FIR2022-0082_Fire_Alarm_Equipment_Specification_Sheets_8.25.2022_2.12.02_PM_3073123 (2)UL LLC
CERTIFICATE OF COMPLIANCE
COVER PAGE
Applicant Subscriber No: 370746-011
Service Center Number: 22
Service Contract No: -
ACTIVE LISTINGS
CCN File No. Vol. No.
CRZM
BP10566
1
CPVX
BP1790
3
CRZH
BP6719
7
UUFX
S2684
20
Listed Service From: IRVING, TX
Alarm Service Company: Service Center:
ADT COMMERCIAL ADT COMMERCIAL
4221 W JOHN CARPENTER FWY 4221 W JOHN CARPENTER FWY
IRVING TX 75063-2924 IRVING TX 75063-2924
(L u Applicant ID No: 370746-011
Service Center No: 22
Expires: 01-JAN-2023
CERTIFICATE OF COMPLIANCE
THIS IS TO CERTIFY that the Alarm Service Company indicated below is included by Underwriters
Laboratories Inc. (UL) in its Product Directories as eligible to use the UL Listing Mark in connection with
Certificated Alarm Systems. The only evidence of compliance with UL's requirements is the issuance of a
UL Certificate for the Alarm System and the Certificate is current under UL's Certificate Verification Service.
This Certificate does not apply in any way to the communication channel between the protected property and
any facility that monitors signals from the protected property unless the use of a UL listed or Classified Alarm
Transport Company is specified on the Certificate.
Listed Service From: IRVING, TX
Alarm Service Company: (370746-011)
ADT COMMERCIAL
4221 W JOHN CARPENTER FWY
IRVING TX 75063-2924
Service Center: (370746-011)
ADT COMMERCIAL
4221 W JOHN CARPENTER FWY
IRVING TX 75063-2924
The Alarm Service Company is Listed in the following Certificate Service Categories:
File - Vol No. CCN Listing Category
BP1790-3 CPVX [Burglar Alarm Systems] Central Station
BP6719-7 CRZH [Burglar Alarm Systems] National Industrial Security Systems
BP10566-1 CRZM Monitoring Stations, National Industrial Security
S2684-20 UUFX [Signal and Fire Alarm Equipment and Services] (Protective Signaling
Services) Central Station
***THIS CERTIFICATE EXPIRES ON 01-JAN-2023***
"LOOK FOR THE UL ALARM SYSTEM CERTIFICATE"
d StarLink
APCO
INTRODUCTION
The StarLink*M SLE-LTEVI-CFBPS, SLE-LTEAI-CFBPS, SLE-LTEVI-
CFB and SLE-LTEAI-CFB Dual -Path Commercial / Residential Fire
alarm capture radio IP communicators are fully supervised,
wireless digital two-way subscriber units. All models are com-
patible with most 12/24VDC alarm control panels (always ad-
here to the documentation provided by the control panel man-
ufacturer). These communicators are for use as the primary
means of communication with the central station and do not
have backup mode capability. See W12140 for programming
information.
The LTE Series radios use data -capture technology that cap-
tures the alarm report from the control panel and transmits the
alarm signals to the Network Operations Center; the alarm sig-
nals are then forwarded to ANY central station via Contact ID or
4/2 central station formats. The radios can also report to a
Sur -Gard System II central station receiver via TCP/IP using
standard line security. The Network Operations Center reports
a trouble signal in the event that the network does not receive
the expected supervision signal from the wireless communica-
tor.
FIRE ALARM COMPATIBILITY
StarLink LTE Series models are compatible with any FACP
STARLINK RADIO REPORTING PATH
The diagram below shows the transmission path of a
signal from the StarLink radio to the central station.
1. Signal from a Control Panel.
2. StarLink radio receives the signal transmission (from
the TIP an RING wires); sends RF signal through the
GPRS network operator.
3. Network Operator, part of the vendor system, a
section of the cellular spectrum.
4. Network Operations Center, receives / routes data.
5. Central Station.
':DATA
StarLink
Radio
2 (3)
FACP
(1) Network
Operator
IIIIIII
(
5 ��� (4)
CENTRAL )
STATION StarLink Network
Operations Center
SLE-LTEVI-CFBPS & SLE-LTEAI-CFBPS
SLE-LTEVI-CFB & SLE-LTEAI-CFB
Commercial / Residential Fire Series
Dual Path Alarm Communicators
Submittal Data Sheet
SLE-LTEVI-CFBPS & SLE-LTEAI-CFBPS: Commercial /
Residential Fire LTE Radio -TCP/IP Communicators in red
metal housing with SLE-ULPS-R power supply and 16.5V /
20VA transformer mounted inside
housing
SLE-LTEVI-CFB & SLE-LTEAI-
CFB: Commercial / Residential Fire
LTE Radio -TCP/IP Communicators in
red metal housing. Powered direct-
ly from control panel (no power
supply, no transformer, rated nomi-
nal 12/24VDC input)
equipped with a DACT that must transmit central station reports
in Contact ID or 4/2 central station formats. The control panel
may also trigger communication events through the use of FACP
dry contacts connecting the (3) radio inputs, capable of trans-
mitting (4) distinct alarm and trouble event reports to the central
station.
