Loading...
FIR2022-0050_Fire_Alarm_Equipment_Specification_Sheets_5.16.2022_12.22.57_PM_2872504EC"ascade Fi& Security BY: CASCADE ALARM P.O. BOX 7459, KENT, WA 98042 • PH: 206-767-5800 • FAX: 253-630-4851 Scope of work FIRE ALARM SYSTEM MODIFICATION RBC WEALTH MANAGEMENT 303 5T" AVE. SOUTH E D M O N DS, WA 98020 1. Relocate 2 existing devices (1 smoke and 1 horn strobe) to common area outside where new offices are being built. 2. Install (2) new conventional smoke detectors (1 in each new office) and tie-in to existing Silent Knight 5208 fire alarm panel. * 24 HOUR SERVICE - LICENSED, BONDED, NICET CERTIFIED, INSURED * Washington State Contractor's License # CASCAAL9633T/CASCAAL962RW "First When Seconds Count" 4,�� SYSTEM Photoelectric Smoke Detectors System Sensor i3- series smoke detectors represent significant advancement in conventional detection. The i3 family is founded on three principles: installation ease, intelligence, and instant inspection. Features Plug-in detector line, mounting base included • Large wire entry port • In -line terminals with SEMS screws • Mounts to octagonal and single -gang back boxes, 4-square back boxes, or direct to ceiling • Stop -Drop 'N Lock attachment to base • Removable detector cover and chamber • Built-in remote maintenance signaling • Drift compensation and smoothing algorithms Simplified sensitivity measurement Wide-angle, dual -color LED indication • Loop testing via EZ Walk feature Built-in test switch Agency Listings & F M X MEA MSFMWs LISTED APOapproved approved c 5911 3011446 7272-1653:152 290-01 " 313C93? Installation ease.The i3 line redefines installation ease with its plug-in design.This allows an installerto pre -wire bases (included with heads). The large wire entry port and in -line terminals provide ample room for neatly routing the wiring inside the base. The base accommodates a variety of back box mounting methods as well as direct mounting with drywall anchors. To complete the installation, i3 heads plug into the base with a simple Stop-Drop'N Lock' action. Intelligence. i3 detectors offer a number of intelligent features to simplify testing and maintenance. Drift compensation and smoothing algorithms are standard with the i3 line to minimize nuisance alarms. 2-wire i3 detectors can generate a remote LED - indicated maintenance signal when connected to the 2W-MOD2 loop test/maintenance module or a panel equipped with the i3 protocol. The SENS-RDR, a wireless device, displays the sensitivityof i3 detectors in terms of percent -per -foot obscuration. Instant inspection. The i3 series provides wide-angle red and green LED indicators for instant inspection of the detector's condition: normal standby, out -of -sensitivity, alarm, or freeze trouble. When connected to the 2W-MOD2 loop test/maintenance module or a panel with the i3 protocol, the EZ Walk loop test feature is available on 2-wire P detectors. This feature verifies the initiating loop wiring by providing LED status indication at each detector. COOPER Notification Series AS Audible Strobe Appliances and Series AH Audibles FARE SERIES AS Description The Wheelock patented 2-wire Series AS Audible Strobe Appliances and Series AH Audibles offer more features with low current draw. Strobe options for wall mount models include 1575cd or the Wheelock patented MCW multi -candela wall strobes with field selectable candela settings of 15/30/75/110cd, or the high intensity MCWH strobe with field selectable 135/185cd. Ceiling mount models incorporate Wheelock's patented MCC multi -candela ceiling strobe with field selectable intensities of 15/30/75/95cd or the high intensity MCCH strobe with field selectable 115/177cd. The audible provides a selectable choice of either a continuous horn or temporal pattern (Code 3) when constant voltage from a Fire Alarm Panel (FACP) is applied. Each tone has 3 dBA settings to choose from. When used with the Wheelock Series DSM Sync Modules, Wheelock Power Supplies or other manufacturers panels incorporating the Wheelock Patented Sync Protocol, synchronization of the continuous horn tone provides the temporal (code 3) tone (mandated by