STRUCTURAL ANALYSIS
SHEAR / SEISMIC
And Beams
PORCH CANOPY
February 17, 2022
PERCO Job #22-018
Owner/Developer:
Randy Rue
20208 87th Ave W
Edmonds, WA 98026
Ph: (206) 245-0967
randyrue!a gmail.com
Prepared by
Perco Engineering, PC
9920 — 271 st St NW
Stanwood, WA 98292
Ph: (360) 629-6710
}�ercoen�ineerina�agniai3.com
24'
rafters are 2x10
on 2' centers .__ ,
beam is support
by 3 "Skyiift" pc
secured to the t
plate of the hou
engineering der,
included
patio cover
beams are
sandwiched
2x12s with a
1/2" plywood
spacer. Engineering
calculations
are uploaded
separately
patio cover posts
are supported by
existing deck beam
4x10 with 4x6 posts
on 6'centers,
photos included
purlins i
2x4 on
centers
Project: Patio Cover Added to existing Deck
Version: 4.1
Page 1: Top View
Randall Rue & Kara Kahier
20208 87th Ave W
Edmonds WA 98026
randyrue@gmail.com
206 245 0967
NORTH
2x10 blocking
between rafters at
center and ends
i
i
i
iTotal size is —18' x 24' = 400 sq ft
t ,Arl lumber is pressure treated hem/fir
'Posts are secured to cover beams
and deck beams with Simpson
iStrong-Tie "AC' post caps.
{Rafters are secured to beams with
lSimpson Strong -Tie "111" hurricane
!ties. End rafters are secured with
i"H2.5A" hurricane ties and 3x7 "TP"
(tie plates.
+Roofing is 31ga corrugated
galvanized steel attached to purlins
with 1.5" washered/self-sealing
screws on 8" centers
Project: Patio Cove
Version: 4.1
Page 2: Front View
Randall Rue & Kara
20208 87th Ave W
Edmonds WA 98021
randyrue@gmail,co
206 245 0967
patio cover posts
are supported by
existing deck beam
4x10 with 4x6 posts
on 6' centers,
photos included
00 w
,._ ... grade
Project: Patic
Version: 4.1
Page 3: Side'
Randall Rue E
20208 87th A
Edmonds WA
randyrue@gn
206 245 OW
pa, Ket'de L -�o hs e
� -
cz
�� _
f lam,{ 44)1 c2,
(iZ
5ba
ZA i�il
AV Iq
,or CDP
I -
67
1 7;5
-----------
0. 14U
Z
Z
.2—
e
L
lh
2-al o c4vat
❑ WoodWorks® Shearwalls SOFTWARE FOR WOOD DESIGN
Canopy.wsw WoodWorks@ Shearwalls 2019 (Update 3) Feb. 12, 2022 18:06:47
All shearwalls, Design group 1:
Exterior surface:
15/32" Structural sheathing w/ 8d nails @ 6/12"
Shear capacity: 364.0 plf
Frame: D.Fir-L @ 16", blocked
Critical Segment: 1-1,2:
Design shear force: 158.3 plf
Combined capacity: 364.0 plf
Elevation View
Shearline 1, at X = 0 ft, Level 1.
Flexible Diaphragm Wind Design.
t✓c) 178
148-4
. 40.00
25'
158.3
IF, 927 1927
A.R. - Aspect ratio; Adj - Adjustment
20'
T ��
10, 7 y
1 2 �� -; Co w'/f� r�' � ✓ t � Ll
A .40.00 �--
des� "� P �( ywci
0.25'
0'
Factored Forces
Vertical
Horizontal
Holddown force (Ibs)
--► Vs - Shearline force (Ibs)
Compression force (Ibs)
-- Vs / diaphragm length (plf)
S - Shear overturning (Ibs)
-- V / full height sheathing (pig
U -Wind uplift (Ibs)
0—► Drag strut force (Ibs)
D - Dead (Ibs)
= Strap/blocking force (Ibs)
Factors: S,U = 0 6, D = 0.6 (tens); 1.0 (comp)
Combined: S- D+ U (tens);
S+ D- U (comp)
Unfactored Loads
JJJ Dead
{ f Wind uplift
South 10, 20'
North
WoodWorks® Shearwalls SOFTWARE FOR WOOD DESIGN
Canopy.wsw Woodworks@ Shearwalls 2019 (Update 3) Feb. 12, 2022 10:09:23
20'
Elevation View
Shearline B, at Y = 18 ft, Level 1.
