Product Data
INDUSTRY LEADING
FEATURES / BENEFITS
A PERFECT BALANCE BETWEEN
BUDGET LIMITS, ENERGY SAVINGS AND
COMFORT.
The MK series ductless split systems are a matched combination of
an outdoor condensing unit and an indoor fan coil unit connected
only by refrigerant tubing and wires.
The fan coil is mounted under the ceiling or on the wall, near the
ceiling. This selection of fan coils permits inexpensive and creative
solutions to design problems such as:
• Add-ons to current space (an office or family room
addition)
• Special space requirements
• When changes in the load cannot be handled by the
existing system.
• When adding air conditioning to spaces that are heated
by hydronic or electric heat and have no ductwork.
• Historical renovations or any application where
preserving the look of the original structure is essential.
• The ideal compliment to your ducted system when it is
impractical or prohibitively expensive to use ductwork.
These compact indoor fan coil units take up very little space in the
room and do not obstruct windows. The fan coils are attractively
styled to blend with most room decors. Advanced system
components incorporate innovative technology to provide reliable
cooling performance at low sound levels.
LOW SOUND LEVELS
BUILT-IN RELIABILITY
When noise is a concern, the ductless systems are the answer. The
indoor units are whisper quiet. There are no compressors indoors,
either in the conditioned space or directly over it, and there is none
of the noise usually generated by air being forced through
ductwork.
When sound ordinances and proximity to neighbors demand quiet
operation, the 24AHA4/25HHA4/124ANS/224ANS unit is the
right choice: The advanced, horizontal blow -through airflow
design distributes air more evenly over the coil.
SECURE OPERATION
If security is an issue, outdoor and indoor units are connected only by
refrigerant piping and wiring to prevent intruders from crawling
through ductwork.
In addition, since 24AHA4/25HHA4/124ANS/224ANS units can be
installed close to an outside wall, coils are protected from vandals and
severe weather.
FAST INSTALLATION
This compact ductless split system is simple to install. A mounting
bracket is standard with the indoor units and only wire and piping
need to be run between indoor and outdoor units. These units are
fast and easy to install ensuring minimal disruption to customers in
the home or workplace. This makes the MK ductless split systems
the equipment of choice, especially in retrofit situations.
SIMPLE SERVICING AND
MAINTENANCE
Removing the top panel on outdoor units provides immediate
access to the control compartment, providing a service technician
access to check unit operation. In addition, the draw through
design of the outdoor section means that dirt accumulates on the
outside surface of the coil. Coils can be cleaned quickly from the
inside using a pressure hose and detergent.
On all indoor units, service and maintenance expense is reduced
due to easy -to -access cleanable filters. In addition, these ductless
systems have extensive self -diagnostics to assist in
troubleshooting.
Ductless split system indoor and outdoor units are designed to
provide years of trouble -free operation.
The indoor units include protection against freeze-up and high
evaporator temperatures on heat pumps.
The condensing units and heat pumps are also protected. There is a
3-minute time delay before the compressor will re -start. An
oversized accumulator (Heat Pump), high pressure switches (or
liquid line pressure switch on the heat pump), and compressor
internal overload protection will ensure a reliable system that is
ideal for light commercial applications.
INDIVIDUAL ROOM COMFORT
Maximum comfort is provided because each space can be
controlled individually based on usage pattern. The air sweep
feature provided permits optimal room air mixing to eliminate hot
and cold spots for occupant comfort. In addition, year-round
comfort can be provided with heat pumps.
ECONOMICAL OPERATION
The ductless split system design allows individual room heating or
cooling when required. There is no need to run large supply -air
fans or chilled water pumps to handle a few spaces with unique
load patterns. In addition, because air is moved only in the space
required, no energy is wasted moving air through ducts.
EASY -TO -USE CONTROLS
The ductless units have microprocessor -based controls to provided
the ultimate in comfort and efficiency. The user friendly wireless
remote control provides the interface between user and the unit.
FLEXIBILITY
A variety of accessories simplify the installation process and help
meet system requirements and weather conditions. See Table 2 on
page 4 for available accessories.
AGENCY LISTINGS
All systems are listed with AHRI (Air Conditioning, Heating &
Refrigeration Institute)-
2
MODEL NUMBER NOMENCLATURE
40 MK
40 = FAN COIL UNIT
MK = MODEL
SYSTEM TYPE
C = COOLING ONLY
O = HEAT PUMP
MAXIMUM NUMBER OF FAN COIL UNITS THAT
CAN BE CONNECTED TO THE OUTDOOR UNIT
B=1:1
NOMINAL CAPACITY
18 = 1— 1/2 TONS
24=2TONS
30=2-1/2TONS
34 = 2 — 5/6 TONS
36 = 3 TONS
48 = 4 TONS
54 = 4 1/2 TONS
INDOOR UNIT
C B 18
VOLTAGE
3 = 208/230-1 —60
NOT USED
INDOOR FAN COIL TYPE
F = Under Ceiling — Floor Console
Use of the AHRI Certified
TM Mark indicates a ANTTEk
manufacturer's
participation in the
program For verification
of certification for individual
products, go to nPL ),IQ
www.ahridirectory.org. C us
J </STED
STANDARD FEATURES AND ACCESSORIES
Table 1— Standard Features and Accessories
Ease Of Installation
Indoor and Outdoor Compact Size
S
Outdoor Unit Wall Mounting Kit
A
Outdoor Unit Stacking Kit
A
Indoor Mounting Bracket
S
Comfort Features
Convertible Under Ceiling - Floor Console
S
Microprocessor Cons
S
Wireless Remote Control
S
Automatic Air Sweep
S
Air Direction Control
S
Auto Restart Function
S
Cold Blow Protection On Heat Pumps
S
Turbo Mode
S
Follow Me
S
Energy Saving Features
Sleep Mode
S
Stop/Start Timer
S
46 ° F Heating Mode(Heating Setback
S
Safety And Reliability
3 Minute Time Delay For Compressor
S
Over Current Protection For Compressor
S
Crankcase Heater (standard on sizes 30 and 36 Heat Pump)
A
Indoor Coil Freeze Protection
S
Indoor Coil High Temperature Protection On Heat Pumps
S
Condenser High Temperature Protection On Heat Pumps
S
Accumulator On Heat Pumps
S
Ease Of Service And Maintenance
Cleanable Filters
S
Diagnostics
S
Liquid Line Pressure Taps
S
Suction And Discharge Pressure Taps
S
Application Flexibility
Law Ambient Controls (-20F) (-28.9C)
A
3-Phase on sizes 34 & 54 (AC) and 36 & 48 (HP)
S
Wind Baffles
A
Condensate Pumps
A
Wired Controls
A
Legend
S Standard
A Accessory
Table 2 — Optional Accessories
Ordering No.
Descriptions
For Models
KSACN0101AAA
Wired Remote Control
All Sizes
53DS-900 --- 118
Condensate Pump (230v)
All Sizes
KSALA0801AAA
Low Ambient Control (for
cooling - 20F)
24AHA4/25HHA4 (208/230V)
KSALA0901AAA
Low Ambient Control (for
cooling - 20F)
24AHA4 (460V-3)
KAACH1401AAA
Crankcase Heater
24AHA4 Sizes 17-36 (208/230V)
KAACH1501AAA
Crankcase Heater
24AHA4 Size 36 (460V-3)
KAACH1201AAA
Crankcase Heater
24AHA4 Size 48 (208/230V)
KAACH1901AAA
Crankcase Heater
24AHA4/25HHA4 Size 48 (460V-3)
KAACH1601AAA
Crankcase Heater
25HHA4 Size 48 (208/230V)
KAAWS0101AAA
Winter Start Kit (for low
ambient on cooling only
systems)
24AHA4 All Sizes
KHAIR0201AAA
Isolation Relay (Required
when using Low Ambient
cooling with HP)
25HHA4 All Sizes
KSAHS1501AAA
Hard Start Kit (Capacitor
& Relay)
24AHA4/25HHA4 (208/230V-1)
53DS-900 --- 087
Wind Baffle
24AHA4 Sizes 18 & 24
53DS-900 --- 071
Wind Baffle
24AHA4 Sizes 30-48 / 25HHA4 Sizes
30 & 36
53DS-900 --- 088
Wind Baffle
25HHA4 Size 48
53DS-900 --- 075
Stacking Kit
24AHA4 Sizes 18,24
53DS-900 --- 076
Stacking Kit
24AHA4 Sizes 30 - 48
53DS-900 --- 077
Wall Mount Kit
24AHA4 Sizes 18, 24
53DS-900 --- 078
Wall Mount Kit
24AHA4/25HHA4 Sizes 30 - 48
KAALS0201LLS
Liquid Line Solenoid for
Cooling Only
24AHA4 All Sizes - Required for Long
Line Applications
KHALSO401LLS
Liquid Line Solenoid for
Heat Pump
25HHA4 All Sizes -Required for Long
Line Applications
INDOOR UNIT ACCESSORIES
Condensate Pump
A07892
Fig. 1 — Condensate Pump Accessory
On ductless fan coils, the condensate pump has a lift capability of
12 ft (3.6 m) on the discharge side with the pump mounted in the
fan coil or 6 ft (1.8 m) on the suction side if the pump is remote
mounted. The pump is recommended when adequate drain line
pitch cannot be provided, or when the condensate must move up to
exit.
Wired Remote Controller
For applications where the use of wireless remote control is not
desired, the MK units can be controlled by means of a wired
wall -mounted control with an LCD display.
Fig. 2 — Wall Mounted Control with LCD Display
OUTDOOR UNIT ACCESSORIES
Low Ambient Kit
Stacking Kit
A fan -speed control device activated by a temperature sensor,
designed to control condenser fan motor speed in response to the
saturated condensing temperatures down to -20GF (-28.9GC), it
maintains condensing temperature at -100F ± 1OF (37.8C ± 6C)
A MotorMaster Low -Ambient Controller or Low -Ambient
Pressure Switch must be used when cooling operation is used at
outdoor temperatures below 55GF (12.8GC), and can be used on all
outdoor units without changing the outdoor fan motor.
