2"
12.7
A3
A4
--
--
16456U
25 mm
--
80.6
1/2"
12.7
A3
Approved Finishes and "A" Dimensions
1* - Chrome, or White Polyester' sprinkler with a Chrome, Brass, or White Polyester Sleeve and
Escutcheon with "A" dimensions 1-1/2" to 45-1/2" (38.1 mm to 1,156 mm)
Approved Temperature Ratings
2* - Chrome, or White Polyester' with "A" dimensions 3-1/4" to 47-1/2" (82.5 mm to 1,207 mm)
A - 155 -F (68 -C), 175 -F (79°C), 200 -F
3 - Chrome, Brass, White Polyester', or ENT' with "A" dimensions 3" to 47" (76.2 mm to 1,194 mm)
(93 °C), and 286 °F (141 °C)
4 - Chrome or Brass with "A" dimensions 3" to 47" (76.2 mm to 1,194 mm)
B - 155 °F (68 °C), 175 °F (79 °C), and
5 - ENT' sprinkler with an ENT' Sleeve and Escutcheon with "A" dimensions 1-1/2" to 45-1/2" (38.1
200 -F (93 -C)
mm to 1,156 mm)
6 - ENT' with "A" dimensions 3-1/4" to 47-1/2" (82.5 mm to 1,207 mm)
*Brass Finish is listed and approved but not standard offering, lead times of 6-8 weeks required.
(Matching Brass escutcheons are not available.)
Footnotes
' Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2 K-Factor applies for standard lengths ("A" Dimensions indicated above).
3 Metric K-factor shown is for use when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
4 This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer
for any additional approvals.
5 Listed by Underwriter's Laboratories for use in the U.S. and Canada for Light Hazard occupancies only.
6 Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E, Vol. 15.
' cULus Listed as corrosion resistant.
DESIGN CRITERIA - UL
(Also refer to Approval Chart 1 above.)
cULus Listing Reguirements:
Quick Response Dry Horizontal Sidewall Sprinklers are cULus Listed as indicated in Approval Chart 1 for installation in accordance with the latest edi-
tion of NFPA 13 for standard spray sprinklers.
• Limited to Light Hazard occupancies only.
• Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13.
• Minimum spacing allowed is 6 ft. (1.8 m).
• Deflector must be positioned between 4" and 6" (102 mm and 152 mm) below the ceiling. Keep the top of the deflector oriented parallel with
the ceiling.
• Locate no less than 4" (102 mm) from end walls.
• Maximum distance from end walls shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured
perpendicular to the wall.
• The sprinkler installation and obstruction rules contained in NFPA 13 for sidewall standard spray sprinklers must be followed.
IMPORTANT. Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614
for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest
edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and
also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
Form No. F_031993 20.04.16 Rev 20.1
Page 5 of 8
® QUICK RESPONSE
DRY HORIZONTAL
N4 I KJ SIDEWALL SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
Approval Chart 2 (FM)
Temperature KEY
Quick Response Dry Horizontal Sidewall Sprinklers Finish
For Light Hazard Occupancies Only AlXFEscutcheon (if applicable)
Maximum 175 PSI (12 bar) WWP
Sprinkler Base
Thread Size
Nominal K-Factor2
Order Length Increment
FM Approvals°
Part No.
SIN
Style
(Refer also to Design Criteria below.)
NPT
BSP
U.S.
metric'
Inches
mm
08384U
VK178
Adjustable Standard
1"
-
5.6
80.6
1/2"
12.7
Al
16458U
--
25 mm
--
80.6
1/2"
12.7
Al
08386U
VK182
Adjustable Recessed
1"
--
5.6
80.6
1/4"
6.35
B2
16454U
--
25 mm
--
80.6
1/4"
6.35
B2
08388U
VK174
Plain Barrel
1"
--
5.6
80.6
1/2"
12.7
A3
16456U
-
25 mm
--
80.6
1 1/2"
12.7
A3
Approved Finishes and "A" Dimensions
1" - Bright Brass, Chrome, White Polyester, or ENT5 with "A" dimensions 1-1/2" to 45-1/2" (38.1
Approved Temperature Ratings
mm to 1,156 mm)
2' - Bright Brass, Chrome, White Polyester, or ENT' with "A" dimensions 3-1/4" to 47-1/2" (82.5
A- 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and
mm to 1,207 mm)
286 °F (141 °C)
3 - Brass, Bright Brass, Chrome, White Polyester, or ENT' "A" dimensions 3" to 47" (76.2 mm to
B - 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C)
1,194 mm)
"Brass Finish is listed and approved but not standard offering, lead times of 6-8 weeks required.
