Loading...
REVIEWED BLD2021-0173+Energy_Calculations+1.29.2021_11.14.34_AM+2020613RECEIVED BLD2021-0173 Jan 29 2021201 5 Washington State Energy Lode Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 CITY OF EDMONDS DEVELOPMENTS RVICES Mechanical Summary MECH-SUMI 2015 Washington State Energy Code Com fiance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised January 2017 Project Information Project Title: GRE EDMONDS 99 Date 12/1/2020 Applicantlnformation. Provide contact information for individual who can respond to For Building Dept. Use inquiries about compliance form information provided. Company Name: Emerald Aire Inc. Company Address: 5108 D st. NW, Auburn, Washington 98001 Applicant Name: Kyle Bambauer Applicant Phone: (253) 329-6740 Project Description 0 New Building ❑ Building Addition ❑ Tenant Improvement ❑ System Retrofit ❑ No System Changes Briefly describe mechanical systems in the text box provided ❑ Total Bldg Performance (TBP) REVIEWED This path includes all mandatory BY provisions per C401.2 Option 2. CITY OF EDMONDS MECH-SUM, MECH-CHK, and C407 Energy Analysis forms required. 0 Load calculation summary ❑ MECH-LOAD-CALC Form Design Load Calculations Provide design load calculations for all mechanical systems and equipment serving the building heating, cooling or ventilating needs. If a load calculation summary is provided with the permit documents that includes all applicable compliance information then the MECH-LOAD-CALC form is not required. 0 Mechanical Plans ❑ MECH-EQ Forms (TBD) Mechanical Schedules Indicate location of equipment compliance information. If provided on plans then MECH-EQ forms are not required, however, include on plans all applicable compliance information listed in MECH-EQ tables. 0 DOAS is required per C403.6 effective July 1, 2017 (office, retail, education, library and fire station occupancies) All occupied, conditioned areas shall be served by a DOAS that delivers required ventilation air in a manner that does not require space conditioning fan operation. Space conditioning fans cycled off when no heating or cooling is required. Dedicated Outdoor Air 0 Ventilation provided via natural ventilation per 2015 IMC in lieu of DOAS (C403.6, Exception 1) System Requirements and ❑ Ventilation and space conditioning provided by a HEVAV system per C403.7 in lieu of DOAS (C403.6, Exception High Efficiency VAV ❑ DOAS included in project, although not required (occupancy not office, retail, education, library or fire station) Alternate 0 DOAS related allowances included in project: ❑ Prescriptive vertical fenestration maximum area allowance increased to 40% per C402.4.1.4 with 100% of conditioned floor area in building served by DOAS. 0 Exception to air economizer per C403.3 Exception 1, include MECH-ECONO form. 0 Project includes HVAC air distribution systems that provide heating and/or cooling If yes, provide a MECH-FANSYS -SUM form. Fan Power ❑ For one or more systems, the total fan motor nameplate hp of all fans in HVAC system exceeds Shp. If yes, provide a seperate MECH-FANSYS form for each HVAC system exceeding the 5 horsepower threshold. Refer to Section C403.2.11 and MECH-FANSYS-DOC for requirements and exceptions. ElHydronic chilled water ElWater-loopheat pump 0 No hydronic systems HVAC Hydronic Systems ❑ Hydronic heating water ❑ Geothermal ❑ C406.2 More efficient HVAC equipment and fan systems Requires 90% of heating and cooling capacity to be equipment listed in tables C403.2.3(1)-(9) or air -to -water heat pumps and heat recovery chillers. All equipment listed in tables C403.2.3(1)-(7) must be 15% more efficient than C406 Additional minimum requirements. All stand alone supply, return, and exhaust fans over 1hp must have FEQ >_ 71 and must be selected within 10% of maximum total or static pressure. Efficiency Options - ❑ C406.6 Dedicated outdoor air system (DOAS) Mechanical Requires 90% of conditioned floor area to be served by a DOAS per C403.6 that delivers required ventilation air in a manner that does not require space conditioning fan operation. ❑ C406.7 Reduced energy in service water heating Requires 90% of floor area be in occupancy types listed in C406.7.1 and that 60% of annual hot water energy use be provided by heat pump, waste heat recovery or solar water -heating systems. 2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 Mechanical Summary, • • 2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised January 2017 Equipment Type (s) ❑ Hot water heating tank(s) ❑ Instantaneous 0 No service water systems Service Water Heating Systems El Dedicated boiler ❑ Heat exchange from space heat boiler or central hot water/steam Distribution Type (s) ❑ Circulation System ❑ On -demand Commissioning Commissioning is required for: 0 Mechanical systems per C408.2 ❑ Service water heating systems per C408.4 If required, commissioning shall be performed for all applicable systems regardless of individual equipment capacity. Exceptions to commissioning requirements: ❑ Total output capacity of all mechanical space conditioning systems in the building do not exceed 240,000 Btu/h cooling or 300,000 Btu/h heating. Mechanical systems commissioning not required. ❑ Capacity of largest service water heating system in building does not exceed 200,000 Btu/h. Service water heating systems commissioning not required. Low Energy and Semi -Heated Spaces (Note 6 and 7) Peak Space Heating Cooling Conditioning Space Area Served, Capacity, Btu/h Capacity, Btu/h Capacity, Compliance Type Location in Plan(s) Space(s) Served square feet (Note 4) (Note 5) Btu/h-sf Check Notes Note 4 - Provide total installed heating output capacity of systems serving Low Energy or Semi -Heated space(s) in btuh. Note 5 - Provide total installed cooling capacity of system serving Low Energy space(s) in Btu/h. Not allowed for semi -heated spaces. Enter 0 if no cooling. Note 6 - Refer to Section C402.1.1 Low Energy Building. Intalled peak space conditioning capacity, heating or cooling, may not exceed 3.4 Btu/h'sf. Note 7 - Refer to Section C402.1.1.1 and Semi -Heated Space definition in Chapter 2. Total heating output capacity may not exceed 8 Btu/h'sf. Only systems without electric resistance heating and no cooling are eligible for the wall insulation exception under semi -heated. 