Loading...
approved FIR2022-0072+Fire_Sprinkler_Equipment_Specification_Sheets+7.26.2022_11.37.53_AM+3012735RECEIVED Aug 03 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT MODERN FIRE PROTECTION RELENTLESSLY FOCUSED 3902 W. Valley Hwy. N. #504 Auburn, WA 98001 FI R2022-0072 www.modernfireseattle.com MODERFP804MA Automatic Fire Sprinkler System Material Submittal Packet Project Name: John Trang Residence Project #: 25475475 Project Address: 23129 74t" Ave W Project Parcel #: 0048880020-0410 Modern Fire Protection, LLC Material Submittal Packet Index Section 1 - Fire Sprinklers Reliable RA0616 RFC49 Reliable F7FRS6 Section 2 - Pipe & Fittings Spears--CPVC Pipe & Fittings Section 3 - Handers & Seismic Supports Afcon_Fig. S70-S7S CPVC Hangers Section 4 - Alarms & Supervisory Devices System Sensor WFDN Flow Switch System Sensor SSV Electric Bell Section 5 - Valves & Backflow Protection Ames_2000B Backflow Section 6 - Miscellaneous Argco_Gauges Spears -One Step Low VOC Cement for CPVC *Note: Material submittal data may reflect like materials depending on availability. Bulletin 006 May 2022 Reliable Features cULus Listed as Residential Sprinklers Push -On cover plate installation Low water flow requirements Product Description Model RFC Series residential sprinklers are flat cover plate, concealed pendent sprinklers intended for installation in accordance with NFPA 13, NFPA 13R, or NFPA 13D. The sprinklers are cULus Listed as Residential Sprinklers in accordance with UL 199. In addition, Model RFCLL Series sprinklers are cULus certified for Health Effects to NSF/ANSI/ CAN 600, cULus certified less than 0.25% Lead Content to NSF/ANSI 372 Annex G, and Australian WaterMark certified. Model RFC Series sprinklers are offered with either a 165°F (74°C) or 212°F (100°C) temperature rated fusible -link operating element. Sprinklers with a 165°F (74°C) temperature rating are ordinary temperature classification and are listed for use with a 135°F (57°C) temperature rated cover plate. Sprinklers with a 212°F (100°C) temperature rating are intermediate temperature classification and are listed for use with a 165°F (74°C) temperature rated cover plate. Model RFC Series sprinklers are installed with a Model G5 cover plate. Model G5 cover plates are installed by pushing the cover plate into the cup and turning in the clockwise direction until it is tight against the ceiling. Model RFC30, RFC30LL, RFC43, RFC43LL, RFC49 and RFC49LL sprinklers allow 1/2" (13 mm) of cover plate adjustment. Model RFC58 and RFC76 sprinklers allow 3/4" (19 mm) of cover plate adjustment. Model G5 cover plates are available in a variety of finishes as listed in Table H. Model RFC Series Residential Sprinklers Flat Concealed Pendent 191 Model RFC30 & RFC30LL Model RFC49 & RFC49LL Model RFC76 cULus Listed Model RFC43 & RFC43LL Model RFC58 t Model G5 Cover Plate Sprinkler Model p Nominal K-Factor gpm/psi'/2 (1/min/bar' 2) Max. Coverage Area ft x ft (m x m) Listings & Approvals Sprinkler Identification Number (SIN) RFC30 3.0(43) 14 x 14 (4.3 x 4.3) cULus RA0611 RFC30LL 3.0(43) 14 x 14 (4.3 x 4.3) cULus, LL, WMCS RA3211 RFC43 4.3(62) 20 x 20 (6.1 x 6.1) cULus RA0612 RFC43LL 4.3(62) 20 x 20 (6.1 x 6.1) cULus, LL, WMCS RA3212 RFC49 4.9(71) 20 x 20 (6.1 x 6.1) cULus RA0616 RFC49LL 4.9(71) 20 x 20 (6.1 x 6.1) cULus, LL, WMCS RA3216 RFC58 5.8(84) 20 x 20 (6.1 x 6.1) cULus RA0613 RFC76 7.6(109) 20 x 20 (6.1 x 6.1) cULus RA0618 cULus: cULus listed for Safety to ANSI/UL199 LL: cULus certified for Health Effects to NSF/ANSI/CAN 600 cULus certified less than 0.25% Lead Content to NSF/ANSI 372 Annex G. WMCS: Australian WaterMark certified, certificate number 23347. www.reliablesprinkler.com Technical Specifications Style: Flat Concealed Pendent Threads: 1/2" NPT or ISO 7-1R1/2 Nominal K-Factor: 3.0 (43 metric) Max. Working Pressure: 175 psi (12 bar) Min. Spacing: 8 ft. (2.4 m) Material Specifications Thermal Sensor: Nickel Alloy Solder Link Sprinkler Body: Brass Alloy Levers: Bronze Alloy Yoke: Brass Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Towers: Copper Alloy Pins: Stainless Steel Deflector: Bronze Alloy Cup: Steel Cover Plate Finishes (See Table H) Sensitivity Fast -response Temperature Rating Ordinary: 165°F (74°C) sprinkler 135°F (57°C) cover plate Intermediate: 212°F (100°C) sprinkler 165°F (74°C) cover plate Cover Plate Model G5 Cover Plate Sprinkler Wrench Model FC (without wrench -able cap) Model W3 (with wrench -able cap) Listings and Approvals* cULus Listed to UL 199 0 r� Bottom View *Note: RFC30LL is also cULus certified for Health Effects to NSF/ANSI/CAN 600, cULus certified less than 0.25% Lead Content to NSF/ANSI 372 Annex G, and Australian WaterMark certified (certificate number 23347). Model RFC30 & RFC30LL Sprinkler Components and Dimensions • - I area, Body Cup Tower Fusible Lit Deflector (retrac Pin (extent Fi Fi Deflector (extended) 1-3/4" (44 mm) +/- 1/4" (6 mm) Nominal face of fitting to ceiling OO6FIG01 02 W � I Model G5 Cover Plate Model RFC30 and RFC30LL Sprinkler Hydraulic Design Criteria 2-5/16" (58 mm) Cup Dia. 3-5/16" (84 mm) Dia. 2-5/8" (67 mm) Hole in Ceiling 3/16" (5 mm) Ceiling Minimum Flow and Residual Pressure Max. Coverage Area IZ> Ordinary Temperature Intermediate Temperature(3) Flow Pressure Flow Pressure ft. x ft. (m x m) gpm psi gpm psi (1/min) (bar) (1/min) (bar) 12x12 9 9.0 9 9.0 (3.6 x 3.6) (34) (0.62) (34) (0.62) 14 x 14 10 11.0 (4.3 x 4.3) (38) (0.76) Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table B above and (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. 