BLD2022-0710_Other_5.31.2022_11.58.38_AM_2901481CONDUIT WIRE RATING DERATE FOR TEMPERATIRE SIC WIRE VOLTAGE DROP CALCULATIONS RUN LENGTH AMPS VOLTAGE DROP VOLTAGE DROP % VOLTAGE AT LOAD A %" PVC SCHEDULE 40 CONDUIT (3) 6 AWG THWN-2 (Black, Red, White) (1) 8 AWG Cu Bond Conductor 6 AWG RATE 90°C = 75A TEMPERATURE DE -RATING @ 104°F = 0.91 75A x 0.91 = 68.25A 11.25 x 10.4 x 1.25 x 1.25 = 6 AWG OK IAW 2 x 12.9 x so' = I z90 x 4zA = Vd -26240 2.06 volts 50 42 2.06 0.86 237.94 (Green or bare) NEC 690.8 (B)(1I 2°x2" B 3 /" EMT CONDUIT (2)10AWG THWN-2 (positive, Negative) 11)8AWG CUBond Conductor 10 AWG RATE 90"C = 40A TEMPERATURE DE -RATING @ 104°F = 0.91 40A x 0.91 = 36.4A 10.4x1.25x1.25= I1.25 x IOAWGOK IAW Zx12.9x 0'=1290x1A_ Vd = = 1.86 volts 50 15 1.86 0,78 238.14 (Green or bare) NEC 690.8 (B)(1) AHJ APPROVAL STAMP C PV WIRE IN FREE AIR MINIMUM 10 AWG Cu POSITIVE, BARE Cu EGC OR INSULATED EGC IN OR THHN IN CONDUIT (90° RATED) WIRE NEGATIVE CONDUIT CONTROLLED CONDUCTORS ARE LIMITED TO: (N) SOIarEdge Power Optimizer S440DC Input (1) STRING OF (14) HANWHA Q-CELL Q.PEAK DUO Power: 440 watts NOT MORE THAN 30 VOLTS AND 240 VOLTAMPERES WITHIN 30 SECONDS OF RAPID SHUTDOWN INITIATION OUTSIDE THE ARRAY. Maximum Input Voltage: 60 Vdc BLK-G8+ 340, MODULES CONNECTED IN SERIES NOT MORE THAN 80 VOLTS AND 240 VOLTAMPERES WITHIN 30 SECONDS OF RAPID SHUTDOWN INITIATION M PPT Range: 8 to 60 Vdc INSIDE THE ARRAY. Maximum Short Circuit Current (ISc): 14.5 Adc ^S THE RAPID SHUTDOWN INITIATION IS PERFORMED BY EITHER DISCONNECTING THE AC FEED TO THE INVERTER, 1 2 O O O 1 14 Maximum Output Current. 15 AC1C per string V p p g OR - IF (E) UTILITY METER THE INVERTER DC SAFETY SWITCH IS READILY ACCESSIBLE- BY TURNING OFF THE DC SAFETY SWITCH. Maximum Output Voltage: 60 Vdc _ CL 200, FMZS, 60Hz I Limitations: 8 to 25 Optimizers per string + + + CAPSTONE 1-PHASE, 3W, 1201240V PHOTOVOLTAIC SYSTEM EQUIPPED WITH Maximum Power Per String: �-'f SOLAR METER #: 76377407 INVERTER -EMBEDDED AUTOMATIC, RAPID SHUTDOWN 570OW for SE3000H-US - SE6000H-US, 6000W for SE760OH-US - SE 1 140OH-US DC DC DC DC DESCRIPTION DATE DWG NO. DC DC O 0 0 DC DC (N) SUPPLY SIDE TAP ROOFTOP PV CONDUCTORS TO BE 1 " ABOVE ROOFTOP AND PROTECTED INI�UNCTION C FROM PHYSICAL DAMAGE VIA B Box N AC DISCONNECT: ( SECUREMENT WITHIN ARRAY I00oV, NEMA3R, UL LISTED OR VISIBLE, LOCKABLE, BOUNDARY OR 3/4" CONDUIT. APPROVED (1) STRINGS OF (10) HANWHA Q-CELL Q.PEAK DUO EQUAL Solar Specialist EXTERNALLY OPERABLE, B IN000V'NONBOx oODV,NEDOR BLK-G8+ 340, MODULES CONNECTED IN SERIES TAYLOR DISCH A UL LISTED OR 60A RATED, 60A FUSES, APPRQVEDEQUAL 240V, NEMA 3R, 1 2 0 0 o g 10 System Engineer TIM WACHTMAN UL LISTED, A EATON DG222NRB Designer