2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 5 of 20 2015 Washinaton State Enerav Code Compliance Forms for Commercial Buildinas includina R2 & R3 over 3 stories and all R1 Revised January 2017 Project Title: GREEDMONDS99 Date 12/1/2020 The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the Washington State Energy Code, Commercial Provisions. Applicable Code Section Code Provision Information Required - Must be in permit documents Location in Building Department es no na Documents Notes Equipment - Sizing, Performance and Type Identify equipment to be used in manufacturing, industrial or commercial processes that do not M0.04 Yes C403.1 Exempt process equipment provide space conditioning; identify provisions applicable to this equipment per C403.1 exception Provide load calculations performed per ASHRAE Std 183 or equivalent, using design M0.01- Yes C403.2.1 Load calculations parameters per C302 and Appendix C; include load adjustments to account for energy M0.03 recovery Equipment and system Indicate that output capacities of heating and cooling equipment and systems are no greater M0.04 Yes C403.2.2 than the smallest available equipment size that exceeds the calculated loads; note exceptions sizing taken Provide equipment schedules on plans or complete MECH-EQ forms indicating type, capacity, M0.04 C403.2.3 HVAC equipment rated and WSEC minimum efficiencies for all heating and cooling equipment; include supply Yes C40 3.2 performance requirements and OSA cfms and operating hours for all air systems; identify heating and cooling equipment C403.2. 2.13.1 (efficiency) that does not have a corresponding WSEC minimum efficiency (manufacturer rated) List all motors z 1/12 hp (that are not integral to a rated piece of equipment) in the mechanical M0.04 C405.8 or electrical equipment schedules on plans; indicate hp, rpm, number of poles and rated Yes C403.2.14 Electric motor efficiency efficiency, or exception applied For fractional hp motors (1/12 - 1 hp), indicate whether they are an electronically commutated motor, have rated efficiency of at least 70% or exception taken For all HVAC fan systems that provide heating and / or cooling, provide system total nameplate hp in MECH-FANSYS-SUM form For all applicable HVAC systems with total fan motor hp > 5hp, verify fan system motor hp or Yes C403.2.11.1 Fan power limitation bhp complies with fan power limits per equations in Table C403.2.11.1(1), provide MECH- FANSYS form for each system Yes C403.2.11.2 Motor nameplate hp For all applicable HVAC systems with total fan motor hp > 5hp, indicate fan motors specified are the smallest available motor hp size greater than fan bhp, note exceptions taken For all applicable HVAC systems with total fan motor hp > 5hp, identify in equipment schedule Yes C403.2.11.3 Fan efficiency all fans required to comply with fan efficiency grade and indicate rated FEG is >_ 67, or exception taken; indicate these fans are sized so total efficiency is within 15 /o of the fan maximum total efficiency Yes C403.2.11.4 Group R occupancy exhaust For all exhaust fans < 400 cfm in Group R occupancies, indicate in equipment schedule the Mo.1 fan efficacy fan flow rate and efficacy cfm/wattor exception taken; refer to Table C403.2.11.4 CE-57 For fan motors z 7.5 hp, indicate method of variable flow control (VSD or equivalent method) in NA C403.2.13 Variable flow capacity - equipment schedule, or exception taken; for equivalent method for an HVAC system refer to fans HVAC S stem Controls for additional requirements Maximum air cooled chiller For chilled water plants and buildings with > 500 tons of cooling capacity, indicate air-cooled NA C403.2.3 chiller capacity is s 100 tons, or exception taken _capacity Large capacity cooling For buildings with z 300 tons of cooling capacity, indicate method of multi -stage or variable NA C403.4 o capacity control (VSD, multiple staged compressors, or max capacity of any single unit < 66 /o systems of the total Non-standard water-cooled For water-cooled centrifugal chillers not designed for operation at standard conditions, provide NA C403.2.3.1 centrifugal chillers calculations documenting maximum full load and part load rated equipment performance requirements C403.2.13.1 Centrifugal fan open -circuit For open -circuit centrifugal fan cooling towers with z 1,100 gpm capacity, indicate cooling NA C403.4.3.2 cooling towers towers comply with efficiency requirements for axial fan open circuit cooling towers For single boilers with > 500,000 Btu/h capacity, indicate multi -stage or modulating burner NA C403.4.2 Large capacity boiler For boiler system (single or multiple) with > 1,000,000 Btu/h capacity, indicate turndown ratio C403.4.2.5 systems per Table C403.4.2.5 and method (multiple single input boilers, modulating boilers, or combination Variable flow capacity - For pump motors >_ 7.5 hp, indicate method of variable flow control (VSD or equivalent method) C403.2.13 in equipment schedule, or exception taken; for equivalent method for a hydronic system refer pumps to H dronic System Controls for additional requirements NA C403.2.3 Gas and oil -fired forced air For forced air furnaces with capacity >_ 225,000 Btu/h and all unit heaters, indicate in furnace and unit heaters equipment schedule intermittent ignition or IID flue or draft damper, and rated 'acket loss NA C403.2.4.8 Combustion heating For combustion heating equipment with output capacity > 225,000 Btu/h, indicate modulating equipment or staged combustion control Yes C403.2.3.3 Packaged electric heating / Verify all packaged electric equipment with > 6,000 Btu/h cooling capacity and any amount of M0.04 cooling equipment heating is a heat um • include in equipment schedules NA C403.2.12 Heating outside a building Indicate systems providing heating in non -enclosed outdoor occupied spaces are radiant systems; refer to HVAC System Controls for additional requirements Yes C403.2.7.1 Kitchen exhaust hoods Indicate on plans the type, duty and exhaust air rate of each kitchen hood, refer to HVAC M0.04 S stem Controls for additional requirements Outdoor supply air, exhaust Indicate locations of OSA intake, and exhaust and relief outlet dampers on plans; indicate M0.04 Yes C403.2.4.3 and relief dampers `Whether dampers are Class 1 motorized, or gravity and exception taken (include leakage rating, cfm/s ; refer to HVAC System Controls for additional requirements for OSA dampers Indicate locations of return air dampers that are integral to economizer operation; verify M0.04 Yes C403.2.4.3 Return air dampers dampers are motorized; indicate whether dampers are Class 1, or within packaged equipment eligible for leaks a rating exception include leakage rating, cfm/s Yes C403.2.4.3 Stairway and shaft vent Indicate location of stairway and shaft vent dampers on plans; verify dampers are Class 1 M0.04 dampers motorized; refer to HVAC System Controls for additional requirements For systems serving areas > 25,000 sf or spanning more than one floor, that include areas that NA C403.2.4.4 Zone isolation dampers are expected to be occupied non -simultaneously; identify isolation zone areas on plans and locations of associated isolation dampers in HVAC distribution system; refer to HVAC System Controls for additional requirements For cooling systems with humidification equipment that are also required to have air NA C403.2.3.4 Humidification economizer, indicate humidifier is adiabatic (direct evaporative or fog atomization), or exception taken 2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 6 of 20 2015 Washinaton State Enerav Code ComDliance Forms for Commercial Buildinas includina R2 & R3 over 3 stories and all R1 Revised January 2017 