BLD2022-1312_Structural_Calculations_9.29.2022_2.48.43_PM_3137054SOLGMN
I,'
P O W E R
September 30, 2022
Subject: Proposed Solar Panel Installation
Christopher Glanister Residence, 21732 84th Ave W, Edmonds, WA
To Whom it May Concern,
Our engineering department has reviewed information, gathered by our field crews, related to the proposed solar
panel installation at the above -referenced address. The purpose of our review was to determine the structural
adequacy of the existing roof for the proposed installation. Based on our review and analysis of the available
information, it is our professional opinion that the existing structure requires a retrofit to ensure structural
adequacy to support the proposed installation.
The retrofit shall consist blocking between rafters on roof sheathing with obvious water damage. Install additional
2x4 members in between rafters at 48" O.C. spacing.
Design Parameter Summary
Governing Building Code: 2018 Washington Building Code (2018 IBC)
Risk Category: II
Design Wind Speed: 110 mph (per ASCE 7-16)
Ground Snow Load: 25 psf
Roof Information
Roof Structure: 2x4 Rafters @ 24" O.C.
Roofing Material: Asphalt Shingles (2 layers)
Roof Slope: 18 degrees
Roof Connection Details
RT Minis into 2x rafters or truss top chords at 48" O.C., install per design drawings and manufacturer specs
Locations per design drawings
Note: Required embedment length excludes the tapered tip of the screw, and embedment into sheathing.
Analysis
The proposed installation - including weight of panels, racking, and mounts - will be approximately 2.78 psf. In the
areas where panels are installed, roof live loads will not be present. Also, where applicable, roof snow loads will be
reduced because the slippery surface of the panels will cause the roof to shed additional snow loads relative to the
existing roof surface. The reduction of roof live and snow load is adequate to fully or partially compensate for the
addition of the panel installation. Because the member forces in the area of the solar panels are not increased by
more than 5%, the stresses in the members are not increased by more than 5%, and so per section 806.2 of the
International Existing Building Code (IEBC), the structure need not be altered for gravity loading.
The proposed installation will be 6" max. above the roof surface (flush mounted) and parallel to the roof surface.
Therefore, any increase in wind loading on the building structure from the solar panel installation is expected to be
negligible. Wind is the governing lateral load case. Because the increase in lateral loading is not increased by more
than 10%, per section 806.3 of the adopted IEBC, the structure need not be altered for lateral loading.
Wind uplift on the panels has been calculated in accordance with the relevant provisions of ASCE 7-16. This loading
has been used to verify the adequacy of the connection specified above. Connection locations should be in
accordance with design drawings.
Conclusion
When the retrofits detailed in this letter's opening paragraph are performed, the structure will have adequate
strength to support the proposed installation. Connections to the roof must be made per the "Roof Connection
Details" section above. Copies of all relevant calculations are enclosed.
Limitations and Disclaimers
The opinion expressed in this letter is made in reliance on the following assumptions: the existing structure is in
good condition (apart from the damage which shall be repaired or retrofit per the above); the existing structure is
free from defects in design or workmanship; and the existing structure was code -compliant at the time of its design
and construction. These assumptions have not been independently verified, and we have relied on representations
made by the property owner and his or her agents with respect to the foregoing. The undersigned has not inspected
the structure for patent or latent defects.
Electrical engineering is beyond the scope of this analysis. Solar panels must be installed per manufacturer
specifications. Structural design and analysis of the adequacy of solar panels, racks, mounts, rails, and other
components is performed by each component's respective manufacturer and the undersigned makes no statement
of opinion regarding such components. This letter and the opinions expressed herein are rendered solely for the
benefit of the permitting authority (city or county building department), and may not be utilized or relied on by any
other party.
If you have any questions or concerns, please contact our office at (8SS)-709-1181, or email me directly at
Trevor.Jones@solgenpower.com.
Sincerely,
Trevor A. Jones, P.E.
30/09/2022
The retrofit shall consist blocking between rafters on roof sheathing with obvious water damage.
Install additional 2x4 members in between rafters at 48" O.C. spacing.
