BLD2022-1037_Manufacturer_Specifications_and_Installation_Instructions_8.5.2022_10.40.40_AM_3035098Air Conditioning & Heating
HE4TING INPUT: 40,000-120,000 BTU/H
4
Standard Features
• Heavy-duty aluminized -steel dual -
diameter tubular heat exchanger
• Single -stage gas valve
• Durable Hot -surface igniter
• Quiet, single -speed draft induced
• Self -diagnostic control board
• Color -coded low -voltage terminals
• Multi -speed ECM blower motor
• California Low NOx emissions models available
• Can no longer be installed in California's
South Coast Air Quality Management District
(SCAQMD) on or after October 1, 2019.
• AHRI Certified; ETL Listed
GMES801GCES80
SINGLE -STAGE, MULTI -SPEED ECM,
MULTI -POSITION GAS FURNACE
80% AFUE
Contents
Nomenclature ........................................
2
Product Specifications ...........................
3
Dimensions ............................................
5
Airflow Data...........................................7
Wiring Diagrams..................................15
Accessories..........................................16
Minimum Filter Sizes ..........................16
Cabinet Features
• Installation:
— GMES80-upflow,
horizontal left or right
— GCES80- downflow,
horizontal left or right
• Convenient left or right connection
for gas and electrical service
• Heavy -gauge steel cabinet with
durable baked -enamel finish
• Foil faced insulated heat exchanger
LIFETIME 2 UNIT 10
PARTS ETA L CDMPANV WITH COMPANY WITH
HEAT EXCHANDER LIMITED C IY US ..ALITY SYSTEM ENVIRGNMENTALSYSTEM
LIMITED CERTIFIEDRY DNVGL CERTIFIEDRYDNVGL
LIMITED WARRANTY' YEAR WARRANTY' YEAR WARRANTY' `""=1509001==13019001=
Intertek
* Complete warranty details available from your local dealer or at www.goodmanmfg.com.ToreceivetheLifetimeHeatExchangerLimitedWarrant, BBB.
(good for as long as you own your home), 2-Year Unit Replacement Limited Warranty and 10-Year Parts Limited Warranty, online registration must
be completed within 60 days of installation. Online registration is not required in California or Quebec.
SS-GMES80/13CES80 www.goodmanmfg.com 2/21
Supersedes 2/20
NOMENCLATURE
G M V
C
80 040
4
C * **
4
5,6 7,8,9
1 2 3
10
11 12 13,14
BRAND
ENGINEERING
G- Goodman® Brand
Major /Minor Revisions
* Not used for inventory control.
CONFIGURATION
NOX
M- Upflow/Horizontal
N- Natural Gas
C- Downflow/Horizontal
X- Low NOx
MOTOR
CABINET WIDTH
V- Variable Speed ECM / ComfortBridge-
A- 14" C- 21"
E- Multi -Speed ECM S- Single Speed
B- 17W' D- 24X"
GAS VALVE
MAXIMUM CFM
M- Modulating S- Single Stage
2- 800 CFM 4- 1600 CFM
C- Two Stage
3- 1200 CFM 5- 2000 CFM
AFUE
MBTU/H
80- 80% AFU E
040- 40,000 BTU/h 100- 100,000 BTU/h
060- 60,000 BTU/h 120- 120,000 BTU/h
080- 80,000 BTU/h 140- 140,000 BTU/h
2 www.goodmanmfg.com SS-GMES80/GCES80
GMES80 PRODUCT SPECIFICATIONS
:0
HEATING CAPACITY
Input
40,000
60,000
60,000 60,000
80,000
80,000
80,000
80,000
100,000
120,000
Natural Gas Output
32,000
48,000
48,000 48,000
64,000
64,000
64,000
64,000
80,000
96,000
LP Gas Output
32,000
48,000
48,000 48,000
64,000
64,000
64,000
64,000
80,000
96,000
AFUE'
80
80
80 80
80
80
80
80
80
80
Available AC @ 0.5" ESP
3
3
3 4
3
4
4
5
5
5
Temperature Rise Range(°F)
25-55
20-50
20-50 20-50
35-65
35-65
35-65
35-65
35-65
40-70
CIRCULATOR BLOWER
Size (D x W)
10" x 6"
10" x 6"
10" x 8"
10" x 8"
10" x 8"
10" x 8"
10" x 10"
10" x 10"
10" x 10"
11" x 10"
Horsepower @1075 RPM
0.5
0.5
0.5
0.75
0.5
0.75
0.75
0.75
0.75
1
Speed
5
5
5
5
5
5
5
5
5
5
Vent Diameter Z
4"
4"
4"
4"
4"
4"
4"
4"
4"
4"
No. of Burners
2
3
3
3
4
4
4
4
5
6
ELECTRICAL DATA
Min. Circuit Ampacity s
8.7
8.7
8.7
12.45
8.7
12.45
12.45
12.45
12.45
15.3
Max. Overcurrent Device (amps) °
15
15
15
15
15
15
15
15
15
20
SHIP WEIGHT (LBS)
86
90
100
108
116
120
132
132
132
132
DOE AFUE based upon Isolated Combustion System (ICS)
Z Vent and combustion air diameters may vary depending upon vent length. Refer to the latest editions of the National Fuel Gas Code
NFPA 54/ANSI Z223.1 (in the USA) and the Canada National Standard of Canada, CAN/CSA B149.1 and CAN/CSA B142.2 (in Canada).
s Minimum Circuit Ampacity = (1.25 x Circulator Blower Amps) + ID Blower amps. Wire size should be determined in accordance with
National Electrical Codes. Extensive wire runs will require larger wire sizes.
° Maximum Overcurrent Protection Device refers to maximum recommended fuse or circuit breaker size.
May use fuses or HACR-type circuit breakers of the same size as noted.
