FIR2021-0070+SEISMIC BRACING CALCS+7.9.2021_2.08.56_PM+2292793REVIEWED TOLBraceTM Seismic Bracing Calculations FIR2021-0070 Contractor: �'( ^ E C E I` v, E D Project Address: HWY 99 EDMONDS APTS Address: Jul 12 2021 E F=,'T * N 23326 HIGHWAY99 CITY OF EDMONDS Pawemog8nawsaWOAMwde Phone' DEVELOPMENT SERVICES EDMONDS, WA 98057 Licence: DEPARTMENT Job # NC20001 Calculations based on 2013 NFPA Pamphlet #13 Brace Information TOLCOTM Brace Components Maximum Brace Length 7' 0" (2.134 m) TOLCOTM Component Listed Load Adjusted Load Diameter of Brace 1 Fig. 1001 Clamp 1600 Ibs (726 kg) 1386 Ibs (629 kg) Fig.980 Universal Swivel 2015 Ibs (914 kg) 1745 Ibs (792 kg) Type of Brace Sch.40 See Fastener Information Angle of Brace 60° Min. 'Calculation Based on CONCENTRIC Loading 'Please Note: These calculations are for TOLCOTM components only. Use of any other components voids these calculations and the listing of the assembly. Least Rad. of Gyration 0.42" (11 mm) Seismic Brace Assembly Detail L/R Value 200 Max Horizontal Load 1604 Ibs (728 kg) TOLCO FIG. 980 UNIVERSAL SWAY BRACE ATTACHMENT 0, Fastener Information STEEL PIPE Orientation to Connecting Surface NFPAType F Fastener .a Type KWIKBOLT '� Diameter 5 0� Length 4.5 TOLCO FIG. 1001 Maximum Load 600 Ibs (272 kg) FAST CLAMP Brace Identification on Plans LATERAL BRACE #3 Prying Factor Brace Type Lateral [X] Longitudinal � � 4-Way � � Sprinkler System Load Calculation (Fpw = CpWp) Cp = 0.589 Diameter Type Length Total Length Weight Per Unit Length Total Weight 4" (100 mm) Sch. 7 26 ft (7.9 m) 26 ft (7.9 m) 10.86 lb/ft (16.16 kg/m) 282 Ibs (128 kg) 1.5" (40 mm) Sch. 7 105 ft (32 m) 105 ft (32 m) 2.71 lb/ft (4.03 kg/m) 285 Ibs (129 kg) Subtotal Weight 567 Ibs (257 kg) Wp (incl. 15%) 652 Ibs (296 kg) Main Size Type/Sch. 4" Sch. 7 Spacing (ft) 26 Total (Fpw) Maximum Fpw per 9.3.5.5.2 (if applicable) 384 Ibs (174 kg) 760 lb (344 kg) MI-BraceTMVersion 81 Use of TOLBraceTM is subject to terms and conditions per the end user license agreement TOLBraceTM Seismic Calculation HWY 99 EDMONDS APTS 23326 HIGHWAY 99 Brace Identification Brace Type (Per NFPA#13) Braced Pipe (ft) Spacing of Brace Orientation of Brace Bracing Material Maximum Brace Length Slenderness Ratio used for Load Calculation True Angle of Brace for Calculation Type of Fastener Length of Fastener Job # NC20001 LATERAL BRACE #3 NFPA Type F 4" Sch.7 Steel Pipe 26' 0" (7.92 m) Lateral 1" Sch.40 TO" (2.13m) 200 60' KWIKBOLT 4.5 Summary of Pipe within Zone of Influence 4" Sch.7 Steel Pipe (101.6 mm) 26 ft (7.9 m) 1.5" Sch.7 Steel Pipe (38.1 mm) 1105 ft (32 m) G-Factor Used 0.589 Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 384 Ibs (174 kg) Material Capacity 1604 Ibs (728 kg) Fastener Capacity 600 Ibs (272 kg) Fig. 1001 Clamp 1386 Ibs (629 kg) Fig.980 Universal Swivel 1745 Ibs (792 kg) Structural Member CONCRETE COLUMN OR WALL Calculations prepared by PB * The description of the Structural Member is for informational purposes only. TOLBraceTM software