Additional Retrofit Details and Notes
2 x RAFTER
2 x CEILING JOIST
BEARING WALL
NEW 2 x BLOCKING AT 48"
O.C. OR AT OTHER SPACING
AS NOTED IN LETTER
ROOF SHEATHING
W9-
RIDGEBOARD
TOENAIL NEW BLOCKING INTO
EXISTING WITH (2) 16d NAILS AT
EACH CONNECTION. DO NOT
PENETRATE PLYWOOD ABOVE.
DETAIL NOTES:
1. ALL MEMBERS SHOWN ARE EXISTING
UNLESS LABELED (N) OR NEW.
2. RETROFIT REQUIRED ONLY AT ROOF
AREAS SUPPORTING SOLAR PANELS AND
THAT ARE SAGGING OR SOFT, UNLESS
NOTED OTHERWISE IN LETTER.
Pictures of poor condition - area to be retrofit (where applies)
SOLGr- N
P 0 w E R Note: All calculations per ASCE 7
Load Comparison
This calculation justifies the additional solar load by comparing existing to proposed gravity loads
in the location of the solar panels.
Dead Load
Asphalt Shingles
1/2" Plywood
Framing
Insulation
1/2" Gypsum Ceiling
M,E, & Misc
Solar Panel
Total Dead Load
Snow Load
Ground Snow Load, Pg
Exposure Factor, Ce
Thermal Factor, Ct
Importance Factor, IS
Flat Roof Snow Load
Slope
Unobstructed Slippery Surface?
Slope Factor, CS
Sloped Roof Snow Load
Live Load
Roof Live Load
Load Combination
D+Lr
D + S
Max. Load
% of original
Withniit Cnlnr %A/ith Cnl!3r
5
5
psf
1
1
psf
3
3
psf
1
1
psf
2
2
psf
1.5
1.5
psf
0
2.78
psf
13.5 1 16.28 psf
25
1
1.1
1
19.25
18
No
Yes
1.00
0.87
19.3
16.7
psf
Eqn. 7.3-1 orjurisdiction min.
degrees
psf
20 1 0 psf
33.5
16.3
psf
32.8
33.0
psf
33.5
33.0
psf
98%
Result: Because the total forces are decreased, per the relevant code
provisions stated in the body of the letter, the existing roof
structure is permitted to remain unaltered.
SOLGr- N
P O W E R
RT Mini Connection Calculation
This calculation justifies the connection of the solar panels to existing roof members, by showing the connection
capacity is equal to or greater than the uplift force demands.
Connection Demand
Spacing perpendicular to rail
Spacing parallel to rail
Effective Wind Area on each connection
Roof Angle
Wind Speed
Exposure Coefficient, K,
Topographic Factor, K,t
Directionality Factor, Kid
Elevation Factor, Ke
Velocity Pressure, q,
GCp (max)
Exposed Panels? (YE = 1.5)
Pressure Equalization Factor, Ya
Uplift Force
Max. Uplift Force / Connection (1.0 WL)
ASD Factored (0.6 WL)
Solar Dead Load (0.6 DL)
Max. Uplift Force (0.6 WL- 0.6 DL)
Connection Capacity
Connection Type
Total Allowable Capacity
32.5
in
in
ft2
degrees SOLAR PAt
ROOF
mph
ROOF TEC
MINI
48
10.8
18
110
0.8
1
0.85
1.00
21.1 psf Mount
to existing ratters
Center Zones Edge Zones Corner Zones
1/2 panel length
Max spacing
1.80
2.57
2.57
No
No
No
0.79
0.79
0.79
29.8
42.5
42.5
322.9
460.6
460.6
193.7
276.4
276.4
18.1
18.1
18.1
175.7
258.3
258.3
psf
Ibs
Ibs
Ibs
Ibs
RT Mini into 2x Rafter
447.0 Ibs (per manufacturer)
K
Compare ASD Factored Demand to Capacity
Demand 258.3 Ibs
Capacity 447.0 Ibs
Result Capacity exceeds demands. Therefore, connection passes.