Winter Start Control
Stacking Kits allow stacking of equally sized
smaller units to be stacked on top of larger units.
NOTE: THIS KIT CANNOT BE USED
PUMPS.
The Winter Start Control is a SPST delay relay. The control
bypasses the low pressure switch for approximately 3 minutes to
permit start-up for cooling operation under low load conditions at a;
low ambient temperatures. This relay is recommended on cooling
only systems that have the accessory Low Ambient Kit.
Isolation Relay MOUNTING FEET(6)
BOLTED TO
MOUNTING PAD
The Isolation Relay must be used when Low Ambient Kit is used
with heat pumps to ensure the pressure switch is bypassed when
unit is running in heat pump mode.
Liquid Line Solenoid Valve
The Liquid Line Solenoid Valve is an electrically operated shut-off
valve that is installed at the outdoor unit to stop and start
refrigerant flow in response to compressor operation. The valve
maintains a column of refrigerant in the liquid line between
compressor operating cycles and is required for certain long line
applications and to improve system performance.
Crankcase Heater
The Crankcase Heater is available for units with scroll compressors
and clamps onto the compressor oil sump. It is recommended for
low ambient applications. The Crankcase Heater is standard on
sizes 30 and 36 Heat Pump.
Wind Baffles
The Wind Baffle is a sheet metal shield used to provide improved
unit operation during high winds and is recommended whenever
the low ambient accessory is used.
N�TEN�man�.„�.mm ,
TWO UNITS MOUNTED
(IDENTICAL SIZES)
MOUN ING FEE
IN STACKING RAII
Fig. 3 — Stacking Kit
Wall Mounting Kit
units or permit
WITH HEAT
TWO UNITS MOUNTED
(UNEQUAL SIZES)
A06417
Wall mount brackets are mounted on the outside of the structure to
raise the unit from ground level, or to mount the unit on a wall
adjacent to a sloping roof. Wall mounts are also useful in areas of
heavy snowfall or where space is at a premium.
NOTE: Unit must be at least 6 in. (152.4 mm) from wall.
D06006
Fig. 4 — Wall Mounting Kit
DIMENSIONS - INDOOR
Unit:
Bracket:
W
Hook
A0150266
Fig. 5 — 40MKCB**F, 40MKQB**F Unit and Bracket Dimensions
Table 3 — Dimensions Indoor
Indoor Unit Size
BTU/Hr
Height (H)
in (mm)
Width (W)
in (mm)
Depth (D)
in (mm)
Operating Weight
I (kg)
AC
18K
9.3(235)
42.0 (1068)
26.6 (675)
59.7 (27.1)
24K - 34K
9.3(235)
65.0 (1650)
26.6 (675)
91.9 (41.7)
54K
9.3(235)
65.0 (1650)
26.6 (675)
98.8 (44.8)
HP
30K - 48K
9.3(235)
65.0 (1650)
26.6 (675)
98.8 (44.8)
Bracket
18K AC
38.7 (983)
8.7(220)
24K - 54K AC/HP
61.6 (1565)
8.7(220)
DIMENSIONS - OUTDOOR
U
AIR
Im
Fig. 6 - Outdoor Unit Dimensions
Table 4 - Dimensions Indoor
M
I�
FIELD POWER SUPPLY CONN.
HOLE SIZES PROVIDED:
t 0 7
/8. HOLE WITH
0 1 1/8" KNOCKOUT AND
iONS 0 1 3/8" KNOCKOUT
Dimensions in (mm)
OPERATING
WEIGHT
UNIT
A
B
C
D
E
F
G
H
J
K
L
M
N
P
Ibs.(kg)
24AHA418
31.1
36.9
14.6
16
23.4
17.2
23.1
28.1
13
6.6
11.3
0.6
2.9
5.8
146
(791)
(938)
(370)
(406)
(595)
(437)
(587)
(713)
(330)
(168)
(286)
(16)
(73)
(148)
(66)
24AHA424
31.1
36.9
14.6
16
23.4
17.2
23.1
28.1
14
6.8
11.6
0.8
2.9
5.8
148
(791)
(938)
(370)
(406)
(595)
(437)
(587)
(713)
(356)
(171)
(295)
(19)
(73)
(148)
(67)
Cooling Only
37.1
44.5
17.1
18.4
30.5
19.6
29.1
34.1
13.7
8.1
15.9
0.8
3.4
6.4
183
24AHA430
(943)
(1130)
(433)
(468)
(775)
(498)
(740)
(865)
(348)
(206)
(403)
(19)
(86)
(162)
(83)
24AHA436
37.1
44.5
17.1
18.4
30.5
19.6
29.1
34.1
13.7
8.1
15.9
0.9
3.4
6.4
184
(943)
(1130)
(433)
(468)
(775)
(498)
(740)
(865)
(348)
(206)
(403)
(22)
(86)
(162)
(83)
24AHA448
37.1
44.5
17.1
18.4
30.5
19.6
29.1
34.1
14.5
8.5
18.9
0.9
3.4
6.4
213
(943)
(1130)
(433)
(468)
(775)
(498)
(740)
(865)
(368)
(216)
(479)
(22)
(86)
(162)
(97)
HHA430
37.1
44.5
17.1
18.4
30.5
19.6
29.1
34.1
13.7
8.1
15.9
0.8
3.4
5.5
196
(943)
(1130)
(433)
(468)
(775)
(498)
(740)
(865)
(348)
(206)
(403)
(19)
(86)
(140)
(89)
Heat Pump
HHA436
37.1
44.5
17.1
18.4
30.5
19.6
29.1
34.1
13.7
8.1
15.9
0.9
3.4
5.5
197
(943)
(1130)
(433)
(468)
(775)
(498)
(740)
(865)
(348)
(206)
(403)
(22)
(86)
(140)
(89)
HHA448
43.1
44.5
17.1
18.4
30.5
19.6
35.1
40.1
14.5
8.5
18.9
0.9
3.4
5.5
246
(1095)
(1130)
(433)
(468)
(775)
(498)
(892)
(1018)
(368)
(216)
(479)
(22)
(86)
(140)
(112)
NOTE: Dimensions shown in feet -inches. Dimensions in O are millimeters.
CLEARANCES - INDOOR
Fig. 7 — 40MKCB**F, 40MKQB**F Unit Clearance
CLEARANCES - OUTDOOR
Fig. 8 — Outdoor Unit Clearance
Table 5 — Clearances
Air -outlet
A0150267
A08436
UNIT
Coil Facing Wall - in. (mm)
Fan Facing Wall - in. (mm)
A
24 (610)
24 (610)
B
24 (610)
24 (610)
C
20 (508)
6 (152)
D
6 (152)
8 (203)
E
6 (152)
20 (508)
SPECIFICATIONS
Table 6 - Specifications -Cooling Only Under Ceiling Systems
Cooling Only Only
Size
18
24
30
34
34
34
54
54
54
System
Outdoor Model
24AHA418AO03
24AHA424AO03
24AHA43OA003
24AHA436AO03
24AHA436AO05
24AHA436AO06
24AHA448AO03
24ARA448AO05
24AHA448AO06
Indoor Model
40MKCB18F--3
40MKCB34F--3
40MKCB34F--3
40MKCB34F--3
40MKCB34F--3
40MKCB34F--3
40MKCB54F--3
40MKCB54F--3
40MKCB54F--3
Energy Star
NO
NO
NO
NO
NO
NO
NO
NO
NO
Cooling Rated Capacity Btu b
17,100
24,000
28,600
33,200
33,200
33,200
53,000
53,000
53,000
Performance
SEER
14
14
14
14
14
14
14
14
14
EER
12.2
12.2
12.2
12.2
12.2
12.2
11.7
11.7
11.7
Controls
Wireless Remote Controller
( F/ C Convertible)
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Wired Remote Controller ( F/ C
Convertible)
Optional
Optional
Optional
Optional
Optional
Optional
Optional
Optional
Optional
Operating
Cooling Outdoor DB
Min - Max
F
55-125 (-20 F w / Low -Ambient Kit)
Range
Cooling Indoor DB Min
-Max
F
64-90
64-90
64-90
64-90
64-90
64-90
64-90
64-%
64-90
Total Piping Length
Ft
200'
200'
200'
200'
200'
200'
200'
200'
200'
Drop (OD above ID)
Ft.
200'
200'
200'
200'
200'
200'
200'
200'
200'
Lift (OD below ID)
Ft.
65'
65'
65'
65'
65'
65'
65'
65'
65'
Outdoor Pipe Connection
Size - Liquid
In.
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
Piping
Outdoor Pipe Connection
Size - Suction
In.
5/8"
3/4"
3/4"
7/8"
7/8"
7/8"
7/8"
7/8"
7/8"
Indoor Pipe Connection
Size - Liquid
In.
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
Indoor Pipe Connection
Size - Suction
In.
5/8"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
31,V
Type
R-410A
R-410A
R-410A
R-410A
R-410A
R-410A
R-410A
R-410A
R-410A
Refrigerant
Design Pressure
PSIG
550
550
550
550
550
550
550
550
550
Metering Device
Type B Acrurahx
Charge
Lb.
6.4
6.5
8.6
8.9
8.9
8.9
9
9
9
Face Area
Sq. Ft
7.3
7.3
12.1
12.1
12.1
12.1
12.1
12.1
12.1
Outdoor Coil
No. Rows
2
2
2
2
2
2
2
2
2
Fins per inch
20
20
20
20
20
20
20
20
20
Circuits
3
3
3
3
3
3
3
3
3
Face Area (sq. It)
Sq. Ft.
2.5
4.1
4.1
4.1
4.1
4.1
4.35
4.35
4.35
Indoor Coil
No. Rows
3
3
3
3
3
3
4
4
4
Fins per inch
19
19
19
19
19
19
19
19
19
Circuits
7
8
8
8
8
8
6
6
6
Compressor
Type
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Model
ZP16K6E-PFV-130
ZP20K6E-PFV-130
ZP25K5E-PFV-130
ZP29K5E-PFV-130
ZP29K5E-TF5-130
ZP29K5E-TFD-130
ZP40K6E-PFV-130
ZP40K6E-TF5-130
ZP40K6E-TFD-130
Outdoor Voltage, Phase,
Cycle
V/Ph/
Hz
208230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
Indoor Voltage, Phase,
Cycle
V/Ph/
Hz
208230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
Power Supply
Indoor and outdoor units have dedicatrd power supply
Electrical
MCA (Outdoor)
A.