NOTES
• All furnaces are manufactured for use on 115 VAC, 60 Hz, single-phase electrical supply.
• Gas Service Connection %" FPT
• Important: Size fuses and wires properly and make electrical connections in accordance with the National Electrical Code and/or all
existing local codes.
SS-GMES80/GCES80 www.goodmanmfg.com
GCES80 PRODUCT SPECIFICATIONS
HEATING CAPACITY
Input
40,000
60,000
80,000
80,000
100,000
Natural Gas Output
32,000
48,000
64,000
64,000
80,000
LP Gas Output
32,000
48,000
64,000
64,000
80,000
AFUE'
80
80
80
80
80
Available AC @ 0.5" ESP
3
3
4
5
5
Temperature Rise Range (°F)
25-55
30-60
35-65
30-60
40-70
CIRCULATOR BLOWER
Size (DxW)
10"X6"
10"X6"
10"X8"
101,X10"
101,X10"
Horsepower @1075 RPM
1/2
1/2
3/4
1
1
Speed
5
5
5
5
5
Vent Diameter z
4"
4"
4"
4"
4"
No. of Burners
2
3
4
4
5
ELECTRICAL DATA
Min. Circuit Ampacity s
8.7
8.7
12.45
15.3
15.3
Max. Overcurrent Device (amps) °
15
15
15
20
20
SHIP WEIGHT (LBS)
90
94
107
115
115
DOE AFUE based upon Isolated Combustion System (ICS)
a Vent and combustion air diameters may vary depending upon vent length. Refer to the latest editions of the National Fuel
Gas Code NFPA 54/ANSI Z223.1 (in the USA) and the Canada National Standard of Canada, CAN/CSA B149.1 and CAN/CSA
B142.2 (in Canada).
a Minimum Circuit Ampacity = (1.25 x Circulator Blower Amps) + ID Blower amps. Wire size should be determined in accor-
dance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
° Maximum Overcurrent Protection Device refers to maximum recommended fuse or circuit breaker size. May use fuses or
HACR-type circuit breakers of the same size as noted.
NOTES
• All furnaces are manufactured for use on 115 VAC, 60 Hz, single-phase electrical supply.
• Gas Service Connection %" FPT
• Important: Size fuses and wires properly and make electrical connections in accordance with the National Electrical Code
and/or all existing local codes.
www.goodmanmfg.com SS-GMES80/GCES80
GMES80 DIMENSIONS
Alternate Gas Inlet Alt. Flue Outlet — Horizontal Left
A
B 19�„
33%"
Alt. Gas Inlet
20 235/e' Alt. High Voltage
0
High -Voltage Inlet
13'/<" is'
Low -Voltage Inlet Alt. Low Voltage
28" 23„
IGMES800403A*
14"
12%"
GMES800603A*
14"
12%"
GMES8006036*
17%"
16"
GMES8006046*
17%"
16"
GMES80080313*
17%"
16"
GMES800804B*
17%"
16"
GMES800804C*
21"
19'/:"
GMES800805C*
21"
19'/:"
GMES801005C*
21"
19'/:"
GMES801205D*
24%"
23"
• Line voltage wiring can enter tnrougn the rignt or iett siae oT Turnace.
Low -voltage wiring can enter through the right or left side of furnace.
• Conversion kits for high -altitude (4500+ft) natural gas operation are available.
Contact your Goodman distributor or dealer for details.
• Installer must supply the following gas line fittings, according to which entrance is used:
Left: One 902 street elbow; one 2%:" pipe nipple; one 909 elbow; straight pipe; one ground joint union
Right: Straight pipe to reach gas valve
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS
24" clearance for serviceability recommended.
z Single Wall Vent (SW) to be used only as a connector. Refer to the latest editions of the National Fuel Gas
Code NFPA 54/ ANSI Z223.1 (in the USA) and the Canada National Standard of Canada, CAN/CSA B149.1 and
CAN/CSA B142.2 (in Canada).
Note: GMES80 approved for line contact in the horizontal position.
SS-GMES80/GCES80 www.goodmanmfg.com 5
GCES80 DIMENSIONS
18 %"
11W,
A
B
33 W
28"
19%g'�
High -Voltage
Electrical
Low -Voltage ,
Electrical
Gas Inlet
00
0
O
o 0 0
NOTES
• Line voltage wiring can enter through the right or left side of furnace.
Low -voltage wiring can enter through the right or left side of furnace.
• Conversion kits for high -altitude (4500+ft) natural gas operation are avail-
able. Contact your Goodman distributor or dealer for details.
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS
24" clearance for serviceability recommended.
Z Single Wall Vent (SW) to be used only as a connector. Refer to the latest editions of the National Fuel Gas
Code NFPA 54/ ANSI Z223.1 (in the USA) and the Canada National Standard of Canada, CAN/CSA B149.1 and
CAN/CSA B142.2 (in Canada).
Note: GMES80 approved for line contact in the horizontal position.