calculates the brace assembly only, not the structure it is attached to. Calculated with TOI-Brace- 8 Visit us at www.tolco.com EmT*N Pnwem�g 8nsiriess Wwww & TOLBraceTM Seismic Bracing Calculations Contractor: Project Address: HWY 99 EDMONDS APTS Address: EMT N 23326 HIGHWAY 99 Phone: Pawemog8nawsaWOAMwde EDMONDS, WA 98057 Licence: Job # NC20001 Calculations based on 2013 NFPA Pamphlet #13 Brace Information TOLCOTM Brace Components Maximum Brace Length TO" (2.134 m) TOLCOTM Component Listed Load Adjusted Load Diameter of Brace 1 Fig. 4L Clamp 2015 Ibs (914 kg) 1745 Ibs (792 kg) Fig.980 Universal Swivel 2015 Ibs (914 kg) 1745 Ibs (792 kg) Type of Brace Sch.40 See Fastener Information Angle of Brace 60° Min. 'Calculation Based on CONCENTRIC Loading 'Please Note: These calculations are for TOLCOTM components only. Use of any other components voids these calculations and the listing of the assembly. Least Rad. of Gyration 0.42" (11 mm) Seismic Brace Assembly Detail L/R Value 200 TOLCO FIG. 98 Max Horizontal Load 1604 Ibs (728 kg) UNIVERSAL SWAY BRACE ATTACHMENT 0 STEEL PIPE Fastener Information Orientation to Connecting Surface NFPAType C Fastener Q Type KWIK-BOLT TOLCO FIG. 4L O PIPE CLAMP FOR Diameter 5 SWAY BRACING RF Length 4.5 ; Maximum Load 700 Ibs (318 kg) ---------------- O Brace Identification on Plans LONGITUDINAL BRACE #4 Prying Factor Brace Type Lateral � � Longitudinal [X] 4-Way � � Sprinkler System Load Calculation (Fpw = CpWp) Cp = 0.589 Diameter Type Length Total Length Weight Per Unit Length Total Weight 4" (100 mm) Sch. 40 60 ft (18.3 m) 60 ft (18.3 m) 16.4 lb/ft (24.41 kg/m) 984 Ibs (446 kg) Subtotal Weight 984 Ibs (446 kg) Wp (incl. 15%) 1132 Ibs (513 kg) Main Size Type/Sch. Spacing (ft) 4" sch. 40 60 Total (Fpw) Maximum Fpw per 9.3.5.5.2 (if applicable) 667 Ibs (302 kg) N/A fTOLBraceTM Version 81 Use of TOLBraceTM is subject to terms and conditions per the end user license agreement TOLBraceTM Seismic Calculation HWY 99 EDMONDS APTS 23326 HIGHWAY 99 Brace Identification Brace Type (Per NFPA#13) Braced Pipe (ft) Spacing of Brace Orientation of Brace Bracing Material Maximum Brace Length Slenderness Ratio used for Load Calculation True Angle of Brace for Calculation Type of Fastener Length of Fastener Job # NC20001 LONGITUDINAL BRACE #4 NFPA Type C 4" Sch.40 Steel Pipe 60' 0" (18.29 m) Longitudinal 1" Sch.40 TO" (2.13m) 200 60' KWIK-BOLT 4.5 Summary of Pipe within Zone of Influence 4" Sch.40 Steel Pipe (101.6 mm) 60 ft (18.3 m) G-Factor Used 0.589 Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 667 Ibs (303 kg) Material Capacity 1604 Ibs (728 kg) Fastener Capacity 700 Ibs (318 kg) Fig. 4L Clamp 1745 Ibs (792 kg) Fig.980 Universal Swivel 1745 Ibs (792 kg) Structural Member CONCRETE WALL OR COLUMN Calculations prepared by PB * The description of the Structural Member is for informational purposes only. TOLBraceTM software calculates the brace assembly only, not the structure it is attached to. Calculated with TOI-Brace- 