Project Title: GREEDMONDS99 Date 12/1/2020 The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the Washington State Energy Code, Commercial Provisions. Applicable Code Section Code Provision Information Required - Must be in permit documents Location in Building Department es no.na Documents Notes Additional Efficiency Package Option, More Efficient HVAC Equipment & Fan Performance - Must comply with all 3 provisions to be eligible C406.2.1 To comply with additional efficiency package option, calculate the percentage of heating and NA C403.2.3 HVAC system selection cooling equipment in the project (based on output capacity) that do not have a corresponding WSEC listed efficiency; shall be less than 10% to comply NA C406.2.2 Minimum equipment To comply with additional efficiency package option, indicate that all listed heating and cooling C403.2.3 efficiency equipment have a rated efficiency that exceeds WSEC listed efficiency by at least 15% C406.2.3 To comply with additional efficiency package option, indicate rated FEG of stand alone fans is NA C403.2.11.3 Minimum fan efficiency >_ 71; indicate these fans are sized so the fan efficiency at design conditions is within 10% of h maximum total or static efficiency HVAC System Controls Indicate locations of thermostatic and humidity control devices and the zones they serve on plans, including perimeter system zones Where adjacent (neighboring) zones are controlled by separate thermostats (including perimeter systems used to offset heat gain or loss), and are connected by permanent Thermostatic controls openings > 10% of either zone sf area, indicate controls configured to prevent adjacent zones Yes C403.2.4.1 (thermostats and from operating in conflicting modes (one in heat, other in cool); applies to adjacent perimeter humidistats) zones, adjacent nonperimeter zones, and adjacent perimeter and nonperimeter zones If applying Exception 2 to nonperimeter zones adjacent to perimeter zones, indicate that setpoints and deadband settings in these zones are coordinated so cooling in a nonperimeter zone does not occur until the temperature in that zone is 5°F higher than the adjacent perimeter zone temperature in heating Yes C403.2.4.1.1 Heat pump supplementary Indicate staged heating operation with compression as the first stage of heating and M0.04 heat supplemental heating controlled with outdoor lock -out temperature set to 40oF or less NA C403.2.4.1.2 Deadband Indicate zone thermostatic controls configured with 5°F minimum deadband for systems that control both heating and cooling If separate heating and cooling systems with separate thermostatic control devices are used to Setpoint overlap restriction serve a zone, indicate locations of both thermostatic control devices and the zone they serve NA C403.2.4.1.3 (thermostats) on plans Indicate a limit switch, mechanical stop or DDC control with programming to prevent simultaneous heating and cooling C403.2.4.2 Automatic setback and Indicate zone thermostatic controls configured with required automatic setback and manual NA C403.2.4.2.1 shutdown override functions, setback temperatures, and control method (automatic time clock or C403.2.4.2.2 programmable controls); note exceptions taken NA C403.2.4.2.3 Automatic (optimum) start Indicate system controls that adjust equipment start time required to bring each area served 'ust u to desi n tem erature prior to scheduled occupancy Yes C403.2.4.3 Outdoor supply air dampers Indicate automatic controls configured to close OSA damper during unoccupied equipment M0.04 operation; not including economizer cooling,night flush or IMC required OSA / exhaust Yes C403.2.4.3 Stairway and shaft vent Indicate method of activation of stairway and shaft vent dampers (fire alarm or interruption of damperspower) For systems serving areas > 25,000 sf or spanning more than one floor, that include areas that Yes C403.2.4.4 Zone isolation controls are expected to be occupied non -simultaneously; indicate controls that allow for independent space conditionin of isolation zones; or exception taken NA C403.2.12 Heating outside a building Indicate occupancy sensing or timer switch controls configured to automatically shut off heatina s stem when area served is unoccupied NA C403.2.4.5 Snow melt systems Indicate automatic controls configured to shut off system when pavement temperature exceeds 50°F and no precipitation is falling, and when outdoor air temperature exceeds 40°F NA C403.2.4.6 Freeze protection system Indicate automatic controls to shut off system when outdoor temperature exceeds 40°F, or controls conditions protect fluid from freezing Group R1 hotel / motel For hotels and motels with over 50 guest rooms, indicate automatic controls serving guest NA C403.2.4.9 guest rooms rooms that are capable of setback (heating) and set-up (cooling) of temperature setpoint by at least 5°F; indicate control method - activated by room entrV or occupancy sensor 2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 7 of 20 2015 Washinaton State Enerav Code ComDliance Forms for Commercial Buildinas includina R2 & R3 over 3 stories and all R1 Revised January 2017 Project Title: GREEDMONDS99 Date 12/1/2020 The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the Washington State Energy Code, Commercial Provisions. Applicable Code Section Code Provision Information Required - Must be in permit documents Location in Building Department es no na Documents Notes C403.2.4.10 Group R2 / R3 dwelling For primary space conditioning system, indicate 5-2 programmable thermostats capable of two NA C403.2.4.11 units, Group R2 sleeping setback periods per day; for all thermostats indicate purpose (heating only, cooling only, or units both), required temperature range and at minimum a 10°F deadband; or exception taken Indicate method of ventilation air delivery (natural or mechanical) for each zone If mechanically delivered, indicate that systems are configured to provide not more than 150% M0.2 Yes C403.2.6 Ventilation of, but at least the minimum required volume of outdoor air to each zone per IMC, ASHRAE C403.2.11.4 62.1 or other applicable code (WAC, OSHA, etc); or exception taken If delivered via natural ventilation, identify required elements per IMC including minimum o enable area to the outdoors or qualifying adloining spaces Identify spaces > 500 sf with occupant load > 25 people/1,000 sf per IMC; for each space Demand controlled indicate whether it is served by an HVAC system with total design OSA > 3,000 cfm, and / or NA C403.2.6.2 ventilation the system has airside economizer or automatic modulating OSA damper; indicate OSA controls are configured to provide demand controlled ventilation or provide supporting documentation for applied exception For gyms, classrooms, auditoriums and conference rooms > 500 sf, indicate occupancy -based M0.04 Yes C403.2.6.3 Occupancy sensors OSA control when space is unoccupied and method (closes OSA damper or shuts -off equipment); or alternate means