OLD- DNS APPROVED BLD2022-0392+Plumbing_Plan+3.28.2022_3.11.51_PM+2765813PIPE MATERIAL SCHEDULE GENERAL NOTES PLUMBING LEGEND AND SYMBOLS PIPE TYPE PRESSURE SHUT-OFF SERVICE MATERIAL OF FITTINGS RATINGS VALVE & WEIGHT JOINTS MATERIAL PSI - SWP Cast Bronze/ Ball OXYGEN Copper L Tube Soldered Wrought Copper 125 Check Cast Bronze/ Ball MEDICAL VACUUM Copper L Tube Soldered Wrought Copper 125 Check 1. THE TOTAL INSTALLATION SHALL COMPLY WITH ANY AND ALL REQUIREMENTS OF THE LEGALLY CONSTITUTED SYMBOL ABBREV. DESCRIPTION AUTHORITIES HAVING JURISDICTION INCLUDING 2018 INTERNATIONAL BUILDING CODE (IBC), 2018 INTERNATIONAL DETAIL No. MECHANICAL CODE (IMC), 2018 UNIFORM PLUMBING CODE (UPC) WITH WASHINGTON STATE AMENDMENTS AND THE 2018 � DETAIL REFERENCE WASHINGTON STATE ENERGY CODE. SHEET No. A SECTION REFERENCE � � � � � � �� 2. THE CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID AND SHALL THOROUGHLY FAMILIARIZE HIMSELF WITH THE P-� EXISTING CONDITIONS UNDER WHICH HE WILL BE REQUIRED TO WORK. ALL INDICATED DIMENSIONS ARE APPROXIMATE STACK/RISER AND ARE GIVEN FOR ESTIMATE PURPOSES ONLY. � PLUMBING STACK OR RISER REFERENCE ID. No. 3. BEFORE PROCEEDING WITH THE WORK THIS CONTRACTOR SHALL CAREFULLY CHECK AND VERIFY ALL DIMENSIONS, EQUIPMENT SIZES, REQUIRED CLEARANCES AND SHALL ASSUME FULL RESPONSIBILITY FOR THE FITTING OF ALL EQUIPMENT AND EQUIPMENT REFERENCE ID No MATERIALS HEREIN REQUIRED TO OTHER PARTS OF THE WORK OF OTHER TRADES. - CW COLD WATER 4. THE DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC TO THE EXTENT THAT ALL OFFSETS, BENDS, SPECIAL FITTINGS AND - - HW HOT WATER LOCATIONS ARE NOT EXACTLY LOCATED. IN THE PREPARATION OF THESE DOCUMENTS, CERTAIN ASSUMPTIONS ARE MADE REGARDING EXISTING CONDITIONS. SOME OF THESE ASSUMPTIONS MAY NOT BE VERIFIABLE WITHOUT - - - HWR HOT WATER RETURN EXPENDING ADDITIONAL SUMS OF MONEY OR DESTROYING OTHERWISE ADEQUATE OR SERVICEABLE PORTIONS OF TW TEMPERED WATER DESIGN WEST E N G I N E E R I N G EXISTING BUILDINGS AND/OR EQUIPMENT. THEREFORE, THE ENGINEER SHALL NOT BE HELD RESPONSIBLE FOR ANY MECHANICAL. ELECTRICAL. ENERGY CONSULTANTS CHANGES OR ADDITIONAL COSTS INCURRED DUE TO EXISTING CONDITIONS. ---------------- - POP -OFF DRAIN LINE OR HIDDEN WATER LINE 5. ITEMS RELATED TO PLUMBING UTILITIES AND/OR OTHER SERVICE(S); MATERIALS, LABOR, PERMITS, FEES, ETC., SHALL S or W