(Matching Brass escutcheons are not available.)
Footnotes
Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2 K-Factor applies for standard lengths ("A" Dimensions indicated above).
3 Metric K-factor shown is for use when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
° This chart shows the FM Approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for
any additional approvals.
5 FM approved as corrosion resistant.
DESIGN CRITERIA - FM
(Also refer to Approval Chart 2 above.)
FM Approval Reauirements:
The Dry HSW Sprinklers in the Approval Chart above are FM Approved as quick response Non -storage standard spray sprinklers as indicated in the
FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including
2-0) and Technical Advisory Bulletins. FM Global Loss Prevention Data Sheets and Technical Advisory Bulletins contain guidelines relating to, but not
limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflec-
tor distance below the ceiling.
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No.
F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accord-
ance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS
or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever
applicable.
Form No. F_031993 20.04.16 Rev 20.1
Page 6 of 8
® QUICK RESPONSE
DRY HORIZONTAL
N4 I KJ SIDEWALL SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
For 'A' Dimenslorr
1, Determine the distance from the face of
the tee to the face of the finished wall.
2. Round to the nearest 1/4' (6.35 mm)
between 3-1/4' (83 mm) and 47-1/2' (1,207 mm).
NOTF The sprinkler will be recessed approximately
5/16' (7,9 mm) with 5/8' (16 mm) horizontal
adjustment available
F� A
II
Minimum wall opening I
II
vi
2-1/8' (54 mm) diameter.
Maximum wall opening
2-1/2' (63.5 mm) diameter,
w May be allowed up to 18' (457 mm) for certain
FM installations. Refer to the appropriate Installation
standards, including NFPA 13 and/or FM Loss
Prevention Data Sheet 2-0
Ceiling
Wall —7
4' (102 mm) Minimum
6' (152 mm) Maximum*
5/8' (16 mm)
3-1/16'
(77.8 mm)
Available
Adjustment
1-23/32' (43.7 mm) Minimum
2-11/32' (59,5 mm) Maximum
5/16' (7,9 mm) Outward Adjustment
5/16' (73 mm) Inward Adjustment
Figure 5: Adjustable Recessed Dry Horizontal Sidewall Sprinkler with the Model E-1 Escutcheon
Side outlet of �\
Tee turned to
req'd angle for
slope of ceiling
Adjustable
Adapter
Ring
Depth,
1-1/16'
(27 mm)
1/8'
(3.2 mm)
Adjustable
Outer Cup
2-5/8' 4-
(66 ) (102 mm)
mm
Figure
For 'A' Dlmenslorr
1. Measure B Dimension from centerline of the
face of the tee to the horizontal centerline
of the wall opening.
2. Measure C Dimension from the centerline of
the Face of the tee to the finished wall
q 3. Calculate 'A' Dimension using; A = ++ C
NOTE, A Dimension will provide approximately 1/4'
of adjustment in either direction.
Ceiling
Deflector distance
�4-6' (102 to 152 mm)
"�Lr%�below the ceiLing,)K
Minimum wall openingi When measuring for
2-5/8' (66 mm) diameter, the 'A' Dimension,
Maximum wall opening: the exact deflector
3-3/4' (95 mm) diameter. .--Wall distance below the
ceiling must be known.
C 3( May be allowed up to 18' (457 mm)
for certain FM Installations. Refer to
the appropriate installation standards,
including NFPA 13 and/or FM Loss
Prevention Data Sheet 2-0.
Adjustable Recessed Dry Horizontal Sidewall Sprinkler with the Model G-1 Escutcheon
Form No. F_031993 20.04.16 Rev 20.1
Page 7 of 8
® QUICK RESPONSE
DRY HORIZONTAL
N4 I Ki SIDEWALL SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
For "A" Dimension
1, Determine the distance from the face of
the tee to the base of the sprinkler.
2 Round to next highest 1/2' (12.7 mm)
increment, between 3" (76.2 mm) and
47' (1,194 mm).