3. Intermediate temperature listing applies to SIN RA0611 only; not applicable to low -lead version. Bulletin 006 Reliable Page 2 of 8 May 2022 www.reliablesprinkler.com Technical Specifications Style: Flat Concealed Pendent Threads: 1/2" NPT or ISO 7-1R1/2 Nominal K-Factor: 4.3 (62 metric) Max. Working Pressure: 175 psi (12 bar) Min. Spacing: 8 ft. (2.4 m) Material Specifications Thermal Sensor: Nickel Alloy Solder Link Sprinkler Body: Brass Alloy Levers: Bronze Alloy Yoke: Brass Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Towers: Copper Alloy Pins: Stainless Steel Deflector: Bronze Alloy Cup: Steel Cover Plate Finishes (See Table H) Sensitivity Fast -response Temperature Rating Ordinary: 165°F (74°C) sprinkler 135°F (57°C) cover plate Intermediate: 212°F (100*C) sprinkler 165°F (74°C) cover plate Cover Plate Model G5 Cover Plate Sprinkler Wrench Model FC (without wrench -able cap) Model W3 (with wrench -able cap) Listings and Approvals* cULus Listed to UL 199 w� k Bottom View *Note: RFC43LL is also cULus certified for Health Effects to NSF/ANSI/CAN 600, cULus certified less than 0.25% Lead Content to NSF/ANSI 372 Annex G, and Australian WaterMark certified (certificate number 23347). Model RFC43 & RFC43LL Sprinkler Components and Dimensions Threa - Body Cup Tower Fusible Lii Deflector (retrac Pin (extent Deflector (extent 1-3/4" (44 mm) +/- 1/4" (6 mm) Nominal face of fitting to ceiling OO6FIG010200 Model G5 Cover Plate Model RFC43 & RFC43LL Sprinkler Hydraulic Design Criteria 2-5/16" (58 mm) Cup Dia. 3-5/16" (84 mm) Dia. 2-5/8" (67 mm) Hole in Ceiling 3/16" (5 mm) Ceiling Minimum Flow and Residual Pressure I'I Ordinary Temperature Intermediate Temperature Max. Coverage Area (z) ft. x ft. Flow Pressure Flow Pressure (m x m) gpm psi gpm psi (1/min) (bar) (1/min) (bar) 15 x 15 12 7.8 12 7.8 (4.6 x 4.6) (45) (0.54) (45) (0.54) 16 x 16 13 9.1 13 9.1 (4.9 x 4.9) (49) (0.63) (49) (0.63) 18 x 18 18 17.5 (5.5 x 5.5) (68) (1.21) 20 x 20 21 23.8 (6.1 x6.1) (79) (1.64) Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table C above and (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. Bulletin 006 Reliable Page 3 of 8 May 2022 www.reliablesprinkler.com Technical Specifications Style: Flat Concealed Pendent Threads: 1/2" NPT or ISO 7-1R1/2 Nominal K-Factor: 4.9 (71 metric) Max. Working Pressure: 175 psi (12 bar) Min. Spacing: 8 ft. (2.4 m) Material Specifications Thermal Sensor: Nickel Alloy Solder Link Sprinkler Body: Brass Alloy Levers: Bronze Alloy Yoke: Brass Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Towers: Copper Alloy Pins: Stainless Steel Deflector: Bronze Alloy Cup: Steel Cover Plate Finishes (See Table H) Sensitivity Fast -response Temperature Rating Ordinary: 165°F (74°C) sprinkler 135°F (57°C) cover plate Intermediate: 212°F (100°C) sprinkler 165°F (74°C) cover plate Cover Plate Model G5 Cover Plate Sprinkler Wrench Model FC (without wrench -able cap) Model W3 (with wrench -able cap) Listings and Approvals* cULus Listed to UL 199 Bottom View *Note: RFC49LL is also cULus certified for Health Effects to NSF/ANSI/CAN 600, cULus certified less than 0.25% Lead Content to NSF/ANSI 372 Annex G, and Australian WaterMark certified (certificate number 23347). Model RFC49 & RFC49LL Sprinkler Components and Dimensions Threa - Body Cup Tower Fusible Lii Deflector (retrac Pin (exten( Deflector (exten( 1-3/4" (44 mm) +/- 1/4" (6 mm) Nominal face of fitting to ceiling 006FIG01_0203 Model G5 Cover Plate Model RFC49 & RFC49LL Sprinkler Hydraulic Design Criteria 2-5/16" (58 mm) Cup Dia. aw 3-5/16" (84 mm) Dia. 2-5/8" (67 mm) Hole in Ceiling 3/16" (5 mm) Ceiling Minimum Flow and Residual PressureM Max. Coverage Area czl Ordinary Temperature Intermediate Temperature Flow Pressure Flow Pressure ft. x ft. (m x m) gpm psi gpm psi (1/min) (bar) (1/min) (bar) 16 x 16 13 7.0 13 7.0 (4.9 x 4.9) (49.0) (0.48) (49.0) (0.48) 18 x 18 17 12.0 17 12.0 (5.5 x 5.5) (64.3) (0.83) (64.3) (0.83) 20 x 20 20 16.7 21 18.4 (6.1 x6.1) (75.7) (1.15) (79.5) (1.27) Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table D above and (2) the flow required to achieve a mini- mum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. Bulletin 006 Reliable Page 4 of 8 May 2022 www.reliablesprinkler.com Technical