provided to automatically reduce OSA when space is partially occupied C403.2.6.4 Enclosed loading dock For enclosed loading docks, indicate ventilation / exhaust system method of activation (gas NA C403.2.6.4.1 ventilation detection system for CO and NO2, or occupancy sensors), and control method (staged or modulating) Yes C403.2.6.4 Enclosed parking garage For enclosed parking garages, indicate ventilation / exhaust system activated by gas detection M0.04 C403.2.6.4.2 ventilation system for CO and NO2, and control method (staged or modulating); or exception taken Provide calculations that show a balanced accounting of total kitchen exhaust (include all hoods) with % of: supply air, transfer air from adjacent spaces, and make-up air; ff applicable, NA C403.2.7.1 Kitchen exhaust hoods indicate that direct make-up air to each hood does not exceed 10% of hood exhaust For kitchens with total hood exhaust exceeding 2,000 cfm, indicate exhaust air rate per Table C403.2.7.1 and compliance method (DCV, energy recovery, or transfer air that would otherwise be exhausted NA C403.2.7.2 Laboratory exhaust systems Refer to Systems Requiring Energy Recovery for requirements Variable flow capacity - For HVAC fan motors >_ 7.5 hp, indicate method of variable flow control (VSD, or equivalent NA C403.2.13 HVAC system fans control method that reduces design air volume by 50 /o at 1/3 static design pressure); note exception taken DX air handler variable For DX air handlers with economizer and cooling capacity >_ 65,000 Btu/h, indicate number of cooling control cooling stages provided and method (multiple compressors and / or variable speed NA C403.3.1 (Under Integrated compressors); indicate minimum displacement (capacity reduction) as % of full load Indicate control method (cooling capacity controlled in response to space temperature, space Economizer) temperature controlled by modulating supply airflow, or both For DX air handling units with cooling capacity z 65,000 Btu/h and evaporative and chilled water air handling units with fan >_ 0.25 hp, indicate whether system is single zone or multiple zone and related control method (cooling capacity controlled in response to space temperature, space temperature is controlled by modulating supply airflow, or both) For mechanical cooling systems (includes DX and chilled water coils) that control cooling capacity in response to space temperature - Provide a minimum of two stages of fan control; NA C403.2.11.5 Fan airflow control indicate minimum fan speed is 5 66% of full speed drawings 40% of full speed fan power during periods of low cooling or ventilation only For other mechanical cooling systems (includes DX and chilled water coils) that control space temperature by modulating airflow (in lieu of, or in addition to, controlling capacity in response to space temperature) - Provide fan controls for modulating supply airflow; indicate minimum fan speed is 5 50% of full speed drawing 5 30% of full speed fan power during periods of low lcooling or ventilation only; or exception taken Provide central and zone level DDC controls as required based on system application, NA C403.2.4.12 DDC system capabilities capacity or size thresholds and other qualification per Table C403.2.4.12.1 Identify all DDC system input / output control points; indicate capability for trending and graphical display Ducting Systems C403.2.8.1 Indicate on plans that all ductwork is constructed and sealed per IMC M0.0 Yes C403.2.8.3 Duct construction For OSA ductwork, also indicate on plans that ductwork meets air leakage requirements per C402.5 and va or retarder requirements per the IBC M0.0 No C403.2.8.3 Duct pressure classifications Identify location of low, medium and high pressure ductwork on plans NA C403.2.8.3.3 High pressure duct leakage Indicate high pressure duct leakage testing requirements on plans; provide test results to test ruriscliction when completed 2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 8 of 20 2015 Washinaton State Enerav Code ComDliance Forms for Commercial Buildinas includina R2 & R3 over 3 stories and all R1 Revised January 2017 Project Title: GREEDMONDS99 Date 12/1/2020 The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the Washington State Energy Code, Commercial Provisions. Applicable Code Section Code Provision Information Required - Must be in permit documents Location in Building Department es no na Documents Notes For supply and return ductwork located in unconditioned space or outdoors, indicate R-value of insulation on ductwork on plans; identify climate zone; note exceptions taken 1 B/M2.2A For supply ductwork located in conditioned space, identify if design supply temperature is < C403.2.8.1 Yes C403.2.8.2 Duct insulation 55°F or> 105°F and indicate R-value of insulation on this ductwork on plans; note exception taken For OSA ductwork, shafts and plenums, indicate R-value of insulation on these elements on plans ber Table C402.1.3 for steel -framed walls: note exce tion taken M0.0 Piping Systems NA C403.2.9 Piping insulation p g Indicate design temperature range of fluid conveyed in piping and thickness of insulation (in inches) on h dronic piping plans; or exception taken NA C403.2.9.1 Piping insulation exposed to Indicate method of protection of pipe insulation from damage / degradation on hydronic piping weather 1plans Economizers Identify in equipment schedules on plans or in MECH-EQ forms all cooling systems requiring air economizer controls M0.04 Yes C403.3 Air economizer required Provide MECH-ECONO form indicating systems utilizing air economizer exceptions, including those with water -side economizer in lieu of air economizer; indicate on plans eligible exception(s) taken and measures to comply with exception(s) M0.04 NA C403.3.1 Integrated economizer Indicate air and water -side economizers are configured for partial cooling operation even Operation - air and water where additional mechanical cooling is required to meet the load NA C403.3.2 Economizer heating system Verify control method of HVAC systems with economizers does not increase building heating impact - air and water energy usage during normal operation NA C403.3.3.1 Air economizer capacity Indicate modulating OSA and return air dampers are configured to provide up to 100% OSA for cooling Verify mechanical cooling controls are interlocked with air economizer controls so the outside C403.3.1 air damper remains in 100% open position when mechanical cooling is also required to meet NA C403.3.3.2 Integrated air economizer the coolinq load, until the leavinq air temperature is < 45°F For systems with cooling capacity z 65,000 Btu/h, verify that control of economizer dampers is not based only on mixed air temperature; or exception taken NA C403.3.3.3 Air economizer high limit Indicate high limit shut-off control method and required high limit per Table C403.3.3.3 controls For eligible systems where water -side economizer may be provided in lieu of air economizer, NA C403.3.4.1 