A
Outside diameter; 1-5/16'
(33A mm), (Same as 1"
(25 mm) Schedule 40 pipe
Ceiling
Wall 7
4" (102 mm) Minimum
6" (152 mm) Maximumx
2-3/16"
(51 mm)1
=47�1 5/8" (16 mm)
.Be not exceed 6" (152 mm),
Do not recess wrench boss.
x May be allowed up to 18' (457 mm) for certain
FM installations, Refer to the appropriate installation
standards, including NFPA 13 and/or FM Loss
Prevention Data Sheet 2-0.
Figure 7: Quick Response Plain Barrel Dry Horizontal Sidewall Sprinkler
Form No. F_031993 20.04.16 Rev 20.1
Page 8 of 8
® QUICK RESPONSE
DRY HORIZONTAL
N4 I KJ SIDEWALL SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
5-1/8"
a (130.2 mm)—1
Seal the clearance space around the sprinkler barrel to avoid ii ii ii Maximum
leakage of air Into the protected area and consequent formation
of condensate around the sprinkler frame, which could inhibit --
operation or cause premature operation. Refer to Figure 9, I
If humidity and temperature
differential causes condensation
on the exposed dry sprinkler
barrel, consider wrapping the
exposed barrel with insulation,
foam Insulating tape, or equivalent
Install the 1" NPT threaded
end of the dry sldewall sprink-
ler into the 1" NPT outlet of
a malleable iron tee fitting per
ANSI B 16,3 (C(ass 150) or cast
Iron threaded tee fitting per
ANSI 16,4 (Class 125) only,
Minimum wall opening:
diameter: 1-3/4' (445 mm)
Maximum wall opening (Exposed
diameter: 2-1/4' (57 mm),Barrel)
Ambient
xpcsec Barre
Ambient Temperature
Temperature
40°F/4°C 50'F/l0°C 60'F/16°C
of Protected
Area## at the
Ex p osed Minimum Barrel
Discharge End
Lengthy■ Face of the
of the Sprinkler
Tee to the Outer
Surface of the Wall
In. (mm) In. (mm) In. (mm)
40'F WC)
0
0
0
30'F (-1'0
0
0
0
20'F (-7'C)
4 (100)
0
0
10'F (-12'C)
8 (203)
1 (25.4)
0
0'F (-18'C)
12 (305)
3 (76)
0
-10'F (-23'C)
14 (356)
4 (102)
1 (25.4)
-20'F (-29'C)14
(356)
6 (152)
3 (76)
-30'F (-34'C)
16 (406)
8 (203)
4 (102)
-40'F (-40'C)
18 (457)
8 (203)
4 (102)
-50-F (-46'C)
20 (508)10
(254)6
(152)
-60-F (-51'C)
20 (508)
10 (254)
6 (152)
NOTE To locate the
II II II-------------------
Deflector at
deflector at the
IIIIIIIII__________________=
Maximum Distance
From Wall
maximum distance from
IIIIIIIII------------------
the wall, with no
IIIIIIIII
IIIIIIIII 13/16"
adjustment available,
IIIIIIIII
(20.6 mm)
Ceiling
order the standard
IIIIIIIII
or horizontal
side-4'
(102 mm)
Minimum
wall sprinkler 1"
6' (152 mm)
Maximum)K
longer than the "A"
Sleeve finish
matches
dimension.
escutcheon
Up to 2' (50.8 mm)
3-1/16"
adjustment is available,
(77.8 mm)
- 5/8"
- (15.9 mm)
3-1/8'
(79.4 mm)
Minimum
1-1/2'
NOTE To locate the
(38.1 mm)
diameter
n ii ii
deflector the
minimum distance from
Outer
the wall, with no
Surface
adjustment available,
of the Wall
_
order the standard
dry horizontal side-
;;
wall sprinkler 1"
Deflector at shorter than the
Minimum Distance
From Wall
'A' dimension.
#May be allowed up to 18' (457 mm) for certain FM
installations. Refer to the appropriate installation standards,
including NFPA 13 and/or FM Loss Prevention Data Sheet 2-0.
�#The protected area refers to the area below the ceiling,
The ambient temperature is the temperature at the discharge end of the sprinkler,
For protected area temperatures that occur between the
values listed, use the next cooler temperature.
#)KThe minimum required barrel length is not the some as the "A" dimension.
Refer to Figures 3, 5, 6 and 7 for the "A" dimension.