SOIL or WASTE BELOW GRADE (or FLOOR) BE VERIFIED WITH THE RESPECTIVE SERVING UTILITY COMPANY PRIOR TO SUBMISSION OF A BID. THE ACT OF RD/OD RD/OD ROOF &OVERFLOW DRAIN ABOVE &BELOW GRADE (or FLOOR) SUBMITTING A BID SHALL CONSTITUTE FULL RESPONSIBILITY OF THE CONTRACTOR TO INSTALL SERVICES) IN SD SD STORM DRAIN COMPLIANCE WITH THE REQUIREMENTS OF THE SERVING UTILITY COMPANY AND THE MECHANICAL ENGINEER. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CHARGES LEVIED BY THE SERVING UTILITY COMPANY EXCEPTING THE S or W SOIL or WASTE ABOVE GRADE (or FLOOR) FIRST BILLING DEPOSIT. - - - - - - - - V PLUMBING VENT 6. THE CONTRACTOR SHALL COMPLY WITH ALL CONTRACT DOCUMENTS IN LAYING OUT THEIR WORK AND EQUIPMENT. COND COND CONDENSATE DRAIN THEY SHALL COORDINATE THE WORK OF THIS SECTION WITH THE WORK OF OTHER TRADES AND ALL JOB CONDITIONS. G G GAS LOW PRESSURE 7. THE INSTALLATION OF ACCESS PANELS OR OTHER INDICATING EQUIPMENT OR SPECIALTIES REQUIRING READING, MPG MPG GAS MEDIUM PRESSURE ADJUSTMENT, INSPECTION, REPAIRS, REMOVAL OR REPLACEMENT SHALL BE CONVENIENTLY LOCATED WITH CA CA COMPRESSED AIR 110 James St., Suite 106 REFERENCE TO THE FINISHED BUILDING. CA � CAO COMPRESSED AIR OUTLET Edmonds, WA 98020 Phone: 425.458.9700 8. ALL EQUIPMENT AND FIXTURES INSTALLED UNDER THIS CONTRACT SHALL BE HUNG OR ANCHORED IN ACCORDANCE OXY OXY OXYGEN Email: cadd@designwesteng.com WITH 2O18 (IBC) AND 2018 UPC. VAC VAC MEDICAL VACUUM STAMP: 9. THE INTENT OF THE DRAWINGS AND SPECIFICATIONS IS TO CONSTRUCT THE PROJECT IN ACCORDANCE WITH 2O18 ��� BV BALL VALVE WASHINGTON STATE ENERGY CODE. SOV SHUT OFF VALVE 10. WHERE MATERIAL IS SHOWN ON THE DRAWINGS BUT NOT SPECIFIED, IT SHALL BE OF THE SAME TYPE AND QUALITY AS ��J SOV or GC SHUT OFF VALVE OR GAS COCK ON RISER OL E � L EXISTING MATERIAL. � � CV SWING CHECK VALVE � of WA � 11. TEST SYSTEMS) IN ACCORDANCE WITH REQUIREMENTS OF THE GOVERNING AUTHORITIES. �� PRV PRESSURE REDUCING VALVE � o � � PTR PRESSURE -TEMPERATURE RELIEF VALVE 12. ALL CLEANOUTS SHALL BE INSTALLED WHERE READILY ACCESSIBLE AND LOCATED AS PER CODE REQUIREMENTS THE � CONTRACTOR SHALL COORDINATE ALL CLEANOUT LOCATIONS WITH EQUIPMENT CABINETS, ETC. AND THE ARCHITECT RPBFP REDUCED PRESSURE BACKFLOW PREVENTER � 21 oo77a7 � ��.� ��'GISTEg�� PRIOR TO ANY INSTALLATION. ��v �SSIONAL TMV THERMOSTATIC MIXING VALVE ��� 13. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING AND REPAIRING ALL PAVED AREAS WHICH ARE EXCAVATED AND/OR DAMAGED BY THEIR OPERATIONS. IN ADDITION, THE CONTRACTOR SHALL RESTORE TO ORIGINAL CONDITION �0 DN PIPE DOWN ALL PLANTED AREAS DAMAGED BY THEIR OPERATIONS. �p UP PIPE UP 14. ALL CONNECTIONS TO EXISTING SERVICES SHALL BE MADE SUCH THAT INTERRUPTION TIME WILL BE AS SHORT AS � DN TEE DOWN POSSIBLE. THE CONTRACTOR SHALL GIVE THE OWNERS REPRESENTATIVE A MINIMUM OF 72 HOURS NOTICE OF SUCH UP TEE UP INTERRUPTIONS AND THE ACTUAL SHUT -DOWN TIME SHALL BE AT A TIME DESIGNATED BY THE OWNERS REPRESENTATIVE. � C- PIPE RISER &PIPE DROP (UP AND DOWN) - - � FCO FLOOR CLEANOUT 15. POTABLE WATER SYSTEMS SHALL BE DISINFECTED AND FLUSHED PRIOR TO USE BY WATER -CHLORINATION SOLUTION �O--II w AND HAVE BACTERIOLOGICAL EXAMINATION MADE BY AN APPROVED AGENCY PER 2018 UPC 609.9 AND AS PRESCRIBED WCO WALL CLEANOUT � IN AWWA C651. METHODS OF CLEANING/ DISINFECTING FOR NEW OR REPAIR PIPING AS DESCRIBED IN C651 OR NFPA 24. I CO CLEANOUT PLUG z 16. PLUMBING PIPE, FITTINGS AND FIXTURES USED TO CONVEY OR DISPENSE WATER FOR HUMAN CONSUMPTION SHALL BE - - ---� COTG YARD CLEANOUT or CLEANOUT TO GRADE W LEAD-FREE PER 2018 UPC 604.2. CAP ON END OF PIPE v 17. ANY SUBSTITUTION MADE BY THE CONTRACTOR THAT IS DIFFERENT FROM WHAT IS SPECIFIED ON THE DRAWINGS HB HOSE BIBB WITH VACUUM BREAKER NEEDS TO BE APPROVED BY ENGINEER OF RECORD AND OWNER PRIOR TO BID AND SHALL BE CLEARLY INDICATED ON WHA & TP WATER HAMMER ARRESTOR &TRAP PRIMER �/ THE SUBMITTAL AS TO ALL THAT IS BEING SUBSTITUTED. w CS CIRCUIT SETTER 18. SHUT-OFF VALVES SHALL BE PROVIDED IN MAIN BRANCHES, RUNS TO RISERS AND WHERE INDICATED ON DRAWINGS. �� GR GAS REGULATOR 19. NEW NON-RESIDENTIAL WATER CLOSETS SHALL COMPLY WITH 2O18 UPC 411.2 AND SHALL NOT EXCEED 1.6 GALLONS �� GC GAS COCK (or GAS STOP) PER FLUSH. �� GS GAS SOLENOID 20. NEW NON-RESIDENTIAL WALL MOUNTED URINALS SHALL COMPLY WITH 2O18 UPC 412.1 AND SHALL NOT EXCEED 1.0 � EARTHQUAKE VALVE � GALLON PER FLUSH. � P.O.C. POINT OF CONNECTION 21. NEW NON-RESIDENTIAL LAVATORY FAUCETS SHALL COMPLY WITH 2O18 UPC 407.2.1 AND SHALL NOT EXCEED 0.5 � P.O.D. POINT OF DEMOLITION GALLONS PER MINUTE FOR PUBLIC LAVATORY AT 60 PSI. n Ap ACCESS PANEL O 22. ALL FIXTURES, EQUIPMENT, PIPING, FITTINGS, AND MATERIALS SHALL BE LISTED. ABV ABOVE � NO BEL BELOW 23. ALL PLUMBING