11.8
14.1
18.3
18.8
12.5
7.6
24.3
18.3
8.4
MO( P - Fuse Rating
(Outdoor)
A
20
25
30
30
20
15
40
30
15
MCA (Indoor)
A.
3
3
3
3
3
3
3
3
3
MO( P - Fuse Rating
(Indoor)
A
15
15
15
15
15
15
15
15
15
Unit Width
In.
36.9
36.9
44.5
44.5
44.5
44.5
44.5
44.5
44.5
Unit Height
In.
31.1
31.1
37.1
37.1
37.1
37.1
37.1
37.1
37.1
Outdoor
Unit Depth
In.
14.6
14.6
17.1
17.1
17.1
17.1
17.1
17.1
17.1
Net Weight
Lbs.
146
148
183
184
184
184
213
213
213
Airflow
CFM
1,285
1,285
11900
2,615
2,615
2,615
2,615
2,615
2,615
Unit Width
In.
42.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
Unit Height
In.
9.3
9.3
9.3
9.3
9.3
9.3
9.3
9.3
9.3
Unit Depth
In.
26.6
26.6
26.6
26.6
26.6
26.6
26.6
26.6
26.6
Net Weight
Lbs.
59.7
91.9
91.9
91.9
91.9
91.9
98.8
98.8
98.8
Indoor
Number of Fan Speeds
3
3
3
3
3
3
3
3
3
Airflow 0owest ta
highest)
CFM
405/515/695
975/1335/1130
975/1335/1130
975/1335/1130
975/1335/1130
975/1335/1130
1310/1400/1470
1310/1400/1470
1310/1400/1470
Sound Pressure (lowest
in highest)
dB(A)
4Z48/53
50/52t55
50/52t55
50/52t55
50/52t55
50/52/55
55/57/59
55/57/59
55/57/59
Air throw Data
Ft
26
29
29
29
29
29
29
29
29
* Liquid line needs to be Insulated
** Refer to Ductless Split System Long Line Guide for additional information. Long Line accessories required beyond 80 ft (24.4 m).
SPECIFICATIONS (CONT)
Table 7 - Specifications - Heat Pump Under Ceiling Systems
HEAT PUMP
Size
30
36
36
36
48
48
48
System
Outdoor Model
25HHA43OA003
224ANS030000
25HHA436AO03
224ANS036000
25HHA436AO05
224APS036000
25HHA436AO06
224AES036000
25HHA448AO03
224ANSO48000
25HHA448AO05
224APSO48000
25HHA448AO06
224AESO48000
Indoor Model
40MKQB36F--3
40MKQB36F--3
40MKQB36F--3
40MKQB36F--3
40MKQB48F--3
40MKQB48F--3
40MKQB48F-3
Energy Star
NO
NO
NO
NO
NO
NO
NO
Cooling Rated Capacity
Btu/h
29,000
34,200
34,200
34,200
46,400
46,400
46,400
SEER
14
14
14
14
14
14
14
EER
11.5
11
11
11
11.7
11.7
11.7
Performance
Heating Rated Capacity
Btu/h
29,000
34,200
34,200
34,200
46,400
46,400
46,400
HSPF
8.2
8.2
8.2
8.2
8.2
8.2
8.2
COP
W/W
4.1
4.1
4.1
4.1
3.8
3.8
3.8
Wireless Remote Controller (°F/°C Convertible)
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Controls
Wired Remote Controller (°F/°C Convertible)
Optional
Optional
Optional
Optional
Optional
Optional
Optional
Cooling Outdoor DB Min - Max
°F
55-125 (-20°F w / Low -Ambient Kit)
Operating
Heating OutdoorDBMin - Max
°F
17--75
17-75
17-75
17-75
17-75
17-75
17-75
Range
Cooling IndoorDB Min -Max
°F
64-90
64-90
64-90
64-90
64-90
64-90
64-90
Heating IndoorDB Min -Max
°F
32-80
32-80
32-80
32-80
32-80
32-80
32-80
Total Piping Length
Ft.
200'
200'
200'
200'
200'
200'
200'
Drop (OD above ID)
Ft.
200'
200'
200'
200'
200'
200'
200'
Lift (OD below ID)
Ft.
65'
65'
65'
65'
65'
65'
65'
Piping
Outdoor Pipe Connection Size - Liquid
In.
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
Outdoor Pipe Connection Size - Suction
In.
3/4"
7/8"
7/8"
7/8"
7/8"
7/8"
7/8"
Indoor Pipe Connection Size - Liquid
In.
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
Indoor Pipe Connection Size - Suction
In.
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
Type
R410A
R410A
R410A
R410A
R410A
R410A
R410A
Design Pressure
PSIG
550
550
550
550
550
550
550
Refrigerant
Metering Device
Type B Accurator
Charge
Lb.
12.1
12.3
12.3
12.3
10.95
10.95
10.95
Face Area
Sq. Ft.
12.1
12.1
12.1
12.1
14.1
14.1
14.1
No. Rows
2
2
2
2
2
2
2
Outdoor Coil
Fins per inch
20
20
20
20
20
20
20
Circuits
6
5
5
5
6
6
6
Face Area (sq. ft.)
Sq. Ft.
4.4
4.4
4.4
4.4
4.4
4.4
4.4
No. Rows
4
4
4
4
4
4
4
Indoor Coil
Fins per inch
19
19
19
19
19
19
19
Circuits
6
6
6
6
6
6
6
Type
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Compressor
Model
ZP24K5E-PFV-1
30
ZP29K5E-PFV-1
30
ZP29K5E-TF5-1
30
ZP29K5E-TFD-1
30
ZP42K5E-PFV-1
30
ZP42K5E-TF5-1
30
ZP42K5E-TFD-1
30
Outdoor Voltage, Phase, Cycle
V/Ph/Hz
208/230-1-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
Indoor Voltage, Phase, Cycle
V/Ph/Hz
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
Power Supply
Indoor and outdoor units have dedicated power supply
Electrical
MCA (Outdoor)
A.
17.2
19
12.8
7.6
28.8
18.6
8.6
MOCP - Fuse Rating (Outdoor)
A.
30
30
20
15
50
30
15
MCA (Indoor)
A.
3
3
3
3
3
3
3
MOCP - Fuse Rating (Indoor)
A.
15
15
15
15
15
15
15
Unit Width
In.
44.5
44.5
44.5
44.5
44.5
44.5
44.5
Unit Height
In.
37.1
37.1
37.1
37.1
43.1
43.1
43.1
Outdoor
Unit Depth
In.
17.1
17.1
17.1
17.1
17.1
17.1
17.1
Net Weight
Lbs.
196
197
197
197
246
246
246
Airflow
CFM
2,615
2,615
2,615
2,615
2,785
2,785
2,785
Unit Width
In.
65.0
65.0
65.0
65.0
65.0
65.0
65.0
Unit Height
In.
9.3
9.3
9.3
9.3
9.3
9.3
9.3
Unit Depth
In.
26.6
26.6
26.6
26.6
26.6
26.6
26.6
Net Weight
Lbs.
98.8
98.8
98.8
98.8
98.8
98.8
98.8
Indoor
No. of Fan Speeds
3
3
3
3
3
3
3
Airflow (lowest to highest)
CFM
1310/1400/1470
1310/1400/1470
1310/1400/1470
1310/1400/1470
1310/1400/1470
1310/1400/1470
1310/1400/1470
Sound Pressure (lowest to highest)
dB(A)
55/57/59
55/57/59
55/57/59
55/57/59
55/57/59
55/57/59
55/57/59
Air throw Data
Ft.
29
29
29
29
29
29
29
* Liquid line needs to be insulated
** Refer to Ductless Split System Long Line Guide for additional information. Long Line accessories required beyond 80 ft (24.4 m).