Flexible Diaphragm Wind Design. 6C�Jv1 `)
A.R. - Aspect ratio; Adj - Adjustment
All shearwalls, Design group 2:
Exterior surface:
15/32" Structural sheathing w/ 8d nails @ 6/12"
Shear capacity: 364.0 plf
Frame: D.Fir-L @ 16", blocked
Critical Segment: B-1,1:
Design shear force: 49.2 plf
Combined capacity: 364.0 plf
0'
10,
Factored Forces
Vertical Horizontal
C Holddown force (Ibs) —► Vs - Shearline force (Ibs)
Compression force (Ibs) Vs / diaphragm length (plf)
S - Shear overturning (Ibs) V / full height sheathing (plf)
U -Wind uplift (Ibs) 0—► Drag strut force (Ibs)
D - Dead (Ibs) = Strap/blocking force (Ibs)
Factors: S,U = 0.6, D = 0.6 (tens); 1.0 (comp)
Combined: S - D + U (tens); S + D - U'(comp)
Unfactored Loads
JJJ Dead } } Wind uplift
20'
10,
d
West East
F� WoodWorks® Shearwalls SOFTWARE FOR WOOD DESIGN
Canopy.wsw
Level 1 of 1
WoodWorks® Shearwalls 2019 (Update 3)
-5' -2.5' 0' 2.5' 5' 7:5' 10, 12.5' 15' 17.5' 20' 22.5'
Factored shearline force (Ibs) L11J Unfactored applied shear load (plf)
Factored holddown force (Ibs) 0- (9) Unfactored dead load (plf,lbs)
• C Compression force exists Q Unfactored uplift wind load (plf,lbs)
vertical element required Applied point load or discontinuous shearline force (Ibs)
Loads: Directional Case 1 Wind (W); Forces: 0.6W + 0.6D; Flexible distribution
Feb. 12,2022 10:09:23
22.5'
20'
C, 17.5'
I
15,
l �
12.5'
r
v
10,
l
7.5'
c
5'
2.5'
25' 27.5' 30'
WoodWorks® Shearwalls SOFTWARE FOR WOOD DESIGN
WoodWorks® Shearwalls 2019 (Update 3)
Canopy.wsw
Project Information
COMPANY AND PROJECT INFORMATION
Company
Project
Perco Engineering, PC
Rue Deck Cover
9920-271st St NW
Stanwood, WA 98292
(360) 629-6710
DESIGN SETTINGS
Feb. 12, 2022 16:32:49
Design Code Wind Standard Seismic Standard
IBC 2018/AWC SDPWS 2015 ASCE 7-16 Directional (All heights) ASCE 7-16
Load Combinations
Building Code Capacity Modification
For Design (ASD) For Deflection (Strength)
Wind Seismic
0.70 Seismic + 0.60 Dead 1.00 Seismic + 0.90 Dead
�_ =.00
0.60 Wind + 0.60 Dead 1.00 Wind + 0.90 Dead
Service Conditions and Load Duration
Max Shearwall Offset [ft]
Duration Temperature Moisture Content
Plan Elevation
Factor Range Fabrication Service
(within story) (between stories)
Maximum Height -to -width Ratio
Wood panels Fiberboard Lumber Gypsum
Wind Seismic Wind Seismic Blocked Unblocked
i.J
Ignore non -wood -panel shear resistance contribution...
Forces based on...
Wind Seismic
Hold-downs Applied loads
Neer Never
Drag struts Applied loads
Shearwall relative rigidity: wall capacity
Perforated shearwall Co factor: SDPWS 'table 4.3.3.5
Non -identical materials and construction on the shearline: Allowed, except for material type
Deflection Equation: No deflection analysis
Drift limit for wind design: 1 / 500 story height
Force -transfer strap: Discontinuous, at top and bottom of each opening
SITE INFORMATION
Wind
Seismic
ASCE 7-16 Directional (All heights)
ASCE 7-16 12.8
Equivalent Lateral Force Procedure
Design Wind Speed 85 mph
Risk Category
Category II - All others
Serviceability Wind Speed 110 mph
Structure Type
Regular
Exposure Exposure B
Building System
Bearing Wall
Enclosure Partially enclosed
Design Category
D
Min Wind Loads: Walls 16 psf
Site Class
D
Roofs 8 psf
Spectral
S1: ' . 1g
Response Acceleration
Ss: 0.850g
Topographic Information [ft]
Shape Height Length
Fundamental Period
E-W
N-S
- - -
T Used
0.128s
0.128s
Site Location: -
Approximate Ta
Maximum T
0.128s
0.179s
0.128s
0. 179s
Elev: Oft
Rigid building - Static analysis
Response Factor
6.50
6.50
Case 2 E-W loads N-S loads
Fa: - - -
Fv: 1. 86
Eccentricity (%) 15
Loaded at 750
Edmonds
MCE Parameters - Conterminous 48 States
Zip Code - 98026 Central Latitude = 47.839809
Central Longitude =-122.329829
MCE MAP VALUES
Short Period Map Value - Ss = 127.3% g
1.0 sec Period Map Value - S1 = 44.1 % g
RESIDENTIAL DESIGN INFORMATION
Short Period Map Value - Ss = 127.3% g
Soil Factor for Site Class D - Fa = 1.00
Residential Site Value = 2/3 x Fa x Ss = 84.8% g
Residential Seismic Design Category = D2
WoodWorks® Shearwalls Canopy.wsw Feb. 12, 2022 16:32:49
Structural Data
STORY INFORMATION
Story Floor/Ceiling Wall
Elev ftDepth in Height ft
Ceiling
10.83 10.0
Level
0.00 0.0 10.00
Foundation
0.00
SHEATHING MATERIALS by WALL GROUP
Sheathing
Fasteners
Apply
Grp Surf
Material Ratng Thick GU Ply Or Gvtv
Size Type Df Eg Fd Elk
Notes
in in Ibs/in
in in
1 Ext
Struct Sh OSB 32/16 Vert 83500
-?- Nail N -?— ?
2 Ext
Struct Sh OSB 32/16 15/32 Vert 83500
8d Nail N 6 12 Y
Legend:
Grp - Wall Design Group number, used to reference wall in other tables (created by program)
Surf - Exterior or interior surface when applied to exterior wall
Ratng - Span rating, see SDPWS Table C4.2.2.2C
Thick - Nominal panel thickness
GU - Gypsum underlay thickness
Ply - Number of plies (or layers) in construction of plywood sheets
Or - Orientation of longer dimension of sheathing panels
Gvtv - Shear stiffness in Ib/n, of depth from SDPWS Tables C4.2.2A-8
Type - Fastener type from SDPWS Tables 4.3A-D: Nail - common wire nail for structural panels and lumber, cooler or gypsum wallboard nail for GWB,
plasterboard nail for gypsum lath, galvanised nail for gypsum sheathing; Box - box nail; Casing - casing nail; Roof - roofing nail; Screw - drywall screw
Size - Common, box, and casing nails: refer to SDPWS Table Al (casing sizes = box sizes).
Gauges: 11 ga = 0.120"x 1-314" (gypsum sheathing, 25132" fiberboard), 1-1/2" (lath & plaster, 1/2" fiberboard); 13 ga plasterboard = 0.92" x 1-118".
