EOR Field ReportRDEI DIBBLE ENGINEERS INC DATE: May 17, 2022 TO: Sam & Joyce Lu, Homeowners EMAIL: snllu()comcast.net CC: Travis Colliander, PE SE FROM: Michael Doquilo, EIT PROJECT: Lu Kitchen Remodel DEI JOB #: 20-498 Project Description STRUCTURAL EVALUATION Dibble Engineers, inc. (DEI) previously provided a site visit report for the Lu Kitchen Remodel project on January 29, 2021. The site is located at 18104 88th Ave W., Edmonds, WA 98026. Since completion of the project, the City has requested approval of the installation of structural members. The client has opted for reopening the wall to expose the framing and a review of the completed remodel by DEI. This memo presents DEI's review of the completed project. UU=1 VdUUI i DEI was provided photos of the exposed framing by the client, and subsequent retrofits by the client. See attached to this letter. Where the wall was proposed to be removed, an existing pipe was discovered. To leave the pipe in place, the contractor opted to install a new 6x10 beam approximately 5'-6" long at the new opening in lieu of the previously specified glulam beam. The new 6x10 beam is supported on both sides with (2) 2x6 jack studs and a king stud. The existing glulam is supported with an existing 6x6 post. At the ceiling in the garage below the area of work, the ceiling was opened to expose the joist bays below the existing 6x6 and new (2) 2x6 post. Blocking was not observed between the joists as previously specified. conclusions & Recommendations DEI analyzed the alternate 6x10 that was installed and found that it has sufficient capacity to support the loads above. At the floor, blocking was not added per the previously provided SK-2. To provide solid bearing for the posts to transfer their loads to the beam below, new 2x12 blocking was added in the joist bays per the attached Revised SK-2. Based on the photos provided by the client, the work completed was generally acceptable to the specifications provided. No further retrofit should be necessary at this project. Lu Kitchen Remodel it DEI DEI Job #20-498 I'LDIBBLE ENGINEERS INC May 13, 2022 OisclgimP Dibble Engineers review is limited to the areas accessible and readily visible. Dibble Engineers did not conduct a building analysis for either vertical or lateral loads other than described above. Our review and discussion summary does not provide warranty either expressed or implied to the existing conditions or work completed subsequent our visit. cc: Travis Colliander, PE SE Attachments: Revised SK-2, Calculations PAGE 2OF4 It DEI jj.DIBBLE ENGINEERS INC Photo 3 Lu Kitchen Remodel DEI Job #20-498 May 13, 2022 PAGE 3OF4 Joist bays below (E) 6x6 and (N) studs above. Joist bay below (E) 6x6 post. Additional 2x12 blocking per revised SK-2'.' Additional 2x12 blocking per revised SK-2 below (E) 6x6 post. below (N) 2x6 studs. ?--V:q-w<<s to4,i PROJECT NAME SHEET# D E I PROL-.L^ -_ -- � JECT # DATE DIBBLE ENGINEERS INC SUBJECT BY �b �4�� C �) dos T 1N- , �Ll P P vile 1-0 T-1T" W/ (4) %�6 x 9- %" } SFG-n oN W, SU, I I3LAC6 z) R,4:cl,.. Vl Dibble Engineers, Inc. Project Title: 1029 Market Street Engineer: Kirkland, WA 98033 Project ID: (424) 828-4200 Project Descr: DEI Wood Beam Project File: Lu Kitchen Remodel.ec6 LIC# : KW-06014989, Build:20.22.4.26 DIBBLE ENGINEERS INC. (c) ENERCALC INC 1983-2022 DESCRIPTION: (N) HDR CODE REFERENCES Calculations per NDS 2015, IBC 2015, CBC 2016, ASCE 7-10 Load Combination Set: ASCE 7-16 Material Properties Analysis Method : Allowable Stress Design Load Combination ASCE 7-16 Wood Species Douglas Fir -Larch Wood Grade No.1 Beam Bracing : Beam is Fully Braced against lateral -torsional buckling Fb + 1350 psi E : Modulus of Elasticity Fb - 1350 psi Ebend- xx 1600 ksi Fc - Prll 925 psi Eminbend - xx 580ksi Fc - Perp 625 psi Fv 170 psi