10
COOLING PERFORMANCE DATA - COOLING ONLY UNITS
Table 8 - Cooling Performance Data - Cooling Only Units
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES deg F
75
85
95
105
115
125
SIZE
INDOOR UNIT
OUTDOOR UNIT
CFM
EWB
Capacity MBtuht
Total
System
KW**
Capacity MBtuht
Total
System
Ksw-
Capacity MBtuht
Total
System
Ksw-
Capacity MBtuht
Total
System
KVV-
Capacity MBtuht
Total
System
KW-
Capacity MBtuht
Total
System
KW-
Total
Sens$
Total
Sens$
Total
Sens$
Total
Sens$
Total
Sens$
Total
Sens$
405
72
18.58
9.28
1.08
17.83
8.97
1.20
17.04
8.65
1.34
16.18
8.30
1.49
15.25
7.93
1.67
14.23
7.53
1.88
67
16.85
10.96
1.07
16.16
10.65
1.20
15.44
10.32
1.33
14.67
9.98
1.49
13.83
9.61
1.67
12.90
9.21
1.88
63
15.60
10.59
1.07
14.96
10.27
1.20
14.29
9.95
1.33
13.57
9.61
1.49
12.80
9.24
1.67
11.95
8.85
1.88
62
15.28
12.61
1.07
14.65
12.29
1.19
13.99
11.97
1.33
13.29
11.63
1.49
12.53
11.26
1.67
11.71
10.87
1.88
57
14.07
14.07
1.07
13.61
13.61
1.19
13.12
13.12
1.33
12.59
12.59
1.49
12.01
12.01
1.67
11.38
11.38
1.88
18
40MKCB18F--3
24AHA418AO03
124ANS018000
515
72
19.69
10.20
1.10
18.85
9.87
1.22
17.95
9.53
1.36
16.99
9.16
1.52
15.95
8.77
1.70
14.82
8.34
1.90
67
17.87
12.35
1.10
17.10
12.02
1.22
16.29
11.67
1.36
15.42
11.30
1.52
14.48
10.91
1.70
13.45
10.49
1.90
63
16.56
11.90
1.10
15.84
11.56
1.22
15.09
11.22
1.36
14.28
10.85
1.52
13.42
10.47
1.70
12.47
10.05
1.90
62
16.23
14.47
1.10
15.52
14.13
1.22
14.79
13.77
1.36
14.01
13.39
1.52
13.19
12.96
1.70
12.36
12.36
1.90
57
15.49
15.49
1.10
14.94
14.94
1.22
14.37
14.37
1.36
13.76
13.76
1.51
13.09
13.09
1.69
12.34
12.34
1.90
695
72
20.80
11.56
1.14
19.84
11.21
1.27
18.83
10.84
1.40
17.76
10.45
1.56
16.60
10.03
1.74
15.35
9.59
1.94
67
18.89
14.47
1.14
18.02
14.12
1.26
17.10
13.75
1.40
16.12
13.35
1.56
15.08
12.93
1.74
13.95
12.46
1.94
63
17.52
13.87
1.14
16.71
13.52
1.26
15.86
13.14
1.40
14.96
12.75
1.56
13.99
12.33
1.74
12.95
11.87
1.94
62
17.28
17.13
1.14
16.57
16.57
1.26
15.88
15.88
1.40
15.15
15.15
1.56
14.35
14.35
1.74
13.46
13.46
1.94
57
17.19
17.19
1.14
16.55
16.55
1.26
15.86
15.86
1.40
15.13
15.13
1.56
14.33
14.33
1.74
13.45
13.45
1.94
975
72
28.43
16.34
1.54
27.06
15.84
1.70
25.60
15.32
1.88
24.05
14.76
2.09
22.39
14.18
2.32
20.63
13.56
2.59
67
25.90
20.75
1.53
24.64
20.24
1.69
23.33
19.71
1.87
21.92
19.14
2.08
20.42
18.52
2.31
18.84
17.84
2.58
63
24.10
19.88
1.52
22.93
19.37
1.68
21.71
18.84
1.87
20.42
18.27
2.07
19.04
17.65
2.31
17.58
16.96
2.58
62
24.08
24.08
1.52
23.13
23.13
1.69
22.11
22.11
1.87
21.02
21.02
2.07
19.83
19.83
2.31
18.53
18.53
2.58
57
24.05
24.05
1.52
23.10
23.10
1.69
22.09
22.09
1.87
21.00
21.00
2.07
19.81
19.81
2.31
18.51
18.51
2.58
24
40MKCB34F--3
24AHA424AO03
124ANS024000
1130
72
28.86
17.43
1.58
27.43
16.92
1.74
25.92
16.38
1.92
24.31
15.82
2.13
22.59
15.22
2.36
20.77
14.58
2.63
67
26.31
22.48
1.57
25.01
21.95
1.73
23.65
21.38
1.91
22.20
2077.
2.12
2068.
2007.
2.35
19.11
19.11
2.62
63
24.50
21.48
1.57
23.29
20.95
1.73
2203.
2038.
1.91
20.71
1976.
2.11
19.31
1904.
2.35
17.92
17.92
2.62
62
25.08
25.08
1.57
24.05
24.05
1.73
22.96
22.96
1.91
21.77
21.77
2.12
2049.
2049.
2.35
1909.
1909.
2.62
57
25.05
25.05
1.57
24.02
24.02
1.73
22.93
22.93
1.91
21.75
21.75
2.12
20.47
20.47
2.35
19.08
19.08
2.62
1335
72
29.24
18.81
1.63
27.75
18.29
1.79
26.18
17.74
1.98
24.51
17.16
2.18
22.73
16.55
2.41
20.85
15.91
2.68
67
26.72
24.65
1.62
25.39
24.07
1.79
24.00
23.41
1.97
22.57
22.57
2.17
21.18
21.18
2.41
1968.
1968.
2.68
63
24.91
23.47
1.62
23.68
22.87
1.78
22.40
22.18
1.96
21.14
21.14
2.17
19.83
19.83
2.40
18.42
18.42
2.67
62
26.12
26.12
1.62
25.01
25.01
1.78
23.82
23.82
1.97
22.54
22.54
2.17
21.16
21.16
2.41
1966.
1966.
2.67
57
26.10
26.10
1.62
24.99
24.99
1.78
23.80
23.80
1.97
22.52
22.52
2.17
21.14
21.14
2.41
19.64
19.64
2.67
975
72
33.46
17.95
1.84
31.93
17.37
2.04
30.31
16.77
2.27
28.57
16.12
2.52
26.67
15.42
2.80
24.60
14.67
3.11
67
30.40
22.13
1.82
29.01
21.55
2.02
27.54
20.95
2.24
25.96
20.30
2.49
24.22
19.60
2.78
22.32
18.83
3.10
63
28.18
21.26
1.80
26.90
20.69
2.00
25.55
20.09
2.22
24.07
19.44
2.47
22.46
18.74
2.76
20.69
17.97
3.09
62
27.64
26.15
1.79
26.42
25.52
1.99
25.14
24.81
2.22
23.84
23.84
2.47
22.54
22.54
2.76
21.10
21.10
3.09
57
27.00
27.00
1.79
26.02
26.02
1.99
24.97
24.97
2.22
23.81
23.81
2.47
22.52
22.52
2.76
21.08
21.08
3.09
30
40MKCB34F--3
24AHA43OA003
124ANS030000
1130
72
34.21
19.05
1.89
32.60
18.46
2.09
30.89
17.83
2.31
29.07
17.17
2.56
27.08
16.46
2.84
24.92
15.69
3.16
67
31.09
23.87
1.86
29.63
23.28
2.06
28.08
22.65
2.29
26.42
21.98
2.54
24.61
21.25
2.82
22.65
20.44
3.14
63
28.85
22.88
1.84
27.49
22.29
2.04
26.06
21.67
2.27
24.53
21.00
2.52
22.84
2027.
2.80
21.02
1945.
3.13
62
28.42
28.42
1.84
27.32
27.32
2.04
26.16
26.16
2.27
24.90
24.90
2.52
23.50
23.50
2.81
21.95
21.95
3.14
57
28.35
28.35
1.84
27.29
27.29
2.04
26.13
26.13
2.27
24.87
24.87
2.52
23.48
23.48
2.81
21.92
21.92
3.14
1335
72
34.92
20.44
1.95
33.22
19.83
2.15
31.43
19.19
2.37
29.51
18.51
2.62
27.44
17.78
2.90
25.20
17.00
3.21
67
31.75
26.10
1.92
30.21
25.48
2.12
28.60
24.82
2.34
26.87
24.11
2.59
25.00
23.32
2.88
23.01
22.41
3.20
63
29.48
24.95
1.90
28.06
24.33
2.10
26.57
23.67
2.32
24.97
22.96
2.57
23.25
22.15
2.86
21.40
21.19
3.18
62
29.85
29.85
1.91
28.67
28.67
2.11
27.41
27.41
2.33
26.03
26.03
2.59
24.50
24.50
2.87
22.82
22.82
3.19
57
29.82
29.82
1.91
28.64
28.64
2.11
27.38
27.38
2.33
26.00
26.00
2.59
24.48
24.48
2.87
22.80
22.80
3.19
COOLING PERFORMANCE DATA - COOLING ONLY UNITS (CONT)
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES deg F
75
85
95
105
115
125
SIZE
INDOOR UNIT
OUTDOOR UNIT
CFM
EWB
Capacity MBtuht
Total
System
Kw-
Capacity MBtuht
Total
System
KW-
Capacity MBtuht
Total
System
KW**
Capacity MBtuht
Total
System
KW-
Capacity MBtuht
Total
System
KW**
Capacity MBtuht
Total
System
Kyy**
Total
Sens$
Total
Sens$
Total
Sens$
Total
Sens$
Total
Sens$
Total
Sens$
975
72
38.57
20.08
2.15
36.82
19.40
2.38
34.94
18.67
2.64
32.90
17.90
2.93
30.68
17.07
3.25
28.28
16.18
3.62
67
35.06
24.40
2.13
33.47
23.71
2.36
31.77
22.99
2.62
29.92
22.22
2.90
27.91
21.39
3.23
25.73
2050.
3.61
63
32.51
23.50
2.11
31.05
22.82
2.34
29.47
22.10
2.60
27.76
21.34
2.89
25.91
20.51
3.22
23.89
1963.