Water economizer capacity indicate system is capable of 100% design cooling capacity at 50oF db / 45°F wb OSA temperatures NA C403.3.4.2 Water economizer Indicate pressure drop across precooling coils and heat exchangers in water economizer maximum pressure drop system do not exceed pressure drop limit NA C403.3.1 DX air handling equipment For DX air handlers with economizer and cooling capacity >_ 65,000 Btu/h, refer to HVAC control System Controls for requirements DX equipment economizer For DX air handlers with economizer and cooling capacity >_ 54,000 Btu/h, provide a fault NA C403.2.4.7 fault detection and detection and diagnostics (FDD) system to monitor economizer system operation and report dia nostics faults Systems Requiring Energy Recovery For systems with design OSA > 5,000 cfm, or design supply air cfm and % OSA exceeding the values in Tables C403.5.1(1) or (2), indicate exhaust air ER method; or exception taken with Energy recovery (ER) - supporting calculations For rooms served by multiple systems with aggregate design OSA > 5,000 cfm, or aggregate Yes C403.5.1 ventilation / exhaust systems design supply air cfm and % OSA exceeding the values in Tables C403.5.1(1) or (2), indicate exhaust air ER method; or exception taken with supporting calculations Indicate ER rated effectiveness that increases OSA enthalpy by >_ 50% based on delta between OSA and return air enthalpies at design conditions M0.04 Laboratory exhaust systems For buildings with total lab exhaust > 5,000 cfm, indicate method of energy recovery used to NA C403.2.7.2 (energy recovery) pre -condition laboratory make-up air; ER effectiveness (min 25°F); or alternative method per exception (VAV exhaust semi -conditioned makeup, or CERM calculation For buildings with pools or spas with water surface area > 200 sf, indicate exhaust air ER C404.10.4 Pools and permanent spas method and use of waste heat (preheat ventilation air, pool water or service hot water); or NA (under exhaust systems exception taken Indicate ER system has the rated effectiveness and is configured to decrease the exhaust air C404.11) (energy recovery) temperature at desi n conditions by >_ 36°F Energy recovery - For buildings with on -site steam heating systems, indicate condensate water ER For buildings that use off -site generated steam where condensate is not returned to the NA C403.5.2 steam condensate systems source indicate on -site condensate water ER 2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 9 of 20 2015 Washinaton State Enerav Code ComDliance Forms for Commercial Buildinas includina R2 & R3 over 3 stories and all R1 Revised January 2017 Project Title: GREEDMONDS99 Date 12/1/2020 The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the Washington State Energy Code, Commercial Provisions. Applicable Code Section Code Provision Information Required - Must be in permit documents Location in Building Department es no na Documents Notes For buildings with food service, meat or deli departments that have >_ 500,000 Btu/h of remote refrigeration capacity for coolers / freezers, indicate condenser ER and use of captured energy (service water heating, space heating, or dehumidification reheating) NA C403.5.3 Energy recovery - For buildings with >_ 40,000 sf conditioned floor area and with >_ 1,000,000 Btu/h of remote cooler / freezer condensers refrigeration capacity for coolers / freezers, indicate condenser ER and use of captured energy for service water heating and also for space heating, or dehumidification reheating For buildings with 24-hour operation and with > 1,500,000 Btu/h of heat rejection capacity and NA C403.5.4 Energy recovery - design service hot water load > 250,000 Btu/h, indicate condenser ER to pre -heat service condenser systems water; or exception taken. Provide calculations showing the amount of recovered heat that is utilized ° fpeak heat relection load or pre -heat rvi water to 85'Fl. Hydronic System Controls For hydronic system pump motors z 7.5 hp, indicate method of variable flow control (VSD or C403.2.13 Variable flow control - equivalent method that requires >_ 30% design wattage at 50% design fluid flow); note NA C403.4.2.7 hydronic system pumps exception taken Identify whether hydronic coils have DDC controls and associated manner of pump speed control differential pressure, zone hydronic demand etc For boilers that provide building heating, indicate controls that provide heating water temperature setback based on outdoor temperature For heating and chilled water systems >_ 300,000 Btu/h, indicate systems are configured to C403.2.5 Hydronic system setback automatically reset supply water temperature based upon demand; or exception taken. NA C403.4.2.4 and part load controls If system pump motor hp z 3 hp, also indicate controls automatically reduce flow by z 50%. For chilled water systems (z 300,000 Btu/h, pump motor hp t 3 hp) that serve water-cooled unitary air conditioners, indicate VSD or staged pumps in chilled water system and heat rejection loop that reduce pump flow so that one control valve is nearly wide open, or to maintain a minimum differentialpressure; or exception taken NA C403.4.2 Boiler sequencing Indicate automatic controls that sequence operation of multiple boilers NA C403.4.6 Hot gas bypass limitation For cooling equipment with hot gas bypass, provide either multiple step unloading or continuous capacity modulation; indicate bypass capacity er Table C403.4.6 NA C403.4.2.2 Two -pipe changeover Indicate changeover deadband (min 15°F), heating / cooling mode scheduling and systems changeover temperature range limit 30°F NA C403.4.2.6 Chiller / boiler plant pump Indicate controls are configured to automatically reduce overall plant flow and shut-off flow isolation through individual chillers and boilers when not in use For cooling towers with fan motors >_ 7.5 hp, indicate VSD and method to adjust fan speed C403.2.13.1.1 Heat rejection equipment - (adjusted based on leaving fluid temperature or condenser temperature / pressure of heat NA C403.4.3.1.1 variable flow control refection device) For multiple -cell heat rejection equipment with VSD, indicate controls that ramp all fans in C403.4.3.1.2 unison NA C403.4.3.3 Heat rejection equipment - Indicate open -circuit cooling towers with multiple pumps or VSD control are designed so all cooling tower flow turndown cells can be run in parallel NA C403.4.2.3.1 Water loop heat pump - Indicate capability of central equipment to provide minimum 20°F water supply temperature deadband deadband between heat rejection and heat addition modes; or exception taken NA C403.4.2.3.2.1 Water loop heat pump - heat Indicate type of cooling tower (open- or closed-circuit) in equipment schedule; indicate method rejection equipment, Zone 4 used to limits stem heat loss when heat rejection is not needed NA C403.4.2.3.2.2 Water loop heat pump - heat For open- or closed-circuit cooling towers, provide a heat exchanger that separates the cooling rejection