8 Visit us at www.tolco.com EmT*N Pnwem�g 8nsiriess Wwww & TOLBraceTM Seismic Bracing Calculations Contractor: Project Address: HWY 99 EDMONDS APTS Address: EMT N 23326 HIGHWAY 99 Phone: Pawemog8nawsaWOAMwde EDMONDS, WA 98057 Licence: Job # NC20001 Calculations based on 2013 NFPA Pamphlet #13 Brace Information TOLCOTM Brace Components Maximum Brace Length TO" (2.134 m) TOLCOTM Component Listed Load Adjusted Load Diameter of Brace 1 Fig. 4A Clamp 2015 Ibs (914 kg) 1425 Ibs (646 kg) Fig.980 Universal Swivel 2015 Ibs (914 kg) 1425 Ibs (646 kg) Type of Brace Sch.40 See Fastener Information Angle of Brace 45° Min. 'Calculation Based on CONCENTRIC Loading 'Please Note: These calculations are for TOLCOTM components only. Use of any other components voids these calculations and the listing of the assembly. Least Rad. of Gyration 0.42" (11 mm) Seismic Brace Assembly Detail L/R Value 200 TOLCO FIG. 980 Max Horizontal Load 1310 Ibs (594 kg) UNIVERSAL SWAY BRACE p ATTACHMENT TYP. STEEL PIPE V, r Fastener Information Orientation to Connecting Surface NFPAType H Fastener Type Dual Through -Bolts - Fig.906 TOLCO FIG. 4A A ' PIPE CLAMP FOR Diameter 1/2in. (13 mm) SWAY BRACING Length Minimum 4x Wood Member 0 Maximum Load 600 Ibs (272 kg) Brace Identification on Plans LATERAL BRACE #5 Prying Factor N/A Brace Type Lateral [X] Longitudinal [ ] 4-Way [ ] Sprinkler System Load Calculation (Fpw = CpWp) Cp = 0.589 Diameter Type Length Total Length Weight Per Unit Length �23.03 Total Weight 6" (150 mm) Sch. 10 32 ft (9.8 m) 32 ft (9.8 m) lb/ft (34.27 kg/m) 737 Ibs (334 kg) Subtotal Weight 737 Ibs (334 kg) Wp (incl. 15%) 848 Ibs (384 kg) Main Size Type/Sch. Spacing (ft) s" Sch. 10 32 Total (Fpw) Maximum Fpw per 9.3.5.5.2 (if applicable) 499 Ibs (226 kg) 2269 Ib (1029 kg) fTOLBraceTM Version 81 Use of TOLBraceTM is subject to terms and conditions per the end user license agreement TOLBraceTM Seismic Calculation HWY 99 EDMONDS APTS 23326 HIGHWAY 99 Brace Identification Brace Type (Per NFPA#13) Braced Pipe (ft) Spacing of Brace Orientation of Brace Bracing Material Maximum Brace Length Slenderness Ratio used for Load Calculation True Angle of Brace for Calculation Type of Fastener Length of Fastener Job # NC20001 EmT*N Pnwem�g 8nsiriess Wwww & LATERAL BRACE #5 NFPA Type H 6" Sch.10 Steel Pipe 32' 0" (9.75 m) Lateral 1" Sch.40 TO" (2.13m) 200 45' 1/2 (13 mm) Dual Through -Bolts Perpendicular to Beam - TOLCO Fig Minimum 4x Wood Member Summary of Pipe within Zone of Influence 6" Sch.10 Steel Pipe (152.4 mm) 32 ft (9.8 m) G-Factor Used 0.589 Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 499 Ibs (226 kg) Material Capacity 1310 Ibs (594 kg) Fastener Capacity 600 Ibs (272 kg) Fig. 4A Clamp 1425 Ibs (646 kg) Fig.980 Universal Swivel 1425 Ibs (646 kg) Structural Member WOOD BEAM Calculations prepared by PB * The description of the Structural Member is for informational purposes only. TOLBraceTM software calculates the brace assembly only, not the structure it is attached