APPROVED BLD PLN RESUB 1 BLD2022-0853+Plans+7.14.2022_8.57.31_PM+2991218EDMONDS 99 6.94 KW SOLAR PHOTOVOLTAIC SYSTEM 23400 HWY 99, EDMONDS, WA 98026 Approved by Fire DRAWING INDEX rooftop between r disconne:(at Number Title trical roomrrays) clearly :and [arrays connect.PV-001 COVER SHEE in electricm for final PV-101 SITE PLAN PV-201 ARRAY DIMENSIONS PV-202 RACKING DIMENSIONS PV-301 RACKING PV-401 EQUIPMENT SITEPLAN PV-402 EQUIPMENT ELEVATION PV-501 SINGLE LINE DIAGRAM PV-601 LABELS & PLACARDS N/A DATASHEETS & REPORTS 4 DESCRIPTION OF WORK INSTALLATION OF A 6.94 KW SOLAR PHOTOVOLTAIC SYSTEM ON THE ROOF OF 23400 HWY 99, EDMONDS, WA 98026. (19) REC TWINPEAK REC365TP4 BLACK MODULES TO BE MOUNTED AT 10' TILT, 180' AZIMUTH ON UNIRAC RM10 RACKING. MODULES TO BE CONNECTED TO (19) ENPHASE IQ7+ MICROINVERTERS. THE COMBINED PV SYSTEM OUTPUT TO CONNECT TO AN AC DISCONNECT SAFETY SWITCH LOCATED ON THE EXTERIOR WALL OF THE ELECRICAL ROOM 105A - LEVEL P1. THEN TO AN EXISTING SWITCHBOARD HP 1200A 120/208V 3P4W VIA A DEDICATED PV INTERCONNECTION BREAKER LOCATED AT THE OPPOSITE END OF THE BUSBAR FROM THE MAIN, SWITCHBOARD LOCATED IN ELECRICAL ROOM 105A - LEVEL P1. ELECTRICAL CONTRACTOR RESPONSIBLE FOR PROVIDING FUNCTIONING ETHERNET CABLE TO SOLAR MONITORING DEVICE. APPROVED BY PLANNING 7/18/2022 PROJECT DIRECTORY X GENERAL CONTRACTOR SOLAR DESIGN & INSTALL GOODMAN REAL ESTATE PUGET SOUND SOLAR 2801 ALASKAN WAY ALL WORK SUBJECT 805 RAINIER AVE S SITE MAP SEATTLE, WA 98121 TO FIELD SEATTLE, WA98144 INSPECTION FOR CODE COMPLIANCE --- _.-- zabni- sr-sw a" 3 S - 991 OBTAIN ELECTRICAL PERMIT FROM APPROVED -- STATE LABOR & PLANS MUST BE INDUSTRIES ON JOB SITE CODES & STANDARDS 2018 WASHINGTON STATE ENERG 2018 INTERNATIONAL BUILDING C( 2018 INTERNATIONAL FIRE CODE ,d 2020 NATIONAL ELECTRICAL CODE 22 " s' s SUBMITTED BY LYUDMILA ARSENIY COMMERCIAL PROJECT ENGINEER PUGET SOUND SOLAR TEL: 206-706-1931 CEL: 206-619-3818 a' LARSENIY@PUGETSOUNDSOLAR.COM City Of Edmonds Building Department Work ----------------SOLAR------- --_--__-_--__-_--__-_---------__--' Address 23400 HIGHWAY 99 ---------------------------------- ---------------------------------- GRE APT - ECpproved Date 7/26/2022 Building Official -D.. W. x 01A. Permit Number. - BLD2022-0853 PUGE-rSOUND S❑LAR 805 Rainier Ave S Seattle, WA 98144 Tel: 206-706-1931 � �FGISTERtiv �IONAL �� ES 08/02/ @2p c 10 oax G) o w o< CO 007 0) ga=a 0 Q =oso Z = u) -EE- Ia�; O o o �'oo o owN� w; 0 N 2 ww�� W p ao g§ LU ��Go �o ==ow OUF omo �oW 0 PERMIT SET 06/21/22 REV DESCRIPTION DATE DRAWN BY CHECKED BY PROJECT NO. LA JH 15637 SUBMITTED TO COVER SHEET ROB KRALIS RESUB PROJECT MANAGER GOODMAN REAL ESTATE Jul 15 2022 TEL: 206-225-3242 RKRALIS GOODMANRE.COM @ CILOPM ET ERVI DEVELOPMENT SERVICES DEPARTMENT P` ,_00 V II PV SYSTEM DETAILS N DC SIZE 6.94KW AC SIZE 3.27KW MODULES (19) REC TWINPEAK REC365TP4 BLACK INVERTER (19) ENPHASE IQ7+ DEAD LOAD 8.49PSF 34'-0" 22'-0" i6'-3" i6'-3" 22'-0" AZIMUTH / TILT 180° / 10° BUILDING HEIGHT 50FT RACKING JUNIRAC RM 10 Ll X, � v i BAYS SOLAR XE \ MODULES 23. XD 7, xC ,.q 4' SETBACK PER FIRE DEPARTMENT XB MAIN ENTERENCE PROPERTY LINE *z SCALE: 1" = 40' 22'-0, 18'-3" 18'.3" 12•.8' 31•.3, \ r ® — v m J ' v \ i ELECRICAL ROOM 105A - LEVEL P1 UTILITY METER ESUB J / 52022 P` H G CD D C CC \ B A EDMONDS E EL ENT SERVICES DEPARTMENT 1% PUGET SOUND SOLAR 805 Rainier Ave S Seattle, WA 98144 Tel: 206-706-1931 52035 ��CISTEO �� �sS ICNAL �1yG FOR PV RACKING Off RES 08/02/2 P� c a3w� 'o �ax � o m�Q wmo U 13, �a�Q } Q s N� p =oo5 Z = vi �N�LL o o p ��oo S G o M 0 owWz N W LU ==tea �a �=ow �OUr omo' W¢ 0 PERMITSET 06/21/22 REV DESCRIPTION DATE DRAWN BY CHECKED BY PROJECT NO. LA JH 15637 SITE PLAN PV-101 P N M L K J 1 '-3" 34'-0" 22'-0" 16'-3" 16'-3" 22'-0" 22'-0" 1 1/2" PUGET SOUND SOLAR 805 Rainier Ave S Seattle, WA 98144 Tel: 206-706-1931 Y, Zq C )� ti^ / 14' .�� �FGISTE � — '-10" 11'-5" 9'-10��' — �SIONA 7'-4"L E� / A FOR PV RA IN OWNY o / A EX IRES 08/02/ c 5'-9" \ oho / \ \ (D / 17'-4" \ 5'-8" C" o � wo< / rn cr 00 TF55 1 �z SCALE: 1" = 16' \ V rn rn sa 34'-9" I 34-8", Z z vi LL o 00 F77 CD z CD O �� 1 N 0 �o o 17'-4" / [ 17'-5" ILL]w s X4 \ ==tea o" 'o omw / 3r EN w� 6-5" �-4 3'-6" 01 29'-1" 21'-5" 29'-4" —1 F\� — 20'-1" 10" 2�6'-9" - 0 PERMIT SET 06/21/22 REV DESCRIPTION DATE 19'-2" / DRAWN BY LA CHECKED BY JH PROJECT NO. 15637 ARRAY DIMENSIONS RESUB Jul 15 2022 NOTE: DIMENSIONS ARE SHOW IN P NT=AvD PV_201 ROUNDED TO THE NEAREST ON'ff=H N M L K J 34'-0" 22'-0" 16'-3" 16'-3" 22'-0" 22'-0" NOTE: SEE PAGE 32 OF 33 OF THE PLANS FOR THE BALLAST BLOCK LAYOUT. — I PUGET SOUND SOLAR 805 Rainier Ave S Seattle, WA 98144 Tel: 206-706-1931 K. Zq CX. V )2 52035 rC � 1GISTER� 1� 1'-8" TYP IDNAL FOR PV RACKING O"-Y / EECFIRES 08/02/ c o=o 4'-11" / ro o wmo / UQ 5'-9" 4'-11 " .2M = o o \ / 5'-9" TYP / Z z CD LL 4'-11„ a� N O oww� 0 LU p ww�z wH �o�a =� a 4'-11" / O U 6 �0 / 5' TYP �z SCALE: 1" = 16' F— FF\� — 0 PERMITSET 06/21/22 REV DESCRIPTION DATE — J DRAWN BY LA CHECKED BY JH PROJECT NO. 15637 RACKING DIMENSIONS RESUB Jul 15 2022 NOTE: DIMENSIONS ARE SHOW IN P NT=AvD PV_202 ROUNDED TO THE NEAREST ON'ff=H TOP VIEW SIDE VIEW CRACKING VIEWS SCALE:NOT TO SCALE MODULE FRAME UNIRAC RM10 ALL DIMENSIONS ARE NOMINAL 1. PRODUCT NAME: UNIRAC RM10 2. MATERIAL: MILL FINISH ALUMINUM 3. BALLAST BLOCK: 32LB CMU 4"X8"X16'I 4. SLIP SHEETS PROVIDED BY ROOFING CONTRACTOR, INSTALLED BY PSS 5. 25 YEAR PRODUCT WARRANTY 6. UL 2703 LISTED FOR BONDING - LOCATE LUGS AS DIRECTED IN PROJECT REPORT 7. SYSTEM FIRE RATING: CLASS A WITH TYPE 1, 2, AND 3 MODULES STRUCTURAL NOTES 3 SCALE:NOT TO SCALE M �211s"� 1716' 6" FRONT VIEW SIDE VIEW CRACKING DETAIL SCALE:NOT TO SCALE ALL DIMENSIONS ARE NOMINAL RESUB 4 RACKING 3D VIEW Jul152022 SCALE:NOT TO SCALE CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT fL� PUGET SOUND S❑L 805 Rainier Ave S Seattle, WA 98144 Tel: 206-706-1931 Iq ? ��GISTER�v �SIONAL CO acax 0') N O m m Wg¢ 0') c6 oo 0') � Q o�yw Z = vS ��LLLL O CD o �aN< Q CD A o > owy= w N 2 ww = o w aF, w=�o h3�g O z o O U Q W JQ 0 PERMIT SET 06/21/22 REV DESCRIPTION DATE DRAWN BY CHECKED BY PROJECT NO. LA JH 15637 RACKING PV-301 *Z C9 C14 1 CE CD CC GCB, ELECRICAL ROOM 105A - LEVEL P1 SCALE: 1" = 24' ELECRICAL ROOM 105A - LEVEL P1 PV SUBPANEL 100A PV CONNECTION TO BUILDING ELEC. PV AC DISCONNECT CO -LOCATED WITH NET METER ON EXTERIOR WALL r ------------ I� *Z PUGET SOUND SOLAR 805 Rainier Ave S CONDUCTORS Seattle, WA 98144 TO PV ON ROOF Tel: 206-706-1931 -r' I I I I �_EP 9J I I ATS—EP ❑ 'I I ATS E- I I IE- I ms r- 1 I I o = -A I I Rw II ' BHP II 0, Z O U O lil Z = �N�LL l v 0 owe Q N MDP U lil W z Q 0 3 III W oil =ha Z III=o� o iil Qm0- > o_ lil III — 7-7-1111- 0 PERMITSET 06/21/22 — — — — — REV DESCRIPTION DATE DRAWN BY LA CHECKED BY JH PROJECT NO. 15637 EQUIPMENT SITEPLAN RESUB DETAIL: ELECRICAL ROOM 105A - LEVEI�R322 SCALE: 1" = 12 CITY OF EDMONDS DEVELOPMENTSERVICES DEPARTMENT PV-401 1 -8 MONITORING DEVICE PV SUBPANEL 100A MONITORING DEVICE LIVE ETHERNET DROP (BY OTHERS) FLOOR ELECRICAL ROOM 105A - LEVEL P1 SCALE: 1" = 1' �L 81 y 8 0 0 1'-3$" AC DISCONNECT 6'-7" MAX EAST EXTERIOR WALL OF ELEC. RO ESUB .