FIXTURES SHALL MEET THE FLOW REQUIREMENTS SPECIFIED IN THE 2018 UPC. AGA AMERICAN GAS ASSOCIATION 24. PUBLIC LAVATORIES SHALL HAVE CONTROLS TO LIMIT THE WATER TEMPERATURE TO 120°F. CONN CONNECTION m \w \ CONT CONTINUATION � APPLICABLE CODES (E) EXISTING � Q (N) NEW � � 1. BUILDING CODE: 2018 INTERNATIONAL BUILDING CODE WITH WASHINGTON STATE AMENDMENTS DN DOWN � ADA AMERICAN DISABILITY ACT � 7� 7� 7 � L 2. PLUMBING CODE: CHAPTER 13 OF 2018 UNIFORM PLUMBING CODE WITH WASHINGTON STATE AMENDMENTS IE INVERT ELEVATION O � O 3. MECHANICAL CODE: 2018 INTERNATIONAL MECHANICAL CODE WITH WASHINGTON STATE AMENDMENTS (TYP) U.O.N. TYPICAL UNLESS OTHER NOTED 4. ELECTRICAL CODE: 2020 NATIONAL ELECTRICAL CODE (NFPA 70 - 2020) INC. ANNEX A, B, AND C VTR VENT THROUGH ROOF Q � Q 5. FIRE/LIFE SAFETY: 2018 INTERNATIONAL FIRE CODE WITH WASHINGTON STATE AMENDMENTS W� WITH W N W FU PLUMBING FIXTURE UNIT 6. ADA AND ACCESSABILITY GUIDELINES (LATEST EDITION) SEC COND SECONDARY CONDENSATE 7. ENERGY: 2018 WASHINGTON STATE ENERGY CODE B.F.F. BELOW FINISH FLOOR 8. NATIONAL FIRE PROTECTION ASSOCIATION: 1999 NFPA 99 R.I.C. ROUGH IN CONNECT ANCHORAGE AND BRACING NOTES �, PIPES, DUCTS AND CONDUITS SHALL BE SUPPORTED AND BRACED PER THE SMACNA "GUIDELINES FOR SEISMIC RESTRAINTS OF MECHANICAL SYSTEMS AND PLUMBING SYSTEMS", THE "SUPERSTRUT SEISMIC RESTRAINT SYSTEM" FOR PIPES AND CONDUITS ONLY. REV BY DESCRIPTION DATE 1 2 3 4 5 6 s 9 10 SHEET INDEX SHEET TITLE SHEET NUMBER SHEET TITLE P1.1 PLUMBING LEGENDS NOTES AND SCHEDULES P2.1 PLUMBING FIRST FLOOR PLAN PLUMBING LEGENDS NOTES AND SCHEDULES SCALE: AS NOTED DRAWN DATE APPROVED DATE SHEET NUMBER P1.1 GENERAL NOTES 1. MEDICAL GAS WILL BE REQUIRED TO BE CERTIFIED BY A QUALIFIED MEDICAL GAS INSPECTION COMPANY. THIS WILL BE PERFORMED BY OXYGEN MEDICAL GAS SERVICES. CONSTRUCTION NOTES tgb � architects DESIGN WEST ENGINEERING MECHANICAL, ELECTRICAL, ENERGY CONSULTANTS 110 James St., Suite 106 Edmonds, WA 98020 Phone: 425.458.9700 Email: cadd@designwesteng.com STAMP: oLE �L G �F WASIT '� � � ���� 21007747 �c,4' ���' ��GISTEg�'� ��v �SSIONAL ��� w Z w U w C� cry O �o Q O � o� °° j Q Q Q � � 0 � c� 0 � Z � Z O �O � � � � � � w N w REV BY DESCRIPTION DATE 1 2 3 4 5 6 7 8 9 10 SHEET TITLE PLUMBING FIRST FLOOR PLAN SCALE: AS NOTED I DRAWN DATE APPROVED DATE SHEET NUMBER P2.1 PLUMBING FIRST FLOOR PLAN I SCALE:1/4"=��-o�� � 1