equipment, Zone 5 tower and heat pump loop NA C403.4.2.3.3 Water loop heat pump - For hydronic heat pump systems with total system power > 10 hp, indicate 2-way isolation isolation valves valves on each heat pump and variable flows stem control Dedicated Outdoor Air Systems (DOAS) - Optional through 6/30/16, Prescriptive 7/1/2016 For buildings with office, retail, education, library and fire station spaces, identify these spaces No C403.6 Dedicated outdoor air on plans; indicate that ventilation air in each occupied space is provided via a DOAS system; C403.6.3 systems or document compliance with C403.6.3 Impracticality; or exception taken (buildings complying with C402.4.1.4 or C406.6 maV not utilize exceptions) Energy recovery ventilation For all DOAS systems, indicate exhaust air ER method; or exception taken with supporting Yes C403.6.1 with DOAS calculations. Indicate ER rated effectiveness that increases OSA enthalpy by >_ 50 /o based on delta between OSA and return air enthalpies at design conditions. M0.04 Indicate equipment associated with the delivery of zone level heating and cooling (fans, Heating / cooling system hydronic pumps, primary air dampers, etc) are configured to shut off, and central equipment is No C403.6.2 controls with DOAS confiqured to turn down, when there is no call for heatinq or coolinq in the zone they serve If applying Exception to heating / cooling fans used for air mixing in the space during deadband periods, include fan watts per cfm in equipment schedule 2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 10 of 20 2015 Washinaton State Enerav Code ComDliance Forms for Commercial Buildinas includina R2 & R3 over 3 stories and all R1 Revised January 2017 Project Title: GREEDMONDS99 Date 12/1/2020 The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the Washington State Energy Code, Commercial Provisions. Applicable Code Section Code Provision Information Required - Must be in permit documents Location in Building Department es no na Documents Notes C402.4.1.4 Increased prescriptive Yes C403.6 maximum vertical Indicate that all occupied, conditioned spaces are served by a DOAS per C403.6 fenestration area with DOAS M0.04 Additional Efficiency Package Option, Dedicated Outside Air Systems (DOAS) NA C406.6 Bprovided with To comply with additional efficiency package option, indicate that 90% or more of all occupied, DOAS conuilding ditioned s aces are served by a DOAS per C403.6 Multiple Zone Air Systems Air systems serving multiple Identify supply air systems serving multiple zones and the zones they serve on plans; indicate NA C403.4.4 whether system is VAV and method of primary air control; or provide supporting zones documentation for applied exception to VAV Provide equipment schedules on plans or MECH-EQ form that list all VAV air terminals and types For each air terminal include: maximum airflow rates for primary supply air during zone peak VAV systems serving NA C403.4.4 multiple zones heating and zone peak cooling; maximum airflow during reheating, recooling or mixing; minimum airflow rate to maintain required ventilation, and the basis for these values; if IMC or ASHRAE 62.1 multiple zone equation is basis for minimum flow rates, provide calculation on tans NA C403.4.4.1 Single duct VAV terminal Indicate single duct terminal units are configured to reduce primary supply air before reheating units or recoolin NA C403.4.4.2 Dual duct systems - terminal For systems with separate warm air and cool air ducts, indicate terminal units are configured to units reduce the flow from one duct to minimum before mixing with air from the other duct Indicate locations of duct static pressure sensors on plans; include at least one sensor per VAV system static major duct branch; verify controller setpoint pressure at each sensor is 5 1.2 inch w.g. For systems with zone level DDC, indicate controls are configured to monitor zone damper NA C403.4.1.1 C403.4.1.2 pressure sensors - positions and reset static pressure setpoint based on the zone requiring most pressure; sensors and DDC set points include control logic that automatically detects and generates an alarm if any zone excessively drives reset logic, and allows building operators to exclude zones from reset logic Multiple -zone VAV system For systems with zone level DDC controls, indicate controls are configured to automatically NA C403.4.4.3 ventilation optimization reduce outdoor airflow in response to changes in system ventilation efficiency; or exception controls taken NA C403.4.4.4 VAV system supply air reset Indicate controls automatically reset supply air temperature in response to building loads or outdoor air temperature; or exception taken Multiple Zone HVAC Systems, High Efficiency VAV - Required for systems utilizing C403.6 DOAS Exception 2, must comply with all 16 provisions NA C403.7, Air economizer Indicate system is configured for 100% air economizer operation and complies with all related Item 1 economizer requirements per C403.3 without economizer exceptions) NA C403.7, Direct digital controls (DDC) Provide DDC controls for all components of system; identify all DDC system input / output Item 2 control oints indicate capability for trending and graphical display For systems with minimum OSA > 2,500 cfm, indicate outdoor airflow monitoring station that NA C403.7, Outdoor airflow measures OSA intake under all load conditions; indicate control sequence that increases or Item 3 measurement and reduction reduces system OSA cfm based on VAV terminal feedback of ventilation efficiency (per C403.4.4.3 without exceptions) or DCV(per C403.2.6.2 NA C403.7, Supply airflow measurement For systems with minimum OSA > 2,500 cfm, indicate supply airflow monitoring station capable Item 4 of measuring supply air delivered to VAV terminals under all load conditions C403.7, Zone isolation and Verify maximum area served by a single HEVAV system is 550,000 sf, or one entire floor, NA Item 5 maximum area served whichever is greater; in addition if a system serves > 25,000 sf, that includes areas that are expected to be occu ied non-simultaneously,indicate zone isolation controls per C403.2.4.4 C403.7, Interior / exterior zone Verify that VAV terminals serving interior cooling driven loads are sized per design supply air NA Item 6 design supply air temperature that is 5°F higher than VAV terminals serving exterior zones temperature C403.7, Maximum air terminal inlet Identify air terminals with minimum primary airflow setpoints > 50% of maximum setpoint in NA Item 7 velocity equipment schedule or MECH-EQ form; indicate air terminal inlet velocity does not exceed 900 f m NA C403.7, Sequence of operation Indicate DDC system sequences of operation are designed and configured per ASHRAE GPC Item 8 36 NA C403.7, Maximum allowable system Verify fan system bhp is <_ 90% of the bhp limit per Option 2 equation in Table C403.2.11.1(1), Item 9 brake horsepower MECH-FANSYS form for each system all series and parallel terminal