REVIEWED BLD BLD2021-1206+Sturctural_Plans+8.30.2021_4.18.56_PM+2384119CODE: INTERNATIONAL BUILDING CODE (IBC) 2018 LOADINGS FLOOR LIVE LOAD ..................................................... 40 PSF DECK LIVE LOAD ..................................................... 60 PSF ROOF SNOW LOAD ..................................................... 25 PSF WIND CRITERIA BUILDING CLASSIFICATION ............................... II ULTIMATE WIND SPEED ...................................... 110 MPH WIND EXPOSURE ........................................... B TOPOGRAPHIC FACTOR, Kzt................. 1.0 SEISMIC CRITERIA SEISMIC RISK CATEGORY .............................. II SPECTRAL RESPONSE COEFFICIENT, Sds .... 0.85 SPECTRAL RESPONSE COEFFICIENT, Sd1 .... 0.50 SEISMIC SITE CLASS ................................. D SEISMIC DESIGN CATEGORY ............................... D STRUCTURALSYSTEM REPLACEMENT OF EXISTING ROTTEN DECK GENERAL CONDITIONS 1. THE CONTRACTOR SHALL EXAMINE THE STRUCTURAL DRAWINGS AND SHALL NOTIFY THE STRUCTURAL ENGINEER IN WRITING OF ANY DISCREPANCIES HE MAY FIND BEFORE PROCEEDING WITH THE WORK. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS, ELEVATIONS AND SITE CONDITIONS BEFORE STARTING WORK. 2. ALL OMISSIONS OR CONFLICTS BETWEEN THE VARIOUS ELEMENTS OF THE WORKING DRAWINGS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT AND THE STRUCTURAL ENGINEER BEFORE PROCEEDING WITH ANY WORK SO INVOLVED. 3. SPECIFIC NOTES AND DETAILS SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS. WHERE THE NOTES, DRAWINGS, AND/OR SPECIFICATIONS DIFFER, THE MORE STRINGENT REQUIREMENT SHALL APPLY. 4. IF A SPECIFIC DETAIL IS NOT SHOWN FOR ANY PART OF THE WORK, THE CONSTRUCTION SHALL BE THE SAME AS FOR SIMILAR WORK. 5. WORKING DIMENSIONS SHALL NOT BE SCALED FROM PLANS, SECTIONS, OR DETAILS ON THESE DRAWINGS. 6. THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE ARCHITECT AND THE STRUCTURAL ENGINEER OF ANY CONDITION THAT, IN HIS OPINION, MIGHT ENDANGER THE STABILITY OF THE STRUCTURE OR CAUSE DISTRESS TO THE STRUCTURE. 7. THE CONTRACTOR SHALL SUPERVISE AND DIRECT HIS WORK AND HE SHALL BE SOLELY RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES AND PROCEDURES. PROVIDE ADEQUATE SHORING AND BRACING OF ALL STRUCTURAL MEMBERS DURING CONSTRUCTION. NOTIFY ENGINEER OF ALL FIELD CHANGES PRIOR TO INSTALLATION. 8. REFER TO THE ARCHITECTURAL DRAWINGS FOR INFORMATION NOT COVERED BY THESE GENERAL NOTES OR THE STRUCTURAL DRAWINGS. 9. ALL CONSTRUCTION SHALL BE DONE WITH MATERIALS, METHODS, AND WORKMANSHIP ACCEPTED AS GOOD PRACTICE BY THE CONSTRUCTION INDUSTRY AND IN CONFORMANCE WITH THE PROVISIONS OF PREVAILING CODE EDITION OF THE "INTERNATIONAL BUILDING CODE" (IBC) AND STANDARDS REFERENCED THEREIN. 10. PIPES, DUCTS, SLEEVES, OPENINGS, POCKETS, CHASES, BLOCK -OUTS, ETC., SHALL NOT BE PLACED IN SLABS, FOUNDATIONS, ETC., NOR SHALL ANY STRUCTURAL MEMBER BE CUT FOR SUCH ITEMS, UNLESS SPECIFICALLY DETAILED ON THESE STRUCTURAL DRAWINGS. 11. ALTERNATE ASSEMBLIES AND MATERIALS WILL BE CONSIDERED FOR REVIEW. ENGINEER MAY REQUEST PAYMENT FOR REVIEW. 