APPROVED FIR FIR2021-0117+Fire_Sprinkler_Plan+11.2.2021_2.00.42_PM+2497270A B C D
I I I
9 I
8
co
M
CD
0
I
q
T-6" T-11 7/16" 13'-11 9/16" 2'-8"
_ I
68'-5 1/2"
T-11 1/2"
DRY'R
BEDROOM 5 120CFM
q � i
_ CONNECT T
WATER CLU ET
SUPPLY.
I I
N 3/4
80 CFM 1_0
BATHV.T.O
I I i
I I I
N
5 M �
q
CID
_ 4'-0"
T-15" BED 00M 4
4
RECREATION RM.
I
J
I I I
1
ALERT FOR CONTRACTORS ALL TRA ,S: 6'-111/2"
THIS PROJECT USES BLAZEMASTER PIPE & FITTINGS THAT ARE SPECIFICALLY
FOR FIRE SPRINKLER SYSTEMS. THEY ARE MADE FROM A SPECIALTY
THERMO PLASTIC KNOWN AS POST CHLORINATED POLYVINYL CHLORIDE.
(CPVC) DO NOT USE OR PLACE IN CONTACT ANY MATERIAL THAT ARE
INCOMPATIBLE WITH CPVC SUCH AS PETROLEUM OR SOLVENT BASED
SEALANT, FIRE STOP INSULATION, ETC. PLEASE REFER TO LUBRIZOL FBC
SYSTEM COMPATIBILITY PROGRAM FOR GUIDANCE REGARDING CHEMICAL
COMPATIBILITY OF CERTAIN MATERIALS GO TO BLAZEMASTER.COM
iF�
O
i V.T.O.
WHOLE HOUSE
FAN w1 TIMER UWASFHF'R
LAUNDRY
8-0 1-4 1, FIRE SPRINKLERS ARE NOT
it
REQUIRED IN CRAWL SPACES
PER NFPA 13D.
THRU WALL
ACCESS TO
CRAWLSPACE
CRAWLSPACE
E F G
I
32'-5"
0'-5 1/2"
FIRE SPRINKLER
GAS HOT WATER
RISER LOCATION
SYSTEM (1.51E.C. TOR
SEE RISER DET.
1'
10-0 o`
1-51/ti loo 3-4
W
o
GASFURNACE
v
o
Drain to be terminated
MECH. ROOM
outside.
Basement.
I/ 11�11_011
a �
BAR
SINK
I
I
_I-
dw
IX U
LL Q
wCL
Of 07
Floo
--- -- STORAGE UNDER
STAIRS. 1/2" GWB.
UP
Q
Z
Q
I I I
I I I
I I I
I I I
I I
I
N W
I
I
I I
I I
1.Approved set of plans must be on site at the time of inspection.
Failure to provide the approved set may result in a re -inspection
fee. System drain(s) required at riser and must drain to the
exterior. If riser is above lowest grade, 2nd drain required and
signage at riser indicating location. Systems require signage IAW
NFPA 13D.
2.Coverage required to the following areas: Clothes closets, linen
closets and pantries exceeding 24 square feet in area, with the
smallest dimension greater the 3' and having wall and ceiling
surfaces of gypsum board. Bathrooms more than 55 square feet
in area. When fuel fired equipment is present on covered decks or
porches, or if living space above, at least one quick -response
intermediate temperature sprinkler shall be installed above the
equipment or area under living space. All fuel fired appliances,
except attics if above all living areas.
3.Residential 13R add: Vertical back flow preventer must be
tested annually. Strongly recommend system be monitored by fire
GENERAL NOTES:
1
THIS SYSTEM
IS
DESIGNED PER SPRINKLER MANUFACTURER'S LISTING.
SEE ATTACHED CUT SHEETS FOR MANUFACTURER'S MIN. REQUIREMENTS.
A TOTAL OF
(2)
HEADS OPERATING USING RESIDENTIAL, CONCEALED.
2
INSTALLATION
TO
CONFORM WITH NFPA #13D & EDMONDS FIRE DEPT.
3
ALL MATERIAL
TO BE NEW, U.L. LISTED, AND PER NFPA #13.
4
ALL FITTINGS
TO
BE CPVC U.N.O.
5
ALL PIPE TO
BE
CPVC U.N.O.