NFPA72) simultaneously for all audible appliances. This ensures a distinct temporal (code 3) pattern when 2 or more audibles are within hearing distance. If not synchronized the temporal sound could overlap and not be distinctive. At the same time the strobes will be synchronized. This provides the ability to comply with ADA guidelines concerning photosensitive epilepsy and the NFPA standards when installing 2 or more visual appliances within the field of view all of this plus the ability to silence the audible is achieved by using only 2 wire. 0 s0 FM MEA F""' APPROVED E5946 151-92-E 7125-0785:131 S5391 SERIES AH Features • Approvals include: UL Standard 1971, UL Standard 464 New York City (MEA), California State Fire Marshal (CSFM), Factory Mutual (FM), and Chicago (BFP). See approvals by model in Specifications and Ordering Information • ADA/NFPA/UFC/ANSI Compliant • Wall mount models are available with Field Selectable Candela Settings of 15/30/75/110cd or 135/185cd (Multi - Candela models) or 1575cd (single candela model) • Ceiling mount models are available with field selectable candela settings of 15/30/75/95cd or 115/177cd (multi -candela ceiling models) • Selectable Continuous Horn or Temporal (Code 3). • 3 Selectable dBA settings (99, 95 and 90 dBA) in both tones • Patented 2-Wire Audible Strobe Appliance. • Patented Universal Mounting Plate • Weatherproof models are available for outdoor use • Strobes produce 1 flash per second over the regulated voltage range • 12 and 24 VDC models with wide UL "Regulated Voltage Range" using filtered DC or unfiltered FWR input voltage • Synchronize using the Wheelock Sync Modules or panels with built-in Wheelock Patented Sync Protocol • Fast installation with IN/OUT screw terminals using #12 to #18 AWG wires For Weatherproof Series AS, See Datasheet S9004 NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.COOPERNOTIFICATION.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes: • Strobes are designed to flash at 1 flash per second minimum over their "Regulated Voltage Range'. Note that NFPA-72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. • All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. • "Regulated Voltage Range" is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology "Listed Voltage Range". Table 1: Ratings Per UL 1971 Model Number Input Voltage VDC Regulated Voltage Range VDC/FWR Strobe Candela (cd) AS-24MCW 24 16.0 - 33.0 15/30/75/110 AS-24MCCH 24 16.0 - 33.0 115/177 AS-241575W 24 16.0 - 33.0 15 (75 on Axis) AS-121575W 12 8.0 - 17.5 15 (75 on Axis) AS-24MCC 24 16.0 - 33.0 15/30/75/95 AS-24MCWH 24 16.0 - 33.0 135/185 ASWP-2475W 24 16.0 - 33.0 75 @ -31 T Table 3: Average RMS Current Table 2: dBA Ratings for 12 VDC and 24 VDC Series AS/ AH 12 and 24 VDC Audible Reverberant Anechoic Description Volume dBA dBA per UL 464 @10ft. @10ft. High 91 99 Continuous Medium 88 95 Horn Low 83 90 High 87 99 Medium 84 95 Code 3 Horn Low 79 90 Audible I Wall Mount Audible Strobe Models Ceiling Mount Audible Strobe Models 24 VDC Models AH-24 AS-241575W 1575cd High (99) dBA 24 vdc 0.062 0.100 UL max* 0.080 0.121 Med (95) dBA 24 vdc 0.033 0.080 UL max* 0.043 0.107 Low (90) dBA 24 vdc 0.017 0.072 UL max* 0.021 0.100 12 VDC Models Audible Wall Mount Audible Strobe AH-12 AS-121575W High (99) 0.163 0.260 �lL?vcic Umax* 0.192 0.320 dBA Med (95) 12 vdc 0.076 0.195 UL max* 0.108 0.275 dBA Low (90) 12 vdc 0.039 0.175 UL max* 0.058 0.265 dBA AS-24MCW AS-24MCWH AS-24MCC AS-24MCCH 15cd 30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 115cd 177cd 0.080 0.102 0.150 0.194 0.250 0.320 0.088 0.114 0.165 0.205 0.250 0.320 0.088 0.125 0.200 0.267 0.355 0.480 0.095 0.138 0.221 0.285 0.355 0.480 0.060 0.084 0.132 0.173 0.230 0.305 0.066 0.092 0.145 0.186 0.230 0.305 0.074 0.110 0.190 0.253 0.340 0.465 0.080 0.122 0.201 0.269 0.340 0.465 0.052 0.076 0.121 0.158 0.220 0.295 0.056 0.082 0.132 0.173 0.220 0.295 0.068 0.105 0.182 0.245 0.335 0.460 0.074 0.113 0.198 0.263 0.335 0.460 Table 4: Average Current* (AMPS) For Series ASWP# Voltage High dBA Setting (99) dBA Medium dBA Setting (95) dBA Low dBA Setting (90) dBA 24.0 VDC 0.128 0.105 0.098 UL Max* 0.168 0.155 0.150 * RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions. Wiring Diagrams" SERIES AS APPLIANCES NON -SYNCHRONIZED FROM TO NEXT PRECEDING + ±APPLIANCE APPLIANCE OR EOLR OR FACP Specifications and Ordering Information SERIES AS APPLIANCES SYNCHRONIZED WITH MULTIPLE DSM MODULES DSM #1 Strobe NAC Cir. 