Specifications Style: Flat Concealed Pendent Threads: 1/2" NPT or ISO 7-1R1/2 Nominal K-Factor: 5.8 (84 metric) Max. Working Pressure: 175 psi (12 bar) Min. Spacing: 8 ft. (2.4 m) Material Specifications Thermal Sensor: Nickel Alloy Solder Link Sprinkler Body: Brass Alloy Levers: Bronze Alloy Yoke: Brass Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Towers: Copper Alloy Pins: Stainless Steel Deflector: Chrome Plated Bronze Alloy Cup: Steel Cover Plate Finishes (See Table H) Sensitivity Fast -response Temperature Ratings Ordinary: 165°F (74°C) sprinkler 135°F (57°C) cover plate Intermediate: 212°F (100°C) sprinkler 165°F (74°C) cover plate Cover Plate Model G5 Cover Plate Sprinkler Wrench Model FC (without wrench -able cap) Model W3 (with wrench -able cap) Listings and Approvals cULus Listed to UL 199 Model RFC58 Sprinkler Components and Dimensions Bottom View 2- (58 mm) Threads Cup Dia. Body Cup Tower 2-5/8" (67 mm) Fusible Link 1 7/8" (48 mm) +/- 3/8" (9 mm) Hole in Ceiling Nominal face of fitting to ceiling 3/16" Deflector (retracted) — (5 mm) Pin (extended) H H "06FG04A Deflector (extended)—3-==F��3== F 3-5/16" Model G5 Cover Plate (84 mm) Ceiling Dia. Model RFC58 Sprinkler Hydraulic Design Criteria Minimum Flow and Residual Pressure(') Max. Coverage Area (2) Flow Pressure ft. x ft. gpm psi (m x m) (1/min) (bar) 16 x 16 16 7.6 (4.9 x 4.9) (60.6) (0.53) 18 x 18 18 9.6 (5.5 x 5.5) (68.1) (0.66) 20 x 20 20 11.9 (6.1 x 6.1) (75.7) (0.82) Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table E above and (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. Bulletin 006 Reliable Page 5 of 8 May 2022 www.reliablesprinkler.com Technical Specifications Style: Flat Concealed Pendent Threads: 3/4" IN PT or ISO 7-1R3/4 Nominal K-Factor: 7.6 (109 metric) Max. Working Pressure: 175 psi (12 bar) Min. Spacing: 8 ft. (2.4 m) Material Specifications Thermal Sensor: Nickel Alloy Solder Link Sprinkler Body: Brass Alloy Levers: Bronze Alloy Yoke: Brass Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Towers: Copper Alloy Pins: Stainless Steel Deflector: Bronze Alloy Cup: Steel Cover Plate Finishes (See Table H) Sensitivity Fast -response Temperature Ratings Ordinary: 1657 (74°C) sprinkler 1357 (57°C) cover plate Intermediate: 2127 (100°C) sprinkler 1657 (74°C) cover plate Cover Plate Model G5 Cover Plate Sprinkler Wrench Model FC (without wrench -able cap) Model W3 (with wrench -able cap) Listings and Approvals cULus Listed to UL 199 Model RFC76 Sprinkler Components and Dimensions Threads Body Cup ___` Tower Fusible Link Deflector (retracted) — Pin (extended) — Deflector (extended) Bottom View 2-5/16" (58 mm) Cup Dia. 1-7/8" (48 mm) +/ 3/8" (9 mm) Nominal face of fitting to ceiling OO6FIG05A Model G5 Cover Plate Model RFC76 Flat Concealed Sprinkler Hydraulic Design Criteria 3-5/16" (84 mm) Dia. 2-5/8" (67 mm) Hole in Ceiling 3/16" (5 mm) Ceiling Minimum Flow and Residual Pressure0) Max. Coverage Area (2) Flow Pressure ft. x ft. gpm psi (m x m) (1/min) (bar) 16 x 16 21 7.6 (4.9 x 4.9) (79.5) (0.52) 18 x 18 24 9.9 (5.5 x 5.5) (90.8) (0.68) 20 x 20 34 20 (6.1 x 6.1) (128.7) (1.4) Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table E above and (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. Bulletin 006 Reliable Page 6 of 8 May 2022 www.reliablesprinkler.com Cover Plate Finishes') Standard Finishes Special Application Finishes White Paint Off White Paint Black Paint Raw Brass Chrome Bright Brass Finished Bronze Custom Color Paint(z) Satin Chrome Stainless Steel Clad(') Custom Printed Notes: 1. Paint or any other coating applied over the factory finish will void all approvals and warranties. 2. Custom color paint is semi -gloss, unless specified otherwise. 3. Stainless steel clad cover plates are Type 316 Stainless Steel on the finished side and C102 Copper Allow on the back side. Cover plates are not listed or approved as corrosion resistant. Installation Dimensions Recommended Min. to Min. to Max. Sprinkler Cover Cover Plate Hole Diameter Cover Plate Max. Face Dropped Deflector Cover Plate Model Plate Diameter in Ceiling Adjustment of Fitting to Distance below Temperature Model inch (mm) inch (mm) inch (mm) Ceilings') Ceiling Rating inch (mm) inch (mm) RFC30, RFC30LL, 135°F(2) RFC431 G5 3-5/16 2-5/8 1/2 1-1/2 to 2 1/2 to 1 (57°C) RFC43LL, (84) (67) (13) (38 to 51) (13 to 25) or 165°F(3) RFC49, (74-C) RFC49LL RFC58, G5 3-5/16 2-5/8 3/4 1-112 to 2-1/4 1/4 to 1 13or 16 (57°C) 0 3 RFC76 (84) (67) (19) (38 to 57) (6 to 25) (74 C) Notes: 1. Face of fitting to ceiling dimensions are based on a nominal thread make up. Verify dimensions based on fitting and thread sealing method prior to installation. A 1/2" x 112" brass nipple extension (Reliable P/N 6999991900) is available where necessary for replacement of existing sprinklers. 2. For use with 165T (74°C) temperature rated sprinklers where the maximum ceiling temperature does not exceed 100T (38°C). 