Exposed minimum barrel lengths are inclusive up to 30 mph wind velocities,
Figure 8: Dry Horizontal Sidwall Sprinkler Required Minimum Barrel Length Based on Ambient Temperature in the Protected Area
(Adjustable Standard Dry HSW Sprinkler is Shown)
Figure y: Dry Sprinkler Seal (Adjustable Standard Dry NSW Sprinkler is Shown)
Replaces Form No. F_031993 Rev 19.2
Form No. F_031993 20.04.16 Rev 20.1 (Removed cover 15610.)
Fig. 23 - Hanger for CPVC Plastic Pipe
Double Fastener Strap Type
Size Range — 3/4" thru 3" CPVC pipe
Material — Pre -Galvanized Steel
Function — Intended to perform as a hanger/restrainer to support
CPVC piping used in automatic fire sprinkler systems. Fig. 23 can
be installed on the top, bottom or side of a beam. The Fig. 23 also
functions as a restrainer to prevent the upward movement of the
sprinkler head during activation.
Approvals — Underwriters' Laboratories Listed in the USA (UL)
and Canada (cUL) sizes 3/4" thru 2" to support fire sprinkler piping.
May be installed in wood using fasteners supplied with product,
or into minimum 20 gauge steel using (2) 1/4" x 1 " tek type screw.
Meets and exceeds the requirements of NFPA 13, 13R and 13D.
Features — Fig. 23 incorporates features which protect the pipe
and ease installation. The flared edge design protects the CPVC
pipe from any rough surface. It also incorporates snap restrain-
ers allowing easier and faster installation. Easily attaches to the
building structure using the two UL Listed hex head self thread-
ing screws* furnished with the product. It is recommended that
rechargeable electric drills fitted with a hex socket attachment be
used as installation tools. No impact tools (such as a hammer) are
allowed. Damage has been known to result from installations using
impact type tools. No pre -drilling of a pilot hole in wood is required.
Finish — Pre -Galvanized
Order By — Figure number and pipe size
* Hardened hex head self threading screw is furnished with the
product and is the minimum fastener size acceptable.
1<C
C UL US LISTED
Dimensions • Weights
CPVC Max. Hanger Fastener Hex Approx.
Pipe Size A B C Spacing (Ft.) Head Size Wt./100
3/4 31/8 19/16 13/16 51/2 5/16 9
1 33/8 1 11/16 13/16 6 5/16 9
1 1/4 43/16 23/32 13/16 61/2 5/16 11
11/2
47/16
27/32
13/16
7
5/16
12
2
47/8
27/16
13/16
8
5/16
15
2112
109/32
211/16
13/16
Consult Factory
5/16
22
3
117/8
3
13/16
Consult Factory
5/16
25
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266 i
www.tolco.com
Fig. 24 - Hanger for CPVC Plastic Pipe
Double Fastener Strap Type - Side Mount
Size Range — 3/4" thru 2" CPVC pipe
Material — Pre -Galvanized Steel
Function — Intended to perform as a hanger/restrainer to support
CPVC piping used in automatic fire sprinkler systems. Can be installed
on the top or on the bottom of a beam. The Fig. 24 can also function
as a restrainer to prevent the upward movement of the sprinkler head
during activation.
Approvals — Underwriters' Laboratories Listed in the USA (UL) and
Canada (cUL) to support fire sprinkler piping. May be installed in wood using
fasteners supplied with product, or into minimum 20 gauge steel using (2)
1/4" x 1 " tek type screws. Meets and exceeds the requirements of NFPA 13,
13R and 13D.
Features — Fig. 24 incorporates features which protect the pipe and
ease installation. The flared edge design protects the CPVC pipe from
any rough surface. Easily attaches to the building structure using the two
UL Listed hex head self threading screws* furnished with the product. It
is recommended that rechargeable electric drills fitted with a hex socket
attachment be used as installation tools. No impact tools (such as a ham-
mer) are allowed. Damage has been known to result from installations using
impact type tools. No pre -drilling of a pilot hole in wood is required.
Finish — Pre -Galvanized
Order By — Figure number and pipe size
* Hardened hex head self threading screw is furnished with the
product and is the minimum fastener size acceptable.
A'
C& US usreo
Dimensions • Weights
CPVC Max. Hanger Fastener Hex Approx.