�4 Zo22 SCALE: 1" = 1' CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT It PUGET SOUND SOLAR 805 Rainier Ave S Seattle, WA 98144 Tel: 206-706-1931 m� oy z o�� 10 aoax O') IN O °° m Wg¢ o�u�iw -oho Z = '�LLLL O CD Q CD A ZO > owy� w N 2 ww = Lu LLI a, o� w��o h3�g U z o O U Q w� 0 PERMIT SET 06/21/22 REV DESCRIPTION DATE DRAWN BY CHECKED BY PROJECT NO. LA JH 15637 EQUIPMENT ELEVATION PV-402 SOLAR PV SYSTEM SPECIFICATIONS MAX POWER OUTPUT 6.94KW DC / 3.27 KW AC TOTAL MODULES 19 TOTAL MICRO -INVERTERS 19 MIN DESIGN TEMPERATURE -12'C MAX SYSTEM VOLTAGE 45V DC / 208V AC MAX SYSTEM CURRENT AC MODULE SPECIFICATIONS SOLAR MODULE BLACK MPP VOLTAGE 34.3V MPP CURRENT 10.65A OPEN CIRCUIT VOLTAGE 40.9V SHORT CIRCUIT CURRENT 11.36A VOC TEMP COEFFICIENT -0.26%/'C MICRO -INVERTER SPECIFICATIONS MANUFACTURER& MODEL ENPHASEIQ7+ INVERTER RATED POWER 290W INVERTER RATED CURRENT 1.39 @ 208V 3q) MAX INPUT VOLTAGE 60V MAX INPUT CURRENT 15A CERTIFICATION UL1741, IEEE1547 MODULES PER INVERTER 1 MAX MODULES IN STRING 7 BRANCH MAX AMPERAGE 9.73A FEEDER SCHEDULE (1) ENPHASE CABLES �z (6) #10 THWN-2 + (1) #12 GND IN 3l4" EMT �3 (4) #12 THWN-2 + (1) #12 GND IN 3/4"EMT ® (4) ENPHASE-SUPPLIED CT LEADS IN 3/4" EMT O (3) #12 THWN-2 +(1) #12 THWN-2 NEUT + (1) #12 GND IN 3/4" EMT FLAG NOTES 1 PV INTERCONNECTION BREAKER MUST BE LOCATED AT OPPOSITE END OF BUSBAR FROM MAIN OCPD CONDUIT FOR SOLAR TO ROOF FURNISHED & INSTALLED BY ELECTRICAL CONTRACTOR GENERAL LINE DIAGRAM NOTES: 1. THE DISTANCE ABOVE THE ROOF TO THE BOTTOM OF ROOFTOP CONDUIT SHALL BE GREATER THAN 7/8" 2. NEC 690.12 RAPID SHUTDOWN REQUIREMENTS ARE MET BY INSTALLING RAPID SHUTDOWN DEVICE(S). 3. FEEDERS ARE COPPER UNLESS OTHERWISE NOTED 4. EQUIPMENT TO BE FULLY RATED FOR AVAILABLE FAULT CURRENT PER NEC 100.9 AND 110.10 4 PUGET SOUND SOLAR 805 Rainier Ave S Seattle, WA 98144 Tel: 206-706-1931 WORK BY PSS WORK BY OTHERS PV SUBPANEL 100A MLO HP 1200A MILO MDP 5000A MLO d 120/208V 3PH 4W 120/208V 3PH 4W 120/208V 3PH 4W Rd O O 20A 2P 1200A 3P UTILITY o z y 20A 2P o SERVICE a 3 30A AC DISCONNECT o ^ ^ " co a o S x 20A 2P (CO -LOCATED WITH 04 w m NET METER) 20A 3P m 0 00 m o JUNCTION o 20A 3P ✓ o 5 o to w BOX Q } o oG zOUO ® (A)sT Z O = O o2LL 0 (D INTERNET CT NET METER Z(LOC o w z DAS — 0 PROVIDEDION BY EXTERIOR EAST w N ENPHASE IQ OTHERS WALL OF 105A) C) a o COMMERCIAL LV l oo o o ENVOY y3No z 2 o O U Q �oN ROOF IELECRICAL ROOM 105A- LEVEL P1 (UNLESS NOTED OTHERWISE) RESUB Jul 15 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT 0 PERMIT SET 06/21/22 REV DESCRIPTION DATE DRAWN BY CHECKED BY PROJECT NO. LA JH 15637 SINGLE LINE DIAGRAM PV-501 DC CONDUITS & BOXES DC J-BOXES A RNI G PV DC POWER SOURCE NO OTHER CIRCUITS PEACE AT DC JUNG71ON BOXES AC J-BOXES AWARNING PV AC POWER SOURCE NO OTHER CIRCUITS PEACE AT DD JUNCTION BOXES NET METER AC COMBINER(S)/ PV SUB AC DISCONNECTS (OTHER THAN MAIN) AWARNING PHOTOVOLTAIC DISCONNECTAC PHOTOVOLTAIC SYSTEM COMBINER PANEL OPERATING • DO NOT ADD LOADS OPERATING PLACE AT AC COMBINER PANELS PER NEC SX—,6S 3 PLACE AT AD """NECTI PC_ OF INTERCONNECTION A RNIN THIS EQUIPMENT FED FROM MULTIPLE SOURCES. TOTAL RATING OF ALL OVERCURRENT DEVICES, EXCLUDING MAIN SUPPLY OVERCURRENT DEVICE, SHALL NOT EXCEED AMPACITY OF BUSBAR. PEN7SB12UU PLACE AT INTERCONNECTION LOCATIONFOR LOAD SIDE TAP MEETING THE REQUIREMENTS OF NEC TOS 1XEX2DXC) PLACE AT PANELBOARDS FED FROM MULTIPLE SOURCES AT MAIN SERVICE DISCONNECT SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN TURN RAPID SHUTDOWN SWITCH TO THE SOLAR ELECTRIC "OFF" POSITION TO PV PANELS SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN THE ARRAY PER 690 B)C) LOCATE ON OR NO MORE THAN SET FROM THE SERVICE DISCONNECTING MEANS TO WHICH THE PV SYSTEM IS CONNECTED. MUST INDICATE THE LOCATION OF ALL IDENTIFIED RAPID SHUTDOWN SWITCHES IF NOT AT SAME LOCATION NOTES: 1. PLACE LABELS AS DESCRIBED BELOW EACH LABEL 2. UNLESS OTHERWISE NOTED, ALL LABELS SHALL MEET ANSI Z535.1. THE HEADER BACKGROUND COLOR IS ASSOCIATED WITH TYPE OF LABEL AND SHALL BE COLORED AS FOLLOWS: DANGER: SAFETY RED - PANTONE 485C WARNING: SAFETY ORANGE - PANTONE 152C CAUTION: SAFETY YELLOW - PANTONE 109C 3. LABELS REQUIRED BY THE INTERNATIONAL FIRE CODE ARE TO BE RED WITH REFLECTIVE LETTERING AND ARE NOTED AS SUCH 4. LABELS REQUIRED TO BE PHENOLIC PLACARD TYPE ARE NOTED AS SUCH 5. PLACARDS AND LABELS SHOWN HERE MAY NOT BE TO SCALE A CAUTION POWER TO THIS SERVICE IS SUPPLIED FROM MULTIPLE SOURCES: 1. UTILITY: DISCONNECT LOCATED HERE, IN ELECRICAL ROOM 105A- LEVEL P1 2. SOLAR PV: DISCONNECT LOCATED HERE, IN ELECRICAL ROOM 105A- LEVEL Pi PLACE AT SERVICE EQUIPMENT LOCATION AWARNING ELECTRIC SHOCK HAZARD DO NOT TOUCH TERMINALS TERMINALS ON BOTH THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION PLIGET 5❑UND S❑LAR 805 Rainier Ave S Seattle, WA 98144 Tel: 206-706-1931 PER NEC PEACE ATADDISCOECT POINT OF CONNECTION TO BUILDING ELECTRICAL CIRCUITS AWARNINGW POWER SOURCE OUTPUT CONNECTION m �a DO NOT RELOCATE THIS OVERCURRENT DEVICE y PER ME. B. (F)R�PucEAT INTERCONNECTION BREROOA LOAD SIDE CONNECTION oiy ACAUTION aoa SOLAR ELECTRIC BREAKER IS BACKFE co 4¢ PLACE AT INTERCONNECTION BREAKER FOR LOAD SIDE TAP 00 m I PHOTOVOLTAIC SYSTEo DO ? > � w o oG IJ S > Z O U O DISCONNECTAC Z = U)CD ti�LLLL OPERATING AMPS Q � O �zo 1. N W w 0 PC,UTOFINTER-NNETIDN LLl It F= w=? ACAUTION �=o POWER TO THIS SERVICE IS o . N SUPPLIED FROM MULTIPLE SOURCES: m o F. 1. UTILITY: DISCONNECT LOCATED HERE, IN " ELECRICAL ROOM 105A - LEVEL P1 2. SOLAR PV: DISCONNECT LOCATED HERE, IN ELECRICAL ROOM 105A - LEVEL P1 PLACE AT SERVICE EQU'P`MENT LOCANION THIS PANEL SUPPLIED BY • POWER SOURCESTWO POWER SOURCES0 PERMIT SET 06/21/22 . • • - PV 208 VOLTS,• •: VOLTS,REV DESCRIPTION DATE DRAWN BY LA JTILITY 0: VOLTS,•• AMPS UTILITY 208 VOLTS,00 CHECKED BY JH PLACE ATPAHELBOARDSFED FROM MULTIPLE SOURDES PEACE ATPANELBOARDSFED FROM MULTIPLESOURCES PROJECT NO. 15637 RAPID SHUTDOWN SWITCH (BREAKER OR DISCONNECT) LABELS &PLACARDS 'A' DOB FOR SOLAR PV SYSTEM 022 LFCT��LETTERING DEVELOPMENTSERVICES SERVICES RED BA PLgcEAER NEC "A NENTATION) DEPARTMENT PV 601 DATASHEETS REC TWINPEAK 4 BLACK SERIES PREMIUM SOLAR PANELS WITH SUPERIOR PERFORMANCE REC TwinPeak 4 Black Series solar panels feature an aesthetically -pleasing full -black design with high panel efficiency and power output, enabling customers to get the most out of the space used for the