Cooler or gypsum wallboard nail: 5d = .086" x 1-5/8"; 6d = .092" x 1-7/8'; 8d =. 113" x 2-3/8"; 6/8d = 6d base ply, 8d face ply for 2-ply GWB.
Drywall screws: No. 6, 1-114"long.
518" gypsum sheathing can also use 6d cooler or GW8 nail
Df - Deformed nails ( threaded or spiral), with increased withdrawal capacity
Eg - Panel edge fastener spacing
Fd - Field spacing interior to panels
Bk - Sheathing is nailed to blocking at all panel edges; Y(es) or N(o)
Apply Notes - Notes below table legend which apply to sheathing side
? - Design for unknown parameter not performed for reasons given in notes below.
FRAMING MATERIALS and STANDARD WALL by WALL GROUP
Wall
Species Grade
b d Spcg
SG E Standard Wall
Grp
in in in
pSiA6
1
D.Fir-L Stud
1.50 5.50 ?
0.50 1.40
2
D.Fir-L Stud
1.50 5.50 16
0.50 1.40
Legena:
Wall Grp - Wall Design Group
b - Stud breadth (thickness)
d - Stud depth (width)
Spcg - Maximum on -centre spacing of studs for design, actual spacing may be less.
SG - Specific gravity
E - Modulus of elasticity
Standard Wall - Standard wall designed as group.
Notes:
Check manufacture requirements for stud size, grade and specific gravity (G) for all shearwall hold-downs.
NA
WoodWorks® Shearwalls Canopy.wsw Feb. 12, 2022 16:32:49
SHEARLINE, WALL and OPENING DIMENSIONS
North -south
Type
Wall
Location
Extent [ft]
Length
FHS
Aspect
Height
Shearlines
Group
X ft
Start
End
IN
ft
Ratio
IN
Line 1
Level 1
Line 1
0.00
6.00
18.00
12.00
0.00
-
10.00
Wall 1-1
NSW
0.00
6.00
18.00
12.00
0.00
-
-
Segment 1
-
-
6.00
6.25
0.25
-
40.00
-
Opening 1
-
-
6.25
17.75
11.50
-
-
9.00
Segment 2
-
-
17.75
18.00
0.25
-
40.00
-
Line 2
Level 1
Line 2
24.00
6.00
18.00
12.00
0.00
-
10.00
Wall 2-1
NSW
24.00
6.00
18.00
12.00
0.00
-
-
Segment 1
-
-
6.00
6.25
0.25
-
40.00
-
Opening 1
-
-
6.25
17.75
11.50
-
-
9.00
Segment 2
-
-
17.75
18.00
0.25
-
40.00
-
East -west
Type
Wall
Location
Extent [ft]
Length
FHS
Aspect
Height
Shearlines
Group
Y ft
Start
End
IN
ft
Ratio
ft
Line A
Level 1
Line A
1
6.00
0.00
24.00
24.00
0.00
-
10.00
Wall A-1
Seg
1
6.00
0.00
24.00
24.00
0.00
-
-
Segment 1
-
-
0.00
0.50
0.50
-
20.00
-
Opening 1
-
-
0.50
23.75
23.25
-
-
9.00
Segment 2
-
-
23.75
24.00
0.25
-
40.00
-
Line B
Level 1
Line B
2
18.00
0.00
24.00
24.00
16.00
-
10.00
Wall B-1
Seg
2
18.00
0.00
24.00
24.00
16.00
-
-
Segment 1
-
-
0.00
16.00
16.00
-
0.63
-
Opening 1
-
-
16.00
22.00
6.00
-
-
7.00
Segment 2
-
-
22.00
24.00
2.00
-
5.00
-
Legend:
Type - Seg = segmented, Pit = perforated, FT = force -transfer, NSW = non-shearwall
Location - Dimension perpendicular to wall
FHS - Length of full -height sheathing used to resist shear force. For perforated walls, it is based on the factored segments Li defined in SDPWS 4.3.4.3
Aspect Ratio - Ratio of wall height to segment length (hlbs), for force -transfer walls, the aspect ratio of the central pier
Wall Group - Wall design group defined in Sheathing and Framing Materials tables, where it shows associated Standard Wall
If two wall group numbers listed, they are for rigid diaphragm and flexible diaphragm design.
WoodWorks® Shearwalls
Canopy.wsw Feb. 12, 2022 16:32:49
Loads
EAD LOADS (for hold-down calculations)
Shear Level Profile Tributary Location [ft] Mag [Ibs,psf,psi]
Line Width [ft] Start End Start End
A i Line 0.00 24.00 y .,J
B 1 Line 0.00 24.00 31.0
4
WoodWorks® Shearwalls Canopy.wsw Feb. 12, 2022 16:32:49
Design Summary
SHEARWALL DESIGN
Wind Shear Loads, Flexible Diaphragm
All shearwalls have sufficient design capacity.
Seismic Loads, Flexible Diaphragm /
All shearwalls have sufficient design capacity. J
HOLDDOWN DESIGN
Wind Loads, Flexible Diaphragm
All hold-downs have sufficient design capacity.
Seismic Loads, Flexible Diaphragm
All hold-downs have sufficient design capacity.
Refer to the Deflection table for possible issues regarding fastener slippage (SDPWS Table C4.2.2D) for walls that otherwise pass.
WoodWorks® Shearwalls Canopy.wsw Feb. 12, 2022 16:32:49
Flexible Diaphragm Wind Design
ASCE 7 Directional (All Heights) Loads
SHEAR RESULTS
N-S
W
For
ASD Shear Force [plf]
Asp -Cub
Allowable Shear [plf]
Resp.
Shearlines
Gp
Dir
v vmax/vft V Ibs
Int Ext Int
Ext Co C Cmb
V Ibs
Ratio
E-W
W
For
ASD Shear Force [plf]
Asp -Cub
Allowable Shear [plf]
Resp.