NFPA 13 D
6
PROTECTION
OF
HEADS FROM PAINT BY OTHERS.
7
. ALL ELECTRICAL
WIRING BY OTHERS.
HYDRAULIC CALCULATIONS ARE BASED ON TWO
SPRINKLER HEADS SPACED AT 16'x16' MAXIMUM.
90 ELBOW
rOR
PTO SYSTEM
PRESSURE GAUGE
SPARE HEAD CABINET
W/ HEADS & WRENCH
Q
LO W C (OPTIONAL)
No Bell Required
Drain valve
TO DOMESTIC
NOR -TECH WORK BEGINS
CONTROL VALVE
BOR
1 RISER RM FINISH FLOOR
Maximum Water pressure 80 psi
SIPPLY
Flow-Thru
Riser Detail
A 112' OUTLET WITH
POINT OF CONNECTION FOR DOMESTIC SUPPLY TO 112' POTABLE PLUG
WATER CLOSET/LAVATORY. POC TO BE LEFT WITH 1/2 AT 6 FT, A,F,F,
POTABLE PLUG TO BE REMOVED BY PLUMBER TO
MAKE CONNECTION AFTER HYDROSTATIC TESTING & NOR -TECH TO PIPE
ROUGH -IN INSPECTED WITH FIRE MARSHAL. PLUMBER DOWN TO 6'-0' A.F.F.
TO USE ONLY CPVC COMPATIBLE CONNECTION. DO NOT WITH 112' OUTLET &
OVER TIGHTEN. 112' POTABLE PLUG
� I
N �1112' WATER LINE
r Plan
I I 1 " WATER wN0 I
METER Approved
PROPERTY LINE
DFM Chr%s gust
wril
South County Fire
Date: 11 /03/2021
1" COPPER
PUBLIC MAIN
CC
11-03-2021
PLAN REVIEW
Approved with condition:
1. System must drain to
exterior.
DFM Burt
CONDITION: System
must drain to the
exterior.
FIR2021-0117
RECEIVED
Nov 02 2021
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
�r�rrrrrrrrrrrr��rrrrrrrrrrrrR
i wASI Mu"w! WAVE ;
OLRTIFIoATE aF oaerP+r
FIRE M W 11112QTIt11! Sr UIN KL}7l SIVOTEltli
Khosrow (David) Farahani T_
a 7325-0195-C Lavel 3 N E
Nor -Tech Fire Protection, Inc. N R
NORTEFPa51P6 !so
-?AA11=11-1
attx� iRAilli
�.. _ a
WATER FLOW INFORMATION:
STATIC: 105 PSI
WATER DEPARTMENT JURISDICTION: EDMONDS
HANGER LEGEND
STANDARD SYMBOLS
SPRINKLER
HEAD
SYMBOLS
MK
DATE
BY
REVISIONS - LOCATE BY GRID COORDINATES
FIELD INSPECTION BY
PHONE
CONTRACT WITH
xxx
NORTH
PROJECT Wardak Residence
ADDRESS: 541 12th Ave North
CITY Edmonds, WA 98020
SPRINKLERS
SYMB.
MODEL
ID #
THREAD
"K"
FINISH
ESCUTCH.
TYPE
DEGREE
QTY.
1.Edmonds Fire Dept.
xx
2
xxxx
VIKING RESIDENTIAL SPRINKLER
®
VK494
20759
1 /z'
4,9
BRASS
WHITE
CONC.
200°
14
.
3.
CITY
4.
123
TITLE: FIRE SPRINKLER PLAN
WATER DEPT.
ARCHITECThe Leren Company
®- ®
NOR -TECH FIRE PROTECTION INC.
DESIGNED:
D.F.
DATE:
11 /2/21
21 TRACT # 5
20030 NE Novelty Hill Road -Box B
REDMOND, WASHINGTON 98053
425-898-9111 FAX: 425-898-7772
LICENSE NO. NORTEFP051P6
ADDRESS
P.O. Box 12863
CITY
CITY Mill Creek, WA 98082
SHEEP N0.