installation. Combined with industry -leading product quality and the reliability of a strong and established European brand, REC TwinPeak 4 Black Series panels are ideal for residential and commercial rooftops worldwide. I yPID FREE MORE POWER FEATURING REC'S PIONEERING 100% OUTPUT PER Ms TWIN DESIGN PID FREE SUPER -STRONG FRAME GENERALDATA Celltype: 120 half -cut mono c-Si p-type cells, 6 strings of 20 cells in series Glass: 3.2 mm solarglasswith anti -reflective surface treatment in accordancewith EN 12150 Backsheet: Highly resistant polymer (black) Frame: Anodized aluminum (black) with silver support bars Junction box: 3-part, 3 bypass diodes, lead-free IP68 rated, in accordance with IEC 62790 Connectors: Staubli MC4 PV-KBT4/KST4 (4 mm2) in accordance with IEC 62852, IP68 onlywhen connected Cable: 4 mm2 solar cable, 1.1 m+1.2m in accordancewith EN 50618 Dimensions: 1755 x1040x30 mm (1.83 m2) Weight: 20.0 kg Origin: Made in Singapore 175532.5 169.10 30.11 ,1 - , 28 [1.11 _ 845 [33.271 455 [17.9111 h ❑ 156 [6.14] -------------------------- 1100 [43.3] t 5.5±0.2 [0.2230.01 ] y 11±0.2 [0.43 30.1 ] - - 1200 [47.21 zo.5±o.5 m [0.8 i0.02] 156 [6.14] ..'�. 45 [1.8] } 22.5 [0.91 638 ±1 [25.1 ±0.04] 30 [1.2] Measurements in mm [in] ELECTRICAL DATA Product Code': RECxxxTP4 Black Power Output - PMAx(Wp) 350 355 360 365 370 Watt Class Sorting-(W) 0/+5 0/+5 0/+5 0/+5 0/+5 Nominal Power Voltage - VMpp(V) 33.1 33.5 33.9 34.3 34.7 Lj Nominal Power Current - IMpp(A) 10.57 10.60 10.62 10.65 10.68 1n Open Circuit Voltage - Vcc(V) 40.6 40.7 40.8 40.9 41.1 Short Circuit Current- Isc (A) 11.22 11.27 11.31 11.36 11.41 Panel Efficiency(%) 19.1 19.4 19.7 20.0 20.3 Power output -PMAx(Wp) 264 268 272 276 280 Nominal Power Voltage - VMpp(V) 31.0 31.3 31.7 32.1 32.5 Nominal Power Current -I,(A) 8.54 8.56 8.58 8.60 8.63 F Open Circuit Voltage - Voc(V) 38.0 38.1 38.2 38.2 38.4 z Short Circuit Current - Isc(A) 9.06 9.10 9.13 9.18 9.22 Values at standard test conditions (STC: air mass AM 1.5, irradiance 1000 W/m2, temperature 25°C), based on a production spread with a tolerance of PM Von&I5c±3%within one watt class. Nominal module operating temperature (NMOT: air mass AM 1.5, irradiance 800 W/m2 temperature 20°C, windspeed 1 m/s). *Where xxx indicates the nominal power class (P_x) at STC above. MAXIMUM RATINGS WARRANTY Operational temperature: -40...+85°C Standard REC ProTrust Maximum system voltage: 1000V Installed by an REC No Yes Yes Certified Solar Professional Maximum test load (front): +7000 Pa (713kg/m2)' System Size All g25 kW 25-500 kW Maximum test load (rear): -4000Pa(407kg/m2)' Product Warranty (yrs) 20 25 25 Max series fuse rating: 25A Power Warranty (yrs) 25 25 25 Max reverse current: 25A Labor Warranty (yrs) 0 25 10 See installation manual for mounting instructions. Power in Year] 98% 98% 98% Design load =Test load/1.5(safetyfactor) Annual Degradation 0.5% 0.5% 0.5% Power in Year 25 86% 86% 86% See warranty documents for details. Conditions apply TERTIFICATIONS IEC 61215:2016, IEC 61730:2016, UL 61730 IEC62804 PID IEC 61701 Salt Mist IEC 62716 Ammonia Resistance ISO 11925-2 Ignitability (Class E) IEC 62782 Dynamic Mechanical Load IEC 61215-2:2016 Hailstone (35mm) ISO 14001, ISO 9001, IEC 45001, IEC 62941 UVE c Eib C take!way take-e-way WEEE-compliant hwmk recydingscheme TEMPERATURE RATINGS - Nominal Module Operating Temperature: 44.6*C (±2*C) Temperature coefficient of PMAx: -0.34 %/°C Temperature coefficient ofVoc: -0.26%/-C Temperature coefficient of Isc: 0.04 %/°C "The temperature coefficients stated are linearvalues LIVERY INFORMATION Panels per pallet: 33 Panels per40ft GP/high cube container: 858(26 pallets) Panels per13.6 m truck: 924 (28 pallets) Panels per 53 ft truck: 924 (28 pallets) Typical low irradiance performance of module at STC: o I a i w '---- Irradiance(W/m=) _ Founded in 1996, REC Group is an international pioneering solar energy company dedicated to empowering consumers with clean, affordable solar power. As Solar's Most Trusted, REC is committed to high quality, innovation, and a low carbon footprint in the solar materials and solar panels it manufactures. Headquartered in Norway with operational headquarters in Singapore, REC also has regional hubs in North America, Europe, and Asia -Pacific. v 0 z 0410 o m 0 n N N n1 O d 7 O www.recgroup.com cE Data Sheet Enphase Microinverters Region: AMERICAS Enphase IQ7and IQ7+ Microinverters a HE To learn more about Enphase offerings, visit enphase.com The high-powered smart grid -ready Enphase IQ 7 MicroTM and Enphase IQ 7+ MicroTM dramatically simplify the installation process while achieving the highest system efficiency. Part of the Enphase IQ System, the IQ 7 and IQ 7+ Microinverters integrate with the Enphase IQ EnvoyTM, Enphase IQ BatteryTM, and the Enphase Enlighten' monitoring and analysis software. IQ Series Microinverters extend the reliability standards set forth by previous generations and undergo over a million hours of power -on testing, enabling Enphase to provide an industry -leading warranty of up to 25 years. Easy to Install • Lightweight and simple • Faster installation with improved, lighter two -wire cabling • Built-in rapid shutdown compliant (NEC 2014 & 2017) Productive and Reliable • Optimized for high powered 60-cell and 72-cell* modules • More than a million hours of testing • Class II double -insulated enclosure • UL listed Smart Grid Ready • Complies with advanced grid support, voltage and frequency ride -through requirements • Remotely updates to respond to changing grid requirements • Configurable for varying grid profiles • Meets CA Rule 21 (UL 1741-SA) * The IQ 7+ Micro is required to support 72-cell modules. � ENPHASE Enphase IQ 7 and IQ 7+ Microinverters INPUT DATA (DC) IQ7-60-2-US / IQ7-60-B-US IQ7PLUS-72-2-US / IQ7PLUS-72-B-US Commonly used module pairings' 235 W - 350 W + 235 W - 440 W + Module compatibility 60-cell PV modules only 60-cell and 72-cell PV modules Maximum input DC voltage 48 V 60 V Peak power tracking voltage 27 V - 37 V 27 V - 45 V Operating range 16 V - 48 V 16 V - 60 V Min/Max start voltage 22 V / 48 V 22 V / 60 V Max DC short circuit current (module Isc) 15 A 15 A Overvoltage class DC port II 11 DC port backfeed current 0 A 0 A PV array configuration 1 x 1 ungrounded array; No additional DC side protection required; AC side protection requires max 20A per branch circuit OUTPUT DATA (AC) IQ 7 Microinverter IQ 7+ Microinverter Peak output power 250 VA 295 VA Maximum continuous output power 240 VA 290 VA Nominal (L-L) voltage/range2 240 V / 208 V / 240 V / 208 V / 211-264 V 183-229 V 211-264 V 183-229 V Maximum continuous output current 1.0 A (240 V) 1.15 A (208 V) 1.21 A (240 V) 1.39 A (208 V) Nominal frequency 60 Hz 60 Hz Extended frequency range 47 - 68 Hz 47 - 68 Hz AC short circuit fault current over 3 cycles 5.8 Arms 5.8 Arms Maximum units per 20 A (L-L) branch circuit3 16 (240 VAC) 13 (208 VAC) 13 (240 VAC) 11 (208 VAC) Overvoltage class AC port III III AC port backfeed current 0 A 0 A Power factor setting 1.0 1.0 Power factor (adjustable) 0.85 leading ... 