3.60
62
31.86
28.62
2.11
30.43
27.92
2.34
28.90
27.16
2.60
27.26
26.33
2.88
25.47
25.47
3.21
23.82
23.82
3.59
57
30.45
30.45
2.10
29.35
29.35
2.34
28.16
28.16
2.59
26.85
26.85
2.88
25.40
25.40
3.21
23.79
23.79
3.59
34
40MKCB34F--3
24AHA436AOOx
124AxS036000
1130
72
39.58
21.26
2.20
37.72
20.56
2.43
35.73
19.81
2.69
33.58
19.01
2.97
31.23
18.16
3.30
28.73
17.25
3.67
67
36.01
26.24
2.17
34.31
25.54
2.41
32.51
24.79
2.66
30.56
24.00
2.95
28.43
23.14
3.28
26.16
22.22
3.65
63
33.41
25.22
2.16
31.85
24.52
2.39
30.18
23.78
2.64
28.37
22.99
2.93
26.41
22.14
3.26
24.30
21.22
3.64
62
32.81
31.05
2.16
31.32
30.28
2.39
29.74
29.40
2.64
28.18
28.18
2.93
26.59
26.59
3.26
24.85
24.85
3.64
57
32.09
32.09
2.15
30.88
30.88
2.38
29.57
29.57
2.64
28.14
28.14
2.93
26.56
26.56
3.26
24.82
24.82
3.64
1335
72
40.56
22.74
2.26
38.58
22.01
2.49
36.47
21.24
2.75
34.21
20.43
3.03
31.74
19.54
3.36
29.12
18.62
3.73
67
36.91
28.59
2.23
35.12
27.86
2.47
33.20
27.09
2.72
31.15
26.26
3.01
28.93
25.36
3.33
26.57
24.38
3.71
63
34.28
27.41
2.22
32.61
26.68
2.45
30.84
25.91
2.70
28.95
25.09
2.99
26.90
24.19
3.32
24.73
23.20
3.69
62
33.93
33.93
2.21
32.58
32.58
2.45
31.14
31.14
2.71
29.56
29.56
3.00
27.82
27.82
3.33
25.92
25.92
3.70
57
33.88
33.88
2.21
32.54
32.54
2.45
31.10
31.10
2.71
29.53
29.53
3.00
27.79
27.79
3.33
25.89
25.89
3.70
1310
72
62.74
32.88
3.71
60.01
31.83
4.08
57.07
30.70
4.52
53.87
29.50
5.02
50.33
28.19
5.59
46.46
26.77
6.24
67
57.20
40.15
3.66
54.76
39.11
4.04
52.10
38.00
4.47
49.19
36.79
4.97
45.97
35.47
5.54
42.43
34.04
6.20
63
53.18
38.72
3.63
50.93
37.69
4.00
48.49
36.59
4.43
45.81
35.39
4.93
42.83
34.08
5.50
39.56
32.66
6.16
62
52.18
47.28
3.62
49.99
46.22
4.00
47.64
45.08
4.43
45.06
43.80
4.92
42.28
42.28
5.50
39.62
39.62
6.16
57
50.23
50.23
3.61
48.53
48.53
3.98
46.65
46.65
4.42
44.56
44.56
4.92
42.21
42.21
5.50
39.56
39.56
6.16
54
40MKCB54F--3
24AHA448AOOx
124AxSO48000
1400
72
63.45
33.74
3.74
60.65
32.67
4.12
57.65
31.54
4.55
54.35
30.32
5.05
50.73
28.99
5.62
46.78
27.56
6.28
67
57.89
41.51
3.70
55.36
40.45
4.07
52.63
39.32
4.50
49.65
38.10
5.00
46.35
36.76
5.58
42.75
35.31
6.23
63
53.84
39.99
3.66
51.51
38.94
4.04
49.01
37.82
4.47
46.25
36.61
4.96
43.21
35.28
5.54
39.88
33.83
6.19
62
52.87
49.09
3.66
50.64
48.00
4.03
48.23
46.80
4.46
45.66
45.40
4.96
43.11
43.11
5.54
40.36
40.36
6.20
57
51.43
51.43
3.65
49.64
49.64
4.02
47.68
47.68
4.46
45.51
45.51
4.96
43.05
43.05
5.54
40.31
40.31
6.20
1470
72
63.94
34.39
3.77
61.10
33.32
4.14
58.03
32.18
4.58
54.68
30.94
5.08
51.01
29.61
5.65
47.00
28.17
6.30
67
58.35
42.55
3.72
55.77
41.48
4.10
53.00
40.34
4.53
49.96
39.10
5.03
46.61
37.75
5.60
42.97
36.29
6.25
63
54.28
40.96
3.69
51.92
39.90
4.06
49.36
38.77
4.49
46.56
37.54
4.99
43.48
36.20
5.56
40.09
34.74
6.21
62
53.38
50.47
3.68
51.11
49.34
4.06
48.70
48.07
4.49
46.24
46.24
4.99
43.72
43.72
5.57
40.89
40.89
6.23
57
52.28
52.28
3.67
50.45
50.45
4.05
48.42
48.42
4.49
46.18
46.18
4.99
43.66
43.66
5.57
40.84
40.84
6.23
t Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
t Sensible capacities shown are based on 80° F (27° C) entering air at the indoor coil. For sensible capacities at other than 80* F (27* C), deduct 835 Btuh
(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80° F (27° C), or add 835 Btuh (245 kW) per 1000 CFM (480 US) of indoor coil air per degree above 80' F (27' C).
** System kw is total of indoor and outdoor unit kilowatts.
EWB - Entering Wet Bulb
NOTES:
1. Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per AHRI standard 210/240-2008. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.
2. When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
COOLING PERFORMANCE DATA - HEAT PUMP UNITS
Table 9 - Cooling Performance Data - Heat Pump Units
• •7 • •
K•].L1:1 61 :1 A :1 11:1VI lr1e1IA141,,1:j:I 111:7�Y.t�_7
Erg MOM-11"M
��6-7'
I■�af3'�i
�•
����a'
'i��:�.�a�a�a�'■�'��:�c■�:�a�a
•t
t •
�a�
.��.
���',
t •
•t
���
t •'
• •
• •
cam.,
��c
�. G ��fi�fi��,,
�I�
`�%a
`�%a�■
`�I' I■
`�I' I■�'a
`�I■
`�I■
t •
t • •
t • �
�a�a�aia�ia��r�■�r�■r�■
�a�a�a�a�■�■�_
� '•�asa�_�ar�sa�_rsf.�rs�a�'ar�a
' • •
��iS■
�.��a��
t '•
�a�
• 'c
�r�ars���r�'��■rsi���•�r�ar���■�as'a
t Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
t Sensible capacities shown are based on 80° F (27° C) entering air at the indoor coil. For sensible capacities at other than 80° F (27° C), deduct 835 Btuh
(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80° F (27° C), or add 835 Btuh (245 kW) per 1000 CFM (480 US) of indoor coil air per degree above 80° F (27° C).
** System kw is total of indoor and outdoor unit kilowatts.
EWB — Entering Wet Bulb
NOTES:
1. Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per AHRI standard 210/240-2008. If additional tubing length and/or indoor unit is located above outdoor unit, a slight
variation in capacity may occur.
2. When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
HEATING PERFORMANCE DATA - HEAT PUMP UNITS
Table 10 - Heating Performance Data - Heat Pump Units
INDOOR AIR
OUTDOOR COIL ENTERING AIR TEMPERATURES deg F
17
27
37
47
57
67
SIZE
INDOOR UNIT
OUTDOOR UNIT
EDB
CFM
Capacity MBtuh
Total
System
KWt
Capacity MBtuh
Total
System
KWt
Capacity MBtuh
Total
System
KWt
Capacity MBtuh
Total
System
KWt
Capacity MBtuh
Total
System
KWt
Capacity MBtuh
Total
System
KWt
Total
Integ*
Total
Integ*
Total
Integ*
Total
Integ*
Total
Integ*
Total
Integ*
65
1310
16.42
14.97
1.82
20.90
18.56
1.89
24.80
22.57
1.94
29.15
29.15
1.98
34.27
34.27
2.04
40.12
40.12
2.11
1400
16.57
15.11
1.84
21.04
18.69
1.90
24.97
22.72
1.94
29.34
29.34
1.99
34.51
34.51
2.04
40.41
40.41
2.10
1470
16.67
15.20
1.85
21.15
18.78
1.91
25.08
22.82
1.95
29.49
29.49
1.99
34.69
34.69
2.04
40.61
40.61
2.10
30
40MKQB36F--3
22
24ANS030000 003 4ANS030
70
1310
15.91
14.51
1.90
19.96
17.73
1.96
24.39
22.19
2.02
28.68
28.68
2.07
33.66
33.66
2.12
39.41
39.41
2.19
1400
16.05
14.64
1.91
20.16
17.91
1.97
24.55
22.34
2.02
28.87
28.87
2.07
33.90
33.90
2.12
39.69
39.69
2.19
1470
16.16
14.73
1.92
20.31
18.04
1.98
24.66
22.44
2.03
29.00
29.00
2.07
34.07
34.07
2.12
39.90
39.90
2.19
75
1310
15.37
14.02
1.98
19.36
17.19
2.04
24.00
21.84
2.10
28.21
28.21
2.16
33.07
33.07
2.21
38.71
38.71
2.28
1400
15.51
14.14
1.99
1952.
17.34
2.05
24.15
21.97
2.11
28.39
28.39
2.16
33.31
33.31
2.21
38.99
38.99
2.28
1470
15.62
14.24
2.00
19.65
17.45
2.05
24.25
22.06
2.11
28.53
28.53
2.16
33.47
33.47
2.21
39.19
39.19
2.28
65
1310
19.33
17.63
2.15
23.84
21.17
2.21
29.39
26.74
2.29
34.35
34.35
2.36
40.13
40.13
2.45
46.81
46.81
2.57
1400
19.51
17.79
2.15
24.04
21.35
2.21
29.58
26.92
2.29
34.60
34.60
2.35
40.44
40.44
2.44
47.23
47.23
2.55
1470
19.64
17.91
2.16
24.19
21.48
2.22
29.74
27.06
2.29
34.77
34.77
2.35
40.67
40.67
2.43
47.52
47.52
2.54
36
40MKQB36F--3
224AxS036000
224AxSO36000
70
1310
18.69
17.04
2.24
23.16
20.57
2.30
28.88
26.28
2.40
33.79
33.79
2.47
39.42
39.42
2.56
45.98
45.98
2.68
1400
18.87
17.20
2.25
23.36
2075.