Shearlines
Gp
Dir
v vmax/vft V Ibs
Int Ext Int
Ext Co C Cmb
V Ibs
Ratio
Line A
Level 1
Wall A-1
1
Both
- - 375
- 1.0 -
0 - -
-
-
Seg. 1
-
Both
0.0 0.0 0
- 1.0 -
0 - -
-
-
Seg. 2
-
Both
0.0 0.0 375
- 1.0 -
0 - -
-
-
Line B
LnB, Levl
-
Both
- - 788
- - -
- - -
5824
-
Wall B-1
2
Both
- - 788
- 1.0 -
364 - -
5824
-
Seg. 1
-
Both
49.2 0.0 788
- 1.0 -
364 - 364
5824
0.14S
Seg. 2
-
Both
0.0 0.0 0
- 1.0 -
364 - 364
-
-
yam....
W Gp - Wall design group defined in Sheathing and Framing Materials tables, where it shows associated Standard Wall. "A" means that this wall is critical for
all walls in the Standard Wall group.
For Dir - Direction of wind force along shearline.
v - Design shear force on segment = ASD-factored shear force per unit length of full -height sheathing (FHS)
vmax/vft - Perforated walls: Collector and in -plane anchorage force as per SDPWS eqn. 4.3-9 = V/FHS/Co. FHS is factored for narrow segments as per
4.3.4.3
Force -transfer walls: Shear force in piers above and below either openings or piers beside opening(s). Aspect ratio factor does not apply to these piers.
V - ASD factored shear force. For shearline: total shearline force. For wall: total of all segments on wall. For segment: force on segment
Asp/Cub —For wall: Unblocked structural wood panel factor Cub from SDPWS 4.3.3.2. For segment or force -transfer pier: Aspect ratio adjustment from
SDPWS 4.3.3.4.1
Int - Unit shear capacity of interior sheathing; Ext - Unit shear capacity of exterior sheathing. For wall: Unfactored. For segment: Include Cub factor and
aspect ratio adjustments.
Co - Adjustment factor for perforated walls from SDPWS Table 4.3.3.5.
C - Sheathing combination rule, A = Add capacities, S = Strongest side or twice weakest, G = Stiffness -based using SDPWS 4.3-3.
Cmb - Combined interior and exterior unit shear capacity including perforated wall factor Co.
V — Total factored shear capacity of shearline, wall or segment.
Crit Resp —Response ratio = v/Cmb = design shear force/unit shear capacity. "S" indicates that the wind design criterion was critical in selecting wall.
Notes:
Refer to Elevation View diagrams for individual level for uplift anchorage force t for perforated walls given by SDPWS 4.3.6.4.2,4.
" WARNING - Shearline has zero capacity because it does not contain allowable materials for the seismic design category.
WoodWorks® Shearwalls Canopy.wsw Feb. 12, 2022 16:32:49
HOLD-DOWN DESIGN (flexible wind design)
Level 1
Line-
Wall
Posit'n
Location [ft]
X Y
Load
Case
Tensile ASD
Holddown Force [Ibs]
Shear Dead Uplift Cmb'd
Hold-down
Cap
Ibs
Crit
Res .
Line A
A-1
L End
0.12 6.00
6
A-1
L Op 1
0.38 6.00
285
A-1
R Op 1
23.88 6.00
285
Line B
B-1
L End
0.12 18.00
Min
500 149 351
Plate
4000
0.09
B-1
L Op 1
15.88 18.00
Min
500 205 296
Plate
4000
0.07
B-1
R Op 1
22.13 18.00
74
B-1
R End
23.88 18.00
19
Legena:
Line -Wall:
At wall or opening — Shearline and wall number At vertical element - Shearline
Posit'n - Position of stud that hold-down is attached to:
V Elem - Vertical element. column or strengthened studs required where not at wall end or opening
L or R End - At left or right wall end
L or R Op n - At left or right side of opening n
t @ Op n - Uplift force t at opening n from offset opening in perforated wall above, from SDPWS 4.3.6.2.1
Location - Co-ordinates in Plan View
Load Case - Results are for critical load case:
ASCE 7 All Heights: Case 1 or 2 from Fig. 27.3-8
ASCE 7 Low-rise: Windward corner(s) and Case A or B from Fig. 28.3-1
ASCE 7 Minimum loads (27.1.5 / 28.3.4)
Hold-down Forces:
Shear— Wind shear overturning component, based on shearline force, factored forASD by 0.60. For perforated walls, T from SDPWS 4.3-8 is used.
Dead — Dead load resisting component, factored for ASD by 0.60
Uplift - Uplift wind load component, factored for ASD by 0.60. For perforated walls, T from SDPWS 4.3-8 is used.
Cmb'd - Sum of ASD-factored overturning, dead and uplift forces. May also include the uplift force t from perforated walls from SDPWS 4.3.6.2.1 when
openings are staggered.
Hold-down — Device used from hold-down database
Cap — Allowable ASD tension load
Crit. Resp. - Critical Response = Combined ASD force /Allowable ASD tension load
Notes:
Refer to Shear Results table for factor Co, and shearline dimensions table for the sum of Li, used to calculate tension force T for perforated walls from
SDPWS Eqn. 4.3-8.
WoodWorks® Shearwalls Canopy.wsw Feb. 12, 2022 16:32:49 1
Flexible Diaphragm Seismic Design
SEISMIC INFORMATION
Level
Mass Area
Story Shear [Ibs]
Diaphragm Force [Ibs]
Ibs s .ft
E-W N-S
E-W: Fpx Design N-S: Fpx Design
1
8161 288.0
825 825
751 751 751 751
All
8161 -
825 825
- - - -
Legend:
Mass — Sum of all generated and input building masses on level = wx in ASCE 7 equation 12.8-12.
Story Shear— Total unfactored (strength -level) shear force induced at level x, = Fx in ASCE 7 equation 12.8-11.