0.85 lagging 0.85 leading ... 0.85 lagging EFFICIENCY @240 V @208 V @240 V @208 V Peak efficiency 97.6 % 97.6 % 97.5 % 97.3 % CEC weighted efficiency 97.0 % 97.0 % 97.0 % 97.0 % MECHANICAL DATA Ambient temperature range Relative humidity range Connector type (IQ7-60-2-US & IQ7PLUS-72-2-US) Connector type (IQ7-60-B-US & IQ7PLUS-72-B-US) Dimensions (WxHxD) Weight Cooling Approved for wet locations Pollution degree Enclosure -400C to +65°C 4%to 100%(condensing) MC4 (or Amphenol H4 UTX with additional Q-DCC-5 adapter) Friends PV2 (MC4 intermateable). Adaptors for modules with MC4 or UTX connectors: PV2 to MC4: order ECA-S20-S22 PV2 to UTX: order ECA-S20-S25 212 mm x 175 mm x 30.2 mm (without bracket) 1.08 kg (2.38 Ibs) Natural convection - No fans Yes PD3 Class II double -insulated, corrosion resistant polymeric enclosure Environmental category / UV exposure rating NEMA Type 6 / outdoor FEATURES Communication Power Line Communication (PLC) Monitoring Enlighten Manager and MyEnlighten monitoring options. Both options require installation of an Enphase IQ Envoy. Disconnecting means The AC and DC connectors have been evaluated and approved by UL for use as the load -break disconnect required by NEC 690. Compliance CA Rule 21 (UL 1741-SA) UL 62109-1, UL1741/IEEE1547, FCC Part 15 Class B, ICES-0003 Class B, CAN/CSA-C22.2 NO. 107.1-01 This product is UL Listed as PV Rapid Shut Down Equipment and conforms with NEC-2014 and NEC-2017 section 690.12 and C22.1-2015 Rule 64-218 Rapid Shutdown of PV Systems, for AC and DC conductors, when installed according manufacturer's instructions. 1. No enforced DC/AC ratio. See the compatibility calculator at https://enphase.com/en-us/support/module-compatibility. 2. Nominal voltage range can be extended beyond nominal if required by the utility. 3. Limits may vary. Refer to local requirements to define the number of microinverters per branch in your area. To learn more about Enphase offerings, visit enphase.com u E N P H AS E © 2018 Enphase Energy. All rights reserved. All trademarks or brands used are the property of Enphase Energy, Inc. 2018-11-19 Data Sheet Enphase Networking Enphase IQ Commercial Envoy LISTED To learn more about Enphase offerings, visit enphase.com The Enphase IQ Commercial EnvoyTM gateway delivers solar production and energy consumption data to Enphase EnlightenT" monitoring and analysis software for comprehensive, remote maintenance and management of three-phase Enphase IQ Systems. With integrated production metering and optional consumption monitoring, the Envoy IQ is the platform for total energy management and integrates with the IQ MicroinvertersTm and Enphase IQ BatteryTM. Smart • Enables web -based monitoring and control • Bidirectional communications for remote upgrades • Supports power export limiting and zero - export applications Simple • Easy system configuration using Enphase Installer Toolkit'" mobile app • Flexible networking with Wi-Fi, Ethernet, or cellular Reliable • Designed for installation indoors or outdoors in an enclosure • Five-year warranty ENPHASE Enphase IQ Commercial Envoy MODEL NUMBERS Enphase IQ Commercial Envoy" Three-phase communications gateway with integrated PV production metering (+/- 0.5%) ENV-IQ-AM3-3P and optional consumption monitoring (+/- 2.5%). Includes three 200A continuous rated production CTs. ACCESSORIES (order separately) Enphase Mobile Connect- Plug and play industrial grade cellular modem with five-year data plan (expandable to CELLMODEM-M1 (4G LTE Category M1) 12 years) for systems up to 60 microinverters (expandable). Available in the US, Canada, CELLMODEM-M1-B (4G LTE Category M1) Mexico, Puerto Rico, and the US Virgin Islands, where there is adequate cellular service in the installation area. Consumption Monitoring CTs Split -core current transformers enable consumption metering. CT-200-SPLIT (order three or six, as needed) POWER REQUIREMENTS Power requirements 208Y/120 VAC three-phase 220Y/127 VAC three-phase Max 20 A overcurrent protection required Typical Power Consumption 5W CAPACITY Number of microinverters polled Up to 300 MECHANICAL & ELECTRICAL DATA Dimensions (WxHxD) 21.3 x 12.6 x 4.5 cm (8.4" x 5" x 1.8") Weight 17.6 oz (498 g) Ambient temperature range -40' to 65' C (-40° to 149° F) -40° to 46° C (-40° to 115* F) if installed in an enclosure Environmental rating IP30. For installation indoors or in an NRTL-certified, NEMA type 3R enclosure. Altitude To 2000 meters (6,560 feet) Production CTs Are limited to 200A of continuous current / 250A OCPD - 72kW AC Allow for parallel connected CTs for up to 500A - 144kW AC (if possible) Internal aperture measures 19.36mm to support 250MCM THWN conductors (max) Accuracy of +/-0.5% for production metering Consumption CTs For electrical services to 250A with parallel runs up to 500A Internal aperture measures 0.84" x 0.96" (21.33mm x 24.38mm) to support 3/0 THWN conductor CT wire insulation rating of 600V Accuracy of +/-2.5% for consumption monitoring INTERNET CONNECTION OPTIONS Integrated Wi-Fi 802.11b/g/n Ethernet 802.3, Cat5E (or Cat 6) UTP Ethernet cable, not included Mobile Optional, CELLMODEM-M1 (LTE), CELLMODEM-01 (3G), or CELLMODEM-03 (4G), not included COMPLIANCE Compliance UL 916 CAN/CSA C22.2 No. 61010-1 47 CFR, Part 15, Class B, ICES 003 IEC/EN 61010-1:2010, EN50065-1, EN61000-4-5, EN61000-6-1, EN61000-6-2 To learn more about Enphase offerings, visit enphase.com © 2021 Enphase Energy. All rights reserved. Enphase, the Enphase logo, IQ Commercial Envoy, and other trademarks or service names are the E N P H A S E trademarks of Enphase Energy, Inc. Data subject to change. 