The following features are included:
• Power limited output to the StarLink radio PC board 12V input
terminals
• Battery connection red and black flying leads
• Monitored battery charging and Active battery test circuits
• Requires a sealed lead acid min 4AH / max 7AH battery for
minimum 24-hour standby time (max charge current 200mA).
• Trouble relay output (C, N/O and N/C terminals) to wire to a
panel zone dedicated to "GSM Trouble" (dry contacts). Re-
move jumper " J2" isolate relay OUT1 common from ground
• Green AC ON LED visible from the exterior housing
• Yellow TROUBLE LED on PC board. Flashes signify:
One flash: AC fail / brownout (2 hour delay)
Two flashes: Low battery
Three flashes: Charging circuit trouble
Four flashes: StarLink radio trouble
The housing -mounted transformer (when provided) is mounted
inside its own housing compartment with a replaceable UL
Listed .5A fast blow primary fuse. 120VAC connections are to be
made by a licensed electrician using suitable connectors, in ac-
cordance with N.E.C. and local code requirements.
ADDITIONAL COMPONENTS
In addition to the models listed above, the following accessories
NAPCO Security Technologies, Inc., 333 Bayview Ave, Amityville, NY 11701 (800) 645-9445; Fax (631) 789-9292 A755A 10/19
13
are available and permitted by UL:
SLE-WIFI-MODULE - Allows your Napco StarLinkrM device to
connect to the Internet by means of a wireless (Wi-Fi) link,
eliminating a wired Ethernet cable connection. Note:
7AH battery required when using the SLE-WIFI-MODULE.
For more information, see WI2191.
SLE-DLCBL - Download Cable, 6 feet
SLE-ANTEXT30 - Extended antenna with 30 feet of cable
SLE-ANTEXT50 - Extended antenna with 50 feet of cable
SLE-ANTEXT75 - Extended antenna with 75 feet of cable
SLE-ANTEXT100 - Extended antenna with 100 feet of cable
(Any suitable external cellular antenna is permitted by UL).
Always follow the manufacturer's installation instructions.
GEM-Tamperkit - Tamper switches and screws to protect
metal housing.
SPECIFICATIONS
The following specifications apply to all StarLink radio models
unless otherwise stated:
Electrical Ratings for 120VAC, 60Hz
For Models with Power Supply (SLE-LTEVI-CFBPS &
SLE-LTEAI-CFBPS)
• Input Voltage: 120VAC nominal
• Input Current: 200mA maximum
• Maximum Charging Current: 200mA
Electrical Ratings for +12V / 24V
For Models without Power Supply (SLE-LTEVI-CFB &
SLE-LTEAI-CFB)
• Input Voltage: 10-25VDC regulated (power -limited out-
put from Listed control panel).
• Input Current:
10VDC standby: 162mA
12VDC standby: 125mA
15VDC standby: 110mA
24VDC standby: 100mA (Commercial Fire models)
25VDC standby: 100mA (Commercial Fire models)
Wi-Fi Module: (Optional) Add 40mA to the above.
(With peak RF transmission current of 300mA).
Electrical Ratings for the IN 1 Fire Input:
• Input Voltage: 9-25VDC.
• Maximum Input Current: Up to 2mA from FACP NAC cir-
cuit
Electrical Ratings for IN 2, IN 3, IN 4, and IN 5:
(Inputs IN 2, IN 3, IN 4, and IN 5 are Class B)
• Maximum Loop Voltage: 25VDC.
• Maximum Loop Current: 1.2mA
• End of Line Resistor (EOLR) Value: 10K (2 req'd)
Electrical Ratings for PGM3 Output:
• Open Collector Output: Maximum Voltage 3V when ac-
tive; 25V maximum when not active.
• Maximum PGM Sink Current: 50mA (up to 15VDC), 25mA
(15.1VDC - 25VDC)
Physical (W x H x D)
• Metal Housing: 11% x 9% x 3%" (29.2 x 24.1 x 8.9cm)
• Mounting: Metal housing includes two keyhole slots for
wall mounting (see measurements in WI2327)
Environmental
• Operating Temperature: 0°C - 49°C (327-120°F)
• Humidity: Maximum 93% Non -Condensing
• Indoor / dry location use only
NOTICE TO AUTHORITIES HAVING JURISDICTION, USERS, INSTALLERS,
DEALERS, AND OTHER AFFECTED PARTIES
FIRE PROGRAMMING OPTION
PERMITTED IN
AVAILABLE SETTINGS
REQUIRED UL 864 SETTINGS
UL864? (Y/N)
Unattended Remote Downloading
No
Enable / Disable
Disabled (Jumper 1 installed). Also required for Commercial installations.
IN2, IN3, IN4 and IN5 Unsupervised
Yes
Supervised / Unsupervised
Unsupervised using conduit within 20 feet of FACP (default). If not using
conduit, install Jumpers 4 and 5 and EOL Resistors.
200 seconds, 5 minutes, 6
200 seconds, 5 minutes, 60 minutes. 6 Hours permitted in Commercial
7 Day Supervision, Radio to NOC
No
minutes, 60 minutes, 6
Fire UL 864 with Dual Path enabled.
hours, 7 days
Trouble on Radio or IP Path
Yes
Either Path or Both Paths
Either Path (annunciation and report of trouble)
(Annunciate /Report)
Wi-Fi Module
Yes
Enable / Disable
May be enabled as a primary reporting path for Fire