FP-1 of 2
TOTAL
SPRINKLERS
THIS
DRAWING
14
PHONE
PHONE 206-954-4145
SCALE:
1/4"=1'-0"
Composite Wood Joist \
NB-1 Headset Mounting Bracket
and No Block Hanger
Offset Hanger
Headset
Gyp. Board Ceiling
CPVC HANGER DETAIL "A"
Wood Joist
NB-2 Headset Mounting Bracket
and No Block Hanger
Offset Hanger
c
z
c
Headset
/ Gyp. Board Ceiling
CPVC HANGER DETAIL "B"
ATTIC
FIRE SPRINKLER PIPE
(ON WARM SIDE OF INSULATION).
(D4
/_ INSULATION (::
3
TRUSS AND
GYPSUM WALL
BOARD CEILING
SPRINKLER PPE IN THE ATTIC
NO SCALE
HYDRAULIC CALCULATIONS ARE BASED ON TWO
SPRINKLER HEADS SPACED AT 16'x16' MAXIMUM.
ALERT FOR CONTRACTORS &ALL TRADE...
THIS PROJECT USES BLAZEMASTER PIPE & FITTINGS THAT ARE SPECIFICALLY
FOR FIRE SPRINKLER SYSTEMS. THEY ARE MADE FROM A SPECIALTY
THERMO PLASTIC KNOWN AS POST CHLORINATED POLYVINYL CHLORIDE.
(CPVC) DO NOT USE OR PLACE IN CONTACT ANY MATERIAL THAT ARE
INCOMPATIBLE WITH CPVC SUCH AS PETROLEUM OR SOLVENT BASED
SEALANT, FIRE STOP INSULATION, ETC. PLEASE REFER TO LUBRIZOL FBC
SYSTEM COMPATIBILITY PROGRAM FOR GUIDANCE REGARDING CHEMICAL
COMPATIBILITY OF CERTAIN MATERIALS GO TO BLAZEMASTER.COM
Main Floor Plan
NO. OF SPRINKLERS CALCULATED:
COVERAGE PER SPRINKLER: 16'x16'
DESIGN DENSITY: 10.05 GPM & or per MFG listing
N TOTAL AREA OF DISCHARGE: 512 SF.
MIN. GPM REQUIRED PER HEAD: 13 GPM
TOTAL SPRINK DEMAND AT B.O.R. 26.4 GPM @ 35.7 PSI
AVAILABLE AT THE B.O.R. 126.4 GPM @ 93.2 PSI
�rrrrrrrrrrrrrrrrrrrrrrrrrrrrR
WAMI1111me lMl a'ra"
elRTIFIOAT@ nF coupe IBOV
FIRE 110111111101111201 4 WRIMKLER •TSTEP
Khosrow (David) Farahani N f
7325-0195-C Luvel3 N a
Nor -Tech Fire Protection, Inc, N e
NORTEFP051PS o !in
•
14Ri7li ��
WATER FLOW INFORMATION:
STATIC: 105 PSI
WATER DEPARTMENT JURISDICTION: EDMONDS
HANGER LEGEND
STANDARD SYMBOLS
SPRINKLER
HEAD
SYMBOLS
MK
DATE
BY
REVISIONS — LOCATE BY GRID COORDINATES
FIELD INSPECTION BY
PHONE
CONTRACT WITH
O'Dell Homes
NORTH
PROJECT
Wardak Residence
ADDRESS: 541 12th Ave North
CITY Edmonds, WA 98020
SPRINKLERS
SYMB.
MODEL
ID #
THREAD
"K"
FINISH
ESCUTCH.
TYPE
DEGREE
QTY.
1.Edmonds Fire Dept.
xx
2.
xxxx
VIKING RESIDENTIAL SPRINKLER
®
VK494
20759
1 /z'
4,9
BRASS
WHITE
CONC.
200°
24
3.
CITY
4.
123
TITLE: FIRE SPRINKLER PLAN
WATER DEPT.
ARCHITECThe Leren Company
® _ ®
NOR —TECH FIRE PROTECTION INC.
DESIGNED:
D.F.
DATE:
11 /2/21
21 TRACT # 5
20030 NE Novelty Hill Road —Box B
REDMOND, WASHINGTON 98053
425-898-9111 FAX: 425-898-7772
LICENSE NO. NORTEFP051P6
ADDRESS
P.O. Box 12863
CITY
CITY Mill Creek, WA 98082
SHEEP N0.
FP-2 of 2
TOTAL
SPRINKLERS
THIS
DRAWING
24V\I
PHONE
PHONE 206-954-4145
SCALE:
1/4"=1'-0"