to. Calculated with TOLBrace- 8 Visit us at www.tolco.com TOLBraceTM Seismic Bracing Calculations Contractor: Project Address: HWY 99 EDMONDS APTS Address: EMT N 23326 HIGHWAY 99 Phone: Pawemog8nawsaWOAMwde EDMONDS, WA 98057 Licence: Job # NC20001 Calculations based on 2013 NFPA Pamphlet #13 Brace Information TOLCOTM Brace Components Maximum Brace Length TO" (2.134 m) TOLCOTM Component Listed Load Adjusted Load Diameter of Brace 1 Fig. 4L Clamp 2015 Ibs (914 kg) 1745 Ibs (792 kg) Fig.980 Universal Swivel 2015 Ibs (914 kg) 1745 Ibs (792 kg) Type of Brace Sch.40 See Fastener Information Angle of Brace 60° Min. 'Calculation Based on CONCENTRIC Loading 'Please Note: These calculations are for TOLCOTM components only. Use of any other components voids these calculations and the listing of the assembly. Least Rad. of Gyration 0.42" (11 mm) Seismic Brace Assembly Detail L/R Value 200 Max Horizontal Load 1604 Ibs (728 kg) TOLCO FIG. 980 UNIVERSAL SWAY BRACE ATTACHMENT 00.1 STEEL PIPE Fastener Information Orientation to Connecting Surface NFPAType F i Fastener Type Through -Bolt TOLCO FIG. 4L PIPE CLAMP FOR O Diameter 3/4in. SWAY BRACING-- ---------n Length 5-1/2in. Maximum Load 1065 Ibs (483 kg) ------------- 0 Brace Identification on Plans LONGITUDINAL BRACE #6 Prying Factor N/A Brace Type Lateral [ ] Longitudinal [X] 4-Way [ ] Sprinkler System Load Calculation (Fpw = CpWp) Cp = 0.589 Diameter Type Length Total Length Weight Per Unit Length �23.03 Total Weight 6" (150 mm) Sch. 10 64 ft (19.5 m) 64 ft (19.5 m) lb/ft (34.27 kg/m) 1474 Ibs (669 kg) Subtotal Weight 1474 Ibs (669 kg) Wp (incl. 15%) 1695 Ibs (769 kg) Main Size Type/Sch. Spacing (ft) 6" Sch. 10 64 Total (Fpw) Maximum Fpw per 9.3.5.5.2 (if applicable) 998 Ibs (453 kg) N/A fTOLBraceTM Version 81 Use of TOLBraceTM is subject to terms and conditions per the end user license agreement TOLBraceTM Seismic Calculation HWY 99 EDMONDS APTS 23326 HIGHWAY 99 Brace Identification Brace Type (Per NFPA#13) Braced Pipe (ft) Spacing of Brace Orientation of Brace Bracing Material Maximum Brace Length Slenderness Ratio used for Load Calculation True Angle of Brace for Calculation Type of Fastener Length of Fastener Job # NC20001 LONGITUDINAL BRACE #6 NFPA Type F 6" Sch.10 Steel Pipe 64' 0" (19.51 m) Longitudinal 1" Sch.40 TO" (2.13m) 200 60' 3/4in. x 5-1/2in. Through -Bolt 5-1/2in. Summary of Pipe within Zone of Influence 6" Sch.10 Steel Pipe (152.4 mm) 64 ft (19.5 m) G-Factor Used 0.589 Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 998 Ibs (453 kg) Material Capacity 1604 Ibs (728 kg) Fastener Capacity 1065 Ibs (483 kg) Fig. 4L Clamp 1745 Ibs (792 kg) Fig.980 Universal Swivel 1745 Ibs (792 kg) Structural Member WOOD BEAM Calculations prepared by PB * The description of the Structural Member is for informational purposes only. TOLBraceTM software calculates the brace assembly only, not the structure it is attached to. Calculated with TOLBrace- 8 Visit us at www.tolco.com EmT*N Pnwem�g 8nsiriess Wwww &