Diaphragm Force — Minimum ASD-factored force for diaphragm design, used by Shearwalls only for drag strut forces, as per Exception to 12.10.2.1. Fpx is
from Eqns. 12.10-1, -2, and -3. Design = The greater of the story shear and Fpx + transfer forces from discontinuous shearlines, factored by overstrength
(omega) as per 12.10.1.1. Omega = 2.5 as per 12.2-1.
Redundancy Factor p (rho):
E-W 1.00, N-S 1.00
Automatically calculated according to ASCE 7 12.3.4.2.
Vertical Earthquake Load Ev
Ev = 0 for Seismic Design Category A as per ASCE 7 12.4.2.2.
WoodWorks® Shearwalls Canopy.wsw Feb. 12, 2022 16:32:49
SHEAR RESULTS (flexible seismic design)
N-S
W
For
ASD Shear Force [plf]
Asp -Cub
Allowable Shear [plf]
Resp.
Shearlines
Gp
Dir
v vmax/vft V Ibs
Int Ext Int
Ext Co C Cmb
V Ibs
Ratio
E-W
W
For
ASD Shear Force [plf]
Asp -Cub
Allowable Shear [plf]
Resp.
Shearlines
Gp
Dir
v vmax/vft V Ibs
Int Ext Int
Ext Co C Cmb
V Ibs
Ratio
Line A
Level 1
Wall A-1
11
Both
- - 337
- 1.0 -
0 - -
-
-
Seg. 1
-
Both
0.0 0.0 0
- 1.0 -
0 - -
-
-
Seg. 2
-
Both
0.0 0.0 337
- 1.0 -
0 - -
-
-
Line B
LnB, Levl
-
Both
- - 578
- - -
- - -
4160
-
Wall B-1
2^
Both
- - 578
- 1.0 -
260 - -
4160
-
Seg. 1
-
Both
36.1 0.0 578
- 1.0 -
260 - 260
4160
0.14
Seg. 2
-
Both
0.0 0.0 0
- 1.0 -
260 - 260
-
-
Legend:
W Gp - Wall design group defined in Sheathing and Framing Materials tables, where it shows associated Standard Wall. "A" means that this wall is critical for
all walls in the Standard Wall group.
For Dir — Direction of seismic force along shearline.
v - Design shear force on segment = ASD-factored shear force per unit length of full -height sheathing (FHS)
vmaxlvft - Perforated walls: Collector and in -plane anchorage force as per SDPWS eqn. 4.3-9 = V/FHS/Co. FHS is factored for narrow segments as per
4.3.4.3
Force -transfer walls: Shear force in piers above and below either openings or piers beside opening(s). Aspect ratio factor does not apply to these piers.
V - ASD factored shear force. For shearline: total shearline force. For wall: total of all segments on wall. For segment: force on segment
Asp/Cub — For wall: Unblocked structural wood panel factor Cub from SDPWS 4.3.3.2. For segment or force -transfer pier: Aspect ratio adjustment from
SDPWS 4.3.3.4.1
Int - Unit shear capacity of interior sheathing; Ext - Unit shear capacity of exterior sheathing. For wall: Unfactored. For segment: Include Cub factor and
aspect ratio adjustments.
Co - Adjustment factor for perforated walls from SDPWS Table 4.3.3.5.
C - Sheathing combination rule, A = Add capacities, S = Strongest side or twice weakest, G = Stiffness -based using SDPWS 4.3-3.
Cmb - Combined interior and exterior unit shear capacity including perforated wall factor Co.
V — Total factored shear capacity of shearline, wall or segment.
Crit Resp — Response ratio = v/Cmb = design shear force/unit shear capacity. 'W' indicates that the wind design criterion was critical in selecting wall.
Notes:
Refer to Elevation View diagrams for individual level for uplift anchorage force t for perforated walls given by SDPWS 4.3.6.4.2,4.
** WARNING - Shearline has zero capacity because it does not contain allowable materials for the seismic design category.
Woodworks® Shearwans Canopy.wsw Feb.12, 2022 16:32:49
HOLD-DOWN DESIGN (flexible seismic design)
Level 1
Line-
Wall
Posit'n
Location [ft]
X Y
Tensile ASD
Holddown Force [Ibs]
Shear Dead Ev Cmb'd
Hold-down
Cap
Ibs
Crit
Res .
Line A
A-1
L End
0.12 6.00
6
A-1
L Op 1
0.38 6.00
285
A-1
R Op 1
23.88 6.00
285
Line B
B-1
L End
0.12 18.00
367 149 218
Plate
4000
0.05
B-1
L Op 1
15.88 18.00
367 205 162
Plate
4000
0.04
B-1
R Op 1
22.13 18.00
74
B-1
R End
23.88 18.00
19
Legend:
Line -Walla
At wall or opening — Shearline and wall number
At vertical element - Shearline
Posit'n - Position of stud that hold-down is attached to:
V Elem - Vertical element: column or strengthened studs required where not at wall end or opening
L or R End - At left or right wall end
L or R Op n - At left or right side of opening n
t @ Op n - Uplift force t at opening n from offset opening in perforated wall above, from SDPWS 4.3.6.2.1
Location - Co-ordinates in Plan View
Hold-down Forces:
Shear— Seismic shear overturning component, factored forASD by 0.7. For perforated walls, T from SDPWS 4.3-8 is used
Dead — Dead load resisting component, factored for ASD by 0.60
Ev — Vertical seismic load effect from ASCE 7 12.4.2.2 =-0.2Sds x ASD seismic factor x unfactored D = 0.000 x factored D. Refer to Seismic Information
table for more details.
Cmb'd - Sum of ASD-factored overturning, dead and vertical seismic forces. May also include the uplift force t from perforated walls from SDPWS
4.3.6.2.1 when openings are staggered.