07-12-2021 `� Product Selection Product Selection Table 8-38. Safety Switch Catalog Numbering System Switch Type DP= General -Duty! Plug Fuse DG= General-Dutvi Cartridge Fuse DH = Heavy -Duty DT= Double Throw DR= Ratary Switch DS= Classified Location with DS Interior PolesfBlades 1 = 1-Pale 2= 2-Poles 3= 3-Poles 4= 4-Poles 6= 6-Poles "240 TTG 1 Ampates 1 = 3OAmps 2 = 6O Amps 3 = 100AMPS d= 20OAmps 5 = 400 Arnps 6 = 600 Arnps 7 = 800 Arnps S = 1200 Amps Fusiblefl4or -Fusible or Neutral F = Fusi b I@ wit h out Neutral U = Non -Fusible N= Fusiblewit h Neutral N U KLW NEMA Endosure Ratings G= NEMA 1 R = NEMA 3R D= NEMA 12or12MR P = NEMA 4 (Painted Steel) W = NEMA 4X Corrosion -Resistant (904 Grade Stainless Steel) C = NEMA 4){ Non -Metallic (for Type DH) X= NEMA7l9 +.for Type ❑S) X= NEMA4){ Non -Metallic (for Type DR) EiT* N February 2007 Options i W =_ = Up perViewing Window LW f=Lower Viewing Window X = EnviroLine Stainless (Enclosure and Mechanism) GCL = Mill -duty sores K= Design All General -Duty Switches Above 200Arnperes and All Heavy -Duty Switches Incorporate KSeries Switch Design Features Listed Below B= Design General -Duty 30 — 100 Amperes H = General -Duty Double Throw Switch (Compact Design 30 — 100 Arnperes) See Pagea&81through 9-11 for additional Flex Center options. Effective August 2002, 90— 100 ampere windowswitches are replaced byafull viewwindow which allows blade position verification and blown fuse indication. See Page B-37 forcatalog numbers. Nate: This table is intended for use in breaking down existing catalog numbers. It is not intended for building newcatalog numbers. E:T•N Product Selection 600 Vac Heavy -Duty, Non -Fusible, Single Throw Specifications ■ 30 - 1200 amperes. ■ Horsepower rated. ■ Suitable for service entrance use, except 1200 ampere on 480Y/277 or 600Y/347 grounded wye systems, per NEC 215-10 and 230-95, and 4-pole switches. ■ UL listed File No. E5239. ■ For factory modifications, refer to Pages 8-8 through 8-11. © Table 8-45. Non -Fusible 277/480 - 600 Volts DH362UGK February 2007 System Ampere Rating Maximum Horsepower Ratings NEMA 1 Enclosure Indoor NEMA 3R Enclosure Rainproof Single -Phase ac 3-Phase ac do Catalog Number Price U.S. $ Catalog Number Price U.S. $ 240 Volt 1 480 Volt F600 Volt 240 Volt 1 480 Volt 1600 Volt 250 Volt 1600 Volt 2-Pole — 480 Vac — 600 Vac or do O (Suitable for Service Entrance Use with a Neutral Kit Installed) 30 3 7-1/2 10 — — — — 15 DH261UGK DH261URK 60 10 20 25 — — — — 25 DH262UGK DH262URK 100 20 30 40 — 25 DH26UGK DH26URK 200 15 50 50 - _ — 50 DH264UGK DH264URK 400 50 DH265UGK DH265URK 600 — — — — — — — — DH266UGK DH266URK 800 — — — — — DH267UGK DH267URK 1200 1 — — — — — — I— — O — 3-Pole — 480 Vac — 600 Vac, 250 Vdc (Suitable for Service Entrance Use with a Neutral Kit Installed) 30 3 7-1/2 10 10 20 30 5 — DH361UGK DH361URK 60 10 20 25 20 50 60 10 — DH362UGK DH362URK 100 20 40 50 40 75 100 20 — DH363UGK DH363URK 200 15 50 50 60 125 150 40 — DH364UGK DH364URK q Ss 400 125 250 350 50 DH365UGK DH365URK 600 — — — 200 400 500 — — DH366UGK DH366URK 800 — — — — 500 500 — — DH367UGK DH367URK 1200 — — — — 500 500 — — DH368UGK DH368URK 4-Pole — 480 Vac — 600 Vac, 2-Phase ac 3-Phase ac 250 Vdc 30 10 20 25 10 20 30 5 — DH461UGK (A 60 20 40 50 20 50 60 10 — DH462UGK O 100 40 50 50 40 75 10 20 DH46UGK O 200 50 50 50 60 125 150 40 - DH464UGK OO 400 50 125 250 350 50 DH465UGK z s 600 200 400 500 — — DH466UGK z a 800 — — — — — — — — C2 z 3 O do rating for 400 - 800 ampere switches is 250 volts. (1) Contact the Safety Switch Flex Center (1-888-329-9272) for availability of this product. O NEMA 12 enclosures (30 - 1200 amperes) can be field modified to meet NEMA 313 rainproof requirements when a factory provided drain hole is opened. Discount Symbol ........................ 22CD For more information visit: www.eaton.com CA08101001 E E_T•N February 2007 Technical Data and Specifications Dimensions Note: Dimensions are for estimating purposes only. Table 8-31. Heavy -Duty, Non -Fusible, 600 Volt, 3-Pole, Single Throw Ampere NEMA 1, 311 NEMA 12, 4X Stainless Steel, 4 Rating Dimensions in Inches (mm) Weight Dimensions in Inches (mm) Weight Lbs (kg) Lbs (kg) Width I Height I Depth Depth Width I Height Depth Depth (W) (H) (D) (D2) (W) (H) (D) (D2) 30 8.13 15.88 10.00 5.25 16 8.13 12.13 10.00 5.50 17 (206.5) (403.4) (254.0) (133.3) (7.264) (206.5) (308.1) (254.0) (139.7) (7.718) 60 8.13 15.88 10.00 5.25 16 8.13 12.13 10.00 5.50 17 (206.5) (403.4) (254.0) (133.3) (7.264) (206.5) (308.1) (254.0) (139.7) (7.718) 100 11.13 21.69 10.00 5.25 22 11.13 24.00 10.25 5.50 28 (282.7) (550.9) (254.0) (133.3) (9.988) (282.7) (609.6) (260.4) (139.7) (12.712) 200 16.00 27.63 11.25 6.14 46 16.00 34.38 11.50 6.44 55 (406.4) (701.8) (285.8) (156.0) (20.884) 1 (406.4) (873.3) (292.1) (163.6) (24.97) 400 23.00 45.19 12.63 7.27 110 23.00 57.63 12.63 7.19 125 (584.2) (1147.8) (320.8) (184.7) (49.94) (584.2) (1463.8) (320.8) (182.6) (56.75) 600 24.00 52.70 14.25 8.95 135 24.00 63.00 14.25 8.88 167 (609.6) (1338.6) (362.0) (227.3) (61.29) (609.6) (1600.2) (362.0) (225.6) (75.818) 800 25.38 56.69 14.25 8.95 158 25.38 71.75 14.25 8.88 175 (644.7) (1439.9) (362.0) (227.3) (71.732) (644.7) 1 (1822.5) (362.0) (225.6) (79.45) 1200 41.47 70.31 19.94 12.44 430 41.47 70.31 1 19.94 1 13.51 475 (1053.3) (1785.9) (506.5) (316.0) (195.22) (1053.3) (1785.9) (506.5) (343.2) (215.65) Table 8-32. Heavy -Duty, Fusible, 240 Volt and 600 Volt, 3-Pole Solid Neutral, Single Throw Ampere NEMA 1, 311 NEMA 12, 4X Stainless Steel, 4 Rating Dimensions in Inches (mm) Weight Dimensions in Inches (mm) Weight Lbs (kg) Los (kg) Width Height Depth Depth Width Height Depth Depth (W) I (H) I (D) (D2) (W) I (H) (D) I (D2) 30 8.13 15.88 10.00 5.25 20 8.13 17.88 10.00 5.50 22 (206.5) (403.4) (254.0) (133.3) (9.08) (206.5) (454.2) (254.0) (139.7) (9.988) 60 8.13 15.88 10.00 5.25 20 8.13 17.88 10.00 5.50 22 (206.5) (403.4) (254.0) (133.3) (9.08) (206.5) (454.2) (254.0) (139.7) (9.988) 100 11.13 21.69 10.00 5.25 27 11.13 24.00 10.25 5.50 30 (282.7) (550.9) (254.0) (133.3) (12.258) (282.7) (609.6) (260.4) (139.7) (13.62) 200 16.00 27.63 11.25 6.14 52 16.00 34.38 11.50 6.44 61 (406.4) (701.8) 1 (285.8) (156.0) (23.608) (406.4) (873.3) 1 (292.1) (163.6) (27.694) 400 23.00 45.19 12.63 7.27 120 23.00 57.63 12.63 7.19 135 (584.2) (1147.8) (320.8) (184.7) (54.48) (584.2) (1463.8) (320.8) (182.6) (61.29) 600 24.00 52.70 14.25 8.95 153 24.00 63.00 14.25 8.88 203 (609.6) (1338.6) (362.0) (227.3) (69.462) (609.6) (1600.2) (362.0) (225.6) (92.162) 800 25.38 56.69 14.25 8.95 168 25.38 71.75 14.25 8.88 213 (644.7) (1439.9) (362.0) (227.3) (76.272) (644.7) (1822.5) (362.0) (225.6) (96.702) 1200 41.47 70.31 19.94 12.44 465 41.47 70.31 19.94 13.51 510 (1053.3) (1785.9) (506.5) (316.0) (211.11) (1053.3) (1785.9) (506.5) (343.2) (231.54) Figure 8-4. NEMA 1-313 Heavy -Duty 30 -1200 Amperes Figure 8-5. NEMA 4, U and 12 Heavy -Duty 30 -1200 Amperes CA08101001 E For more information visit: www.eaton.com Catalog numbering system—Pow-R-Stock panelboard interiors PRUA tPRL2A = PRL1a = PRL2a 1 = Single-phase 3 = Three-phase 100 = 100A 225 = 225A 400 = 400A EZB 20 36 R BS 1 225 X 42 A S X indicates no main/ use main breaker or main lug kit A = Aluminum bus C = Copper bus S = Short —no TFL or SFB provisions Special note: This option applies only to 42 circuit 225A interiors. Note: Top -feed provision for main lugs or main breaker, no provision for through -feed lugs or sub -feed breaker. EZB are available boxes used for all Type 1 PRL1a, PRL2a, and PRL3a panels Width in