2.31
29.08
26.46
2.39
34.03
34.03
2.46
39.73
39.73
2.54
46.38
46.38
2.66
1470
19.00
17.32
2.25
23.51
20.88
2.31
29.23
26.60
2.39
34.20
34.20
2.46
39.95
39.95
2.54
46.67
46.67
2.64
75
1310
17.99
16.41
2.33
22.46
19.95
2.40
27.59
25.11
2.49
33.22
33.22
2.58
38.72
38.72
2.67
45.15
45.15
2.80
1400
18.17
16.57
2.34
22.67
20.13
2.41
27.91
25.39
2.49
33.44
33.44
2.57
39.03
39.03
2.66
45.55
45.55
2.78
1470
18.30
16.69
2.35
22.82
20.27
2.41
28.16
25.63
2.49
33.61
33.61
2.57
39.25
39.25
2.65
45.82
45.82
2.76
65
1310
26.47
24.13
3.02
32.32
28.70
3.15
39.75
36.17
3.33
46.52
46.52
3.49
53.91
53.91
3.67
62.41
62.41
3.90
1400
26.71
24.36
3.02
32.62
28.97
3.14
40.40
36.77
3.31
46.88
46.88
3.45
54.39
54.39
3.62
63.03
63.03
3.83
1470
26.89
24.51
3.02
32.83
29.16
3.13
40.63
36.97
3.30
47.13
47.13
3.43
54.73
54.73
3.59
63.48
63.48
3.79
48
40MKQB48F--3
224AxSO48000
224AxSO48000
70
1310
25.69
23.42
3.13
31.47
27.95
3.27
38.21
34.77
3.44
45.83
45.83
3.64
53.06
53.06
3.83
61.41
61.41
4.07
1400
25.93
23.64
3.13
31.77
28.22
3.26
38.71
35.22
3.42
46.17
46.17
3.60
53.52
53.52
3.78
62.01
62.01
4.00
1470
26.11
23.80
3.13
31.99
28.41
3.26
39.08
35.57
3.41
46.40
46.40
3.58
53.85
53.85
3.75
62.44
62.44
3.95
75
1310
24.85
22.66
3.26
30.61
27.18
3.41
37.15
33.80
3.58
45.14
45.14
3.80
52.24
52.24
4.00
60.43
60.43
4.24
1400
25.10
22.88
3.26
30.90
27.45
3.39
37.53
34.15
3.55
45.44
45.44
3.76
52.68
52.68
3.94
61.01
61.01
4.18
1470
25.29
23.06
3.26
31.11
27.63
3.39
37.81
34.41
3.54
45.69
45.69
3.74
53.00
53.00
3.91
61.43
61.43
4.13
"* The Btuh heating capacity values shown are net integrated values from which the defrost effect has been subtracted. The Btuh heating from supplement heaters should be added to those values to obtain total system capacity.
t The kW values include the compressor, outdoor fan motor, and indoor blower motor. The kW from supplement heaters should be added to these values to obtain total system kilowatts.
NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
EDB - Entering Dry Bulb"
APPLICATION DATA
UNIT SELECTION
Table 12—Heating Operating Range
The horizontal units are available as cooling only and heat pumps.
For most applications, the cooling load dictates the size selection.
Select equipment to either match or be slightly less than anticipated
peak load. This provides better humidity control, fewer unit cycles,
and better low load performance.
For units used in spaces with high sensible loads, base equipment
selection on unit sensible load, not on total anticipated load to
avoid oversizing the equipment.
UNIT MOUNTING (INDOOR)
Unit leveling - For reliable operation, units should be level in all
planes.
Clearance - Provide adequate clearance for airflow (see Fig. 7).
Unit location - Select a location which will provide the best air
circulation for the room.
The Under Ceiling units should be mounted near the ceiling and
against a wall. The unit should be centered in the room for best
performance. Locating the unit on an outside wall makes piping easier,
however units can also be mounted away from a wall if desired. If
unit is mounted away from a wall, the rear panel of the unit may need
a field -supplied trim strip for improved appearance. Locate the fan
coil return over an area which is not normally occupied for quietest
operation. Do not block air discharge for a minimum of 15 ft (4.6 m)
to prevent dumping of cold air and drafts.
Support - The structure must provide adequate support for the weight
of the fan coil. Refer to the Physical Data section for fan coil weights.
Mounting Template - The fan coil units are furnished with
cardboard mounting templates to mark the hole locations for
wiring and refrigerant lines.
UNIT MOUNTING (OUTDOOR)
Unit leveling - For reliable operation, units should be level in all
planes.
Clearance - Minimum clearance, as shown in Fig. 10, must be
provided for airflow. The condensing units are designed for free -blow
application. Air inlets and outlets should not be restricted.
Unit location - A location which is convenient to installation and
not exposed to strong wind. If the unit is exposed to strong winds it
is recommended that a wind baffle accessory be used.
A location which can bear the weight of outdoor unit and where
the outdoor unit can be mounted in a level position.
SYSTEMS OPERATING CONDITIONS
Table 11—Cooling Operating Range
Maximum
Minimum
DB °F (oQ
WB °F (oQ
DB °F (oQ
WB °F (oQ
Outdoor
Unit
125 (51.7)
--
55 (12.8)
--
Indoor
Unit
90 (32.2)
84 (29)
64 (18)
59 (29)
Maximum
Minimum
DB °F (oQ
WB °F (oQ
DB °F (oQ
WB °F (oQ
Outdoor
Unit
75 (23.9)
67 (19.4)
17 (-8.3)
--
Indoor
Unit
80(27)
--
32(0)
--
Low Ambient Operation
Both the cooling only and heat pumps operate to cool down to
55°F (12.8°C). When equipped with a Low Ambient Controller,
the unit operates down to -20°F (-28.9°C).
For proper operation of colling only units, a Winter Start Kit), a
Crankcase Heater (prevents refrigerant migration during
compressor -off cycle), and a Wind Baffle should also be installed.
On heat pumps, a Winter Start Kit will not be required. An
Isolation Relay, to bypass the Low Ambient Controller when unit
is in heating mode, is required.
Metering Devices
The metering device(s) for these systems is a type B accurator. The
cooling accurator is installed with the indoor unit, while the
heating accurator is installed with the outdoor unit. One Accurator
is required for the cooling only system and two are required for the
heat pump systems. Refer to Table 13 for the accurator size.
Table 13—Metering Device
System Size
kBTU/hr
Cooling Only
Heat Pumps
40MKCB**C
40MKQB**C
25HHA4/224ANS
018
TXV
024
TXV
-
030
TXV
TXV
0.055'
034
TXV
-
054
TXV
-
036
-
TXV
0.063"
048
TXV
0.073"
DRAIN CONNECTIONS
When the unit is installed close to an outside wall, a downward
sloped condensate line can be used to dispose of the water (do not
trap condensate line). If this is not feasible, an accessory
condensate pump that can be installed inside the unit is available.
When using a condensate pump, the drain pipe can be routed
through the top of the unit, if desired.
Install drains to meet local sanitation codes. If adequate gravity
drainage cannot be provided, unit should be equipped with
accessory condensate pump.
15
CONTROL SYSTEM
REFRIGERANT LINES
General refrifferant line sizing
1. Refrigerant lines can access the Under Ceiling unit from
either the top -right or rear -right when facing the unit.
2. Refrigerant lines should not be buried in the ground. If it is
necessary to bury the lines, not more than 36-in (914 mm)
should be buried. Provide a minimum 6-in (152 mm) vertical
rise to the service valves to prevent refrigerant migration.
3. Both lines must be insulated. Use a minimum of 1/2-in.
(12.7mm) thick insulation. Closed -cell insulation is
recommended in all long -line applications.
4. Special consideration should be given to isolating
interconnecting tubing from the building structure. Isolate the
tubing so that vibration or noise is not transmitted into the
structure.
NOTE: Since the same outdoor unit can be matched with
different types of indoor units, it may not have enough
refrigerant charge. Refer to the Physical Data tables to
determine if additional charge is required.
Long Line Applications
The minimum length between the indoor and outdoor units is 10 ft.
(3m). Refer to the following table for the maximum lengths
allowed.
Table 14—Long Line Applications
Outdoor
Unit Size
Max Equivalent
Length* ft (m)
Max Elevation (ID
over OD) ft (m)
Max Elevation (OD
over ID ft (m)
18-54K
250 (76.2)
65 (19.8)
200 (61)
NOTE: For lengths greater than 25 ft (7.6 m), refer to the
Residential Long Line guide.
* Maximum actual length not to exceed 200 ft (61 m)
Total equivalent length accounts for losses due to elbows or fitting.
See the Long Line Guideline for details.
The ductless unit is equipped with a microprocessor controls to
operate the system and provide optimum levels of comfort and
operating efficiency.
The main microprocessor is located in the control box of the fan
coil unit with thermistors located in the fan coil inlet and on the
indoor coil. These thermistors monitor the system operation and
control the operating mode. To change the settings or the modes of
operation, use the factory supplied wireless remote control or
accessory wired controller.
The ductless unit has 5 operating modes:
• Fan Only
• Auto (heat pump models only)
• Heating (heat pump models only)
• Cooling
• Dehumidification (Dry)
FAN ONLY - In the Fan Only mode, the system filters and
circulates the room air without changing the room air temperature.
AUTO - In Auto mode, the system will automatically select one of
the following operating modes: cooling, heating or fan only based
on the difference between the room temperature and the set point
temperature.
HEATING - In the Heating mode, the system heats and filters
room air.
COOLING - In the Cooling mode, the system cools, dries and
filters room air.
DEHUMIDIFICATION (DRY) - in Dehumidification (Dry)
mode, the system dries, filters and slightly cools room temperature.
This mode does not take the place of a dehumidifier.
In addition to the above modes that are selected by using the
remote control. The unit can run in two other modes selected by
the manual button:
• EMERGENCY RUN
• TEST MODE
EMERGENCY mode - is used when the remote control is
misplaced or the batteries in the remote control have expired.
Pushing the manual button under the front cover will put the unit
in Auto mode with a predetermined set point (73.4°F/ 23°C).
TEST mode - is used when a technician needs to diagnose the
unit for a malfunction. The unit can be set into TEST mode using
the remote control. It will run regardless of the set point.
The microprocessor controls offer additional comfort and economy
features like SLEEP mode, TIMER and AUTO SWEEP. Refer to
the Owner's Manual for additional details on these features.
USER INTERFACE
The units come standard with a wireless remote control. The
wireless remote has a range of 25 ft (8 m) when pointed toward the
unit.
For some applications (commercial), a wired remote may be more
desirable. A wired remote control is offered as an accessory.