www.goodmanmfg.com SS-GMES80/GCES80
GMES80 HEATING AIRFLOW DATA
CFM & TEMPERATURE RISE v5. EXTERNAL STATIC PRESSURE
EXTERNAL STATIC PRESSURE, (INCHES
WATER COLUMN)
11!G!!!�E
OFF OFF
658 45 603 49 550 54 495 60
441 67
388
76 331 90 286
104
580
ON OFF*
750 40 703 42 651 46 600 49
553 54
504
59 456 65 409
72
03A*
ON ON
923 32 865 34 824 36 802 37
759 39
715
41 674 44 631
47
OFF ON**
1138 N/A 1093 N/A 1057 N/A 1016 N/A
981 N/A
945
N/A 912 N/A 876
N/A
OFF OFF
681
65
617
72
566
79
511
87
458
97
405
110
358
124
311
143
G MES80
ON OFF*
1328
33
1274
35
1231
36
1192
37
1155
38
1114
40
1081
41
1047
42
0603A*
ON ON
964
46
906
49
856
52
810
55
788
56
745
60
702
63
662
67
OFF ON
1151
39
1091
41
1050
42
1007
44
964
46
926
48
885
50
850
52
OFF OFF
752
59
678
66
608
73
547
81
474
94
403
110
335
133
263
169
G MES80
ON OFF*
1330
33
1280
35
1229
36
1187
37
1146
39
1103
40
1061
42
1018
44
0603B*
ON ON
1155
38
1100
40
1048
42
1002
44
952
47
907
49
861
52
816
54
OFF ON**
1418
N/A
1376
N/A
1333
N/A
1288
N/A
1248
N/A
1206
N/A
1163
N/A
1124
N/A
OFF OFF
757
59
683
65
618
72
558
80
486
91
414
107
354
126
278
160
G MES80
ON OFF*
1320
34
1264
35
1217
37
1171
38
1131
39
1091
41
1049
42
1007
44
0604B*
ON ON
1406
32
1358
33
1314
34
1267
35
1226
36
1205
37
1189
37
1147
39
OFF ON**
1590
N/A
1542
N/A
1499
N/A
1454
N/A
1418
N/A
1413
N/A
1390
N/A
1356
N/A
OFF OFF
706
84
631
94
563
105
486
122
404
147
338
175
280
212
232
255
G MES80
ON OFF*
1231
48
1185
50
1136
52
1093
54
1049
56
1004
59
956
62
908
65
0803B*
ON ON
1133
52
1009
59
956
62
903
66
856
69
804
74
774
77
722
82
OFF ON
1160
51
1107
54
1060
56
1011
59
965
61
920
64
868
68
818
72
OFF OFF
743
80
668
89
599
99
522
114
432
137
366
162
312
190
258
230
G MES80
ON OFF*
1408
42
1369
43
1319
45
1282
46
1242
48
1219
49
1193
50
1150
52
0804B*
ON ON
1179
50
1123
53
1073
55
1025
58
972
61
949
62
924
64
869
68
OFF ON**
1574
N/A
1521
N/A
1481
N/A
1439
N/A
1398
N/A
1374
N/A
1335
N/A
1295
N/A
OFF OFF
822
72
754
79
652
91
566
105
499
119
428
138
346
171
294
202
G MES80
ON OFF*
1352
44
1281
46
1218
49
1152
51
1076
55
1026
58
964
61
901
66
0804C*
ON ON
1466
40
1399
42
1347
44
1290
46
1230
48
1170
51
1112
53
1054
56
OFF ON**
1669
N/A
1595
N/A
1527
N/A
1463
N/A
1407
N/A
1363
N/A
1336
N/A
1289
N/A
OFF OFF
822
72
754
79
652
91
566
105
499
119
428
138
346
171
294
202
G MES80
ON OFF*
1352
44
1281
46
1218
49
1152
51
1076
55
1026
58
964
61
901
66
0805C*
ON ON**
1669
N/A
1595
N/A
1527
N/A
1463
N/A
1407
N/A
1402
N/A
1363
N/A
1336
N/A
OFF ON**
1904
N/A
1832
N/A
1777
N/A
1727
N/A
1678
N/A
1630
N/A
1579
N/A
1523
N/A
OFF OFF
789
94
719
103
637
116
545
136
458
162
378
196
324
229
273
271
G MES80
ON OFF*
1567
47
1516
49
1466
51
1423
52
1388
53
1342
55
1293
57
1243
60
1005C*
ON ON
1424
52
1378
54
1330
56
1274
58
1226
60
1172
63
1119
66
1071
69
OFF ON**
1810
N/A
1764
N/A
1718
N/A
1682
N/A
1633
N/A
1596
N/A
1549
N/A
1510
N/A
OFF OFF
815
109
742
120
662
134
590
151
503
177
422
211
362
246
299
297
G MES80
ON OFF*
1701
52
1641
54
1591
56
1544
58
1497
59
1453
61
1408
63
1372
65
1205D*
ON ON
1434
62
1388
64
1336
67
1281
69
1230
72
1202
74
1178
75
1121
79
OFF ON**
1831
N/A
1770
N/A
1723
N/A
1677
N/A
1630
N/A
1590
N/A
1547
N/A
1506
N/A
at 0.5" ESP
Notes:
• CFM in chart is without filter(s). Filters do not ship with this furnace, but must be provided by the installer. If the furnace requires two return filters, this chart
assumes both filters are installed.
• All furnaces ship as high-speed cooling and medium -speed heating. Installer must adjust blower cooling and heating speed as needed.
• For most jobs, about 400 CFM per ton when cooling is desirable.
• INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON THE RATING PLATE.
• This chart is for information only. For satisfactory operation, external static pressure must not exceed value shown on the rating plate.
• The dashed ( ---- ) areas indicate a temperature rise not recommended for this model.
• At higher altitudes, a properly derated unit will have approximately the same temperature rise at a particular CFM, while ESP at the CFM will be lower.