fans have electronically commutated motors; indicate NA C403.7, Fan -powered terminal unit rDDntrolsystem is configured to vary air terminal fan speed as a function of the load; Item 10 motor and control fan speed during periods of low heating, low cooling, or ventilation only is <_ 66% of eak des' n air flow or provide supporting documentation for applied exception 2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 11 of 20 2015 Washinaton State Enerav Code ComDliance Forms for Commercial Buildinas includina R2 & R3 over 3 stories and all R1 Revised January 2017 Project Title: GREEDMONDS99 Date 12/1/2020 The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the Washington State Energy Code, Commercial Provisions. Applicable Code Section Code Provision Information Required - Must be in permit documents Location in Building Department es no na Documents Notes C403.7, Application of single duct Indicate VAV terminal types on plans; verify fan -powered terminal units only serve perimeter NA Item 11 and fan -powered terminal zones with envelope loads; verify all other zones are served by single duct terminal units units C403.7, Fan -powered terminal unit Indicate DDC controls are configured to automatically reset the primary supply air cfm setpoint NA Item 12 primary air reset of all fan -powered terminal units to the minimum required to maintain ventilation during occupied heating or deadband, based upon the VAV air handling unit OSA ventilation fraction For spaces > 150 sf with occupant density >_ 25 people / 1000 sf, indicate space is served by a NA C403.7, High occupancy space dedicated terminal unit with DCV control that resets terminal unit ventilation setpoint; also Item 13 controls indicate occupancy sensor control that automatically reduces minimum ventilation to zero and sets back room heating and cooling setpoints bV z 5°F For server, electronic equipment, telecom or similar spaces with cooling loads > 5 W/sf, Yes C403.7, Dedicated HVAC systems indicate spaces are served by independent HVAC systems that are separate from HPVAV Item 14 systems serving rest of building; indicate dedicated HVAC systems have air economizer controls or enerqV recovery per C403.3 Exception 9 M0.04 Indicate whether systems are served by a high efficiency heating water plant, or a high efficiency chilled water plant If complying via high efficiency heating water plant: Indicate all VAV terminals have hydronic heating coils served by heating water system with either gas -fired boiler(s) with thermal NA C403.7, Central plant efficiency efficiency >_ 90%, air -to -water heat pumps, or heat recovery chillers If complying via high efficiency chilled water plant: Indicate all VAV air handlers have cooling Item 15 coils served by chillers with rated IPLV efficiency that exceeds WSEC listed IPLV by at least 25% per Table C403.2.3(7) (note water-cooled IPLV is max, all others are min); indicate smallest chiller or compressor in plant is <_ 20% of total plant capacity, or provide thermal stora a sized for < 20% of total plant capacity C403.7, Fault detection and Indicate DDC system includes a fault detection and diagnostics (FDD) system configured to NA Item 16 diagnostics I monitor operation and provide fault reporting of required parameters for all VAV air handlers and VAV air terminal units in the HPVAV system HVAC Equipment Energy Use Metering HVAC equipment energy For new buildings > 50,000 sf and building additions > 25,000 sf, verify energy use metering of NA C409.3.1 use metering all equipment used to provide space heating and cooling, dehumidification and ventilation will be brovided ber C409: indicate a ui ment eligible for exce lion Documentation and System Specific Requirement To Support Commissioning Indicate that all mechanical systems, equipment, and controls for which the WSEC requires control functions and / or configuration to perform specific functions are required to be Scope of mechanical commissioned; For buildings with >_ 240,000 Btu/h total output cooling capacity or >_ 300,000 Btu/h total output Yes C408.2 systems commissioning heating capacity, indicate that all mechanical systems regardless of individual capacity are required to be commissioned; or provide building heating / cooling capacity calculation demonstrating eligibilitV for exception Indicate in plans and specifications that Cx per C408 is required for all applicable mechanical systems; Include general summary with at a minimum of Items 1 thru 4 of the Cx plan per C408.1.2 C403.2.10 C408.1.1 Commissioning including: narrative description of activities, responsibilities of the Cx team, schedule of Yes C408.1.2 requirements in construction activities including verification of project close out documentation per C103.6, and conflict of C408.1.4.2 documents interest plan (if required); Include in general summary that a Cx project report or Compliance Checklist (Figure C103.6 C408.1.4.2) shall be completed by the Certified Cx Professional and provided to the owner prior to the final mechanical inspection. Air system and hydronic Indicate in plans that air and fluid flow rates shall be tested and balanced within the tolerances NA C408.2.2 system balancing defined in the specifications; indicate systems shall be balanced in a manner to first minimize throttling losses then adjusted to meet design flow conditions Yes C408.2.2.1 Air system balancing Indicate devices that provide the capability to balance all supply air outlets, zone terminals and devices air handling equipment requiring system balancing NA C408.2.2.2 Hydronic system balancing Indicate devices that provide the capability to isolate, balance and measure flow across all devices hydronic equipment requiring system balancing including heating and cooling coils and pumps NA C408.2.3 Functional performance Identify in plans and specifications the intended operation of all equipment and controls during testin criteria all modes of operation, including interfacing between new and existin -to-remain s stems Project Close Out Documentation Documentation and project Indicate in plans that project close out documentation and training of building operations Yes C103.6 close out submittal personnel is required for all mechanical components, equipment and systems governed by this requirements code; indicate close out documentation shall include: record documents, O&M manuals, applicable WSEC m lin forms n I I in 2015 Washington State Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1Revised January 2017 Project Title: GRE EDMONDS 99 1 Date 12/1/2020 All cooling systems shall be configured to provide air economizer operation, regardless of system capacity, for new construction and mechanical system alterations. Various exceptions to this requirement are available. Identify all systems that an economizer exception will be applied to and additional information as noted below. For Building Dept. Use Economizer Exception Summary Refer to Section C403.3 for descriptions of economizer