'Y " �+ AS AS F r DSM #2 Audible NAC Cir A Strobe NAC Cir. Sync AS AS C �+ Audible NAC Cir DSM #3 P Sync Strobe NAC Cir. 0 + AS AS DSM Interconnecting wiring shown. Maximum of twenty (20) n For detail using DSM Sync Module refer to Data Sheet S3000 or Installation Instructions P83177 for DSM. For wiring informationon the power supplies refer to Installation Instructions P84905 for Wheelock Power Supplies. Model Number Order Code Strobe Candela Non- Sync Sync DSM or Wheelock Power Supplies 24 VDC 12 VDC Wall Mount Ceiling Mount Mounting Options*** Agency Approvals UL MEA CSFM FM BFP AS-24MCW-FR 9024 15/30/75/110 X X X - X - A,B,D,E,F,G,H,J,N,O,R,X X X X X X AS-24MCW-FW 9025 15/30/75/110 X X X - X - A,B,D,E,F,G,H,J,N,O,R,X X X X X X AS-24MCWH-FR 3468 135/185 X X X - X - A,B,D,E,F,G,H,J,N,O,R,X X X X X - AS-24MCWH-FW 3469 135/185 X X X - X - A,B,D,E,F,G,H,J,N,O,R,X X X X X - AS-241575W-FR 7405 15 (75 on Axis) X X X - X - A,B,D,E,F,G,H,J,N,O,R,X X X X X X AS-121575W-FR 7410 15 (75 on Axis) X X - X X - A,B,D,E,F,G,H,J,N,O,R,X X X X X X AS-24MCC-FR 3161 15/30/75/95 X X X - - X A,B,D,E,F,G,H,J,N,O,R,X X X X X - AS-24MCC-FW 3162 15/30/75/95 X X X - - X A,B,D,E,F,G,H,J,N,O,R,X X X X X - AS-24MCCH-FW 3467 115/177 X X X - - X A,B,D,E,F,G,H,J,N,O,R,X X X X X - ASWP-2475W-FR** 9012 75 @ -31'F X X X - X - I (see Data Sheet S9004) X X X X X AH-24-R 7892 - X X X - X X A,B,D,E,F,G,H,J,N,O,R,X X X X X X AH-24-W 7893 - X X X - X X A,B,D,E,F,G,H,J,N,O,R,X X X X X X AH-12-R 7891 - X X - X X X A,B,D,E,F,G,H,J,N,O,R,X X X X X X AH-12-W 7894 - X X - X X X A,B,D,E,F,G,H,J,N,O,R,X X X X X X AH-24WP-R** 7416 - X X X - X X K X X X - X AH-12WP-R** 7415 - X X - X X X K X X X - X **For Weatherproof Series AS/AH specifications see data sheet S9004. *PENDING ***Refer to Data Sheet S7000 for Mounting Options. Note: Models are available in either Red or White. Contact Customer Service for Order Code and Delivery. NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. Architects and Engineers Specifications The notification appliances shall be Wheelock Series AS Audible Strobe appliances and Series AH Audible appliances or approved equals. The Series AS Audible be listed for UL Standard 1971 (Emergency Devices for the Hearing -Impaired) for Indoor Fire Protection Service. The Series AH Audible shall be UL Listed under Standard 464 (Fire Protective Signaling). Both shall meet the requirements of FCC Part 15 Class B. All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP). The audible portion of the appliance shall have a minimum of three (3) field selectable settings for dBA levels and shall have a choice of continuous or temporal (Code 3) audible outputs. The strobe portion of the appliance shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens. The Series AS shall be of low current design. Where Multi - Candela appliances are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 at 15/30/75/110 or 135/185 candela for wall mount and 15/30/75/95 or 115/177 candela for ceiling mount. The selector switch for selecting the candela shall be tamper resistant. The 1575 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on -axis is required (e.g. ADA compliance). When synchronization is required, the appliance shall be compatible with Wheelock's DSM Sync Modules, Wheelock Power Supplies or other manufacturers panels with built-in Wheelock Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobe shall revert to a non -synchronized flash -rate. The appliance shall also be designed so that the audible signal may be silenced while maintaining strobe activation when used with Wheelock synchronization. The Series AS Audible Strobe and Series AH Audible shall incorporate a Patented Universal Mounting Plate that shall allow mounting to a single -gang, double -gang, 4-inch square, 