3. For use with 212T (100°C) temperature rated sprinklers where the maximum ceiling temperature does not exceed 150°F (66°C). Installation Model RFC series sprinklers are intended to be installed in accordance with NFPA 13, NFPA 13R, or NFPA 13D, as well as the requirements of applicable authorities having jurisdiction. Model RFC series sprinklers must not be installed in ceilings with positive pressure in the space above. Model RFC series sprinklers are shipped with a wrench -able protective cap that should remain on the sprinkler until the sprinkler system is placed in service following construction. Model RFC series sprinklers can be installed without removing the wrench -able protective cap using the Model W3 wrench. Alternatively, Model RFC series sprinklers can be installed using the Model FC wrench by temporarily removing the protective cap during installation of the sprinkler. The use of any other wrench to installed Model RFC series sprinklers is not permitted and may damage the sprinkler. Fully insert the Model W3 wrench over the cap until it reaches the bottom of the cup, or the Model FC wrench over the sprinkler until the wrench engages the body. Do not wrench any other part of the sprinkler/cup assembly. The Model W3 and FC wrenches are designed to be turned with a standard 1/2" square drive. Tighten the sprinkler into the fitting after applying a PTFE based thread sealant to the sprinkler's threads. Recommended installation torque for iron pipe fittings is 8 to 18 ft-Ibs (11 to 24 N-m) for 1/2" thread sprinklers and 14 to 20 ft-Ibs (19 to 27 N-m) for 3/4" thread sprinklers. Note: When used with gasketed fittings, follow fitting manufacturer's installation instructions regarding tightening to achieve a leak -free connection. Do not exceed the maximum recommended torque. Exceeding the maximum recommended torque may cause leakage or impairment of the sprinkler. Use care when inserting or removing the wrench from the sprinkler to avoid damage to the sprinkler. Install the cover plate by hand by pushing the cover plate into the cup and turning the cover in the clockwise direction until it is tight against the ceiling. Bulletin 006 May 2022 Page 7 of 8 www.reliablesprinkler.com Model FC For use with Model RFC Series sprinklers without wrench -able cap installed Model W8 High -strength plastic wrench for limited (emergency) use with Model RFC Series sprinklers without wrench -able cap installed. Meets NFPA requirements for sprinkler wrench on premises. Maintenance Model RFC series sprinklers should be inspected and the sprinkler system maintained in accordance with NFPA 25. Do not clean sprinklers with soap and water, ammonia or any other cleaning fluids. Remove dust by gentle vacuuming. Replace any sprinkler cover plate assembly which has been painted (other than factory applied) or damaged in any way. A stock of spare sprinklers should be maintained to allow quick replacement of damaged or operated sprinklers. Prior to installation, sprinklers should be maintained in the original cartons and packaging until used to minimize the potential for damage to sprinklers that would cause improper operation or non -operation. Guarantee For the Reliable Automatic Sprinkler Co., Inc. guarantee, terms, and conditions, visit www.reliablesprinkler.com. Model W3 For use with Model RFC Series sprinklers with wrench -able cap installed Listings and Approvals cULus Listed for Safety to ANSI/UL199 Additional Listings for RFC30LL, RFC43LL, and RFC49LL: • cULus Certified for Health Effects to NSF/ANSI/CAN 600 • cULus Certified less than 0.25% Lead Content to NSF/ ANSI 372 Annex G. • Australian WaterMark Certified, certificate number 23347. Patents Model RFC30, RFC30LL, RFC43, RFC43LL, RFC49, RFC49LL, RFC58, and RFC76 sprinklers are covered by U.S. Patent No. 9,248,327 and U.S. Patent No. 7,275,603. Model RFC30, RFC30LL, RFC43 and RFC43LL sprinklers are additionally covered by U.S. Patent No. 8,776,903. Ordering Information Specify the following when ordering. Sprinkler • Model (RFC30, RFC30LL, RFC43, RFC43LL, RFC49, RFC49LL, RFC58, RFC76) • Temperature Rating Cover Plate • Model G5 • Temperature Rating • Finish (See Table H) Sprinkler Wrench • Model FC • Model W3 • Model W8 (Limited use) N O r- 0) M i :1 Bulletin 006 May 2022 Page 8 of 8 www.reliablesprinkler.com Bulletin 014 December 2021 Reliable Model F1 FR56 Sprinkler Types Standard Spray Upright Standard Spray Pendent Conventional Upright/Pendent Vertical Sidewall Horizontal Sidewall Model F1 FR56 Recessed Sprinkler Types Standard Spray Pendent Horizontal Sidewall Model F1 FR56 Concealed Sprinkler Types Standard Spray Pendent Model F1 FR42, F1 FRXLH & F1 FR28 Sprinkler Types Standard Spray Upright Standard Spray Pendent Model F1 FR40 Sprinkler Types Standard Spray Pendent Model F1 FR42, F1 FR40, F1 FRXLH & F1 FR28 Recessed Sprinkler Types Standard Spray Pendent Model F1 FR56LL & F1 FR42LL Low Lead Sprinkler Types Standard Spray Pendent with less than 0.25% Lead Con- tent Listing & Approvals The following organizations provide Listings or Approvals for various Model F1 FIR series sprinklers. See the Design and Installation table in this Bulletin for information on specific listings and approvals applicable to each sprinkler. 