provisions and exceptions. For alterations refer to Section C503.4 and Table C503.4. ECONOMIZER EXCEPTIONS -NEW CONSTRUCTION AND ADDITIONS Exp 1 Cooling equipment serving spaces that are provided with a dedicated outdoor air system (DOHS) per C403.6. Spaces served shall have year- round design cooling loads from lights and equipment less than 5 watts per square foot. System ID Lighting + Equipment Loads W/s FC-1 0.54 FC-4 0.54 FC-5 0.54 FC-6 0.54 FC-9 0.54 FC-3A 0.68 FC-3B 0.68 Exp 2 Single zone unitary or package systems with dehumidification that affect other systems such that air economizer would increase energy consumption. System ID Exp 3 High efficiency single zone unitary or packaged systems. Equipment cooling efficiency shall be better than the WSEC required minimum efficiency by at least 64% in Climate Zone 4C and 59% in Climate Zone 5B per Table C403.3. System ID Exp 4 Equipment that provides hydronic chilled water for chilled beams and chilled ceiling systems that is served by a water economizer system per C403.3.4 in lieu of air economizer. System ID Exp 5 Water -source heat pumps with heat recovery. Heat pump efficiency shall be 15% better than WSEC required minimum efficiency. Provide at minimum 60% air economizer. Energy recovery to preheat OSA shall have at least 50% effectiveness. Additional system requirements apply. System ID Exp 6 Cooling equipment serving Group R occupancies. Per unit limit is less than 20,000 Btu/h cooling capacity for equipment installed outdoors or in a mech room adjacent to the outdoors. For cooling equipment installed in other locations the unit limit is less than 54,000 Btu/h. Efficiency shall be 15% better than WSEC required minimum efficiency. System ID Equipment Location Cooling Capacity Btu/h FC-7 Other 9,000 FC-8A Other 9,000 I FC-813 Other 9,000 Exp 7 Variable refrigerant flow (VRF) systems with energy recovery. Outdoor unit shall be a reverse -cycle heat pump with variable speed compressor(s) and condenser fan(s). Outdoor unit cooling capacity shall be not less than 65,000 Btu/h. Energy recovery to preheat outdoor air shall have at least 50% rated effectiveness. System shall be capable of providing simultaneous heating and cooling by tranferring recovered energy from zone(s) in cooling mode to other zone(s) that are in heating Outdoor Unit System ID Cooling Capacity Btu/h Exp 8 Cooling equipment serving Controlled Plant Growth Environments. Equipment cooling efficiency shall be better than WSEC required minimum efficiency by at least 20%. Not eligible: unitary and applied heat pumps. System ID SEER, EER, & IEER Exp 9 Cooling equipment with energy recovery. Spaces served shall have year-round design cooling loads from lights and equipment greater than 5 watts per square foot. Energy recovery system shall utilize recovered energy for on -site space heating or preheating of service hot water. Provide calculations to the code official that demonstrate the amount of recovered energy used for on -site heating purposes is equivalent to the annual energy that would be saved by the cooling system with air System ID Lighting + Equipment Loads W/s 2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 Economizer Exceptions,cont.• • 2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1Revised January 2017 Project Title: Date 12/1/2020 Economizer Exception Summaryeconomizer Refer to Section C403.3 scrip for descriptions of economizer provisions and exceptions. For alterations refer to Section C503.4 and Table C503.4. ECONOMIZER EXCEPTIONS - NEW CONSTRUCTION AND ADDITIONS, CONTINUED Compliance Exp 10 Cooling equipment for dedicated server, electronic equipment or liance System ID p telecom switch rooms. Per building limit for this exception is y Option 240,000 Btu/h cooling capacity or 10% of required building air capacity, whichever is greater. Part load control FC-2 Option a required over 85,000 Btu/h. Additional requirements apply. Option a - Cooling equipment efficiency shall be 15% better than the WSEC required minimum efficiency.. Option b - Waterside economizer required. Cooling equipment efficiency shall be 5% better than the WSEC required minimum efficiency. Option c - Waterside economizer required. All cooling equipment is subject to ASHARE Standard 127. Total Claimed Exempt Capacity: Total building air economizer capacity (if claimed > 240 kBtu/h): Alternate Ex 10 Capacity Limit: p p y Cooling Capacity p y Btu/h 14,000 14,000 ECONOMIZER EXCEPTIONS -MECHANICAL SYSTEM ALTERATIONS OR REPLACEMENT C503.4 Pre -approved design alternative to full compliance with air economizer Exp 1 requirement. An alternative for mechanical system alterations where existing building constraints make full compliance with air economizer requirement impractical. Provide calculations to the code official that demonstrate the proposed alternate design strategy provides similar energy savings to the annual energy that would be saved by the cooling system with air economizer per C403.3. System ID Alt. Strategy ECONOMIZER EXCEPTIONS - SIMPLE SYSTEMS C503.4 Qualifying small equipment. Per unit limit less than 33,000 Btu/h. Per System ID Exp 2 building limit for this exception is 72,000 Btu/h cooling capacity or 5% of required building air economizer capacity, whichever is greater. Cooling equipment efficiency shall be 15% better than WSEC required minimum efficiency. Not eligible: non -unitary equipment, unitary equipment installed outdoors or in mech room adjacent to outdoors, equipment installed during new construction, shell -and -core construction, or initial tenant improvement. Total Claimed Exempt Capacity: Total building air economizer capacity (if claimed > 72,000 Btu/h): Alternate C503.4 Exp 2 Capacity Limit: Cooling Capacity Btu/h C503.4 Equipment that provides hydronic chilled water for chilled water terminal Exp 3 units. Equipment part load cooling efficiency (IPLV) shall be better than System ID WSEC required minimum efficiency by at least 25%. Per building limit for this exception is 480,000 Btu/h cooling capacity or 20% of required building air economizer capacity, whichever is greater. Chilled water terminal units serving Group R occupancies are not included in the building capacity total. Total Claimed Exempt Capacity: Total building air economizer capacity (if claimed > 480,000 Btu/h): Alternate C503.4 Exp 3 Capacity Limit: Cooling Capacity Btu/h Table Compliance Options for alteration or replacement of existing C503.4 mechanical cooling equipment per Table C503.4. Refer to table and all applicable table footnotes for full requirements. Applies to the following retrofit conditions: Option a - Any new or replacement equipment Option b - Replacement equipment of same type with same or smaller cooling output capacity. Option c - Replacement equipment of same type with large cooling output capacity. Option d - New equipment added to existing system or replacement equipment that is different than existing being replaced. System ID Equipment Type Compliance Path