Table 15—Air Throw Data
Air Throw Data ft (m)
18 (AC)
26(7.9)
24-54 (AC)
29 (8.8)
30-48 (HP)
16
SOUND RATINGS
Outdoor Units
Table 16-A-WEIGHTED SOUND POWER (dBA)
Outdoor Unit Size
Standard
Typical Octave Band Spectrum (dBA, without tone adjustment)
Rating
(dBA)
125
250
500
1000
2000
4000
8000
18
69
50.5
57.0
59.5
64.5
60.5
53.5
43.0
Cooling Only
24
66
50.5
58.5
60.5
59.5
56.5
51.0
41.5
30
68
55.5
59.5
61.5
63.5
60.0
58.0
49.5
36
71
59.5
59.5
62.0
65.5
63.5
62.0
55.0
30
72
58.0
61.0
64.0
66.5
64.0
63.5
57.0
Heat Pump
36
71
59.5
59.5
62.5
65.0
63.0
61.5
55.0
48
70
1 57.5
1 59.5
1 63.0
65.0
62.5
60.0
54.0
NOTE: Tested in accordance with AHRI Standard 270-08 (not listed in AHRI).
Table 17-Indoor Units
ESTIMATED UNDER CEILING SOUND PRESSURE LEVEL
Under -ceiling
AC:18
AC: 24-34
AC:54
HP: 30 - 48
Cooling operation Indoor Sound Pressure for CO and HP cooling mode (at
Different Speeds)
dBa (cfm)
53/48/42 (695/515/405)
55/52/50
(1335/1130/975)
59/57/55 (1470/1400/1310)
Heating operation Indoor Sound Pressure for HP heating mode (at Different
Speeds)
dBa (cfm)
NA
NA
58/55/54 (1470/1400/1310)
ESTIMATED UNDER CEILING SOUND POWER LEVEL
Under -ceiling
AC:18
AC: 24-34
AC:54
HP: 30 - 48
Cooling operation Indoor Sound Pressure for CO and HP cooling mode (at
Different Speeds)
dBa (cfm)
63/58/52(695/515/405)
65/62/60(1335/1130/975)
69/67/65 (1470/1400/1310)
Heating operation Indoor Sound Pressure for HP heating mode (at Different
Speeds)
dBa (cfm)
NA
NA
68/65/64 (1470/1400/1310)
NOTES:
1. Sound power ratings are tested in accordance with AHRI standard 270---95 (not listed in AHRI) and AHRI 350.
2. Sound pressure ratings are estimated sound pressure, 3 feet (.91 m) from the unit, based on sound power data.
17
WIRING
The indoor and outdoor units have their own power supply. Refer to installation instructions for Wiring instructions.
ELECTRICAL DATA
Table 18-24AHA4/124ANS Electrical Data
UNIT SIZE --
voltage,series
V/PH
OPER VOLTS*
COMPR
FAN
MCA
MAX FUSE**
or
CKT BRK
AMPS
MAX
MIN
LRA
RLA
FLA
18--30
208/230/1
253
197
56.3
9
0.5
11.8
20
24--30
62.9
10.9
0.5
14.1
25
30--30
73
14.1
0.7
18.3
30
36--30
77
14.1
1.2
18.8
30
48--30
124
18.5
1.2
24.3
40
36--50
208/230/3
253
197
71
9
1.2
12.5
20
48--50
83.1
13.7
1.2
18.3
30
36--60
460/3
506
414
38
5.6
0.6
7.6
15
48--60
41
6.2
0.6
8.4
15
Table 19-25HHA4/224ANS Electrical Data
MAX FUSE**
UNIT SIZE --
OPER VOLTS*
COMPR
FAN
V/PH
MCA
or
CKT BRK
voltage,series
MAX
MIN
LRA
RLA
FLA
AMPS
30--30
208/230/1
253
197
64
12.8
1.2
17.2
30
36--30
77
14.2
1.2
19
30
48--30
117
21.8
1.45
28.8
50
36--50
208/230/3
253
197
71
9.3
1.2
12.8
20
48--50
83.1
13.7
1.45
18.6
30
36--60
460/3
506
414
38
5.6
0.6
7.6
15
48--60
41
6.2
0.8
8.6
15
Table 20-40MKCB**F Electrical Data
Indoor Unit Size
BTU/Hr
V-Ph-Hz
Voltage Range
Fan
Power
Min (V)
Max (V)
FLA (A)
Min Ckt Amp (A)
Max Fuse) Amp
(A)
18K
208-230-1-60
187
253
0.71
1
15
24K - 34K
208-230-1-60
187
253
0.7 x 2
3
15
54K
208-230-1-60
187
253
0.95 x 2
3
15
Table 21-40MKQB**F Electrical Data
Indoor Unit Size
BTU/Hr
V-Ph-Hz
Voltage Range
Fan
Power
Min (V)
Max (V)
FLA (A)
Min Ckt Amp
Max Fuse CB
(A)
Amp (A)
30K- 48K
208-230-1-60
187
253
0.95 x2
3
15
LEGEND
FLA -Full Load Amps
HACR- Heating, Air Conditioning, Refrigeration
LRA- Locked Rotor Amps
NEC- National Electrical Code
RLA- Rated Load Amps (compressor)
*Permissible limits of the voltage range at which the unit will operate satisfactorily
**Time- Delay fuse.
Complies with 2007 requirements of ASHRAE Standards 90.1
18
II
I I
DISPLAY
BOARD
TO WIRED REMOTE CONTROLLER CONNECTOR
Legend:
—I
........Model specific feature
L
GMl I GM3 I XPI
CAP: C apacitor
T
! xS1
CN 1: Live wire Ll/Null line L2
CN 213: Transformer interface
CN 25:Controls 24V signal interface(C)
L
CNTSensor interface
i
CN 20: Network module interface
CN72
I CN10 I CN15 I CN11
CN 12: Vertical swing motor Interface
(WHITE)
(RED) I
CN 13: horizontal swing motor interface
— --I
L—_ —�
C N 10. D isplay board interface
MAIN CONTROL BOARD
CN15:Compressor signal interface
CN 11: Water level detection switch
CN7
CN 16: Motor interface
XP2
RT1: Room temperature sensor
xS2
ON25
CN3 crvz cN1 CN16
RT2: PICE temperature s ensor
T3/4:Transformer
XP4
T4
G M1 /3: L evel s wing motor
GM2:Vertical swingmotor
XS/XP: Connectors
RT2
2
RTl
T3
L I I
FAN1 FAN2
—I
I I
WHITE WHITE IWHITE WHITE I
Y�C ��
CAP I L — _ CAP2_ — — — —
—
Notes: � I
24V— Controls 1.Tobewiredinaccordance with National I NET MODULE TO CCM
$w1 0 signal to POWER Electric opper conductors
odes.
Mode outdoor unit SUPPLY 2.Use Copper conductors only.
FLOOR CEILING Use conductors suitable for at least 75°C(167°F),I gN2.
FACTORY 3. Ifany ofthe original wires, as supplied I J
_ _ _ _ _ _ _
SETRNG must be replaced, use the same or equivalent wire. —
Fig. 9 — 40MKCB**F wiring diagram
OUTDOOR UNIT SCHEMATIC DIAGRAM
I L1 L2 COMP 1
D
C
*LPS *DTS *HPS
T1 T3
*CTD
*LLS
CONT
Fig. 10 — 24AHA4/124ANS Wiring Diagram 208/230V 1 Phase
19
I
I
I
I
EQUIF
GND
j L1 L2 L3
COMP I 0 ,
CONT
* HPS ' LIPS T2
LOGI
T1 T3
Q * CTD r D
IFR
a---------------------------------
R C------------i
INDOOR
THERMOSTAT EXTERNAL POWER SUPPLY 24 V
Fig. 11— 24ARA4/124ANS Wiring Diagram 208/230 - 460V 3 phase
DISPLAY O
BOARD
GM2 V
Xs11
2N12 2N13 I CN10 CN15 I CN71 i LCN20
(WHITE) (RED)
MAIN CONTROL BOARD
CNT
CN25 CN3 CN2 CN7 CNl6
XP4 T4
,34
RT2
RTI[fl I T3
XP3
�XS31
FAN1
CAP1
WIRED REMOTE CONTROLLER CONNECTOR
Legen d:
................Model specific fe ature
CAP: Capac itor
CN1: Livewire Ll /Null lineL2
CN2/3:Transformer interface
CN 25 Controls 24V signal interface(R /CI
CN 7: Sens or interface
CN 20 : Network module interface
CN 12 :Vertical swing motor interface
CN 13 : horizontal swing motor interface
CN 10 : Disp lay board interface
CN 15 :Sign al inte rface(Y/0)
CN 1 l: Wa ter level detection switch
CN 16:Motor interface
RTI: Room temperature Sens or
RT2: Pipet emperature sensor
T3/4: Trans former
GM1/3: Leve I swin g motor
GM 2: Vert ical s wing motor
XS/XP :Connectors
I
Y/G I
I FAN2
I I
I WHITE WHITE
Xa _ I
0AP2 11 — J
24V-- I POWER Notes: r — 1
Controls SUPPLY 1.Tobewired inaccordancewith NationaI
ON
SW1 Q signal to TO CCM
outdoor ElectricRE.C. a nd local cod es. � NET MoouLE
MODE FLOOR CEILING unit Use
nductoopper con itablefuctors ontl
Use c onductors s uitable for at lea st 75° C(167 °F). I
FACTORY 3. If a ny of the original wires, as s upplied I cN2o I
SETTING must be re place d,use the s ame o r equ ivalen t wire. L — — — — — — — — —
Fig. 12 — 40MKQB**F wiring diagram
20
I (OUTDOOR UNIT SCHEMATIC DIAGRAM
2 _
I I I
CONT COMP R
I — 11 21 C I
I
5 2 *SC S *ST
EQUIP +t
GND 1 H
*SR CONT
* CHS DR OFM C T 23 23
*CH OF1 OF2 F CAP
D\/C _
Fig. 13 — 25HHA4/224ANS Wiring Diagram 208/230V 1 Phase
L1 L2 L3
I I I I
I I CONT
I r2COMP -------� I
L — — 11 21
_ T1 T
EQUIP
GND
DR OFM CAP
CONT
*CHS *CH OF1 OF2 3 13
RVS
Fig. 14 — 25HHA4/224ANS Wiring Diagram 208/230V 3 phase
21
L1
I I
CONT
EQUIP
GND
*CHS
o
0
0
*CH
L2 I L3
T2
COMP — J
------
T I
T1
OFM CAP
OFR
3 LNTCO
RVS
Fig. 15 — 25HHA4/224ANS Wiring Diagram 460V 3 phase
22
GUIDE SPECIFICATIONS
INDOOR UNDER CEILING DUCTLESS UNITS
PART 1 - GENERAL
1.01 System Description
Indoor, under ceiling, direct -expansion fan coils are matched with
cooling only or heat pump outdoor unit.