inches = 20 Height in inches = 36, 48, 60, or 72 R = Right-hand flange EZT 20 36 S EZT are available laser cut trims used on all PRL1a, PRL2a, and PRL3a panels Width in inches = 20 Height in inches = 36, 48, 60, or 72 Mounting S = Surface F = Flush BK ED 100 T Breaker kit Breaker frame ED or FD or KD Trip rating 100, 125 150, 175, 200, 225, 250, 300, 350, 400 Mounting T=Top B = Bottom 6 EATON CORPORATION www.eaton.com Pow-R-Stock Plus program reference guide Unassembled panelboards—EZ Box" and EZTrim" Catalog Numbers Maximum Interiors (Less Main Device) Boxes Trims (NEMA® 1) Ampere Number NEMA 3R Rating of Poles Aluminum Bus Copper Bus NEMA 1 Surface Flush Enclosures Single -Phase, Three -Wire, 120/240V 100 18 PRLIA110OX18A PRLlA1100X18C EZB2036R EZT2036S EZT2036F GWPBQ2036PR 100 30 PRL1A110OX30A PRLlA1100X30C EZB2048R EZT2048S EZT2048F GWPBQ2048PR 225 30 PRL1A1225X30A PRL1A1225X30C EZB2048R EZT2048S EZT2048F GWPBQ2048PR 225 42 PRL1A1225X42AS PRL1A1225X42CS EZB2048R EZT2048S EZT2048F GWPBQ2048PR 225 2 PRL1A1225X42A PRL1A1225X42C EZB206OR EZT2060S EZT206OF GWPBQ2060PR 42 PRU A1400X42A PRL1A1400X42C EZB2072R EZT2072S EZT2072F GWPBQ2072PR Three -Phase, Four -Wire, 208Y/120V 100 = 18 PRU A3100X18A I PRLlA310OX18CJ EZB2036R EZT2036S EZT2036F GWPBQ2036PR 100'30 PHLIA310OX30A PRL1A3100X30C EZB2048R EZT2048S EZT2048F GWPBQ2048PR 225 30 PRL1A3225X30A PRU A3225X30C EZB2048R EZT2048S EZT2048F GWPBQ2048PR 225 42 PRL1A3225L42AS PRL1A3225L42CS EZB2042R EZT2042S EZT2042F GWPB Q2042PR Note: The colors shown in the table 225 42 PRL1A3225X42AS PRL1A3225X42CS EZB2048R EZT2048S EZT2048F GWPBQ2048PR to the right correspond to the color- 225 42 PRL1A3225X42A PRL1A3225X42C EZB206OR EZT2060S EZT206OF GWPBQ2060PR coding on the trim, interior and box 400 42 PRUA3400X42A PRL1A3400X42C EZB2072R EZT2072S EZT2072F GWPBQ2072PR product packaging labels. Be sure that all three parts match when Three -Phase, Four -Wire, 480Y/277V delivering to your customer. 100 18 PRL2A3100X18A PRL2A3100X18C EZB2036R EZT2036S EZT2036F GWPBQ2036PR 100 30 PRL2A3100X30A PRL2A3100X30C EZB2048R EZT2048S EZT2048F GWPBQ2048PR 225 30 PRL2A3225X30A PRL2A3225X30C EZB2048R EZT2048S EZT2048F GWPBQ2048PR 225 42 PRL2A3225L42AS PRL2A3225L42CS EZB2042R EZT2042S EZT2042F GWPB Q2042PR 225 42 PRL2A3225X42AS PRL2A3225X42CS EZB2048R EZT2048S EZT2048F GWPBQ2048PR 225 42 PRL2A3225X42A PRL2A3225X42C EZB206OR EZT2060S EZT206OF GWPBQ2060PR 400 42 PRL2A3400X42A PRL2A3400X42C EZB2072R EZT2072S EZT2072F GWPBQ2072PR Summary of branch breakers available Breaker Poles Ampere Rating Voltage kAIC Rating Example Panel Type BAB 1 15-60 120V 10 BAB1020 PRL1A 2 15-100 120/240V 10 BAB2020 PRL1A 2 15-100 240V 10 BAB2040H PRL1A QBGF 3 1 15-100 15-30 240V 120V 10 10 BAB3030H QBGF1020 PRL1A PRL1A QBHW 2 1 15-40 15-60 120/240V 120V 10 22 QBGF2040 QBHW1020 PRL1A PRL1A 2 15-100 120/240V 22 QBHW2020 PRL1A 2 15-100 240V 22 QBHW2040H PRL1A 3 GHQ GHB 1 15-100 15-20 15-100 240V 277V 277V 22 14 QBHW3030H GHQ1020 GHB1020 PRL1A PRL2A PRL2A 2 15-100 480Y/277V 14 GH B2040 PRL2A 3 15-100 480Y/277V 14 GH B3060 PRL2A FITON Powering Business Worldwide Panelboards and Li2htin2 Control 10.3 Pow-R-Line C Panelboards Approximate Dimensions in Inches (mm) PRL2a Panelboard Sizing Main Breaker Types Sub -Feed Breaker Types Maximum No. of Box Dimensions 1' and Mounting Position and Mounting Position Branch Circuits YS Box LTTrim EZ Box EZ Trim Panelboard (H) = Horizontal (H)=Horizontal Including Catalog Catalog Catalog Catalog Types (V)=Vertical IV1=Vertical Provisions Height Width Depth Number Number Number Number 100A Main breaker BAB, QBHW - 15 36.00 (914.4) 20.00 (508.0) 5.75 (146.1) YS2036 LT2036S or F EZB2036R EZT2036S or F (H) - 27 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F 39 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F 42 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB206OR EZT2060S or F Main lugs or EHD - 18 36.00 (914.4) 20.00 (508.0) 5.75 (146.1) YS2036 LT2036S or F EZB2036R EZT2036S or F main breaker FD, HFD, FDE HFDE - 30 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F (V) - 42 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F Main lugs or main breaker EHD EHD 18 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048SorF EZB2048R EZT2048SorF through -feed with 1r OA sub -feed lugs orsub-feed breaker FD, FDE HFD, HFDE HFD 30 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F (V) (V) 42 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB206OR EZT2060S or F 225A Main lugs or EDB, EDS, ED, - 18 36.00 (914.4) 20.00 (508.0) 5.75 (146.1) YS2036 LT2036S or F EZB2036R EZT2036S or F main breaker EDH, FD, HFD FDE, HFDE - 30 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F (V) - 42 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F JD, HJD - 18 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F JDC (V) 30 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB206OR EZT2060S or F - 42 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F Main lugs or main breaker EHD, FD, HFD, EHD,FD, HFD, 18 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048SorF EZB2048R EZT20MorF with A through -feed EDB, EDS, ED, EDB, EDS, ED, lugs ors r sub -feed breaker EDH EDH (V) 30 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT20M or F FDE, HFDE 42 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB206OR EZT2060S or F (V) JD, HJD EHD, FD, HFD, 18 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB206OR EZT2060S or F JDC EDB, EDS, ED, (V) EDH (V) 30 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F 42 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F 400A Main lugs or DK, KD, HKD, - 18 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB206OR EZT2060S or F main breaker KDC, LHH (V) 30 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB206OR EZT2060S or F - 42 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F Main lugs or main breaker DK, KD, HKD, EHD,FD,HFD, 18 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060SorF EZB206OR EZT2060SorF A through -feed with r sub -feed breaker lugs ors KDC, LHH IV) EDB, EDS, ED, EDH IVI 30 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F 42 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F Main lugs or main breaker DK, KD, HKD, JD, HJD, JDC, 18 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072SorF EZB2072R EZT2072SorF with through -feed KDC, LHH DK, KD, lugs orsu or sub -feed breaker (V) HKD, KDC 30 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB209OR EZT2090S or F (V) 42 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB209OR EZT2090S or F Note 0 Smaller panelboard box sizes are available if required. Contact Eaton for application information Volume 2-Commercial Distribution CA08100003E-December 2010 www.eaton.com 