SS-GMES80/GCES80 www.goodmanmfg.com
GMESSO CIRCULATION AIRFLOW DATA
CFM & TEMPERATURE RISE vs. EXTERNAL STATIC PRESSURE
EXTERNAL
STATIC
PRESSURE, (INCHES
WATER COLUMN)
OFF OFF*
658 603
550
495 441
388
331 286 238 198
G MES80
ON OFF
750 703
651
600 553
504
456 409 362 322
0403A*
OFF ON
1138 1093
1057
1016 981
945
912 876 836 744
ON ON
1367 1321
1286
1255 1223
1190
1160 1133 1099 1068
OFF OFF*
681
617
566
511
458
405
358
311
265
215
G M ES80
ON OFF
1328
1274
1231
1192
1155
1114
1081
1047
1013
978
0603A*
OFF ON
1151
1091
1050
1007
964
926
885
850
813
800
ON ON
1389
1341
1295
1258
1221
1176
1140
1105
1076
1043
OFF OFF*
752
678
608
547
474
403
335
263
232
195
G MES80
ON OFF
1330
1280
1229
1187
1146
1103
1061
1018
977
936
0603B*
OFF ON
1418
1376
1333
1288
1248
1206
1163
1124
1085
1050
ON ON
1465
1416
1382
1340
1299
1257
1219
1181
1142
1106
OFF OFF*
757
683
618
558
486
414
354
278
237
204
G MES80
ON OFF
1320
1264
1217
1171
1131
1091
1049
1007
965
923
0604B*
OFF ON
1590
1542
1499
1454
1418
1390
1356
1321
1282
1245
ON ON
1804
1757
1712
1676
1637
1600
1566
1529
1501
1466
OFF OFF*
706
631
563
486
404
338
280
232
194
118
G M ES80
ON OFF
1231
1185
1136
1093
1049
1004
956
908
862
835
0803B*
OFF ON
1160
1107
1060
1011
965
920
868
818
794
741
ON ON
1402
1358
1317
1274
1234
1195
1154
1113
1069
1033
OFF OFF*
743
668
599
522
432
366
312
258
213
158
G MES80
ON OFF
1408
1369
1319
1282
1242
1193
1150
1109
1069
1025
0804B*
OFF ON
1574
1521
1481
1439
1398
1374
1335
1295
1259
1219
ON ON
1810
1756
1711
1675
1637
1602
1569
1536
1500
1462
OFF OFF*
822
754
652
466
499
428
346
294
246
202
G MES80
ON OFF
1352
1281
1218
1152
1076
1026
964
901
833
790
0804C*
OFF ON
1669
1595
1527
1463
1407
1363
1336
1289
1238
1190
ON ON
1904
1932
1777
1727
1678
1630
1579
1523
1469
1426
OFF OFF*
822
754
652
466
499
428
346
294
246
202
G MES80
ON OFF
1352
1281
1218
1152
1076
1026
964
901
833
790
0805C*
OFF ON
1904
1932
1777
1727
1678
1630
1579
1523
1469
1426
ON ON
2202
2137
2080
2033
1985
1947
1903
1859
1791
1721
OFF OFF*
789
719
637
545
458
378
324
273
222
179
G M ES80
ON OFF
1567
1516
1466
1423
1388
1342
1293
1243
1195
1146
1005C*
OFF ON
1810
1764
1718
1682
1633
1596
1549
1510
1466
1425
ON ON
2111
2085
2052
2027
1988
1968
1949
1917
1876
1840
OFF OFF*
815
742
662
590
503
422
362
299
232
179
G MES80
ON OFF
1701
1641
1591
1544
1497
1453
1408
1372
1340
1295
1205D*
OFF ON
1831
1770
1723
1677
1630
1593
1547
1506
1464
1416
ON ON
2226
2165
2126
2083
2048
2011
1983
1945
1905
1875
at 0.5" ESP
Notes:
• CFM in chart is without filter(s). Filters do not ship with this furnace, but must be provided by the
installer. If the furnace requires two return filters, this chart assumes both filters are installed.
• All furnaces ship as high-speed cooling and medium -speed heating. Installer must adjust blower
cooling and heating speed as needed.
www.goodmanmfg.com SS-GMES80/GCES80
GMES80 COOLING AIRFLOW DATA
CFM & TEMPERATURE RISE VS. EXTERNAL STATIC PRESSURE
SWITCHES
EXTERNAL
STATIC
PRESSURE, (INCHES
WATER COLUMN)
MODELDIP
OFF OFF OFF
658 603
550
495 441
388 331 286 238 198
OFF ON ON
658 603
550
495 441
388 331 286 238 198
ON OFF ON
658 603
550
495 441
388 331 286 238 198
GMES80
ON ON ON
658 603
550
495 441
388 331 286 238 198
0403A*
ON OFF OFF
750 703
651
600 553
504 456 409 362 322
ON ON OFF
923 865
824
802 759
715 674 631 597 551
OFF ON OFF
1138 1093
1057
1016 981
945 912 876 836 744
OFF OFF ON*
1367 1321
1286
1255 1223
1190 1160 1133 1099 1068
OFF OFF OFF
681
617
566
511
458
405 358
311
265
215
OFF ON ON
681
617
566
511
458
405 358
311
265
215
ON OFF ON
681
617
566
511
458
405 358
311
265
215
GMES80
ON ON ON
681
617
566
511
458
405 358
311
265
215
0603A*
ON OFF OFF
1328
1274
1231
1192
1155
1114 1081
1047
1013
978
ON ON OFF
964
906
856
810
788
745 702
662
622
588
OFF ON OFF
1151
1091
1050
1007
964
926 885
850
813
800
OFF OFF ON*
1389
1341
1295
1258
1221
1176 1140
1105
1076
1043
OFF OFF OFF
752
678
608
547
474
403 335
263
232
195
OFF ON ON
752
678
608
547
474
403 335
263
232
195
ON OFF ON
752
678
608
547
474
403 335
263
232
195
GMES80
ON ON ON
752
678
608
547
474
403 33S
263
232
195
0603B*
ON OFF OFF
1330
1280
1229
1187
1146
1103 1061
1018
977
936
ON ON OFF
1155
1100
1048
1002
952
907 861
816
789
741
OFF ON OFF
1418
1376
1333
1288
1248
1206 1163
1124
1085
1050
OFF OFF ON*
1465
1416
1382
1340
1299
1257 1219
1181
1142
1106
OFF OFF OFF
757
683
618
558
486
414 354
278
237
204
OFF ON ON
757
683
618
558
486
414 354
278
237
204
ON OFF ON
757
683
618
558
486
414 354
278
237
204
GMES80
ON ON ON
757
683
618
558
486
414 354
278
237
204
0604B*
ON OFF OFF
1320
1264
1217
1171
1131
1091 1049
1007
965
923
ON ON OFF
1406
1358
1314
1267
1226
1189 1147
1108
1070
1031
OFF ON OFF
1590
1542
1499
1454
1418
1390 1356
1321
1282
1245
OFF OFF ON*
1804
1757
1712
1676
1637
1600 1566
1529
1501
1466
OFF OFF OFF
706
631
563
486
404
338 280
232
194
118
OFF ON ON
706
631
563
486
404
338 280
232
194
118
ON OFF ON
706
631
563
486
404
338 280
232
194
118
GMES80
ON ON ON
706
631
563
486
404
338 280
232
194
118
0803B*
ON OFF OFF
1231
1185
1136
1093
1049
1004 956
908
862
835
ON ON OFF
1133
1009
956
903
856
804 774
722
661
606
OFF ON OFF
1160
1107
1060
1011
965
920 868
818
794
741
OFF OFF ON*
1402
1358
1317
1274
1234
1195 1154
1113
1069
1033
SS-GMES80/GCES80 www.goodmanmfg.com
GMES80 COOLING AIRFLOW DATA (CONTD.)