100mm European type backboxes, or the SHBB Surface Backbox. If required, an NATP (Notification Appliance Trimplate) shall be provided. All notification appliances shall be backward compatible. Fs wmwffw� WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY S8100 AS/AH 06/11 Wheelock® MEDC SAFEPATH' WAVES, Notification (-L3) Smoke Detector Specifications Smoke detector shall be a System Sensor i3 Series model number listed to Underwriters Laboratories UL 268 for Fire Protection Signaling Systems.The detector shall be a photoelectric type (Model 2W-B, 4W-B) or a combination photoelectric/thermal (Model 2WT-B, 4WT-B) with thermal sensor rated at 135°F (57.2°C).The detector shall include a mounting base for mounting to 31/2-inch and 4-inch octagonal, single -gang, and 4-inch square back boxes with a plaster ring, or direct mount to the ceiling using drywall anchors. Wiring connections shall be made by means of SEMS screws. The detector shall allow pre -wiring of the base and the head shall be a plug-in type. The detector shall have a nominal sensitivity of 2.5 percent -per -foot nominal as measured in the UL smoke box. The detector shall be capable of automatically adjusting its sensitivity by means of drift compensation and smoothing algorithms. The detector shall provide dual - color LED indication that blinks to indicate power up, normal standby, out of sensitivity, alarm, and freeze trouble (Model 2WT-B, 4WT-B) conditions. When used in conjunction with the 2W-MOD2 module, 2-wire models shall include a maintenance signal to indicate the need for maintenance at the alarm control panel and shall provide a loop testing capability to verify the circuit without testing each detector individually. Operating Voltage Nominal: 12/24V non -polarized Minimum: 8.5 V Maximum: 35 V Maximum Ripple Voltage 30% peak to peak of applied voltage Standby Current 2-wire: 50 NA maximum average; 4-wire: 50 NA maximum average Maximum Alarm Current 2-wire: 130 mA limited by control panel; 4-wire: 20 mA @12 V, 23 mA @ 24 V Peak Standbv Current 2-wire: 100 uA; 4-wire: n/a Alarm Contact Ratings 2-wire: n/a; 4-wire: 0.5 A @ 30 V AC/DC Dimensions (including base) 5.3 inches (127 mm) diameter; 2.0 inches (51 mm) height Weight 6.3 oz (178 g) Operating Temperature Range 2W-B and 4W-B: 32°F to 120°F (0°C to 49°C); 2WT-B and 4WT-B: 32°F to 100°F (0°C to 37.8°C) Operating Humidity Range 0 to 95% RH non -condensing Thermal Sensor 135°F (57.2°C) fixed Freeze Trouble 2WT-B and 4WT-B only: 41 °F (5°C) Sensitivity 2.50/o/ft nominal InqutTerminals 14 to 22 AWG Mounting 31/2-inch octagonal back box 4-inch octagonal back box Single -gang back box 4-inch square back box with a plaster ring Direct mount to ceiling LED Mode Green LED Red LED Condition Duration Power up Blink every 10 seconds Blink every 10 seconds Initial LED status indication 80 seconds Normal (standby) Blink every 5 seconds off Out of sensitivity off Blink every 5 seconds Freeze trouble off Blink every 10 seconds Alarm off Solid Ordering Information Model 2W-B Thermal No Wiring 2-wire Alarm Current 130 mA max. limited by control panel 2WT-B Yes 2-wire 130 mA max. limited by control panel 4W-B No 4-wire 20 mA @ 12 V, 23 mA @ 24 V 4WT-B Yes 4-wire 20 mA @ 12 V, 23 mA @ 24 V Accessories 2W-MOD2 SENS-RDR 2-wire loop test / maintenance module Sensitivity reader RT Removal / replacement tool A77-AB2 Retrofit adapter bracket, 6.6 inch (16.76 cm) diameter it �� \\ �E� m2009 System Sensor. `_ �/ 3825 Ohio Avenue • St. Charles, IL 60174 Product specifications subjectto change without notice.Vsit systemsensoccom for SENSOR Phone:800-SENSOR2•Fax:630-377-6495 current productinformat5-03180i7-6/09latest version ofthisdata sheet. A05-0318-007 •b/09•#2169 3SILENT 0 KNIGHT by Honeywell Model 5208 Fire Alarm Control Panel with Digital Communicator The Fire Alarm Control Designed to Grow with Your Systems Needs, Without The Growing Pains. The SK-5208 is a microprocessor based control panel with built-in UL listed communicator designed for applications requiring smoke detection, manual pull stations, and sprinkler supervision. It features an easy to read LCD display