Ft 675 psi Density 31.21 pcf 6x10 Span = 5.50 ft Applied Loads Service loads entered. Load Factors will be applied for calculations. Beam self weight calculated and added to loading Uniform Load : D = 0.0150, L = 0.040 ksf, Tributary Width = 11.250 ft, (Floor Load) Uniform Load : D = 0.0150, Lr = 0.020, S = 0.0250 ksf, Extent = 0.0 -->> 5.50 ft, Tributary Width = 11.50 ft, (Potential Roof Loac DESIGN SUMMARY • Maximum Bending Stress Ratio = 0.326 1 Maximum Shear Stress Ratio = 0.267 : 1 Section used for this span 6x10 Section used for this span 6x10 fb: Actual = 440.19psi fv: Actual = 45.32 psi Fb: Allowable = 1,350.00psi Fv: Allowable = 170.00 psi Load Combination +D+L Load Combination +D+L Location of maximum on span = 2.750ft Location of maximum on span = 4.717 ft Span # where maximum occurs = Span # 1 Span # where maximum occurs = Span # 1 Maximum Deflection Max Downward Transient Deflection 0.015 in Ratio = 4452 > 480 Span: 1 : L Only Max Upward Transient Deflection 0 in Ratio = 0 <480 n/a Max Downward Total Deflection 0.030 in Ratio = 2212 > 360 Span: 1 : +D+0.750L+0.750S Max Upward Total Deflection 0 in Ratio = 0 <360 n/a Maximum Forces & Stresses for Load Combinations Load Combination Max Stress Ratios Moment Values Shear Values Segment Length Span # M V Cd CF/V Ci Cr Cm C t CL M fb F'b V fv F'v D Only 0.00 0.00 0.00 0.00 Length = 5.50 ft 1 0.159 0.130 0.90 1.000 1.00 1.00 1.00 1.00 1.00 1.33 193.38 1215.00 0.69 19.91 153.00 +D+L 1.000 1.00 1.00 1.00 1.00 1.00 0.00 0.00 0.00 0.00 Length = 5.50 ft 1 0.326 0.267 1.00 1.000 1.00 1.00 1.00 1.00 1.00 3.03 440.19 1350.00 1.58 45.32 170.00 +D+Lr 1.000 1.00 1.00 1.00 1.00 1.00 0.00 0.00 0.00 0.00 Length = 5.50 ft 1 0.189 0.155 1.25 1.000 1.00 1.00 1.00 1.00 1.00 2.20 319.53 1687.50 1.15 32.90 212.50 +D+S 1.000 1.00 1.00 1.00 1.00 1.00 0.00 0.00 0.00 0.00 Length = 5.50 ft 1 0.226 0.185 1.15 1.000 1.00 1.00 1.00 1.00 1.00 2.42 351.07 1552.50 1.26 36.15 195.50 +D+0.750Lr+0.750L 1.000 1.00 1.00 1.00 1.00 1.00 0.00 0.00 0.00 0.00 Length = 5.50 ft 1 0.280 0.229 1.25 1.000 1.00 1.00 1.00 1.00 1.00 3.26 473.10 1687.50 1.70 48.71 212.50 +D+0.750L+0.750S 1.000 1.00 1.00 1.00 1.00 1.00 0.00 0.00 0.00 0.00 Length = 5.50 ft 1 0.320 0.262 1.15 1.000 1.00 1.00 1.00 1.00 1.00 3.42 496.75 1552.50 1.78 51.15 195.50 Dibble Engineers, Inc. Project Title: 1029 Market Street Engineer: Kirkland, WA 98033 Project ID: (424) 828-4200 Project Descr: DEI Wood Beam Project File: Lu Kitchen Remodel.ec6 LIC# : KW-06014989, Build:20.22.4.26 DIBBLE ENGINEERS INC. (c) ENERCALC INC 1983-2022 DESCRIPTION: (N) HDR Maximum Forces & Stresses for Load Combinations Load Combination Max Stress Katios Moment Values Shear Values Segment Length Span # M V Cd CF/V C i Cr Cm C t CL M fb F'b V fv F'v +0.60D 1.000 1.00 1.00 1.00 1.00 1.00 0.00 0.00 0.00 0.00 Length = 5.50 ft 1 0.054 0.044 1.60 1.000 1.00 1.00 1.00 1.00 1.00 0.80 116.03 2160.00 0.42 11.95 272.00 Overall Maximum Deflections Load Combination Span Max. "-" Defl Location in Span Load Combination Max. "+" Defl Location in Span +D+0.750L+0.750S 1 0.0298 2.770 0.0000 0.000 Vertical Reactions Support notation : Far left is #1 Values in KIPS Load Combination Support 1 Support 2 Overall MAXimum 2.491 2.491 Overall MINimum 0.791 0.791 D Only 0.970 0.970 +D+L 2.207 2.207 +D+Lr 1.602 1.602 +D+S 1.760 1.760 +D+0.750Lr+0.750L 2.372 2.372 +D+0.750L+0.750S 2.491 2.491 +0.60D 0.582 0.582 Lr Only 0.633 0.633 L Only 1.238 1.238 S Only 0.791 0.791 Dibble Engineers, Inc. 1029 Market Street Kirkland, WA 98033 (424)828-4200 DEI Project Title: Engineer: Project ID: Project Descr: Wood Column Project File: Lu Kitchen Remodel.ec6 DESCRIPTION: Check (2) Studs Code References Calculations per NDS 2015, IBC 2015, CBC 2016, ASCE 7-10 Load Combinations Used : ASCE 7-16 General Information Analysis Method