1. STRUCTURAL DESIGN COMPLIES WITH SOILS REPORT PRODUCED BY: N.A. FOOTING BEARING PRESSURE: 1500 PSF (ASSUMED) LATERAL EARTH PRESSURE ON RETAINING WALLS N.A. 2. SUBGRADE PREPARATION, DRAINAGE PROVISIONS, AND OTHER RELEVANT SOIL CONSIDERATIONS ARE TO BE IN ACCORDANCE WITH SAID SOILS REPORT. Special Inspections required for this project: 1) Soils 2) Construction and Installation of the Pin Piles DIMENSIONAL LUMBER 1. MEET REQUIREMENTS OF PS 20-70 AND NATIONAL GRADING RULES FOR SOFTWOOD DIMENSIONAL LUMBER. BEAR STAMP OF WWPA. 2. MINIMUM DIMENSIONAL LUMBER GRADES TO BE: WALL STUDS, 2X, 3 X........ HF STUD GRADE WALL PLATES, 2X, 3X........ HF STANDARD GRADE U.N.O JOISTS, 2 X 6: ............. HF #2 JOISTS, 2 X 8 AND UP....... DF #2 BEAMS, HEADERS, 6X ........ DF #2 BEAMS, HEADERS, 4X......... DF #2, WWPA GRADING POSTS, 4X, 6X.............. DF #2 U.N.O LUMBER NOT NOTED HERE... DF #2 U.N.O APPROVED PLANS MUST BE ON JOB SITE ALL WORK SUBJECT TO FIELD INSPECTION FOR CODE COMPLIANCE i��:Z�Z�11�1/_1►1�7_1:1�I�1�)tr�U�97:1,i1:� Zi]�L'l_l��y_1►1�1►N)t�y 1y_1:71�[el_[e%U►69r�i�NZ�7� 4. ALL SILLS OR PLATES RESTING ON CONCRETE OR MASONRY THAT IS IN CONTACT WITH OR RESTING ON FOUNDATIONS SHALL BE PRESSURE -TREATED DOUGLAS FIR/HEMFIR. ALL BEARING WALL PLATES SHALL HAVE 5/8" 0 ANCHOR BOLTS PLACED A MAXIMUM OF 9" FROM THE END OF A PLATE AND SPACED AT INTERVALS SHOWN ON THE SHEARWALL SCHEDULE (MAXIMUM 4'4" OC SPACING). PROVIDE 3" X 3" X 1/4" PLATE WASHERS AT ALL FOUNDATION SILL PLATE ANCHOR BOLTS. PROVIDE TWO ANCHOR BOLTS MINIMUM PER SECTION OF SILL. 5. BOLTS IN WOOD SHALL NOT BE LESS THAN 7 DIAMETERS FROM THE END AND 4 DIAMETERS FROM THE EDGE OF THE MEMBER. 6. NAILS: COMMON WIRE NAILS. NAILING IN ACCORDANCE WITH IBC TABLE 2304.9.1. 7. PRESSURE TREATED WOOD: ALL NAILS INTO PT WOOD SHALL BE HOT DIPPED GALVANIZED PER ASTM A153 OR STAINLESS STEEL. ALL METAL CONNECTORS IN CONTACT WITH PT WOOD SHALL BE HOT DIPPED GALVANIZED AND MEET ASTM A653 CLASS G185 (1.85 OZ OF ZINC PER SQ FT MINIMUM) OR TYPE 304 / 316 STAINLESS STEEL SIMPSON Z-MAX CONNECTORS MEET THIS REQUIREMENT. FASTENERS AND CONNECTORS USED TOGETHER SHALL BE OF THE SAME TYPE (E.G. HOT DIPPED NAILS WITH HOT DIPPED HANGERS) 8. ALL LUMBER WITH A LEAST DIMENSION OF 2" (NOMINAL) SHALL BE STAMPED "SURFACE - DRY" AND SHALL HAVE A MOISTURE CONTENT WHEN SURFACED AND WHEN INSTALLED OF NO MORE THAN 19 PERCENT. LUMBER WITH A LEAST DIMENSION OF 4" (NOMINAL) OR GREATER SHALL BE STAMPED "SURFACE -GREEN" AND AIR-DRIED TO A MOISTURE CONTENT OF NOT MORE THAN 19 PERCENT PRIOR TO ITS USE IN FRAMING THE STRUCTURE. 9. NOTCHING AND BORING OF BEAMS AND JOISTS IS NOT ALLOWED WITHOUT PRIOR APPROVAL OF THE STRUCTURAL ENGINEER OF RECORD. REQUIRED? (Y/N) MATERIAL / ACTIVITY Y N 1704.2.5 Inspection of Fabricators Verify fabrication/quality control procedures Y N 1705.1.1 Special Cases (work unusual in nature, including but not limited to alternative materials and systems, unusual design applications, materials and systems with special manufacturer's requirements) 1705.2 Steel Construction Y N 1. Fabricator and erector documents (Verify reports and certificates as listed in AISC 360, chapter N, paragraph 3.2 for compliance with construction documents) Y N 2. Material verification of structural steel Y N 3. Embedments (Verify diameter, grade, type, length, embedment. See 1705.3 for anchors) Y N 4. Verify member locations, braces, stiffeners, and application of joint details at each connection comply with construction documents 5. Structural steel welding: Y N a. Inspection tasks Prior to Welding (Observe, or