Hold-down — Device used from hold-down database
Cap — Allowable ASD tension load
Crit. Resp. — Critical Response = Combined ASD force/Allowable ASD tension load
Notes:
Combined force from ASCE 7 2.4.1 load combination 10 = - (0.6D - 0.7Ev + 0.7Eh); Eh (from 12.4.2.1) _ - shear overturning force
Refer to Shear Results table for factor Co, and shearline dimensions table for the sum of Li, used to calculate tension force T for perforated walls from
SDPWS Eqn. 4.3-8.
10
SkyLift Riser Engineering Express@ ( TER-20-21957
SECTION 2: ALLOWABLE CAPACITIES e
TABLE 1: ALLOWABLE LOAD CAPACTTIFs (Gvnnn SCI IRqTRATF (TNf)T\/Tfll IL\I 1
TYPE
MODEL
DIMENSIONS
SUBSTRATE
UPLIFT
DOWN
F1
F2
W
H
Cd=1.0
Cd=1.6
Cd=1.0
Cd=1.6
STANDARD
SK18-B3.5
3.5 in
18.0 in
WOOD
74316s`
2500lbs
1731bs
G1761bT
581bs
921bs
SK24-63.5
3.5 in
24.0in
WOOD
Ibs
2500lbs
1301bs
2081bs
43lbs
SK18-HD3.5
3.5 in
18.Oin
WOOD
1483lbs
2500lbs
35111bs
480lbs
1541b
„' Ibs
SK18-HD411
4.0in
18.0 in
WOOD
14831bs
2500lbs
3511bs
480lbs
1
7451bs
HEAVYDUTY
SK18-HD5.5
5.5 in
18.0 in
WOOD
1483lbs
2500lbs
351lbs
480lbs
"z.
246lbs
SK18-HD611
6.0in
18.0 in
WOOD
1483lbs
2500lbs
351lbs
4801bs, ;
;- "';:
246lbs
SK24-HD3.5
3.5 in
24.0 in
WOOD
14831bs
2500lbs
263lbs
360 t ;<
115 "484Ibs
SK24-HD411
4.0in
24.0 in
WOOD
14831bs
2500lbs
2631bs
3di"
1151bs' ,.:(bs
SK24-HD5.5
5.5 in
24.0 in
WOOD
14831bs
2500lbs
2631bs
3661bs
1151bs
SK24-HD6R
6.0in
24.0 in
WOOD
14831bs
2500lbs
263ibs
360lbs
1151bs
184(
DESIGNER
SK-DR3.5
3.5 in
12.0in
WOOD
1055lbs
2500lbs
S27,,ft
720lbs I
231lbs
369lbs "
SK-DR4
4.0in
12.Oin
WOOD
1055lbs
2500lbs
"
_ems
7201bs
2311bs
3691bs
SK-DR5.5
5.5 in
12.0in
WOOD
10551bs
2500 lbg,,-
7lbs
7201bs
231lbs
3691bs
SK-DR6 1
6.0in
12.0in
WOOD
1055lbs
2500ftx.'527lbs
7201bs
;, 231lbs
3691bs
TABLE 2: ALLOWABLE LOAD CAPACITIES CONCRETE SU
TYPE MODEL DIMENSIONS H SUBSTRATE UPLIFT DOWN
INDIVIDUAL):
1 1 F2
STANDARD
SK18-13 3.5
3.5 in 18.0 in
CONCRETE
743 Ibs
2500Ib5
2281bs
761bs
SK24-B 3.5
3.5 in 24.0 in
CONCRETE
7431bs
25001bs-
1711bs
571bs
SK18-HD 3.5
3.5 in 18.0 in
CjDNCRE ;
14831bs
1 25001bs
3151bs
1381bs
SK18-HD4R
4.0 in 18.0 in
CONCRETE,
` , j
25001bs
31510s�
;, 1381bs
SK18-HD 5.5
5.5 in 18.0 in
CONCRETE
1483Ibs
250b5..
3151bs
1381bs
HEAVYDUTY
SKIS -HD 6R
6.01n 18.0 in
CONCRETE
148�_I ,;.
25W1bs
,.; 1 Ibs
1381bs
SK24-HD 3.5
3.5 in 24.0 in
CON 'i
I4 ,,Jbs
25001bs
2361bs
1031bs
SK24-HD4R
4.0,1,n. 24,0in
CONCR ""
3lbs
25001bs
2361bs
1031bs
SK24-HD5.5
Irt' `2 in
CONCRETE '
14831bs
25001bs
2361bs
1031bs
SK24-HD6R
60in I Irt
CONCRETE
1483Ibs
25001bs
2361bs
1031bs
SK-DR15 ,"
3.5 in 12 2I,tI'
CONCRETE
1AM5Ibs
25001bs
4721bs
1551bs
DESIGNER
S b 4
4.0in 12tiin
CONCRETE
1 1bs
25001bs
4721bs
1551bs
SK=}.
5.5 in Q.
`;; COETE
10551 bs
25001 bs
4721 bs
1551 bs
SK-0*1,
60ir1;. , 12.1Dtrt
COyCRm
10551bs
25001bs
4721bs
1551bs
CAPACITY TABLE NOTES (ALL Size"Pmf3N51:
1. LOAD Q T� 4, BALL BE DETEkMiNED BY USER. UPLIFT UPLIFT
.
USE# Y ��S Cr:�_ 3ND LOADS APPLICATIONS. IT
21ABLE LOAD CAPAC FISTED HEI�IltE FOR
IVIDUAL FORCES CHECKONLLY. LOAD CO*4ATIONS n
WITH HORIZONTAL AND VERTICAL FORCES SHALL BE
RIFIED BY OTHERS IN ACCOF(OANCE TO ASCE 7-10 AND
7-16 LOAD COMBINATION AND SHALL ADHERE TO 1
LLOWING UNITY EOUATION:
llPLIFT_REQUI
+ [F2 ED/F2]) <
+'LFi_REQUIRED/Fl]
3. WOOD SUB HOSI,ZUCTURE SHALL HAVE
MINIMUM SPE WVY G EQUAL OR BETTER THAN
0.50 AND COMPR �t@r STRENGTH OF 3,000 PSI FOR
CONCRETE SUBSTitIkE:.
