BLD2022-0896_Other_7.8.2022_1.39.14_PM_2978111Generation Solaria Power XT Module 40OR-PM Output 400 W Max Production 15.2 kW Total Modules 38 V(oc) 45.13 V I(sc) 10.5 A EnphaselO 8A Max Output: 366W AC Output Voltage: 240 V AC Max Output Current: 1.45 A Rapid Shut Down Compliant Rating : 125A : 240V Ac Main Lug 2P20A x 4 Solar Strings 38 x 1.45A x 1.25A = 68.9 A PV / Ba ery Disconne Rapid Shutdown Switch [Located adjacent to Net Meter EP20OG-NA-02-RSD Enpower (ATS) 200A Auto Transfer Switch PV OCPD : 2P70A Battery OCPD : 2P30A With Hold down 100A CSR Eaton Main Breaker Main Lug Load Output NEC 2020 Single Line 15.2 kW Photovoltaic Solar System 13.91 kW Max AC output String 1 String 2 String 3 String 3 8 8 11 11 Modules Modules Modules Modules #6 EGC Inverters Inverters Inverters Inverters 4x2#12 ----- ------ ----- ----- Conductors #12 EGC THHN PV AC Combiner LRS 4 #12 Conductors #12 EGC r THHN 3 #6 Conductors Enpower #10 EGC (ATS) THHN PLP I]] 3 #8 Conductors Encharge #10 EGC 10kWh THHN < 5 ft Encharge 3kWh 3 #4 Conductors #10EGC THHN Service Meter O T plySide nection 1 3#3 Conductors THHN House Panel i -10ft i i i i �------------------- 7 i #6 EGC — LoadsProtected 100A Bus Rating : 240V Rating : 200A : 240V Ac Continuous Output : 5.12 kVA Located Adjacent to Enpower Main Breaker 2P60A Main Breaker: 2P200A W/ Hold Down Enpower qualifies as Encharge Disconnect Ryan DeVinaspre 7515 Braemar Dr, Edmonds, WA 98026 Blossom Solar LLC (425) 610-7067 info@blossomsolar.com