perform for each welded joint or member, the QA tasks listed in AISC 360, Table N5.4-1) Y N b. Inspection tasks During Welding (Observe, or perform for each welded joint or member, the QA tasks listed in AISC 360, Table N5.4-1) Y N c. Inspection tasks After Welding (Observe, or perform for each welded joint or member, the QA tasks listed in AISC 360, Table N5.4-3) d. Nondestructive testing (NDT) of welded joints: see Commentary Y N 1) Complete penetration groove welds 5/16" or greater in risk category III or IV Y N 2) Complete penetration groove welds 5/16" or greater in risk category II Y N 3) Thermally cut surfaces of access holes when material t > 2" Y N 4) Welded joints subject to fatigue when required by AISC 360, Appendix 3, Table A-3.1 Y N 5) Fabricator's NDT reports when fabricator performs NDT 6. Structural steel bolting: Y N a. Inspection tasks Prior to Bolting (Observe, or perform tasks for each bolted connection, in accordance with QA tasks listed in AISC 360, Table N5.6-1) Y N b.lnspection tasks During Bolting (Observe the QA tasks listed in AISC 360, Table N5.6-2) 1) Pre -tensioned and slip -critical joints Y N a) Turn -of -nut with matching markings Y N b) Direct tension indicator Y N c) Twist -off type tension control bolt Y N d) Turn -of -nut without matching markings Y N e) Calibrated wrench 2) Snug -tight joints Y N c. Inspection tasks After Bolting (Perform tasks for each bolted connection in accordance with QA tasks listed in AISC 360, Table N5.6-3) Y N 7. Inspection of steel elements of composite construction prior to concrete placement in accordance with QA tasks listed in AISC 360, Table N6.1 1705.2.2 Steel Construction Other Than Structural Steel 1. Material verification of cold -formed steel deck: Y N a. Identification markings Y N b. Manufacturer's certified test reports 2. Connection of cold -formed steel deck to supporting structure: Y N a. Welding Y N b. Other fasteners (in accordance with AISC 360,Section N6) Y N 1) Verify fasteners are in conformance with approved submittal Y N 2) Verify fastener installation is in conformance with approved submittal and manufacturer's recommendations 3. Reinforcing steel Y N a. Verification of weldability of steel other than ASTM A706 Y N b. Reinforcing steel resisting flexural and axial forces in intermediate and special moment frames, boundary elements of special concrete structural walls and shear reinforcement Y N c. Shear reinforcement Y N d. Other reinforcing steel 4. Cold -formed steel trusses spanning 60 feet or greater Y N a. Verify temporary and permanent restraint/bracing are installed in accordance with the approved truss submittal package 1705.3 Concrete Construction Y N 1. Inspection of reinforcing steel installation (see 1705.2.2 for welding) Y N 2. Inspection of prestressing steel installation Y N 3. Inspection of anchors cast in concrete where allowable loads have been increased per section 1908.5 or where strength design is used Y N O 4. Inspection of anchors and reinforcing steel post -installed in hardened concrete: Per research p 9 reports including verification of anchor type, anchor dimensions, hole dimensions, hole cleaning procedures, anchor spacing, edge distances, concrete minimum thickness, anchor embedment and tightening torque Y N 5. Verify use of approved design mix Y N 6. Fresh