MECHANICAL DETAILSt.1., Whole House Ventilation Whole house ventilation system to be installed per 2015 IRC sections M1507.3.1 through M1507.3.7 See whole house ventilation on the schedule sheet for specified option Wtd,WU' IRC Table M1507.3.3(1) Continuous Whole -House Mechanical Ventilation S rstem System Airflow Rate Requirements Airflow in CFM Number of Bedrooms Floor Area, SF_ 2-3 4-5 < 1500 45 60 _ 1,501- 3,000 60 75 3,001- 4,500 75 90 Run time percentage in each (4) hour segment 25% 1 33% 1 50% 66% 1 75% I 100% Factor 4.0 3.0 1 2.0 1 1.5 J 1.3 1.0 A. For ventilation system run time values between those listed, the factors are permitted to be determined by interpolation. B. Extrapolation beyond the table is prohibited by law. IRC Table M1507.3.3(2) Intermittent whole house mechanical ventilation rate factors e-y.(_1--ew subjected to base for the Board shall I retarder in ai Smoke Del All smoke c All detector power from interrupted. such a man All house Carbon Mi Alarms all i code for all alarms Garages Garages assemblies Dryer en \/ Ener Code ctio IMC Setio which alloy tableW4q Credits: within the t Option 2 Medium Dwelling Unit R460..2 permanent 2.5 credits required with R-2 occupancy requiremer Table R406.2 Summary of Credits claimed: 1a Efficient Building Envelope 0.5 Water Kea 2a Air leakage control and efficient ventilation 0.5 In seismic 3d High Efficiency HVAC 1.0 do to earth 5a Efficient Water Heating 0.5 vertical dirr Total Credits claimed 2.5 Appliances Each unit shall have the following: pilot and bL 1. Envelope: furnace an( Roof: SIPS panels Min R38 by gravityti Flat roof: R49 In additions 4.5" min R6.25/in foam at underside of plywood installed pe R28 + R21 min batt insulation below foam Walls: Wood frame: Walls with R21 batt R21 Bui Conc below grade: 1" rigid (R5) on outside face to extend up to finish floor level, furred walls to have 1" of R5 rigid between conc and 2x4 studs Grade Plan with R15 batt R21 northern twr Windows: maximum U value 0.28 % . SE townhor Floors: Slab under heated space to have continuous R10 rigid insulation, with min. 2' high perimeter insulation Building Er inside face of concrete walls R10 Bldg owner, Wood framed fir's over unheated space, (garages) R38 this per Ci , 2. Space Heating: Building C: Mini split system with inverter driven high efficient Building s HSPF elec. heat pumps based on 3 3. Water Heating/Distribution: High efficiency interior elec. heat pump water heater, min. EF>2.0 BUILDING that would supply DHW to all the units through a central water loop APPLICAB. insulated with R-8 minimum pipe insulation. 2015 Interr Low flow water fixtures throughout: showerhead and kitchen sink 2015 Inte faucets installed in the house shall be rated at 1.75 GPM or less. All 2015 Int other lavatory faucets shall be rated at 1.0 GPM or less. 2015 UNIF 4. Air leakage control & efficient Ventilation 2015 Wa Per option 2a, Dwellings shall comply with M 1507.3 of the IRC, are OCCUPA each required to be tested and verified as having an air leakage rate not exceeding 3.0 air changes per hour, Table R406.2. Fans to use Multi Farri Gara a maximum 0.35 w/cfm, and not interlocked with the mini split e system. T of U Mechanical Ventilation criteria: Full Spri 2 CFM Min efficacy of fan Max air Allow tilde F& flow CFM R2 Occu Range Hoods 100 2.8 CFM/watt any Stories a. Floor area In line fan any 2.8 CFM/watt anyJ / Landry 90 2.8 CFM/watt any JFirewallBathrm The following components shall comply with WSEC 1. Exterior headers shall provide minimum insulation between heater and exterior sheathing of R-10 Occupano 2. Ducts are required to be insulated to a minimum of R-8 per R403.3.1. 3. Mechanical system piping is required to be insulated to a minimum of R-6, per FLOOR R403.4. Bell St. G 4. Hot water pipes are required to be insulated to a minimum of R-3, per R403.5.3 ntry Le 5. Mechanical ducts are required to be seal tested in accordance with 403.3.2. Testing 3rd Floor - to comply with WSU RS-33. 4th Floor 6. 75% of all permanently installed lighting shall be high -efficacy R404.1 Total floor Roof & below decks Insulation Criteria: BuildingE 1. Roofing is not to peel and stick membrane set directly onto roof sheathing due to no roof Building wi ventilation is provided. covenant, 2. Spray foam insulation to be: a. Open cell, low density foam insulation. b. Provide a thermal barrier, such as intumescent coating, on the underside of the spray foam insulation prior to the installation of the fiberglass batt insulation. Flo Site/Parcel Data, Leaal DescrW.. OverallC FLOOR AM LOTS 17 AND 18 BLOCK 98 OF THE PLAT OF CITY OF EDMONDS, ACCORDING TO THE PLAT Bell St. G THEREOF RECORDED IN VOLUME 2 OF PLATS, PAGES 39 AND 39A, RECORDS OF Ent Level SNOHOMISH COUNTY AUDITOR. 3rd Floor PARCEL No. 00434209801700 4th Floor ADDRESS: 650 BELL STREET, EDMONDS, WASHINGTON 98020 Total floor°