Loading...
REVIEWED FIR FIR2021-0117+Calculations+10.22.2021_2.29.03_PM+2478875'u , zattmr�,..rexaae�"�s"s Hydraulic Calculations FOR: Wardak Residence 541 12th Avenue North Edmonds, WA 98020 Design Data: Occupancy Classification: Light Hazard Standard: NFPA 13D Density: 0.05 gpm/SF or per MFG listing Area of application: Kitchen Area Coverage of sprinklers: 16'x16' Max. Number of sprinklers calculated: (2) Heads Total Sprinkler Water Flow Demand at BOR: 26.4 gpm @ 35.7 PSI Flow & Pressure Available at B.O.R: 26.4 gpm @ 93.2 PSI Sprinkler make & model: Viking model VK494 Residential Concealed Sprinkler Thread: 1/Z" NPT Sprinkler "K" Factor: 4.9 Design Layout: D.F. Date: October 22, 2021 '................... ■..■... .■.� WASNINCTtAM STATE CERTIFICATE OF COMPETENCY ; FIRE PROTECTION SPRINKLER SVOTEMS Khosrow (David) Farahani j a 7325-0195-C Level Nor -Tech Fire Protection, Inc. NORTEFPO 6 � v � 9 L-2 1'1Yli 1 120.0 I G 100.0 A U G E 80.0 P R E S 60.0 S U R E 40.0 P s 1 20.0 0.0 -14.7 WATER SUPPLY ANALYSIS Static: 105.00 psi Resid: 20.00 psi Flow: 1000.0 gpm FLOW (GPM) Note: (1) Dashed Lines indicate extrapolated values from Test Results (2) On Site pressures are based on hose stream deduction at the source C-1 d O > lJ H tJ y .. H �3 H r o tJ � •• N N N N Ij O ¢ N N H 7d Co N- b ¢ 7d (D H (� x (D r M Cn z H Co F-c H Co N i-3 (t t �3, n � � x (D d Co 7d z � t7 C', 5 > n o / � N � ¢ O Z (j] N H r He �E C-1 W O H 0 O 00 / N � O ,d C7 x / z d � b x w W d � H SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 10/22/2021 C:\HASSDATA\2021 JOBS\WARDAK\WARDAK.SDF JOB TITLE: Wardak Residence 541 12th Ave N Edmonds, WA 98020 NFPA WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) CC 105.0 20.0 1000.0 104.9 26.4 47.4 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 26.4 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM OTHER HOSE STREAM ALLOWANCES 0.0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 26.4 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) 201 19.5 K= 4.90 7.0 13.0 202 19.5 K= 4.90 7.5 13.4 203 19.5 - - - - 9.2 - - - 200 19.5 - - - - 13.0 - - - 100 9.5 - - - - 20.5 - - - TOR 9.5 - - - - 21.6 - - - FSO 6.0 - - - - 23.6 - - - FSI 6.0 - - - - 26.6 - - - BFO 2.0 - - - - 28.7 - - - BFI 2.0 - - - - 34.7 - - - BOR 1.0 - - - - 35.7 - - - UGE -3.0 - - - - 38.8 - - - WMO -3.0 - - - - 38.8 - - - WMI -3.0 - - - - 43.8 - - - CC 1.0 SOURCE 47.4 26.4 NOTES SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 10/22/2021 C:\HASSDATA\2021 JOBS\WARDAK\WARDAK.SDF JOB TITLE: Wardak Residence 541 12th Ave N Edmonds, WA 98020 NFPA PIPE DATA Pipe Tag K-fac Add F1 Add F1 To Fit: L C (Pt) Frm Node E1 (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) To Node E1 (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf) Pipe: 1 4.90 13.0 Disch 13.83 150 0.4 202 19.5 7.5 0.0 F1.000 ---- 0.00 -0.0 201 19.5 7.0 13.0 1.101 13.83 0.031 0.4 Pipe: 2 4.90 13.4 Disch 10.58 150 1.8 203 19.5 9.2 13.0 