ENG-CORRECTION NOTICE 12.4.2019OF ED41 O Est. I S90 CITY OF EDMONDS CORRECTION NOTICE ENGINEERING DIVISION (425) 771-0220 City Website: www.edmondswa.gov DATE: December 4, 2019 PERMIT NUMBER: BLD20191510 OWNER: Charles Von SITE CONTACT: Charles Von ADDRESS: 650 Bell St TYPE OF INSPECTION: Water Service Line ❑ WORK DESCRIBED BELOW HAS BEEN INSPECTED AND APPROVED ❑ APPROVED PLANS AND PERMIT JOB CARD MUST BE AVAILABLE TO INSPECTOR ON SITE ® CORRECTIONS LISTED BELOW MUST BE MADE BEFORE WORK CAN BE APPROVED AND/OR THE NEXT PHASE OF WORK IS STARTED. ® RECALL FOR INSPECTION ❑ REINSPECTION FEE MUST BE PAID PRIOR TO NEXT INSPECTION REQUEST. ❑ STOP WORK UNTIL AUTHORIZED TO CONTINUE BY CITY INSPECTOR 1. All 4 water service lines installed are 1 ". 2. As per plans sheet C04 note 49 water service lines shall be 1 %2" PE installed from the back of the meter to the building. 3. Call for inspection when new 1 1/2" water lines are installed. For inspection scheduling call 425-771-0220 x1326 OR Schedule on-line through Citizens Connect