1.02 Agency Listings
Unit shall be rated per AHRI Standards 210/240 and listed in the
AHRI directory as a matched system.
1.03 Delivery, Storage, And Handling
Units shall be stored and handled per unit manufacturer's
recommendations.
1.04 Warranty (For Inclusion By Specifying
Engineer)
PART 2 - PRODUCTS
2.01 Equipment
A. General:
Indoor, direct -expansion, under ceiling fan coil. Unit shall be
complete with cooling/heating (heat pump systems only) coil, fan, fan
motor, piping connectors, electrical controls, microprocessor control
system, and integral temperature sensing. Unit shall be furnished with
mounting bracket.
B. Unit Cabinet:
1. Unit cabinet shall be zinc -coated bonderized steel finished
with a baked enamel paint.
2. Inlet grilles shall be attractively styled, high impact
polystyrene.
3. Matching mounting brackets shall be provided.
C. Fans:
1. Indoor fans shall be 3-speed centrifugal blower type with
air intake in the bottom rear of the unit and discharge in the
front.
2. Automatic, motor -driven horizontal air sweep shall be
provided standard.
D. Coil:
Coil shall be copper tube with aluminum fins and galvanized steel
tube sheets. Fins shall be bonded to the tubes by mechanical
expansion and specially coated for enhanced wettability. A drip
pan under the coil shall have a drain connection for the hose
attachment to remove condensate.
E. Motors:
Motors shall be open drip -proof, permanently lubricated ball bearing
with inherent overload protection. Fan motors shall be 3-speed.
F. Controls:
Controls shall consist of a microprocessor -based control system
which shall control space temperature, determine optimum fan
speed, and run self diagnostics. the temperature control range shall
be from 62°F to 86°F (17°C to 30°C) in increments of 1°F or
VC, and have 46°F Heating Mode (Heating Setback). The
wireless remote controller shall have the ability to act as the
temperature sensing location for room comfort..
Model Number: 40MKCF/40MKQF
Size Range: 1-1/2 to 4-1/2 Ton Nominal Cooling and Heating Capacity
The unit shall have the following functions as a minimum:
1. An automatic restart after power failure at the same
operating conditions as at failure.
2. A timer function to provide a minimum 24-hour timer
cycle for system Auto Start/Stop.
3. Temperature -sensing controls shall sense return air
temperature.
4. Indoor coil freeze protection.
5. Wireless infrared remote control to enter set points and
operating conditions.
6. Automatic vertical air sweep control to provide on or off
activation of air sweep louvers.
7. Dehumidification mode shall provide increased latent
removal capability by modulating system operation and set
point temperature.
8. Fan -only operation to provide room air circulation when no
cooling is required.
9. Diagnostics shall provide continuous checks of unit
operation and warn of possible malfunctions. Error
messages shall be displayed at the unit.
10. Fan speed control shall be user -selectable: high, medium,
low, or microprocessor controlled automatic operation
during all operating modes.
11. Automatic heating -to -cooling changeover in heat pump
mode. Control shall include deadband to prevent rapid
mode cycling between heating and cooling.
12. Indoor coil high temperature protection shall be provided to
detect excessive indoor discharge temperature when unit is
in heat pump mode (Heat pump units only).
G. Filters:
Unit shall have filter track with factory -supplied cleanable filters.
H. Electrical Requirements:
Indoor units shall be 208/230-1-60 and require their own power
supply. Only control wiring shall run between the indoor and
outdoor units.
I. Operating Characteristics:
The 40MK*F when matched with the appropriate outdoor section,
shall have a minimum listed SEER (seasonal energy efficiency
ratio) of 14 at AHRI conditions, and a minimum HSPF of 8.2
(Heat pump units only).
J. Refrigerant Lines:
All units should have refrigerant lines that can be oriented to
connect from the left, right or back of unit. Both refrigerant lines
need to be insulated.
K. Special Features (Field Installed):
1. Condensate Pump: - The condensate pump shall remove
condensate from the drain pan when gravity drainage cannot
be used. Pump shall be designed for quiet operation. Pump
shall consist of two parts: an internal reservoir/sensor assembly,
and a remote sound -shielded pump assembly. A liquid level
sensor in the reservoir shall stop cooling operation if the liquid
level in the reservoir is unacceptable.
2. Wired Control (Optional): - The wired control can replace
the standard wireless control and provide the User Interface
to control one unit.
23
GUIDE SPECIFICATIONS
PART 1 - GENERAL
1.01 System Description
A. Outdoor air-cooled split system compressor sections suitable for
on -the -ground, rooftop, wall hung or balcony mounting. Units
shall consist of a scroll compressor, an air-cooled coil,
propeller -type blow -through outdoor fan, reversing valve (HP),
accumulator, Accurator metering device(s), and control box. Units
shall discharge air horizontally as shown on the contract drawings.
Units shall function as the outdoor component of an air-to-air
cooling only, or heat pump system.
B. Units shall be used in a refrigeration circuit matched to ductless
cooling only or heat pump fan coil units.
1.02 Agenc, Listings
A. Unit construction shall comply with ANSI/ASHRAE 15, latest
revision, and with the NEC.
B. Units shall be evaluated in accordance with UL standard 1995.
C. Units shall be listed in the CEC directory.
D. Unit cabinet shall be capable of withstanding 500-hour salt spray
test per Federal Test Standard No. 141 (method 6061).
E. Air-cooled condenser coils shall be leak tested at 573 psig.
1.03 Delivery. Storage. And Handling
Units shall be shipped in one piece and shall be stored and handled
per unit manufacturer's recommendations.
1.04 Warranty (For Inclusion By Specifying
Engineer)
PART 2 - PRODUCTS
2.01 Equipment
A. General:
Factory assembled, single piece, air-cooled outdoor unit. Contained
within the unit enclosure shall be all factory wiring, piping, controls,
and the compressor.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of galvanized steel,
bonderized and coated with a baked -enamel finish on inside
and outside.
2. Unit access panels shall be removable with minimal screws
and shall provide full access to the compressor, fan, and
control components.
3. Outdoor compartment shall be isolated and have an acoustic
lining to assure quiet operation.
4. Compressor compartment shall be isolated to allow performing
diagnostics while the system is running.
C. Fans:
1. Outdoor fans shall be direct -drive propeller type, and shall
discharge air horizontally. Fans shall blow air through the
outdoor coil.
2. Outdoor fan motors shall be totally enclosed, single phase
motors with class B insulation and permanently -lubricated
bearings. Motor shall be protected by internal thermal overload
protection.
3. Shaft shall have inherent corrosion resistance.
4. Fan blades shall be metallic and shall be statically and
dynamically balanced.
5. Outdoor fan openings shall be equipped with PVC coated
metal protective grille over fan.
HORIZONTAL DISCHARGE OUTDOOR UNITS
Model Number: 24AHA4/25HHA4/124ANS/224ANS
Size Range: 1-1/2 to 4 - 1/2 Ton Nominal Cooling and Heating Capacity
D. Compressor:
1. Compressor shall be fully hermetic scroll type.
2. Compressor shall be equipped with oil system, operating oil
charge, and motor. Internal overloads shall protect the
compressor from over -temperature and over -current.
3. Motor shall be NEMA rated class F, suitable for operation
in a refrigerant atmosphere.
4. Compressor assembly shall be installed on rubber vibration
isolators.
5. Compressors shall be available in single-phase (sizes
018-036) and three-phase (size 036).
E. Outdoor Coil:
Coil shall be constructed of aluminum fins mechanically bonded to
seamless copper tubes, which are cleaned, dehydrated, and sealed.
F. Refrigeration Components:
Refrigerant circuit components shall include brass external liquid line
service valve with service gage port connections, suction line service
valve with service gage connection port, service gage port connections
on compressor suction and discharge lines with Schrader type fittings
with brass caps, accumulator, reversing valve.
G. Controls and Safeties:
Operating controls and safeties shall be factory selected, assembled,
and tested. The minimum control functions shall include:
1. Controls:
a. A time delay control sequence is provided standard through
the fan coil board.
b. Automatic outdoor -fan motor protection.
2. Safeties:
a. Diagnostics provided by matched indoor unit.
b. Compressor motor current and temperature overload
protection.
c. Outdoor fan failure protection (High Pressure Switch).
d. Low pressure protection.
e. Fusible plug to vent refrigerant safely in case of a fire.
H. Electrical Requirements:
1. All sizes shall operate on single-phase, 60 Hz power at
208/230V or on three-phase, 60 Hz power at either
208/230 or 460 (for 36 & 48 size units).
2. Unit control voltage to the indoor -fan coil shall be 24 VDC.
3. All power and control wiring must be installed per NEC
and all local electrical codes.
I.
J.
Refrigerant Line Lengths:
1. The unit shall be capable of 200 ft (61 m) maximum piping,
a maximum lift (fan coil above) of 65 ft (19.8 m) and a
maximum drop (fan coil below) of 150 ft (45.8 m).
Accessories will be required to achieve these lengths.
Special Features (Field Installed):
1. Low -Ambient Kit: Control shall regulate fan -motor cycles
in response to saturated condensing temperature of the unit.
The control shall be capable of maintaining a condensing
temperature of 100°F ± 10°F (37.78°C ± 5.5°C) with
outdoor temperatures to -20°F (-28.9°C). Installation of kit
shall not require changing the outdoor fan motor.
2. Crankcase Heater
3. Wind baffle
4. Stacking Kit
5. Wall Mounting Kit
24
25
Copyright 2015 CAC/BDP • 7310 W. Morris St. • Indianapolis, IN 46231 Edition Date: 08/15 Catalog No.40MKC(Q)B—F-01 PD
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Replaces: NEW