M
I
OFF OFF OFF
743 668
599
CFM
522 432
CFM CFM CFM
366 312 258
CFM
213
158
OFF ON ON
743 668
599
522 432
366 312 258
213
158
ON OFF ON
743 668
599
522 432
366 312 258
213
158
GMES80
ON ON ON
743 668
599
522 432
366 312 258
213
158
0804B*
ON OFF OFF
1408 1369
1319
1282 1242
1193 1150 1109
1069
1025
ON ON OFF
1179 1123
1073
1025 972
924 869 818
782
719
OFF ON OFF
1574 1521
1481
1439 1398
1374 1335 1295
1259
1219
OFF OFF ON*
1810 1756
1711
1675 1637
1602 1569 1536
1500
1462
OFF OFF OFF
822
754
652
466 499
428 346
294
246
202
OFF ON ON
822
754
652
466 499
428 346
294
246
202
ON OFF ON
822
754
652
466 499
428 346
294
246
202
GMES80
ON ON ON
822
754
652
466 499
428 346
294
246
202
0804C*
ON OFF OFF
1352
1281
1218
1152 1076
1026 964
901
833
790
ON ON OFF
1669
1595
1527
1463 1407
1363 1336
1289
1238
1190
OFF ON OFF
1669
1595
1527
1463 1407
1363 1336
1289
1238
1190
OFF OFF ON*
1904
1932
1777
1727 1678
1630 1579
1523
1469
1426
OFF OFF OFF
822
754
652
466 499
428 346
294
246
202
OFF ON ON
822
754
652
466 499
428 346
294
246
202
ON OFF ON
822
754
652
466 499
428 346
294
246
202
GMES80
ON ON ON
822
754
652
466 499
428 346
294
246
202
0805C*
ON OFF OFF
1352
1281
1218
1152 1076
1026 964
901
833
790
ON ON OFF
1669
1595
1527
1463 1407
1363 1336
1289
1238
1190
OFF ON OFF
1904
1932
1777
1727 1678
1630 1579
1523
1469
1426
OFF OFF ON*
2202
2137
2080
2033 1985
1947 1903
1859
1791
1721
OFF OFF OFF
789
719
637
545 458
378 324
273
222
179
OFF ON ON
789
719
637
545 458
378 324
273
222
179
ON OFF ON
789
719
637
545 458
378 324
273
222
179
GMES80
ON ON ON
789
719
637
545 458
378 324
273
222
179
1005C*
ON OFF OFF
1567
1516
1466
1423 1388
1342 1293
1243
1195
1146
ON ON OFF
1424
1378
1330
1274 1226
1172 1119
1071
1023
972
OFF ON OFF
1810
1764
1718
1682 1633
1596 1549
1510
1466
1425
OFF OFF ON*
2111
2085
2052
2027 1988
1968 1949
1917
1876
1840
OFF OFF OFF
815
742
662
590 503
422 362
299
232
179
OFF ON ON
815
742
662
590 503
422 362
299
232
179
ON OFF ON
815
742
662
590 503
422 362
299
232
179
GMES80
ON ON ON
815
742
662
590 503
422 362
299
232
179
1205D*
ON OFF OFF
1701
1641
1591
1544 1497
1453 1408
1372
1340
1295
ON ON OFF
1434
1388
1336
1281 1230
1178 1121
1063
1017
964
OFF ON OFF
1831
1770
1723
1677 1630
1593 1547
1506
1464
1416
OFF OFF ON*
2226
2165
2126
2083 2048
2011 1983
1945
1905
1875
at 0.5" ESP
Notes:
• CFM in chart is without filter(s). Filters do not ship with this furnace, but must be provided by the installer. If the furnace requires two return
filters, this chart assumes both filters are installed.
• All furnaces ship as high-speed cooling and medium -speed heating. Installer must adjust blower cooling and heating speed as needed.
• For mostjobs, about 400 CFM per ton when cooling is desirable.
• INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON THE RATING PLATE.
• This chart is for information only. For satisfactory operation, external static pressure must not exceed value shown on the rating plate.
• The dashed ( ---- ) areas indicate a temperature rise not recommended for this model.