391 ROOFMOUNT :eMUNIRAC ROOFMOUNT introduces the Power of Simplicity to the ballasted flat roof solar industry. The system consists of only two major components, minimizing preparation work and installation time. Seamlessly design around roof obstacles, support most framed modules and bond the system with just the turn of a wrench. ROOFMOUNT SIMPLE DESIGN TWO MAJOR COMPONENTS. ONE TOOL RM supports most framed PV modules at 10 degree tilt. The component list consists of only two major components -a fully assembled ballast bay and a universal module clip. Our engineers specified a chemical locking hex bolt, providing a UL2703 certified grounding path from module to ballast bay, with just the turn of a wrench. RM is accessory -rich to support your specific installation needs, because it was designed to conveniently work with off the shelf wire management products. A snap into place, membrane -friendly, rubber roof pad is also available as a low-cost option for roof protection. AVAILABILITY NATIONWIDE NETWORK Unirac maintains the largest network of stocking distributors for our racking solutions. Our partners have distinguished their level of customer support, availability, and overall value, thereby providingthe highest level of service to users of Unirac products. Count on our partners for fast and accurate delivery to meet your project needs. Visit Unirac.com for a list of distributors. INTEGRATED DESIGN TOOLS DESIGN, SAVE, AND SHARE YOUR ARRAY VISUALLY U-Builder is the most powerful streamlined design tool for your solar mounting project. Integrated with HelioScope's technology, U-Builder becomes a powerful online tool that streamlines the process of designinga code compliant solar mounting system. Key benefits allow you to quickly plan project sites, analyze design decisions, and simplify your workflow. You will enjoy the ability to share projects with customers; there's no need to print results and send to a distributor, just click and share. o BONDING&GROUNDING N MECHANICAL LOADING SYSTEM FIRE CLASSIFICATION :eM U N I RAC INTEGRATED BONDING CLIP UNIRAC CUSTOMER SERVICE MEANS THE HIGHEST LEVEL OF PRODUCT SUPPORT UNMATCHED EXPERIENCE 9 CERTIFIED QUALITY TECHNICAL SUPPORT Unirac's technical support team is dedicated to answering questions & addressing issues in real time. An online library of documents including engineering reports, stamped letters and technical data sheets greatly simplifies your permitting and project planning process. 1 1 X ENGINEERING EXCELLENCE BANKABLE WARRANTY CERTIFIED QUALITY PROVIDER Unirac is the only PV mounting vendor with ISO certifications for 9001:2008, 14001:2004 and OHSAS 18001:2007, which means we deliver the highest standards for fit, form, and function. These certifications demonstrate our excellence and commitment to first class business practices. a DESIGN TOOLS R1 PERMIT DOCUMENTATION BANKABLE WARRANTY Don't leave your project to chance, Unirac has the financial strength to back our products and reduce your risk. Have peace of mind knowing you are receiving products of exceptional quality. ROOFMOUNT is covered by a 20-year manufacturing warranty on all parts. PROTECT YOUR REPUTATION WITH QUALITY RACKING SOLUTIONS BACKED BY ENGINEERING EXCELLENCE AND A SUPERIOR SUPPLY CHAIN UNIRAC REPORT UNIRAC PROJECT TITLE PROJECT ID ROOFMOUNT RM10 5E6A6918 U-BUILDER PROJECT REPORT VERSION: 3.1.6 CREATED Oct. 21, 2021, 12:26 p.m. NAME Edmonds 99 Designed by sayali@pugetsoundsolar.com ROOFMOUNT RM10 ADDRESS 23400 HIGHWAY 99 REC SOLAR CITY, STATE Edmonds, WA 19 -REC365TP4 Black MODULE REC SOLAR REC365TP4 Black 373.26 ftz 6.94 KW NOTE: Installation of the project is intended to happen within the year of project designed in UBuilder. If it's past one year please rerun the design or contact Unirac Engineering Services. BILL OF MATERIALS LEGEND: ■ Base System Part ■ Accessory PART SUGGESTED NUMBER PARTTYPE DESCRIPTION QUANTITY QUANTITY User Ballast Block Ballast Block 127 Supplied 310710 Ballast Bay RM Ballast Bay 10 Degree 58 310760 RM Roof Pad RM Roof Pad 64 64 310750 Module Clip RM Module Clip 175 175 310751 RM Hex Bolt RM Hex Bolt (Module Clip) 175 175 This design is to be evaluated to the product appropriate Unirac Code Compliant Installation Manual which references International Building Code 2009, 2012, 2015, 2018 and ASCE 7-05, ASCE 7-10, ASCE 7-16 and California Building Code 2010, 2016. The installation of products related to this design is subject to requirements in the above mentioned installation manual. DETAILED PARTS DESCRIPTION Ballast Block UserSupplied Ballast Block Standard 4x8x16 inch cap blocks. Nationwide availability. Please confirm the weight of your ap ballast block as this will affect the total blocks required for your installation. Ballast Bay 310710 RM Ballast Bay 10 Degree Aluminum ballast bay attaches to north and south module edges (for 10 degree tilt installations) and provides ballast placement location. RM Roof Pad 310760 RM Roof Pad TPE 201-73 BK Santoprene Roof Pad. PLEASE NOTE: Depending on your roof type and seismic conditions, some quantity of roof pads may be required. These will be listed separately on your bill of materials. Module Clip 310750 RM Module Clip Aluminum clip fastens module frame to ballast bay and provides bonding path from module to bay to module. RM Hex Bolt 310751 RM Hex Bolt (Module Clip) Hex bolt with integrated locking patch. NOTE: Installation of the project is intended to happen within the year of project designed in UBuilder. If it's past one year please rerun the design or contact Unirac Engineering Services. an 127 41 64 175 175 ENGINEERING REPORT Plan review AVERAGE PSF TOTAL NUMBER OF MODULES TOTAL KW TOTAL MODULE AREA TOTAL WEIGHT ON ROOF RACKING WEIGHT MODULE WEIGHT BALLAST WEIGHT MAX BAY LOAD (DEAD) Loads Used for Design BUILDING CODE BASIC WIND SPEED GROUND SNOW LOAD SEISMIC (Ss) ELEVATION WIND EXPOSURE M RI RISK CATEGORY VELOCITY PRESSURE, QZ Loads Determined by Zip CITY, STATE BASIC WIND SPEED GROUND SNOW LOAD 8.49 psf 19 6.94 KW —602 ft2 5105 Ibs 203 Ibs 838 Ibs 4064 Ibs 208 Ibs ASCE 7-16 110.00 mph 25.00 psf 1.310 310.00 ft B 50 22.61 psf Edmonds, WA 93.00 mph 20.00 psf Inspection PRODUCT MODULE MANUFACTURER MODEL MODULE WATTS MODULE LENGTH MODULE WIDTH MODULE THICKNESS MODULE WEIGHT BALLAST BLOCK (CMU) WEIGHT MAX BLOCKS PER NORTH BAY MAX BLOCKS PER NON NORTH BAY BUILDING HEIGHT ROOF TYPE PARAPET HEIGHT RISK CATEGORY ROOFMOUNT RM10 REC SOLAR REC365TP4 Black 365 watts 69.10" 40.94" 1.20" 44.10 Ibs 32.0 Ibs 6 4 65.00 ft EPDM > 1 Array Height (> 12 inches) 11 Roof Area 1 - Array 1 AVERAGE PSF 8.49 psf MINIMUM SEISMIC SEPARATION (UNATTACHED ARRAYS) ARRAY TO ARRAY: 12.6" TOTAL NUMBER OF MODULES: 19 TO FIXED OBJECT ON ROOF: 25.2" TOTAL KW: 6.94 