Allowable Stress Design Wood Section Name 2-2x6 End Fixities Top & Bottom Pinned Wood Grading/Manuf. Graded Lumber Overall Column Height 10 ft Wood Member Type Sawn (Used for non -slender calculations) Exact Width 3.in Allow Stress Modification Factors Wood Species Hem -Fir Exact Depth 550 in Cf or Cv for Bending 1.30 Wood Grade No.2 .50 Area 16.50 inA2 Cf or Cv for Compressioi 1.10 Fb + 850 psi Fv 150 psi Ix 41.594 inA4 Cf or Cv for Tension 1.30 Fb - 850 psi Ft 525 psi ly 12.375 in 4 Cm :Wet Use Factor 1.0 Fc - Prll 1300 psi Density 26.84 pcf Ct : Temperature Faci 1.0 Fc - Perp 405 psi Cfu : Flat Use Factor 1.0 E : Modulus of Elasticity ... x-x Bending y-y Bending Axial Kf : Built-up columns 1.0 NDS 15.3.2 Basic 1300 1300 1300 ksi Use Cr: Repetitive ? No Minimum 470 470 Brace condition for deflection (buckling) along columns : X-X (width) axis: Fully braced against buckling ABOUT Y-Y Axis Y-Y (depth) axis : Unbraced Length for buckling ABOUT X-X Axis = 10 ft, N Applied Loads Service loads entered. Load Factors will be applied for calculations. Column self weight included : 30.754 Ibs * Dead Load Factor AXIAL LOADS ... RXN (N) HDR: Axial Load at 10.0 ft, D = 2.207, Lr = 0.6330, L = 1.238, S = 0.7910 k DESIGN SUMMARY Bending & Shear Check Results PASS Max. Axial+Bending Stress Ratio = 0.3229 : 1 Maximum SERVICE Lateral Load Reactions. . Load Combination +D+0.750L+0.750S Top along Y-1 0.0 k Bottom along Y-Y 0.0 k Governing NDS Forumla Comp Only, fc/Fc' Top along X-)� 0.0 k Bottom along X-X 0.0 k Location of max.above base 0.0 ft Maximum SERVICE Load Lateral Deflections ... At maximum location values are . Along Y-Y 0.0 in at 0.0 ft above base Applied Axial 3.760 k for load combination : n/a Applied Mx 0.0 k-ft Applied My 0.0 k-ft Along X-X 0.0 in at 0.0 ft above base Fc: Allowable 705.55 psi for load combination : n/a Other Factors used to calculate allowable stresses ... PASS Maximum Shear Stress Ratio = 0.0 : 1 Bending Compression Tension Load Combination +0.60D Location of max.above base 10.0 ft Applied Design Shear 0.0 psi Allowable Shear 240.0 psi Load Combination Results Maximum Axial + Bending Stress Ratios Maximum Shear Ratios Load Combination C D C P Stress Ratio Status Location Stress Ratio Status Location D Only 0.900 0.519 0.2031 PASS 0.0 ft 0.0 PASS 10.0 ft +D+L 1.000 0.479 0.3073 PASS 0.0 ft 0.0 PASS 10.0 ft +D+Lr 1.250 0.401 0.2430 PASS 0.0 ft 0.0 PASS 10.0 ft +D+S 1.150 0.429 0.2602 PASS 0.0 ft 0.0 PASS 10.0 ft +D+0.750Lr+0.750L 1.250 0.401 0.3082 PASS 0.0 ft 0.0 PASS 10.0 ft +D+0.750L+0.750S 1.150 0.429 0.3229 PASS 0.0 ft 0.0 PASS 10.0 ft +0.60D 1.600 0.324 0.1099 PASS 0.0 ft 0.0 PASS 10.0 ft Dibble Engineers, Inc. 1029 Market Street Kirkland, WA 98033 (424) 828-4200 DEI Project Title: Engineer: Project ID: Project Descr: Wood Column Project File: Lu Kitchen Remodel.ec6 DESCRIPTION: Check (2) Studs Maximum Reactions Note: Only non -zero reactions are listed. X-X Axis Reaction k Y-Y Axis Reaction Axial Reaction My - End Moments k-ft Mx - End Moments Load Combination @ Base @ Top @ Base @ Top @ Base @ Base @ Top @ Base @ Top D Only 2.238 +D+L 3.476 +D+Lr 2.871 +D+S 3.029 +D+0.750Lr+0.750L 3.641 +D+0.750L+0.750S 3.760 +0.60D 1.343 Lr Only 0.633 L Only 1.238 S Only 0.791 Maximum Deflections for Load Combinations Load Combination Max. X-X Deflection Distance Max. Y-Y Deflection Distance D Only 0.0000 in 0.000ft 0.000 in 0.000ft +D+L 0.0000 in 0.000ft 0.000 in 0.000ft +D+Lr 0.0000 in 0.000ft 0.000 in 0.000ft +D+S 0.0000 in 0.000ft 0.000 in 0.000ft +D+0.750Lr+0.750L 0.0000 in 0.000ft 0.000 in 0.000ft +D+0.750L+0.750S 0.0000 in 0.000ft 0.000 in 0.000ft +0.60D 0.0000 in 0.000ft 0.000 in 0.000ft Lr Only 0.0000 in 0.000ft 0.000 in 0.000ft L Only 0.0000 in 0.000ft 0.000 in 0.000ft S Only 0.0000 in 0.000ft 0.000 in 0.000ft Sketches 3.0 in +X