1. Underwriters Laboratories Inc. and Certified for Cana- da (cULus) in accordance with ANSI/UL199. 2. FM Approvals (FM) 3. Loss Prevention Certification Board (LPCB) 4. VdS SchadenverhOtung GmbH (VdS) 5. Underwriters Laboratories Inc. and Underwriters Lab- oratories of Canada Certified for Health Effects to NSF/ ANSI Standard 61 Annex G (ULH) 6. EC Certificate: 0786-CPD-40239 (RA1414), 0786- CPD-40251 (RA1425), 0786-CPD-40252 (RA1475) (EC) 7. WaterMark certified. Certificate Number 23347. (WM) UL Listing Category Sprinklers, Automatic & Open (VNIV) Quick Response Sprinkler Model F1 FR Series Quick Response Glass Bulb Sprinklers 6� N Upright Pendent Conventional a Vertical Sidewall Horizontal Sidewall Recessed Pendent/F1/F2 Recessed Concealed Recessed Horizontal Sidewall Pendent Pendent/FP XLH Upright XLH Pendent XLH Recessed Pendent F1/F2 Product Description Reliable Model F1 FR series sprinklers are quick -response automatic sprinklers with a glass bulb thermal element. Model F1 FIR series sprinklers are Standard Spray sprinklers, with the exception of the Model F1 FR56 Conventional sprinkler which is XLH Recessed an Old-style/Conventional sprinkler. Pendent FP The Model F1 FR Series automatic sprinklers utilize a 3.0 mm frangible glass bulb. These sprinklers have demonstrated response times in laboratory tests which are five to ten times faster than standard response sprinklers. This quick response enables the Model F1 FIR Series sprinklers to apply water to a fire faster than standard -response sprinklers of the same tem- perature rating. The glass bulb consists of an accurately controlled amount of special fluid hermetically sealed inside a precisely manufac- tured glass capsule. This glass bulb is specially constructed to provide fast thermal response. Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 At normal temperatures, the glass bulb contains the fluid in both the liquid and vapor phases. The vapor phase can be seen as a small bubble. As heat is applied, the liquid expands, forcing the bubble smaller and smaller as the liquid pressure increases. Continued heating forces the liquid to push out against the bulb, causing the glass to shatter, opening the waterway and allowing the deflector to distribute the discharging water. Model F1 FIR Series sprinklers provide a wide range of options where quick -response, glass bulb sprinklers are used: • Pendent, recessed pendent, upright, horizontal side - wall, and vertical sidewall deflectors • K-factors of 2.8 (40 metric), 4.0 (57 metric), 4.2 (60 metric), and 5.6 (80 metric) • Flush, recessed, and concealed installations See the Design and Installation Information table in this Bul- letin for information on the approvals and availability of specific Model F1 FIR series sprinkler configurations. Model F1 FIR Recessed Pendent and Recessed Horizontal Sidewall sprinklers are required to be used with Reliable Model F1, F2, or FP recessed escutcheons. See the Recessed Es- cutcheon Data table in this Bulletin for listing and approval infor- mation with each specific Model F1 FIR series sprinkler. Model F1 and F2 recessed escutcheons, shown in Fig. 1 and 3, are a friction fit assembly allowing for 3/4-inch (19mm) and 1/2- inch (12.7mm) of adjustment, respectively. Model FP recessed escutcheons, shown in Fig. 2, provide a 1/2-inch (12.7mm) threaded adjustment. Model F1 FR56 Concealed Pendent and Model F1 FR56LL Concealed Pendent sprinklers are required to be used with Model CCP cover plates. A standard profile Model CCP cover plate is available that provides up to 1/2-inch (12.7mm) of cover plate adjustment. In addition, a low profile Model CCP cover plate is also available that provides up to 5/16-inch (8.Omm) of cover plate adjustment. See the Design and Installation Infor- mation and Listed and Approved Temperature Ratings tables in this Bulletin for further information on approved cover plate options. Application Model F1 FIR Series sprinklers are intended for use in ac- cordance with NFPA 13, FM Property Loss Prevention Data Sheets, and the requirements of the Authority Having Juris- diction. Care must be exercised that the k-factor, tempera- ture rating, deflector style, and sprinkler type are in accor- dance with the requirements of the applicable design and installation standards. In addition, Model F1 FIR Series sprin- klers must be used in accordance with their listings and ap- provals, as well as the information provided in this Bulletin. Installation Glass bulb sprinklers have orange bulb protectors or protec- tive