NOTE: Higher lateral values may be achieved by combining this product
with the SkyLift LSS (Lateral Stabilizer Strap). See TER 20-29481.
DESIGNER
OPTION SHOWN,
THIS DIAGRAM
APPLTES TO ALL
RISER TYPES
HEREIN
F1
IN ALL CONDITIONS IT IS THE RESPONSIBILITY OF THE PERMIT HOLDER TO ENSURE THE HOST
STRUCTURE IS CAPABLE OF WITHSTANDING THE LOAD RATING HEREIN. NO WARRANTY OF ANY KIND,
EXPRESSED OR IMPLIED, IS OFFERED BY ENGINEERING EXPRESS AS TO THE INTEGRITY OF THE HOST
STRUCTURE TO CARRY DESIGN FORCE LOADS INCURRED BY THIS PRODUCT. Page 6 of 6
Engineering Express"-" 160 SW 12th Ave. Suite 106 Deerfield Beach, FL 33442
(954) 354-0660 EngineeringExpress.com ^ PY0911 " ENiMenng Expressi� AU Rights Reserved
Simpson Strong -Tie` Wood Construction Connectors
Strong —Drive' SDS HEAVY—DUTY CONNECTOR Screw
1 1 0 Structural Fastener
2
The Simpson Strong -Tie° Strong -Drive SDS Heavy -Duty
Connector screw is a 1/4"-diameter structural wood screw
ideal for various connector installations as well as
wood -to -wood applications. It installs with no predrilling
and has been extensively tested in various applications.
For more information about package quantities,
visit strongtie.com.
Features:
• The Type-17 point reduces installation torque and
makes driving easier with no predrilling and minimal
wood splitting.
• Available with a double -barrier coating or in
Type 316 stainless steel. Carbon steel loads apply
to corresponding stainless -steel models.
• %" hex washer head is stamped with the No -Equal
sign and fastener length for easy identification
after installation.
• For the %" hex -head driver bit, order model
no. BITHEXR38-RI.
Material: Heat -treated carbon steel, Type 316 stainless steel
Finish: Double barrier (all lengths); Type 316 stainless steel
(11/2" thru 31/2" lengths)
Codes: See p.11 for Code Reference Key Chart
S6
I
Length
Thread
length
These products are available with additional corrosion protection. For more information, see p.14.
Strong -Drive SDS Heavy -Duty Connector Screw
Identification on all
SDS screw heads
(1/4" x 6" SDS shown)
Type-17 point
reduces installation
torque and makes
driving easier
)ng-Drive
SDS Heavy -Duty
Connector Screw
® For stainless -steel fasteners, see p.21.
Model
No.
Size
(in.)
Thread
Length
(in.)
Fasteners
per
Cartons
DF/SP Allowable Loads (1h.)4
PF/HF Ilowable Loads (lb.)4
Code
Ref.
Shear(100) Withdrawals
3 100
Wood Side Plate Steel Side Plate ( )
Shear(100)
Withdrawals
100
( )
Wood Side Plate a
Steel Side Plate
11/2
13/4"
SCL
16 ga.
14 ga.
and
12 ga.
10 ga.
or
Greater
Wood or
Steel Side
Plate
11h"
1 Y4 ,
SPF LVL �16
ga.
14 ga.
and
12 ga.
10 ga.
or
Greater
Wood or
Steel Side
Plate
SDS25112
1/4x11h
1
1,500
—
—
250
250
250 170
—
—
180
180
180
120
SDS25200
1/4 x 2
11/4
1,300
—
—
250
290
290
215
—
—
180
210
210
150
SDS25212
1/4 x 21/1
11h
1,100
190
—
250
390
420 255
135
—
1 180
280
300
180
SDS25300
1/4x3
r 2
950
280
1 —
250
420
420
345
200
—
180
300
300
240
IBC
SDS25312
1/4 x 31/2
21/4
900
340
340
250
420
420
385
245
245
180
300
300
270
FL,
SDS25412
1/4 x 41/2
23/4
1800
350
340
250
420
420
475
250
1 245
180
300
300
330
LA
SDS25500
1/4x5
23/4
500
350
340
250
420
1 420 475
250
1 245
180
300
300
330
SDS25600
1/4x6
31/4
600
350
1 340
250
420
420
560
250
245
180
300
300
395
SDS25800
1/4x8
31/4
400
1 350
340
250
420
420 560
1 250
245
180
300
300
395
1. Screws may be provided with the 4CUT" or Type-17 point. W d cS o 2� �2 l r0 7Cfi'
2. Strong -Dave SDS Heavy -Duty Connector screws install best using a low -speed 1/2' arill with a %" hex -head driver.
3. Shear values are valid for connections between two members with full thread penetration into the main member. For other wood side plate values,
see Fastening Systems Technical Guide (C-F-2019TECHSUP) at strongtie.com.
i
4. Allowable loads are shown at a wood load duration factor of CD = 1.0. Loads may be increased_ for load duration per the building code up to a CD = 1.6.
_
Ta u abZ er va es must be multiplied by all applicable NDS adjustment factors.
,) 5. Withdrawal loads shown are in pounds (Ib.) and are based on penetration of the screw's entire threaded section into the main member. If thread
N
penetration into the main member is less than the Thread Length as shown in the table for DF/SP, reduce allowable load by 172 lb./in. of thread not
M
in main member. Use 121 Ib./in. for SPF/HF.
LL
a
6. Fasteners per Carton represents the quantity of screws that are available in bulk packaging. Screws are also available in mini -bulk and retail packs.