F1.000 T: 5.0 5.00 -0.0 202 19.5 7.5 26.4 1.101 15.58 0.114 1.8 Pipe: 3 0.0 0.0 28.50 150 3.8 200 19.5 13.0 26.4 202 F1.000 1: 5.0 5.00 -0.0 203 19.5 9.2 26.4 1.101 33.50 0.114 3.8 Pipe: 4 0.0 0.0 15.25 150 7.4 100 9.5 20.5 26.4 203 F1.000 E: 7.0 12.00 4.3 200 19.5 13.0 26.4 1.101 T: 5.0 27.25 0.114 3.1 Pipe: 5 0.0 0.0 3.33 150 1.2 TOR 9.5 21.6 26.4 200 F1.000 E: 7.0 7.00 -0.0 100 9.5 20.5 26.4 1.101 10.33 0.114 1.2 Pipe: 6 0.0 0.0 3.50 150 1.9 FSO 6.0 23.6 26.4 100 F1.000 ---- 0.00 1.5 TOR 9.5 21.6 26.4 1.101 3.50 0.114 0.4 Pipe: 7 0.0 Fixed Pressure Loss Device FSI 6.0 26.6 26.4 TOR 3.0 psi, 26.4 gpm FSO 6.0 23.6 26.4 Pipe: 8 0.0 0.0 4.00 150 2.2 BFO 2.0 28.7 26.4 FSO F1.000 ---- 0.00 1.7 FSI 6.0 26.6 26.4 1.101 4.00 0.114 0.5 Pipe: 9 0.0 Fixed Pressure Loss Device BFI 2.0 34.7 26.4 FSI 6.0 psi, 26.4 gpm BFO 2.0 28.7 26.4 Pipe: 10 0.0 0.0 5.00 150 1.0 BOR 1.0 35.7 26.4 BFO F1.000 ---- 0.00 0.4 BFI 2.0 34.7 26.4 1.101 5.00 0.114 0.6 Pipe: 11 0.0 0.0 4.50 150 3.0 UGE -3.0 38.8 26.4 BFI F1.000 E: 7.0 7.00 1.7 BOR 1.0 35.7 26.4 1.101 11.50 0.114 1.3 Pipe: 12 0.0 0.0 1.00 150 0.0 WMO -3.0 38.8 26.4 BOR 1.500 ---- 0.00 -0.0 UGE -3.0 38.8 26.4 1.598 1.00 0.019 0.0 Note SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE: 10/22/2021 C:\HASSDATA\2021 JOBS\WARDAK\WARDAK.SDF JOB TITLE: Wardak Residence 541 12th Ave N Edmonds, WA 98020 Pipe Tag K-fac Add F1 Add F1 To Fit: L C (Pt) Frm Node E1 (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Note To Node E1 (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf) Pipe: 13 0.0 Fixed Pressure Loss Device WMI -3.0 43.8 26.4 UGE 5.0 psi, 26.4 gpm WMO -3.0 38.8 26.4 Pipe: 14 Source 0.0 E: 2.0 20.00 150 3.6 CC 1.0 47.4 26.4 WMO K1.000 T: 6.0 8.50 -1.7 WMI -3.0 43.8 26.4 0.995 G: 0.5 28.50 0.187 5.3 NOTES (HASS): (1) Calculations were performed by the HASS 2021 D computer program in accordance with NFPA13 (2016) under license no. 64625258 granted by HRS Systems, Inc. 208 Southside Square Petersburg, TN 37144 (931) 659-9760 (2) The system has been calculated to provide an average imbalance at each node of 0.015 gpm and a maximum imbalance at any node of 0.200 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 10.9 ft/sec at pipe 14. (4) Items listed in bold print on the cover sheet are automatically transferred from the calculation report. (5) PIPE FITTINGS TABLE User Pipe Table Name: custom PAGE: F MATERIAL: CPVC HWC: 150 Diameter Equivalent Fitting Lengths in Feet (in) E T R C B G A D F Ell Tee T-RUN 1.101 7.00 5.00 1.00 5.00 6.00 1.00 10.00 10.00 0.00 1.598 9.00 8.00 1.00 9.00 6.00 1.00 10.00 10.00 0.00 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE: 10/22/2021 C:\HASSDATA\2021 JOBS\WARDAK\WARDAK.SDF JOB TITLE: Wardak Residence 541 12th Ave N Edmonds, WA 98020 PAGE: K MATERIAL: CT-K HWC: 150 Diameter Equivalent Fitting Lengths in Feet (in) E T F R C S G N Ell Tee 45-El TeeRu Coupl SwgCh GatVl NPTee 0.995 2.00 6.00 1.00 0.00 0.00 4.50 0.00 4.50