concrete sampling, perform slump and air content tests and determine temperature of concrete Y N 7. Inspection of concrete and shotcrete placement for proper application techniques Y N 8. Inspection for maintenance of specified curing temperature and techniques 9. Inspection of prestressed concrete: Y N a. Application of prestressing force Y N b. Grouting of bonded prestressing tendons in the seismic -force -resisting system 10. Erection of precast concrete members Y N a. Inspect in accordance with construction documents Y N b. Perform inspections of welding and bolting in accordance with Section 1705.2 Y N 11. Verification of in -situ concrete strength, prior to stressing of tendons in post tensioned concrete and prior to removal of shores and forms from beams and structural slabs Y N 12. Inspection of formwork for shape, lines, location and dimensions Y N 13. Concrete strength testing and verification of compliance with construction documents CONCRETE AND REINFORCING Notes: 1. The inspection and testing agent(s) shall be engaged by the Owner or the Owner's Agent, and not b the Contractor or Subcontractor whose work is to be inspected or tested. An conflict of interest Y P Y must be disclosed to the Building Official prior to commencing work. The qualifications of the Special Inspector(s) and/or testing agencies may be subject to the approval of the Building Official and/or the Design Professional. 2. The list of Special Inspectors may be submitted as a separate document, if noted so above. 3. Special Insepctions as required by Section 1704.2.5 are not required where the fabricator is approved in accordance with IBC Section 1704.2.5.2 4. Observe on a random basis, operations need not be delayed pending these inspections. Perform these tasks for each welded joint, bolted connection, or steel element. 5. NDT of welds completed in an approved fabricator's shop may be performed by that fabricator when approved by the AHJ. Refer to AISC 360, N7. 1. CONCRETE SHALL CONFORM TO THE INDICATED REFERENCE CODES AND STANDARDS EXCEPT AS MODIFIED BELOW: ACI-301 - "STANDARD SPECIFICATIONS FOR STRUCTURAL CONCRETE" ACI-318 - "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE" ACI-305R - "HOT WEATHER CONCRETING" ACI-306R - "COLD WEATHER CONCRETING" ACI-304 - "GUIDE FOR MEASURING, MIXING, TRANSPORTING AND PLACING CONCRETE" 2. CONCRETE MIX SPECIFICATIONS LOCATION COMP. SRENGTH W/C RATIO AIR CONTENT REMARK FOOTING 3000 PSI (MIN. OF 5.5 SACKS OF CEMENT PER CUBIC YARD OF CONCRETE) SLAB ON GRADE 3000 PSI (MIN. OF 5.5 SACKS OF CEMENT PER CUBIC YARD OF CONCRETE) FOUNDATION WALL 3000 PSI (MIN. OF 5.5 SACKS OF CEMENT PER CUBIC YARD OF CONCRETE) TOPPING N.A. a. TOTAL AIR CONTENT IS SPECIFIED IN THE TABLE ABOVE. AIR CONTENT TOLERANCE SHALL BE ± 1 % AND SHALL BE MEASURED AT THE POINT OF PLACEMENT. (AFTER PUMPING IF APPLICABLE). ALL CONCRETE EXPOSED TO THE WEATHER SHALL HAVE AN APPROVED ADMIXTURE TO ENTRAIN AIR - 5% TOTAL AIR REQUIRED. CONCRETE THAT CAN BE SUBJECTED TO FREEZING AND THAWING DURING CONSTRUCTION SHALL BE AIR ENTRAINED. 