with programmable English readout and user friendly tactile keys. The basic unit offers 10 zones of initiation and is expandable up to 30 zones for larger applications. The SK-5208 has a complete line of supervised accessories that provide remote annunciation, auxiliary control zone expansion. Ideal for new and retrofit applications, the SK-5208 delivers the performance to handle your installation. Features • 10 zones, 8 Class B (Style B) and 2 Class A (Style D) or Class B (Style B) zones, expandable to 30 zones • Supervised zone expanders and 1/0 modules can be mounted remotely from the main control panel • Event History Buffer (150 events) with date/time stamp • All zones are compatible with 2- or 4-wire detectors • 8 selectable/programmable output patterns for notification appliance circuits • Built-in Digital Alarm Communicator Transmitter (DACT) • 4 Notification Appliance Circuits • 4 programmable general purpose relays • Programmable smoke verification, pre -alarm delay, cross zoning and enhanced verification mode features that can help minimize false alarms • Programmable from the built-in control panel touchpad, remote annunciator, or Windows@ SKSS downloading software • Direct connect port for on -site up/downloading with Windows@ SKSS downloading software • Built-in walk test feature • Single or dual interlock water releasing capability • Plex door option combines a dead front cabinet door with a clear window, limiting access to the panel while providing single button operation of the reset and silence functions • Programmable AC trouble relay • Built-in synchronization for appliances from AMSECO@, Gentex@, Faraday, System Sensor@, and Wheelock@ • Programmable date settings for Daylight Saving Time • Clock source setting options for 50 Hz, 60 Hz, or internal (uses the panel's internal clock) Specifications Operating Voltage: 24 VDC Primary AC: 120 Vrms @ 60Hz, 2A Total DC Load: 6 Amp Current Draw: Standby: 140 mA Alarm: 460 mA Flush Mounting Dimensions: Height: 24.75" (62.9 cm) Width: 14.5" (36.8 cm) Depth: 3-7/16" (8.73 cm) with 5/8" protruding Overall Dimensions: Height: 26-3/8" (67 cm) Width: 17-3/16" (43.66 cm) Total Depth: 4" (10.16 cm) Operating Temp: 32' to 120' F (0' to 49' C) Humidity: 10 - 93% noncondensing Optional Accessories • SK-5235 LCD Remote Annunciator • SK-5217 10 Zone Expander (2 max. per system) • SK-5280 Status Display Module (8 max. per system) • 5220 Direct Connect Module • 5824 Serial/Parallel Printer Interface Module • SKSS Downloading Software SK-5208 • Plex-2 Door Option • SK-SCK Seismic Compliance Kit Listings and Approvals • UL Listed • CSFM Listed • MEA approval 429-92-E Vol. XIII • OSHPD (CA) OSP-0065-10 Model 5208 Fire Alarm Control Panel with Digital Communicator Engineering Specification The system shall contain a fire alarm control panel to supervise and operate heat and smoke detection devices, manual fire alarm devices, alarm notification devices and visual annunciators. The system shall also be capable of monitoring for sprinkler supervisory and water flow conditions. The system must have a built in UL listed fire communicator that can be enabled/disabled as needed on a per job basis. In addition, the system will sound alarms locally for purpose of evacuation. Telephone Line 1 2 Class A (Style I or Class B (Style Initiation Circuits 8 Class B (Style Initiation Circuits 144 PP_ Telephone Line 2 Direct Connect 4 , ® For On -Site Programming Il Programmable Form C Relays Notification SILENCE V Appliance Circuits 5235 Remote Annunciators SBUS Devices 5280, 5217, & 5824 SILENT This document is not intended to be used for installation purposes. We try to MADE IN AMERICA keep our product information up-to-date and accurate. We cannot cover all 01 KNIGHT specific applications or anticipate all requirements. All specifications are FORM# 350318 Rev E subject to change without notice. For more information, contact Silent Knight © 2013 Honeywell International Inc. by Honeywell 12 Clintonville Road, Northford, CT 06472-1610 Phone: (800) 328-0103, Fax: (203) 484-7118. For Technical support, Please call 800-446-6444. www.silentknight.com