• At higher altitudes, a properly derated unit will have approximately the same temperature rise at a particular CFM, while ESP at the CFM will be lower
10 www.goodmanmfg.com SS-GMES80/GCES80
GCES80 HEATING AIRFLOW DATA
CFM & TEMPERATURE RISE v5. EXTERNAL STATIC PRESSURE
EXTERNAL STATIC PRESSURE, (INCHES
WATER COLUMN)
ICES80
OFF OFF
668 44 650 46 600 49 555 53
507 58
459
65 411 72 352
84
ON OFF*
785 38 754 39 736 40 690 43
650 46
604
49 565 52 527
56
403A*
ON ON
862 34 827 36 823 36 787 38
770 38
733
40 692 43 655
45
OFF ON**
1104 N/A 1058 N/A 1020 N/A 1022 N/A
1013 N/A
981
N/A 952 N/A 918
N/A
OFF OFF
716
62
647
69
592
75
541
82
478
93
420
106
368
121
296
150
GCES80
ON OFF*
1054
42
1002
44
951
47
906
49
861
52
820
54
797
56
754
59
0603A*
ON ON
960
46
900
49
854
52
802
55
782
57
735
60
695
64
639
70
OFF ON
1160
N/A
1102
N/A
1055
N/A
1017
N/A
970
N/A
930
N/A
891
N/A
847
N/A
OFF OFF
784
76
716
83
645
92
583
102
516
115
405
146
334
177
282
210
GCES80
ON OFF*
1295
46
1252
47
1203
49
1153
51
1114
53
1071
55
1022
58
981
60
0804B*
ON ON
1401
N/A
1366
N/A
1320
N/A
1278
N/A
1236
N/A
1213
N/A
1194
N/A
1153
N/A
OFF ON**
1596
N/A
1553
N/A
1512
N/A
1491
N/A
1450
N/A
1411
N/A
1388
N/A
1347
N/A
OFF OFF
1171
51
884
67
667
89
576
103
495
120
399
149
338
175
302
196
GCES80
ON OFF*
1175
50
1098
54
1024
58
947
63
883
67
823
72
764
78
703
84
0805C*
ON ON
1436
N/A
1402
N/A
1362
N/A
1313
N/A
1244
N/A
1182
N/A
1132
N/A
1079
N/A
OFF ON**
1782
N/A
1744
N/A
1715
N/A
1700
N/A
1660
N/A
1619
N/A
1579
N/A
1510
N/A
OFF OFF
803
92
719
103
631
117
540
137
471
157
337
220
298
249
265
280
GCES80
ON OFF**
1424
52
1385
53
1332
56
1284
58
1229
60
1176
63
1130
66
1078
69
1005C*
ON ON
1626
N/A
1574
N/A
1524
N/A
1479
N/A
1433
N/A
1410
N/A
1400
N/A
1358
N/A
OFF ON**
1820
N/A
1769
N/A
1726
N/A
1685
N/A
1642
N/A
1603
N/A
1557
N/A
1521
N/A
at 0.5" ESP
Notes:
• CFM in chart is without filter(s). Filters do not ship with this furnace, but must be provided by the installer. If the furnace requires two return filters, this chart
assumes both filters are installed.
• All furnaces ship as high-speed cooling and medium -speed heating. Installer must adjust blower cooling and heating speed as needed.
• For most jobs, about 400 CFM per ton when cooling is desirable.
• INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON THE RATING PLATE.
• This chart is for information only. For satisfactory operation, external static pressure must not exceed value shown on the rating plate.
• The dashed ( ---- ) areas indicate a temperature rise not recommended for this model.
• At higher altitudes, a properly derated unit will have approximately the same temperature rise at a particular CFM, while ESP at the CFM will be lower.
SS-GMES80/GCES80 www.goodmanmfg.com 11
GCES8O CIRCULATION AIRFLOW DATA
CFM & TEMPERATURE RISE vs. EXTERNAL STATIC PRESSURE
EXTERNAL
STATIC
PRESSURE, (INCHES
WATER COLUMN)
OFF OFF*
668 650
600
555 507
459
411 352
291 259
GCES80
ON OFF
785 754
736
690 650
604
565 527
482 438
0403A*
OFF ON
1104 1058
1020
1022 1013
981
952 918
887 855
ON ON
1348 1294
1261
1250 1229
1233
1205 1182
1156 1129
OFF OFF*
716
647
592
541
478
420
368
296
245
198
GCES80
ON OFF
1054
1002
951
906
861
820
797
754
704
660
0603A*
OFF ON
1160
1102
1055
1017
970
930
891
847
800
780
ON ON
1411
1356
1313
1272
1235
1198
1162
1127
1094
1063
OFF OFF*
784
716
645
583
516
405
334
282
229
197
GCES80
ON OFF
1295
1252
1203
1153
1114
1071
1022
981
931
883
0804B*
OFF ON
1596
1553
1512
1491
1450
1411
1388
1347
1312
1272
ON ON
1757
1713
1691
1664
1625
1588
1552
1522
1488
1447
OFF OFF*
1171
884
667
576
495
399
338
302
260
206
GCES80
ON OFF
1175
1098
1024
947
883
823
764
703
640
567
0805C*
OFF ON
1782
1744
1715
1700
1660
1619
1579
1510
1455
1413
ON ON
2145
2089
2058
2036
2020
2000
1971
1935
1890
1857
OFF OFF*
803
719
631
540
471
337
298
265
217
174
GCES80
ON OFF
1424
1385
1332
1284
1229
1176
1130
1078
1018
923
1005C*
OFF ON
1820
1769
1726
1685
1642
1603
1557
1521
1478
1434
ON ON
2235
2185
2139
2108
2076
2032
2000
1964
1926
1896
at 0.5" ESP
Notes:
• CFM in chart is without filter(s). Filters do not ship with this furnace, but must be provided by the
installer. If the furnace requires two return filters, this chart assumes both filters are installed.
• All furnaces ship as high-speed cooling and medium -speed heating. Installer must adjust blower
cooling and heating speed as needed.