3. PROVIDE GRADE 60 KSI (A615) FOR CONCRETE STEEL REINFORCING EXTENT Periodic Each submittal Periodic Continuous Periodic Observe or Perform as noted (4) Observe (4) Observe or Perform as noted (4) Periodic Periodic Periodic Periodic Each submittal (5) Observe or Perform as noted (4) Observe (4) Periodic Periodic Periodic Continuous Continuous Periodic Perform (4) Observe or Perform as noted (4) Periodic Each submittal Periodic Periodic Periodic Periodic Continuous Continuous Periodic Periodic Periodic. Periodic Continuous Periodic or as required by the research report issued by an approved source Periodic Continuous Continuous Periodic Continuous Continuous In accordance with construction documents In accordance with Section 1705.2 Periodic Periodic Periodic REQUIRED? (Y/N) MATERIAL / ACTIVITY 1705.4 Masonry Construction (A) Level A, B and C Quality Assurance: Y N 1. Verify compliance with approved submittals (B) Level B Quality Assurance: Y N 1. Verification of fm and f'AAC prior to construction (C) Level C Quality Assurance: Y N 1. Verification of f'm and f'AAC prior to construction and for every 5,000 SF during construction Y N 2. Verification of proportions of materials in premixed or preblended mortar, prestressing grout, and grout other than self -consolidating grout, as delivered to the project site Y N 3. Verify placement of masonry units (D) Levels B and C Quality Assurance: Y N 1. Verification of Slump Flow and Visual Stability Index (VSI) of self -consolidating grout as delivered to the project Y N 2. Verify compliance with approved submittals Y N 3. Verify proportions of site -mixed mortar, grout and prestressing grout for bonded tendons Y N 4. Verify grade, type, and size of reinforcement and anchor bolts, and prestressing tendons and anchorages Y N 5. Verify construction of mortarjoints Y N 6. Verify placement of reinforcement, connectors, and prestressing tendons and anchorages Y N 7. Verify grout space prior to grouting Y N 8. Verify placement of grout and prestressing grout for bonded tendons Y N 9. Verify size and location of structural masonry elements Y N 10. Verify type, size, and location of anchors, including details of anchorage of masonry to structural members, frames, or other construction. Y N 11. Verify welding of reinforcement (see 1705.2.2) Y N 12. Verify preparation, construction, and protestion of masonry during cold weather (temperature below 40oF) or hot weather (temperature above 90oF) Y N 13. Verify application and measurement of prestressing force Y N 14. Verify placement of AAC masonry units and construction of thin -bed mortar joints (first 5000 SF of AAC masonry) Y N 15. Verify placement of AAC masonry units and construction of thin -bed mortar joints (after the first 5000 SF of AAC masonry) Y N 16. Verify properties of thin -bed mortar for AAC masonry (first 5000 SF of AAC masonry) Y N 17. Verify properties of thin -bed mortar forAAC masonry (after the first 5000 SF of AAC masonry) Y N 18. Prepare grout and mortar specimens Y N 19. Observe preparation of prisms 1705.5 Wood Construction Y N 1. Inspection of the fabrication process of wood structural elements and assemblies in accordance with Section 1704.2.5 Y N 2. For high -load diaphragms, verify grade and thickness of structural panel sheathing agree with approved building plans Y N 3. For high -load diaphragms, verify nominal size of framing members at adjoining panel edges, nail or staple diameter and length, number of fastener lines, and that spacing between fasteners in each line and at edge margins agree with approved building plans Y N 4. Metal -plate -connected wood trusses spanning 60 feet or greater: verify temporary and permanent restraint/bracing are installed in accordance with the approved truss submittal package 1705.6 Soils Y N 1. Verify materials below shallow foundations are adequate to achieve the design bearing capacity. Y N 2. Verify excavations are extended to proper depth and have reached proper material. Y N 3. Perform classification and testing of controlled fill materials. Y N 4. Verify use of proper materials, densities, and lift thicknesses during placement and compaction of controlled fill Y N 5. Prior to placement of controlled fill, observe subgrade and verify that site has been prepared properly 1705.7 Driven Deep Foundations Y N 1. Verify element materials, sizes and lengths comply with requirements Y N 2. Determine capacities of test elements and conduct additional load tests, as required Y N 3. Observe driving operations and maintain complete and accurate records for each element Y N 4. Verify placement locations and plumbness, confirm type and size of hammer, record number of blows per foot of penetration, determine required penetrations to achieve design capacity, record tip and butt elevations and document any damage to foundation element Y N 5. For steel elements, perform additional inspections per Section 1705.2 Y N 6. For concrete elements and concrete -filled elements perform additional inspections per Section .p p 1705.3 Y N 7. For specialty elements, perform additional inspections as determined by the registered design professional in responsible charge Y N 8. Perform additional inspections and tests in accordance with the construction documents 1705.8 Cast -in -Place Deep Foundations Y N 1.Observe drilling operations and maintain complete and accurate records for each element Y N 2. Verify placement locations and plumbness, confirm element diameters, bell diameters (if applicable), lengths, embedment into bedrock (if applicable) and adequate end -bearing strata capacity. Record concrete or grout volumes Y N 3. For concrete elements, perform additional inspections in accordance with Section 1705.3 Y N 4. Perform additional inspections and tests in accordance with the construction documents 1705.9 Helical Pile Foundations Y N 1. Verify installation equipment, pile dimensions, tip elevations, final depth, final installation torque and other data as required. Y N 2. Perform additional inspections and tests in accordance with the construction documents 1705.10.1 Structural Wood Special Inspections For Wind Resistance Y N 1. Inspection of field gluing operations of elements of the main windforce-resisting system Y N 2. Inspection of nailing, bolting, anchoring and other fastening of components within the main windforce-resisting system 1705.10.2 Cold -formed Steel Special Inspections For Wind Resistance Y N 1.Inspection during welding operations of elements of the main windforce-resisting system Y N 2.Inspections for screw attachment, bolting, anchoring and other fastening of components within the main windforce-resisting system 1705.10.3 Wind -resisting Components Y N 1. Roof cladding Y N 2. Wall cladding Y N 1705.11.1 Structural Steel Special Inspections for Seismic Resistance Inspection of structural steel in accordance with AISC 341 1705.11.2 Structural Wood Special Inspections