Refer to Simpson Strong -Tie Fastening Systems catalog (C-F-2019) at strongtie.com.
7. LSL wood -to -wood applications that require 41/2", 5", 6" or 8" SDS Heavy -Duty Connector screws are limited to interior -dry use only.
8. Where predrilling is required for Strong -Drive SDS Heavy -Duty Connector screws, predrill diameter is she°
9. Minimum spacing, edge, and end distance requirements are listed in ICC-ES ESR-2236. For smaller spacing, please contact Simpson Strong -Tie Engineering.
347
item
weight quantity
ext weight
2x12 beam
58.2
8
465.6
pt plywood
50
1.5
75
2x10 rafter
72
13
936
2x4 purlin
12
30
360 total weight per skylift
hardware
20
1
20 12067.44 2011.24
doesn't factor
in slope and
asymmetrical
2x12 roof panel 10.2 12 122.4 loads
2x8 roof panel 7.37 12 88.44
live load 25 400 10000
dead load / sq ft 5.1686
Simpson Strong -Tie" Wood Construction Connectors
Strong—Drive'SIDS
Structural Fastener
The Simpson Strong -Ties Strong -Drive SDS Heavy -Duty
Connector screw is a 1/4"-diameter structural wood screw
ideal for various connector installations as well as
wood -to -wood applications. It installs with no predrilling
and has been extensively tested in various applications.
For more information about package quantities,
visit strongtie.com.
Features:
• The Type-17 point reduces installation torque and
makes driving easier with no predrilling and minimal
wood splitting.
• Available with a double -barrier coating or in
Type 316 stainless steel. Carbon steel loads apply
to corresponding stainless -steel models.
• %" hex washer head is stamped with the No -Equal
sign and fastener length for easy identification
after installation.
• For the %" hex -head driver bit, order model
no. BITHEXF38-41.
Material: Heat -treated carbon steel, Type 316 stainless steel
Finish: Double barrier (all lengths); Type 316 stainless steel
(11/2" thru 31/2" lengths)
Codes: See p.11 for Code Reference Key Chart
v-
S6
I
Length
1
Thread
length
These products are available with additional corrosion protection. For more information, see p.14.
Strong -Drive SDS Heavy -Duty Connector Screw
Identification on all
SDS screw heads
(1/4" x 6" SDS shown)
Type-17 point
reduces installation
torque and makes
driving easier
mg -Drive
SDS Heavy -Duty
Connector Screw
® For stainless -steel fasteners, see p. 21.
DF/SP Allowable Loads (lb.)'
PF/HIFIlowable Loads (lb.)'
Shear (100)
Withdrawal°
Shear (100)
Withdrawals
Model
Size :
Thread
Length
Fasteners
per
Wood Side
Plate'
Steel Side
Plate
(100)
(100)
Code
Wood Side PlateSteel Side Plate
No.
(in.) I
(in.)
Carton'
Ref.
14 ga. 10 ga. Wood or
14 ga.
"
10 ga.
Wood or
1 Y2
SCL ''16
ga.
and
or
Steel Side
11h"
13/4
16 ga. and
VL
SPF
or
Steel Side
12 ga.
Greater
Plate
12 ga.
Greater
Plate
SDS25112
1/4 x 11/2
1
1,500
—
—
250 250
250
170
—
— 180 180
180
j 120
SDS25200
1/4x2
114
1.300
—
—
250 290
290 1
215
—
— 180 210
210
150
SDS25212
1/4 x 21/2
1'/
1,100
120
—
250 390
420
255
135
! — 180 . 280
300
180
?'SDS25300
1Ax3
I 2
950
280
—
250 420
420
345
200
— 180 300
300
240
IBC,
SDS25312
1/4 x 3Y2
2Y4 1
goo
340 1
340
250
420
420
385
245
245 180 300
300
270
FL,
SDS25412
1/4 x 41/2
23/4 ''1
800
350 1
340
250
420
420
475
250
245 180 300
300
330
LA
SDS25500
1/4 x 5
2 --<
500
350
340
250 1 420
420
475
250
245 180 300
300
330
SDS25600
1/4 x 6
31/4
600
350 1
340
1250 1 420
420
560
250
245 ' 180
300
300
395
SDS25800
1/4x8
31/4
400
350
340
250 420
420
560
250
245 180 300
300
395
1. Screws may be provided with the 4CUT- or Type-17 point. �w (2.
2. Strong -Drive SDS Heavy -Duty Connector screws install best using a low -speed 1/2° rill with a 34" hex -head driver. J
3. Shear values are valid for connections between two members with full thread penetration into the main member. For other wood side plate values. -
see Fastening Systems Technical Guide (C-F-2019TECHSUP) at strongtie.com.
i
4. Allowable loads are shown at a wood load duration factor of CD = 1.0. Loads may be increased for load duration per the building code up to a CD = 1.6.
Ta wanes must be multiplied by all applicable NDS adjustment factors.
y
5. Withdrawal loads shown are in pounds (lb.) and are based on penetration of the screw's entire threaded section into the main member. If thread
*�
penetration into the main member is less than the Thread Length as shown in the table for DF/SP, reduce allowable load by 172 Ib.ln. of thread not
in main member. Use 121 lb./in. for SPF/HF.
LL
6. Fasteners per Carton represents the quantity of screws that are available in bulk packaging. Screws are also available in mini -bulk and retail packs.
Refer to Simpson Strong -Tie Fastening Systems catalog (C-F-2019) at strongtie.com.
7. LSL wood -to -wood applications that require 41/2", 5", 6" or 8" SDS Heavy -Duty Connector screws are limited to interior -dry use only.
8. Where predrilling is required for Strong -Drive SIDS Heavy -Duty Connector screws, predrill diameter is 5/32".
9. Minimum spacing, edge, and end distance requirements are listed in ICC-ES ESR-2236. For smaller spacing, please contact Simpson Strong -Tie Engineering.
347