B -+ - + _+ -System CASEY MILLER NiJUNCTION BOX Customer Info O"N NEMA 3R,LISTEDORDc DD DC DC APPROVEDEQUAL DC DC O 0 O DC DC & WOOD Line +++ +HEATHER Lo 5 73 D PL 22515 73RD PL W PC WIRE IN FREE AIR ORTHHNINCONDUIT EDMONDS, WA 98026 MINIMUM I°AWG °'9°RATeD,wIReVE E. NEGOR PARCEL #00391600300700 RARECPC EGG C INSULATED ''AMMUM 2%VOLLTA E DROP C IN CONDUIT Project Details B (1) STRINGS OF (9) HANWHA Q-CELL Q.PEAK DUO 11.FT KW BLI<-G8+ 340, MODULES CONNECTED IN SERIES ROOFTOP PV ELECTRICAL INSTALLATIONS ;MAIN SYSTEM N SOLAREDGE SE 1 OOOOH-US WILL COMPLY WITH THE 1 2 O ( ) REQUIREMENTS OF THE o 0 o TILT C� (E) MAIN SERVICE INVERTER N.E.C. SEC 690 & 705 5:12 PITCH AZIMUTH PANEL NDING JUMPER OUTPUT: 42A @ 240V Note: 705.31 Note: 705.12(B)(2)(3)(b) - 271 °/ 181 °/ 91 ° NEMA 3R, UL LISTED, + + + -+200A BUSBAR = AR Note: 312.6 & 312.81A1(1) & (2) INTERNAL GFDI Note: 404.6 Exception INI JUNCTION BOX ZOOA MAIN OCPD DC SYSTEM RATING Note: 230.66 & 2p0.70 C I000V,NEMA3R, INTEGRATED DC I) UT LISTED OR DDCDC DC C CDC I 1 Z2 KW ALL ELECTRICAL MATERIALS & EQUIPMENT DISCONNECT WITH RAPID Note: 310.15131(c) APPaoveDEOUAL DD o 0 o DD DC Note: SHALL BE LISTED BY APPROVED TESTING LAB 3D + - + + - + - SHUTDOWN KIT Note:314.241B) .16 AC SYSTEM RATING 10.0 KW Note: 690.12(C) Module Information Inverter Specifications Conductor Calculation Interconnection Method ESTIMATED ANNUAL PRODUCTION PV MODULE: Q CELLS O.PEAK DUO BLK-G8+ 340 SOLAREDGE SE 1 OOOOH-US MAX BRANCH DC CONDUCTOR AMPACITY: CONNECT NEW SOLAR CIRCUIT TO EXISTING 9,473 KWh/Yr 34OW x 14 = 4760W / 400V = 1 1.9A x 125% = 14.88A Drawing ELECTRICAL SYSTEM VIA LINE SIDE TAP; LOAD ELECTRICAL DATA PER MODULE (STC): RATED/MAXIMUM AC POWER OUTPUT: 1 OOOOW S440 MAX OUTPUT CURRENT = 15A SIDE OF NET METER AND SUPPLY SIDE OF MAXIMUM POWER - Pmax 340 MAX. CONTINUOUS OUTPUT CURRENT: 42A 10 AWG Cu 90' RATED = 40A x 91 % = 36AA MAIN SERVICE PANEL IAW ELECTRICAL LINE DIAGRAM GE MAXIMUM POWER VOLTAGE Vmpp MAX.DC INPUT POWER: 15500@240V 36.4A z 14.88A OK TO INSTALL IAW NEC 690.8(B)(1-2) 705.1 1(A)(B)(C)(D)(E), 230.82(6), 690.13, & - (V): 34.34 690.15 Sheet MAXIMUM POWER CURRENT - Im A pp ( ): 9.9 MAX. INPUT VOLTAGE: 480V MAX AC CONDUCTOR AMPACITY: o OPEN CIRCUIT VOLTAGE - Voc (V): 40.7 NOMINAL DC INPUT VOLTAGE: 400V 42A MAXIMUM CONT. OUTPUT CURRENT _ 200A RATED BUSBAR x 120 /o - 240A 240A - 200A MAIN OCPD = 40A SHORT CIRCUIT CURRENT Isc (A): 10.4 MAX. INPUT CURRENT: 27A@240V 42A x 125% = 52.5A 40A ALLOWABLE POWER SOURCE INTERCONNECTION MODULE EFFICIENCY: 19.8% CEC WEIGHTED EFFICIENCY: 99% 6 AWG Cu 90° = 75A x 91 �/a = 68.25A 52.5A MINIMUM - SUPPLY SIDE TAP REQUIRED E 1 MAX. EFFICIENCY: 99.2% 68.25A >- 52.5A OK TO INSTALL IAW NEC 690.8(B)(1-2)