Pipe Size A B C Spacing (Ft.) Head Size Wt./100
3/4
25/16
15/32
13/16
51/2
5/16
9
1
25/8
15/16
13/16
6
5/16
9
11/4
3
11/2
13/16
61/2
5/16
11
11/2
31/4
15/8
13/16
7
5/16
12
2
311/16
127/32
13/16
8
5/16
15
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330 m
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
0 9111111 om
Fig. 28 - "Stand -Off" Hanger & Restrainer for
CPVC Plastic Pipe
Size Range — 3/4" through 2"
Material — Carbon Steel, Pre -Galvanized
Function — Designed to be used as a hanger and restrainer for CPVC piping where
the "stand-off" design will ease installation by eliminating the need for wood blocking.
Features:
• Flared edge design protects CPVC pipe from any rough or abrasive surfaces.
• Unique twist and lock design holds pipe firmly in place and allows retrofit type
of installation.
• The "Stand-Off'I design eliminates the need for wood block extension.
• Can be installed on horizontal or vertical piping regardless of mounting
surface orientation.
• Attaches easily to wood structure with two hex head self -threading screws
furnished with product.
• Installs easily using rechargeable electrical driver with 5/16" extension socket
eliminating impact tool damage to pipe.
• Attaches easily to steel, minimum 18 gauge with (2) 1/4" x 1'I tek type self drilling
tapping screws.
• UL Listed as a hanger and a restrainer for fire sprinkler piping.
Approvals — Underwriters' Laboratory Listed in the USA (UL) and Canada (cUL) to
support automatic fire sprinkler systems. May be installed into wood using fasteners
supplied with product, or into minimum 18 gauge steel using (2) 1/4" x 1 " tek type
screws. Meets and exceeds the requirements of NFPA 13, 13R and 13D. Fig. 28 satis-
fies the UL vertical restraint requirement where needed. UL Listed as a hanger and ver-
tical restraint when installed on 3/8" composite wood material. Use two Fig. 27B Speed
Nuts when used as a hanger and restraint. Use one Fig. 27B Speed Nut on the upper
installed screw when used as a hanger only.
Order by — Figure number and pipe size.
Pat. # 7,455,268, Pat. # 7,832,248
FI G.27B
(1) REQUIRED
HIGH SIDE
OFHANGER
(2)
HANGER APPLICATION HANGER R RESTRAINT
APPLICATION
FIG.2B
FIG.28
FIG. FIG.28
FG�
C &US LISTED
Dimensions • Weights
Pipe
Approx.
Size
A
B
C
Wt.
3/4
31/32
2
31/2
.180
1
35/16
23/1 6
31/2
.210
11/4
35/8
23/8
31/2
.225
11/2
4
21/2
31/2
.310
2
41/2
211/16
35/8
.340
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330 m
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
ARGCO
Fire Sprinkler Pressure Gauges
u�
0-300 psi water
FM
0-300 psi air
0-300 psi air/water
Application: Fluid medium which does not clog connection port or corrode copper alloy.
Specifically designed for the fire sprinkler industry.
Size: 4" (100 mm)
Accuracy ± 3/2/3% of span (ASME B40.1 Grade B)
Working Range
Steady: 3/4 of full scale value
Fluctuating: 2/3 of full scale value
Short time: full scale value
Operating Temperature
Ambient: -40OF to 140OF (-40°C to 60°C)
Media: max. 140°F (+60°C)
Approvals
UL listed (UL-393)
FM approved
Meets NFPA 25 Standards
Temperature Error Standard Scale
Additional error when temperature changes from reference temperature of 680F PSI
(20°C) +0.4% for every 18' F (10°C) rising or falling. Percentage of span.
Standard Features
Connection Material: copper alloy
Lower mount (LM) - not available for 11/2" size
1/4" NPT limited to wrench flat area
Bourdon Tube: Material: copper alloy C-type
Movement: Copper alloy, silicone dampened
Dia: White plastic with stop pin - black & red lettering
Pointer: Black aluminum
Case: Black polycarbonate
E
Window
Acrylic, ultrasonically welded to case
Standard Series • Type 110.10sp
Order Options
water
air/water
air
4` NF'
The information contained herein is produced in good faith and is believed to be reliable but is for guidance only. ARGCO and its agents cannot
assume liability or responsibility for results obtained in the use of its product by persons whose methods are outside or beyond our control. It is the
user's responsibility to determine the suitability of any of the products, methods of use, or preparation prior to use, mentioned in our literature. It is
the user's responsibility to observe and adapt such precautions as may be advisable for the protection of personnel and property in the handling and
use of any of our products.