12 www.goodmanmfg.com SS-GMES80/GCES80
GCES80 COOLING AIRFLOW DATA
CFM & TEMPERATURE RISE v5. EXTERNAL STATIC PRESSURE
MODELDIP
SWITCHES
EXTERNAL
0.10.20.30.40.50.60.7
STATIC
PRESSURE, (INCHES
WATER COLUMN)
OFF OFF OFF
668 650
600
555 507
459 411 352
291
259
OFF ON ON
668 650
600
555 507
459 411 352
291
259
ON OFF ON
668 650
600
555 507
459 411 352
291
259
GCES80
ON ON ON
668 650
600
555 507
459 411 352
291
259
0403A*
ON OFF OFF
785 754
736
690 650
604 565 527
482
438
ON ON OFF
862 827
823
787 770
733 692 655
614
582
OFF ON OFF
1104 1058
1020
1022 1013
981 952 918
887
855
OFF OFF ON*
1348 1294
1261
1250 1229
1233 1205 1182
1156
1129
OFF OFF OFF
716
647
592
541 478
420 368
296
245
198
OFF ON ON
716
647
592
541 478
420 368
296
245
198
ON OFF ON
716
647
592
541 478
420 368
296
245
198
GCES80
ON ON ON
716
647
592
541 478
420 368
296
245
198
0603A*
ON OFF OFF
1054
1002
951
906 861
820 797
754
704
660
ON ON OFF
960
900
854
802 782
735 695
639
601
563
OFF ON OFF
1160
1102
1055
1017 970
930 891
847
800
780
OFF OFF ON*
1411
1356
1313
1272 1235
1198 1162
1127
1094
1063
OFF OFF OFF
784
716
645
583 516
405 334
282
229
197
OFF ON ON
784
716
645
583 516
405 334
282
229
197
ON OFF ON
784
716
645
583 516
405 334
282
229
197
GCES80
ON ON ON
784
716
645
583 516
405 334
282
229
197
0804B*
ON OFF OFF
1295
1252
1203
1153 1114
1071 1022
981
931
883
ON ON OFF
1401
1366
1320
1278 1236
1194 1153
1112
1070
1025
OFF ON OFF
1596
1553
1512
1491 1450
1411 1388
1347
1312
1272
OFF OFF ON*
1757
1713
1691
1664 1625
1588 1552
1522
1488
1447
OFF OFF OFF
1171
884
667
576 495
399 338
302
260
206
OFF ON ON
1171
884
667
576 495
399 338
302
260
206
ON OFF ON
1171
884
667
576 495
399 338
302
260
206
GCES80
ON ON ON
1171
884
667
576 495
399 338
302
260
206
0805C*
ON OFF OFF
1175
1098
1024
947 883
823 764
703
640
567
ON ON OFF
1436
1402
1362
1313 1244
1182 1132
1079
1025
965
OFF ON OFF
1782
1744
1715
1700 1660
1619 1579
1510
1455
1413
OFF OFF ON*
2145
2089
2058
2036 2020
2000 1971
1935
1890
1857
OFF OFF OFF
803
719
631
540 471
337 298
265
217
174
OFF ON ON
803
719
631
540 471
337 298
265
217
174
ON OFF ON
803
719
631
540 471
337 298
265
217
174
GCES80
ON ON ON
803
719
631
540 471
337 298
265
217
174
1005C*
ON OFF OFF
1424
1385
1332
1284 1229
1176 1130
1078
1018
923
ON ON OFF
1626
1574
1524
1479 1433
1400 1358
1309
1266
1218
OFF ON OFF
1820
1769
1726
1685 1642
1603 1557
1521
1478
1434
OFF OFF ON*
2235
2185
2139
2108 2076
2032 2000
1964
1926
1896
at 0.5" ESP
Notes:
• CFM in chart is without filter(s). Filters do not ship with this furnace, but must be provided by the
installer. If the furnace requires two return filters, this chart assumes both filters are installed.
• All furnaces ship as high-speed cooling and medium -speed heating. Installer must adjust blower cool-
ing and heating speed as needed.
SS-GMES80/GCES80 www.goodmanmfg.com 13
A
m
0
0
0-
3
cu
0
3
LP
G)
m
m
00
00
O
G)
m
N
00
0
BTU/H OUTPUT VS. TEMPERATURE RISE CHART
100
90
80
70
w
60
or
Q
or
50
-1411
w
F-
40
30
20
10
30 40 50 60 70 80 90 100 110 120 130 140 150
OUTPUT BTU/H x 1,000
600 CFM
Z--700—
soo
900
1000
1100
1200
1400
1600
1800
2000
2200
2400
CFM
-
FORMULAS
BTU/h Output = CFRM x 1.08 x Rise
BTU/H Output
Rise = _ CFM
CFM x 1.08
_
—
—
—
WIRING DIAGRAM
R C
BL A WARNING:DISCONNECT POWER BEFORE
RD SERVICING.WIRING TO UNIT MUST BE MICRO)
OR PROPERLY POLARIZED AND GROUNDED. CONTROLLED
BK r HUMIDIFIER INTEGRATED
CONTROL MODULE
RD BLOWER I
BL COMPARTMENT I I L
24 VAC DOOR SW ITCH GND (B) GND
4a VA (OPEN WHEN
TRANSFORMER DOOR OPEN) I Mvc (e) C2 VALVE
BK RD L I MV 1121 M1 J
BK 115 VAC C �D BLOWER
AUXILIARY PRESSURE
MITCONTROLS SWITCH
LINE-H FMR- CIRC- AC- `X
E1 f E2 t E3t E25tE32 G PS (1 o) C N,
RI y� TO PSO (4)
O RD I MICRO IHLI (])
N
FUSE OR HLO (1)
W. RD I I Aoro RESET
z t
INTEGRATED
BL VL R IR02 R1) GMRARv
MODULE y coNraoL
' RD GR i R01 (5)
1° YL MANUAL RESET ROLLOUT
LIMIT CONTROL(S)
i PU_(SINGLE CONTROL ON SOME MODELS)
BR XFMR (3) 24VAC
PU BL 4o vA
DIAGNOSTIC TRANSFORMER
LEDXFMR-H 115VAC XFMR-N
FLAME SENSOR
24V THERMOSTAT
CONNECTIONS FP (2)
N. E.C. CLASS WIRE I HOT SURFACE
C G R W V (D D IGNITER
I La � ION
GN-N
IS
L7 D
ID
LL ECM MrR INC BLWR
ND-N
HARNESS G) (1 2
BK D i —( HUMIDIFIER )— y
O
lK
O
9 p CIRCULATOR O
= 9 CIRC-H BLWR CIR-N
GN O 0
BK C
c RD
cxo RD
CIRCULATOR BLOWER
ELECTRONIC
`IR FILTER BLOWER COMPARTMENT LINE-H uNE-N
JUNCTION BOX
BURNER COMPARTMENT
ODOR
RD SWITCH
BK
BK WARNING:
H �WH DISCONNECT POWER DISCONNECT
BEFORE SERVICING.