for Seismic Resistance Y N 1. Inspection of field gluing operations of elements of the seismic -force resisting system Y N 2. Inspection of nailing, bolting, anchoring and other fastening of components within the seismic -force - resisting system 1705.11.3 Cold -formed Steel Light -Frame Construction Special Inspections for Seismic Resistance 1. Inspection during welding operations of elements of the seismic -force -resisting system Y N 2. Inspections for screw attachment, bolting, anchoring and other fastening of components within the Y N seismic -force -resisting system 1705.11.4 Designated Seismic Systems Verification Inspect and verify that that the component label, anchorage or mounting conforms to the certificate of compliance in accordance with Section 1705.12.3 STRUCTURAL AND MISCELLANEOUS STEEL STEEL MEMBERS, HARDWARE, FASTENERS SHALL BE HOT DIPPED GALVANIZED OR EPDXY PAINTED PER ARCHITECT REQUIREMENTS. ALL CUT, REPAIRED AND EXPOSED SURFACE SHALL BE PAINTED WITH (2) COAT OF 95% ZINC RICH PAINT PER ASTM A780. COLOR TO MATCH EXISTING. STEEL SHALL CONFORM TO THE FOLLOWING STANDARDS: TUBE COLUMNS: ASTM A500, GRADE B (Fy = 46 KSI) WIDE FLANGE COLUMNS / BEAMS: ASTM 572 GR50 STEEL PIPE: SCHEDULE 40, CONFORMING TO ASTM A53, TYPE E OR S, GRADE B (Fy = 35 KSI.) ALL OTHER STEEL: ASTM A36 (Fy = 36 KSI) OR ASTM A992 BOLTS: ASTM A307 (WOOD/STEEL CONN) BOLTS: ASTM A325/A490 WITH LOCK WASHERS (STEEL/STEEL AND STEEL/CONC CONN) ANCHOR BOLTS: ASTM A307 (WOOD FRAMING) ANCHOR BOLTS: ASTM A325 (STEEL FRAMING) ALL SLIP CRITICAL CONNECTIONS SHALL BE ASTM A325 BOLTS AND SHALL BE ENGINEER -APPROVED, SELF -LOAD INDICATING TYPES, AND SHALL BE INSTALLED IN STRICT ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. STRUCTURAL STEEL WELDING 1. CONFORM TO THE AWS CODES D1.1 AND D1.3, AND USE ONLY CERTIFIED WELDERS. WELDS NOT SPECIFIED ARE TO BE 1/4" CONTINUOUS FILLET MINIMUM. INCREASE WELD SIZE TO AWS MINIMUM SIZES, BASED ON PLATE THICKNESS. USE DRY E70 ELECTRODES. 2. ALL WELDING SHALL CONFORM TO THE AWS CODES, AND SHALL BE BY CERTIFIED WELDERS. WELDS NOT SPECIFIED SHALL BE 1/4" CONTINUOUS FILLET MINIMUM. USE DRY E70 ELECTRODES. SHEET NUMBER S-0 S-1 Grand total: EXTENT Periodic Periodic Periodic Continuous Periodic Continuous Periodic Periodic Periodic Periodic Level B - Periodic Level C - Continuous Level B - Periodic Level C - Continuous Continuous Periodic Level B - Periodic Level C - Continuous Continuous Periodic Continuous Continuous Level B - Periodic Level C - Continuous Continuous Level B - Periodic Level C - Continuous Level B - Periodic Level C - Continuous Level B - Periodic Level C - Continuous Periodic Periodic Periodic Periodic Periodic Periodic Periodic Continuous Periodic Continuous Continuous Continuous Continuous See Section 1705.2 See Section 1705.3 In accordance with construction documents In accordance with construction documents Continuous Continuous See Section 1705.3 In accordance with construction documents Continuous In accordance with construction documents Continuous Periodic Periodic Periodic Periodic Periodic In accordance with AISC 341 Continuous Periodic Periodic Periodic Periodic DRAWING LIST SHEET NAME GENERAL NOTES AND SPECIFICATIONS FRAMING PLAN AND DETAILS 2 ISSUE DATE 08-06-21 08-06-21 15306 61 ST PLACE NE KENMORE, WA 98028 (425) 318-0031 info@b2engineers.com