caps to minimize bulb damage during shipping, handling and installation. Reliable sprinkler installation wrenches are designed to install sprinklers with bulb protectors in place. Re- move the bulb protector at the time when the sprinkler system is placed in service for fire protection. Removal of the bulb protec- tor before this time may leave the bulb vulnerable to damage. Remove bulb protectors by undoing the clasp by hand. Do not use tools to remove bulb protectors. Model F1 FIR Series sprinklers must be installed with the Reli- able sprinkler installation wrench identified in the Design and Installation Information table in this Bulletin. Any other wrench may damage the sprinkler. A leak tight sprinkler joint can be obtained with a torque of 8 to 18 lb-ft (11 to 24 N-m). Do not tighten sprinklers over the maximum recommended installation torque. Exceeding the maximum recommended installation torque may cause leakage or impairment of the sprinkler. Recessed Sprinklers Model F1 FR Series Recessed sprinklers are to be installed as shown in Fig. 1, Fig. 2, or Fig. 3, as applicable to the specific model being installed. The Recessed Escutcheon Data table in the Bulletin identifies the only recessed escutcheons that are permitted to be used with each Model F1 FIR Series Recessed sprinkler. The use of any other recessed escutcheon will void all approvals and negate all warranties. Concealed Sprinklers Model F1 FIR Series Concealed Pendent sprinklers are to be installed as shown in Fig. 4 or Fig. 5, as applicable to the selected cover plate. Model F1 FR56 Concealed Pendent and Model F1 FR56LL Concealed Pendent sprinklers have a facto- ry -installed Model CCP cup. A protective cap is installed at the factory that should remain on the sprinkler until the sprinkler is installed and should then be reinstalled on the sprinkler until the cover plate is installed. The concealed sprinkler assemblies are completed by the installation of a Model CCP push-on/thread- off cover plate assembly. The cover plate and sprinkler cup as- semblies are joined using a cover plate skirt with flexible tabs for threaded engagement. A choice of two Model CCP cover plate assemblies provides either 1/2-inch (13mm) or 5/8-inch (8mm) of cover adjustment. Do not install Model F1 FIR Series Concealed Pendent sprinklers in ceilings which have positive pressure in the space above. Model F1 FIR Series Concealed Pendent sprinklers require a 2-5/8-inch (67mm) diameter hole to be cut in the ceiling. The Model W4 wrench is used to engage the sprinkler wrenching sur- faces and to install the sprinkler in the fitting. Remove the protective cap to install the sprinkler, then reinstall the protective cap until the cover plate is installed. When inserting or removing the wrench from the sprinkler/cup assembly, care should be taken to prevent dam- age to the sprinkler. Do not wrench any other part of the sprinkler/ cup assembly. Installation is completed by removing the protective cap from the sprinkler and pushing the cover plate onto the cup. Final adjustment is made by hand turning the cover plate until the skirt flange makes full contact with the ceiling. Cover plate removal requires turning the cover plate in the counter clockwise direction. After installation, inspect all sprinklers to ensure that there is a gap between the cover plate and ceiling and that the four cup slots are open and free from any air flow impediment to the space above. Concealed cover plate/cup assemblies are listed only for use with specific sprinklers. The use of any concealed cover plate/ cup assembly other than the Reliable Model CCP with Model F1 FR56 Concealed Pendent and Model F1 FR56LL Concealed Pendent sprinklers or the use of the Model CCP Concealed cover plate assembly on any sprinkler with which it is not spe- cifically listed my prevent good fire protection and will void all guarantees, warranties, listings and approvals. 2. Technical Data: Sensitivity: Quick -response Thread Size: 1/2-inch NPT standard; ISO 7-R1/2 optional Maximum Working Pressure: 175 psi (12 bar) - 100% Factory tested hydrostatically to 500 psi (34.5 bar) SIN RA1425, RA1414 & RA1435 cULus listed for 250 psi (17 bar) Design and Installation Information Model Nominal K-factor Nominal Orifice Diameter Deflector/ Orientation Nominal Sprinkler Height Installation Wrench SIN Listings and Approvals Approval Notes US Metric inches mm inches mm Pendent 2.25 57 W2 RA1411 cULus 2 Recessed Pendent 2.25 57 W4 RA1411 cULus 2 F1 FR28 2.8 40 3/8 10 Upright 2.25 57 W2 RA1421 cULus 1,2 F1 FR40 4.0 57 3/8 10 Pendent 2.25 57 W2 RA1418 VdS Recessed Pendent 2.25 57 W4 RA1418 VdS Pendent 2.25 57 W2 RA1413 cULus 2 F1 FR42 4.2 60 7/16 10 Recessed Pendent 2.25 1 57 W4 RA14131 cULus 2 Upright 2.25 57 W2 RA1423 cULus 1,2 F1 FR42LL 4.2 60 7/16 10 Pendent 2.25 57 W2 RA1410 cULus, ULH Recessed Pendent 2.25 57 W4 RA1410 cULus, ULH F1 FRXLH Pendent 2.25 