KW TO ROOF EDGE WITH QUALIFYING PARAPET: 25.2" TOTAL AREA: 602 ft2 TO ROOF EDGE WITHOUT QUALIFYING PARAPET: 50.4" TOTAL WEIGHT ON ROOF: 5105 lbs MAX ARRAY (SEISMIC) (FOR UNATTACHED ARRAYS) RACKING WEIGHT: 203 lbs MAX NUMBER OF NORTH -SOUTH ROWS: 6 MODULE WEIGHT: 838 lbs MAX NUMBER OF EAST -WEST COLUMNS: 14 BALLAST WEIGHT: 4064 lbs *See ASCE 7-16 Section 13.6.12 for more details RM10 U-BUILDER PRODUCT ASSUMPTIONS RM10 - Ballasted Flat Roof Systems Limitations of Responsibility: It is the user's responsibility to ensure that inputs are correct for your specific project. Unirac is not the solar, electrical, or building engineer of record and is not responsible for the solar, electrical, or building design for this project. Building Assumptions 1. Risk Category III 2. Building Height <- 50 ft 3. Building Height > 50 ft: only where (longest length of building x building height)A0.5 <- 100 ft 4. Roof Slope >- 00 (0:12) and <- 30 (5/8:12) for Seismic Design Category C, D, E and F. For low seismic regions Seismic Design Category A and B (provided Array Importance factor = 1.0), Roof Slope >- 0° (0:12) and <- 7° (1 1 /2:12). 5. Roofing Material Types: EDPM, PVC, TPO, or Mineral Cap 6. Surrounding Building Grade: Level Ballast Blocks The installer is responsible for procuring the ballast blocks (Concrete Masonry Units - CMU) and verifying the required minimum weight needed for this design. CMU should comply with ASM standard specification for concrete roof pavers designation (C1491 or C90 with an integral water repellent suitable for the climate it is placed. It is recommended that the blocks are inspected periodically for any signs of degradation. If degradation of the block is observed, the block should immediately be replaced. The CMU ballast block should have nominal dimensions of 4"x8"xl6". The actual block dimensions are 3/8" less than the nominal dimensions. Ballast blocks should have a weight as specified for the project in the "Inspection" section of this report. Design Parameters 1. Risk Category I to III 2. Wind Design a. Basic Wind Speed: 85-120 mph (ASCE 7-05)/110-150 mph (ASCE 7-10)/90-180 mph (ASCE 7-16) b. Exposure: B, C or D (ASCE 7-05/ASCE 7-10) c. 25 year Design Life/50 year Design Life for ASCE 7-16 d. Elevation: Insertion of the project at - grade elevation can result in a reduction of wind pressure. If your project is in a special case study region or in an area where wind studies have been performed, please verify with your jurisdiction to ensure that elevation effects have not already been factored into the wind speed. If elevation effects have been included in your wind speed, please select 0 ft as the project site elevation. e. Wind Tunnel Testing: Wind tunnel testing coefficients have been utilized for design of the system. 3. Snow Design a. Ground Snow Load: 0-80 psf (ASCE 7-10/ASCE 7-16) b. Exposure Factor: 0.9 c. Thermal Factor: 1.2 d. Roof Snow Load: Calculation per Section 7.3 (ASCE 7-05/ASCE 7-10/ASCE 7-16) e. Unbalanced/Drifting/Sliding: Results are based on the uniform snow loading and do not consider unbalanced, drifting, and sliding conditions 4. Seismic Design a. Report SEAOC PV1-2012/ASCE 7-16 SECTION 13.6.12 - Structural Seismic Requirements and Commentary for Rooftop Solar Photovoltaic Arrays b. Seismic Site Class: A, B, C, or D (ASCE 7-05/ASCE 7-10/ASCE 7-16) c. Importance Factor Array (Ip): 1.0 d. Importance Factor Building (le): 1.0 e. Site Class: D Properties 1. Bay Weight: -3.5 Ibs 2. Module Gaps (E/W) = 0.25 in 3. Bays: North row bays overhang the module by --19.5 inches. Module Properties 1. Module return flange: Minimum of 0.9in (when using 1-3/4 in. clip bolts) is required. 2. Module return flange: Minimum of 0.65in (when using 2 in. clip bolts) is required. Testing 1. Coefficient of Friction 2. Wind Tunnel 3. U L 2703 4. Component Testing (Bay and Clamp) Setbacks For the wind tunnel recommendations in U-Builder to apply, the following setbacks should be observed/followed for U-Builder wind design: 1. Modules should be placed a minimum of 3 feet from the edge of the building in any direction. 2. If the array is located near an obstruction that is 3.5 feet wide and 3.5 feet high or larger, the nearest module of the array must be located a distance from the obstruction that is greater than or equal to the height of the obstruction. Exception: When using ASCE 7-16 Building Code and using the obstruction feature in the module editor to accurately model the size and location of obstruction. 3. Installations within the setbacks listed above require site specific engineering2 4. The setbacks above are for wind. High seismic areas, fire access isles, mechanical equipment, etc., may require larger setbacks than listed above for wind. Site Specific Engineering Conditions listed below are beyond the current capabilities of U-Builder. Site specific engineering is required. 1. Wind designs for a project design life exceeding 25 years1/ASCE 7-16 2. Building assumptions and design parameters outside of U-Builder assumptions2 3. Attachments2 4. Risk Category III or IV projects (U-Builder can be adjusted for the correct wind, but not the seismic or snow design)2 5. Wind tunnel testing reduction factors are not permitted by the Authority Having Jurisdiction (AHJ)3 6. Seismic designs that fall outside SEAOC PV1-2012/ASCE 7-16 SECTION 13.6.12 recommendations (>3% roof slope, or AHJ's that require shake table testing or non -linear site -specific response history analysis)3 7. Signed and sealed site -specific calculations, layouts, and drawings3 Notes: 1 Please contact info@unirac.com. 2 Please contact EngineeringServices@unirac.com for more information. 3Please contact Theresa Allen with PZSE Structural Engineers at theresa@pzse.com. These items will require direct coordination with PZSE to complete the requested services. NOTE: Installation of the project is intended to happen within the year of project designed in UBuilder. If it's past one year please rerun the design or contact Unirac Engineering Services. INSTALLATION AND DESIGN PLAN Roof Area 1 / Roof Area 1 - Array 1 1 2 3 4 LEGEND J Module 9 2 3 4 5 6 Standard corner bay with CMU block count USupplemental bay with CMU block count NOTE Blocks above with values greater than 4 require extra ballast bays, except north -most bays which require extra bays for values greater than 6. The proper number of bays are provided in the Bill of Materials. The installer must install these extra bays as near to the indicated location as possible. Install 2 roof pads to every primary bay. Layout Dimensions NS DIMENSION - 21.56 ft EW DIMENSION - 34.68 ft ROW MODULES BAYS BALLAST BLOCKS (CMU) BALLAST WEIGHT(LBS) 1 6 13 37 1184 2 6 13 28 896 3 4 13 28 896 4 3 12 21 672 5 0 7 13 416