OF WASy S / o 2 43789 CTURAL ENGNG\� SS/ANAL E CHAMBERLAIN - FINLAYSON DECK 8825 SHELL PLACE, EDMONDS, WA 98026 DRAWING INFO ISSUE DATE 08-06-21 ISSUED FOR PERMIT PROJECT NO.19060 ENGINEER gg REVISION SCHEDULE NO. I DATE I DESCRIPTION BLD2021-1206 RECEIVED Aug 31 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT GENERAL NOTES AND SPECIFICATIONS S-0 Copyright b2 Structural Engineers 2008 P1 2 S-1 NEW 18"X18"X12" FOOTINGS W/ 3 - #4 E.W. P2 o P4 I 6X6 I FOUNDATION PLAN 1 /4" = 1 '-0" 2'- 6" CANT DECK LEVEL 1 /4" = 1'-0" I V L V V V /\ V I I I V V I V (DP-1) I 6X6 I >,STEEL PIPE PILE NOTES: 1. P1 TO P8 DENOTES 2" VERTICAL PIN PILES >12. THE PILES SHALL BE 2" STEEL PIPE SCHEDULE 80 (ASTM A500 GRADE B) Y FOR 3 TONS VERTICAL LOAD CAPACITY Y3. PILES SHALL BE DRIVEN USING MIN. 140 LBS VIBRATORY HAMMER DOWN TO REFUSAL WITH CRITERIA OF MIN. RATE OF 60 SECONDS/ INCH FOR (3) >' CYCLES EXISTING BUILDING WALL 0 Special Inspections required for this project: 1) Soils 2) Construction and Installation of the Pipe Piles PROVIDE A35 (BOTH SIDES) - BETWEEN EXISTING RIM BOARD AND EXISTING JOISTS EXISTING WALL SHEATHING TO REMAIN REMOVDE EXISTING SIDING AS NEEDED TO INSERT NEW PT LEDGER; PROVIDE FLASHING / PROVIDE LUS HANGER (TYP.) NEW PT JOISTS PER PLAN Lo P6 o P8 '� 0 — — — P5 P7 SIMPSON DTT1Z 6X6 6X6 AT 48" (TYP.) EXISTING FLOOR JOISTS TO REMAIN PT LEDGER WITH 4" LONG TIMBERLOK SCREWS AT 8"; PROVIDE WATER BARRIER BETWEEN LEDGER AND SHEATHING EXISTING EXTERIOR WALL TO REMAIN FXISTING FI 00R JOISTS, TO RFMAIN NOTES: 1. ALL STEEL BOLTS AND LAG SCREWS SHALL BE HOT -DIPPED GALVANIZED A-307 OR A-36 2. ALL EXPOSED LUMBERS SHALL BE PRESSURED TREATED HF#2 H -Z U 0 i CV 2'- 6" CANT. Detail 1 3/4" = 1'-011 Detail 3 3/4" = 1'-0" Detail 2 3/4" = 1'-0" EXISTING WALL SHEATHING TO REMAIN REMOVDE EXISTING SIDING AS NEEDED TO INSERT NEW PT LEDGER; PROVIDE FLASHING PROVIDE LUS PROVIDE PT BLOCKING 3 HANGER (TYP.) S-1 SIMPSON DTT1Z — NEW PT JOISTS AT 4811 (TYP.) PER PLAN PT LEDGER WITH 4" TIMBERLOK AT 8"; PROVIDE WATER BARRIER BETWEEN LEDGER AND SHEATHING EXISTING EXTERIOR WALL TO REMAIN NEW PT BEAM PER PLAN CCQ POST CAP (TYP.) (0 N PROVIDE KBS1Z KNEE BRACE STABILIZER (BOTH SIDES, TOP AND BOTTOM) 4X4 PT GUARDRAIL POSTS AT 6' MAX W/ EXTERIOR GRADE RAILING TO BE ABLE TO WITHSTAND 200 LBS CONCENTRATED FORCE AT ANY LOCATION A35 ANGLE AT EACH SIDE OF JOISTS AND POSTS - (6) 6" LONG TIMBERLOK SCREWS AT 2" O.C. (2 ROWS) DOUBLE PT RIM BOARD (TYP. AT PERIMETER) PROVIDE H2.5 TIE AT EACH JOIST 6X6 PT KNEE BRACE PER PLAN (4) 5" LONG TIMBERLOK SCREWS AT EACH POST 4X4 PT GUARDRAILS (COPED AT THE POSTS) ih NEW PT POST _ PER PLAN PROVIDE ABU POST BASE & 5/8"X4" STRONG BOLT 2 — o a, 3 - #4 E.W. III IIIIIIII II —_2" PIN PILE WITH CAP PLATE (DRIVEN DOWN =1' 6" SQUARE TO BEARING LAYER)— — GRANULAAR ROCK RETAINING WALL BLOCK IL. UNITS LO CV V COMPACTED SUB -BASE — 15306 61 ST PLACE NE KENMORE, WA 98028 (425) 318-0031 info@b2engineers.com P OF WASy� S',p -CMG 'YCT / p Q- �.A 43789 cTURAL eNONG\� �SS/ONAL E CHAMBERLAIN - FINLAYSON DECK 8825 SHELL PLACE, EDMONDS, WA 98026 DRAWING INFO ISSUE DATE 08-06-21 ISSUED FOR PERMIT PROJECT NO.19060 ENGINEER BB REVISION SCHEDULE NO. i DATE I DESCRIPTION RECEIVED Aug 31 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT FRAMING PLAN AND DETAILS S-1 Copyright b2 Structural Engineers 2008