57 W2 RA1413 cULus 2 Recessed Pendent 2.25 57 W4 RA1413 cULus 2 (F1 FR42 4.2 60 7/16 10 with Pintle) Upright 2.25 57 W2 RA1423 cULus 1,2 cULus, FM, Pendent 2.25 57 W2 RA1414 LPCB, VdS, EC, 1,2,3,4 WM cULus, FM, Recessed Pendent 2.25 57 W4 RA1414 LPCB, VdS, EC, 1,2,3,4 WM F1 FR56 5.6 80 1/2 15 Concealed Pendent 2.25 57 W4 RA1414 cULusn/VIdS,EC, 5,6 cULus, FM, Upright 2.25 57 W2 RA1425 LPCB, VdS, EC, 1,2,3,4 WM "Conventional (Pendent or Upright)" 2.25 57 W2 RA1475 LPCB, VdS, EC, WM 4 Pendent 2.25 57 W2 RA1415 cULus, ULH 1 Recessed Pendent 2.25 57 W4 RA1415 cULus, ULH FlFR56LL 5.6 80 1/2 15 Concealed Pendent 2.25 57 W4 RA1415 cULus, ULH 6 Horizontal Sidewall 2.63 67 W2 RA1435 cULus, FM 1,2,3,7 FlFR56 5.6 80 1/2 15 Recessed Horizontal Sidewall 2.63 67 W4 RA1435 cULus, FM 8 F1 FR56 5.6 80 1/2 15 Vertical Sidewall (Pen- dent or Upright) 2.25 57 W2 RA1485 cULus, FM, LPCB 1,2,3,9 (') cULus Listed Corrosion Resistant sprinkler when ordered with available Polyester coating. (1) cULus Listed Corrosion Resistant sprinkler when ordered with available Electroless Nickel PTFE plating. (1) Available with FM approved Polyester coating in black or white. (4) Available with LPCB and VdS approved Polyester coating. (1) VdS and EC approvals of the F1 FR56 Concealed Pendent sprinkler are for 1550F (68°C) temperature rated sprinklers only. VdS approved sprinklers must use Norbulb brand glass bulbs with the 1/2-inch (12.7mm) adjustment Model CCP cover plate only. (1) Model F1 FR56 Concealed Pendent and Model F1 FR56LL Concealed Pendent sprinklers must be used with Reliable Model CCP cover plates, available as either standard depth with 1/2-inch (12.7mm) of adjustment or low profile with 5/16-inch (8.0 mm) of adjustment. (') cULus Listing of the F1 FR56 Horizontal Sidewall sprinkler is for Light and Ordinary Hazard occupancies only. Minimum to maximum deflector to ceiling distance shall be 4 inches to 12 inches (102mm to 305mm). FM Approval of the F1 FR56 Horizontal Sidewall sprinkler is for Light Hazard occupancies only. (1) cULus Listing and FM Approval of the F1 FR56 Recessed Horizontal Sidewall sprinkler is for Light Hazard occupancies only. (1) The F1 FR56 Vertical Sidewall sprinkler is listed and approved for use only in Light Hazard occupancies. LPCB approval of the F1 FR56 Vertical Sidewall sprinkler is for installation in the Pendent position only. Listed and Approved Temperature Ratings Model Deflector/ Orientation Ordinary Temp. Classification 100T (38°C) Max. Ambient Temp. Intermediate Temp. Classification 150T (65°C) Max. Ambient Temp. High Temp. Classification 225°F (107°C) Max. Ambient Temp. 135°F (57°C) Temp. R ting 155°F (68°C) Temp. Rating 175°F (79°C) Temp. Rating 200°F (93°C) Temp. Rating 286T (141°C) Temp. Rating Orange Bulb Red Bulb Yellow Bulb Green Bulb Blue Bulb Pendent cULus F1 FR28 Recessed Pendent cULus Upright cULus Pendent VdS F1 FR40 Recessed Pendent VdS Pendent cULus F1 FR42 Recessed Pendent cULus Upright cULus FlFR42LL Pendent Recessed Pendent cULus, ULH cULus, ULH Pendent cULus F1 FRXLH Recessed Pendent cULus Upright cULus Pendent cULus, FM, LPCB, VdS, EC, WM Recessed Pendent cULus, FM, LPCB, VdS, EC, WM F1FR56 Concealed Pendent cULus, WM cULus,, dS,EC, WM cULus, WM Upright cULus, FM, LPCB, VdS, EC, WM "Conventional Pendent or Upright)" LPCB, VdS, EC, WM Pendent cULus, ULH FlFR56LL Recessed Pendent cULus, ULH Concealed Pendent* cULus, ULH Horizontal Sidewall cULus, FM F1 FR56 Recessed Horizontal Sidewall cULus, FM F1 FR56 Vertical Sidewall (Pen- dent or Upri ht cULus, FM, LPCB * Model F1 FR56 Concealed Pendent and F1 FR56LL Concealed Pendent sprinklers must be used with Reliable Model CCP cover plates. For Ordinary Temperature Classification sprinklers use a 135°F (57°C) temperature rated cover plate. For In- termediate Temperature Classification sprinklers use a 165°F (74°C) temperature rated cover plate. Recessed Escutcheon Data Listed and Approved Recessed Escutcheons Model F1 Model F2 Model FP Model Deflector/ (Fig. 1 & 3) (Fig. 1 & 3) (Fig. 2) SIN Orientation 3/4-inch (19mm) 1/2-inch (12.7mm) 1/2-inch (12.7mm) adjustment adjustment adjustment F1FR28 Recessed Pendent cULus cULus cULus RA1411 F1 FR40 Recessed Pendent VdS VdS VdS RA1418 F1FR42 Recessed Pendent cULus cULus cULus RA1413 FlFR42LL Recessed Pendent cULus, ULH cULus, ULH cULus, ULH RA1410 F1FR42XLH Recessed Pendent cULus cULus cULus RA1413 F1FR56 Recessed Pendent cULus, LPCB, VdS, cULus, FM, LPCB, cULus, VdS, EC, WM RA1414 EC, WM VdS, EC, WM FlFR56LL Recessed Pendent cULus, ULH cULus, ULH cULus, ULH RA1415 F1FR56 Recessed Horizontal Sidewall cULus cULus, FM cULus RA1435 9 TURN COLLAR UNTIL TIGHT AGAINST SPRINKLER WRENCH BOSS --�\\ F7 ESCUTCHEONr//1� 3/4'[19mm] e1 ADJUSTMENT F2 ESCUTCHEON 112'T 12.7mm] ADJUSTMENT 2 114" HOLE DIA. [57.2mmJ 1 15116" DIA [49.2mmJ l F S i i -1 II II L J� 2 27132" DIA. [72.2mmJ 1" X 1/2" REDUCER FACE OF FITTING TO FACE OF CEILING