W IRING TO UNIT
INDUCED AUTO RESET RD PROPERLY
MUST BE
DRAFT PRIMARY LIMIT 1
GND BLOWER CONROL RD POLARIZED
AND GROUNDED. 1
L GND N
YL TO 115VAC/ 1 /60 HZ POWER SUPPLY WITH
YL(. ;�. [/���j}�\/CPU OVERCURRENT PROTECTION DEVICE
BK
_(p/ PU—G)--PU
GR JUNCTION BOX
MANUAL RESET ROLLOUT LIMIT CONTROLS)
WH ID BLOWER (SINGLE CONTROL ON 40K BU) OR WH
PRESSURE GND —LINE-N
SWITCH R� — 1GND
C2 BL 1
2 CIRCUIT NO
CONNECTOR
HOT MI BR BK —LINER
SURFACE AUXILLARY SWITCH FLAME T0115 VAC/1/6oHZ
GAS VALVE POWERSUPPLY WITHOVERCURRENT
IGNITER
SENSOR PROTECTION DEVICE
o STEADY ON = NORMAL OPERATION COLOR CODES: EQUIPMENT GND
OFF =CONTROL FAILURE YL YELLOW
1 1 FLASH =SYSTEM LOCKOUT (RETRIES/RECYCLES EXCEEDED) OR ORANGE FIELD GND 1
PU PURPLE 1
2 FLASHES = PRESSURE SWITCH STUCK CLOSED GR GREEN FIELD SPLICE
S 3 FLASHES = PRESSURE SWITCH STUCK OPEN BK BLACK SWITCH (TEMP.) o--�
4 4 FLASHES = OPEN HIGH LIMIT PK PINK r a
5 5 FLASHES = FLAME SENSE WITHOUT GAS VALVE W BROWN IGNITER L-
s 6 FLASHES = OPEN ROLLOUT B EI LIE SWITCH (PRESS.) v Cv
] 7 FLASHES = LOW FLAME SIGNAL GY GRAY OVERCURRENT
8 FLASHES = IGNITER RELAY FAULT RD RED PROT. DEVICE
9 FLASHES = TWINNING FAULT LOW VOLTAGE (24V)
10 FLASHES = OPEN FUSE LOW VOLTAGE FIELD — —
1 11 FLASHES = IGNITER OPEN HI VOLTAGE (115V)
12 FLASHES =INDUCER RELAY ERROR
C RAPID FLASHES = REVERSED 115 VAC POLARITYNERIFY GND HI VOLTAGE FIELD — —
NOTES: JUNCTION
1. SET HEAT ANTICIPATOR ON ROOM THERMOSTAT AT 0.7 AMPS. TERMINAL �
2. MANUFACTURER'S SPECIFIED REPLACEMENT PARTS MUST BE USED WHEN SERVICING.
3. IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNACE MUST BE INTERNAL TO
REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE INTEGRATED CONTROL
RATING OF AT LEAST 105C. USE COPPER CONDUCTORS ONLY. !• PLUG CONNECTION
4. REQUIREMENTS SO AS TO PROVIDE THE CORRECT E HEATING TEMPERATURE R TO MATCH THE LRISEOAND THE
CORRECT COOLING CFM. (SEE SPEC SHEET FOR AIR FLOW CHART) 0140F02483-A
5. UNIT MUST BE PERMANENTLY GROUNDED AND CONFORM TO N.E.C. AND LOCAL CODES.
C
� Y c
o 3
w
ao a
c ma
M 0
o ,
y0 tlq O.
u c
u'
w '3 0
L W
Y N
O o
c
3 ^y c
SS-GMES80/GCES80 www.goodmanmfg.com 15
ACCESSORIES
LPT-03'
HANG20
AFE18-60A
MVK-01 2
MVK-02 2
TK-400
LP Conversion Kit
High -Altitude Natural Gas Kit (4500+ ft)
Fossil Fuel Kit
Masonry Vent Kit
Masonry Vent Kit (for GMS81205D* & GMS81405D* only)
Twinning Kit
' White -Rodgers and Honeywell valves
Z Upflow applications only
DOWNFLOW SUB -BASE FOR:
MINIMUM FILTER SIZES
Note: Other size filters of equal or greater surface area may be used; filters may also be centrally located.
' Use 2- 16 x 25 filters on side returns or 20 x 25 filter on bottom return if furnace is connected to a cooling unit over 4 tons nominal capacity.
Goodman Manufacturing Company, L.P., reserves the right to discontinue, or change at any time, specifications or designs without
notice or without incurring obligations. 02021 Goodman Manufacturing Company, L.P. • Houston, Texas • Printed in the USA.
16 www.goodmanmfg.com SS-G M ES80/GCES80