DIMENSION F1 ESCUTCHEON AT MAXIMUM RECESS = i'[25.4mm] AT MINIMUM RECESS = 318'T9.5mm] F2 ESCUTCHEON AT MAXIMUM RECESS = 3/4'[19mm] AT MINIMUM RECESS = 318'T9.5mmj F1 ESCUTCHEON AT MAXIMUM RECESS = 7/8'T22.2mm] [3.2mmJ AT MINIMUM RECESS = 1-5/8'[41.3mm] F2 ESCUTCHEON AT MAXIMUM RECESS = 1-1/8'[28.6mm] AT MINIMUM RECESS = 1-5/8'T41.3mm] Fig. 1 Model F1 FR56, F1 FR56LL, F1 FR42, F1 FR40, F1 FR42LL, F1 FRXLH & F1 FR28 Recessed Pendent sprinkler with Model F1 or F2 escutcheon I I 1 " X 1/2"' REDUCER -----I----- 2 5/8" DIA. [66.7mm] HOLE IN CEILING 1 I 2 5/16" DIA. [58.7mm] CUP L J CEILING FACE OF FITTING TO FACE OF CEILING DIMENSION - AT MAXIMUM RECESS = 1-1/2"T38mm] AT MINIMUM RECESS = 1 'T25.4mm] AT MAXIMUM RECESS = 9/16'T14.3mm] %2'T 12.7mm] AT MINIMUM RECESS = 1 'T25.4mm] ADJUSTMENT 3 1/4" DIA. [82.6mm] Fig. 2 Model F1 FR56, F1 FR56LL, F1 FR42, F1 FR40, F1 FR42LL, F1 FRXLH & F1 FR28 Recessed Pendent sprinkler with Model FP escutcheon 5. FACE OF FITTING TO FACE OF CEILING DIMENSION F1 ESCUTCHEON AT MAXIMUM RECESS = I 'T25.4mm] AT MINIMUM RECESS = 318'T9.5mm] E2 ESCUTCHEON AT MAXIMUM RECESS = 3/4'T 19mm] AT MINIMUM RECESS = 3/8'T9.5mm] 2 114" HOLE DIA. [57.2mm] 1" X 112" REDUCER i i um I 1 15116" DIA. / uw [49.2mm] of um � um i TURN COLLAR UNTILu TIGHT AGAINST SPRINKLER WRENCH BOSS. 118" [3.2mm] F1 ESCUTCHEON AT MAXIMUM RE ESS 1 3 8" 34 9 C = - / [ . mm] AT MINIMUM RECESS = 2-1/16'T52.4mm] F2 ESCUTCHEON AT MAXIMUM RECESS = 1-5/8'T41.3mm] AT MINIMUM RECESS = 2-1/16'T52.4mm] 2 27/32" DIA. [72.2mm] F1 ESCUTCHEON 3/4'T 19mm] ADJUSTMENT F2 ESCUTCHEON 1/2'T 12.7mm] ADJUSTMENT 1 (1) 4"-12" [101.6mm-304.8mm] CEILING TO DEFLECTOR oiarcoM RECESSED HSW W/F1 OR F2 ESCUTCHEON (1) FM APPROVED FOR 4" - 6" [101.6MM - 152.4MM] CEILING TO DEFLECTOR WITH F2 ONLY. Fig. 3 Model F1 FR56 Recessed Horizontal Sidewall sprinkler with Model F1 or F2 escutcheon I" x 112" REDUCING TEE OR ELBOW 2 5116" DIA — CUP CEILING 2 518 " DIA. HOLE IN CEILING 1 112 " MAX. FACE OF FITTING TO FACE OF CEILING DIMENSION I 112 " MAX. COVER ADJUSTMENT j COVER PLATE / ASSEMBL Y 3 5116 " DIA SPRINKLER 15/16" CONCEALED. 1 /2" ADJUSTMENT 017FG01A Fig. 4 Model F1 FR56/F1 FR56LL Concealed Pendent sprinkler with standard depth 1/2-inch (12.7mm) adjustment - Model CCP cover plate Al I" x TEE 112" REDUCING OR ELBOW _ 2 5116" CEILING 5116 " MAX. --I COVER ADJUSTMENT COVER PLATE ASSEMBLY SPRINKLER - 2 518" DIA. HOLE IN CEILING CONCEALED, 5/16" ADJUSTMENT 1 112 " MAX. FACE OF FITTING TO FACE OF CEILING DIMENSION 017FG02A 514" Fig. 5 - Model F1 FR56/F1 FR56LL Concealed Pendent sprinkler with low profile 5/16- inch (8.Omm) adjustment - Model CCP cover plate Maintenance The Model F1 FIR Series sprinklers should be inspected and the sprinkler system maintained in accordance with NFPA 25. Do not clean sprinklers with soap and water, ammonia or any other cleaning fluids. Remove dust by using a soft brush or gen- tle vacuuming. Replace any sprinkler which has been painted (other than factory applied) or damaged in any way. A stock of spare sprinklers should be maintained to allow quick replace- ment of damaged or operated sprinklers. Finishes (1)(2) Standard Finishes Sprinkler Escutcheon Cover plate Bronze Brass Chrome Chrome Chrome White White Polyester (3)(6)(7) White Special Application Finishes Sprinkler Escutcheon Cover plate Electroless Nickel PTFE(3)(4) Electroless Nickel PTFE Bright Brass Black Polyester (3)(6)(7) Bright Brass Black Bright Brass (5) Black Off White Off White(6)(7) Off White Satin Chrome Satin Chrome Satin Chrome (') Other finishes and colors may be available on special order. Consult the factory for details. (1) Paint or any other coating applied over the factoryfinish will void all approvals and warranties. (3) cULus Listed as Corrosion Resistant. (4) FM Approved as Corrosion Resistant for SIN RA1414, RA1425, RA1435, and RA1485. (5) 200*F (93*C) maximum temperature rated sprinkler only. (5) VdS Approved for RA1425, RA1414, RA1418, and RA1475. (7) LPCB Approved for RA1425, RA1414, and RA1475. Material Data Frame: DZR Brass, QM Brass, or Low Lead Brass Deflector: CDA Alloy 220, 260, or 510 Load Screw\Pintle: CDA Alloy 360 or 544 Cup: CDA Alloy 651 or 693 Washer: Nickel Alloy 440 or 360, coated with PTFE Adhesive Tape Bulb: Glass Ordering Information Specify: 1. Sprinkler Model: [F1 FR28][F1 FR40][F1 FR42] [F1 FR42LL][F1 FRXLH][F1 FR56][F1 FR56LL] 2. Sprinkler Deflector/Orientation: [Pendent][Recessed Pendent] [Upright][Conventional][Horizontal Sidewall] [Recessed Horizontal Sidewall][Vertical Sidewall] 3. Sprinkler threads: [1/2-inch NPT][ISO 7-R1/2] 4. Sprinkler Temperature Rating: [135'F (57°C)][155'F (68°C)][175°F (79°C)][200°F (93°C)][286°F (141°C)] 5. Sprinkler Finish 6. Escutcheon Model: [F1][F2][FP] 7. Escutcheon Finish (where applicable) 8. Cover plate Model: [standard profile CCP 1/2-inch (12.7mm) adjustment][low profile CCP 5/16-inch (8.Omm) adjustment] 9. Cover plate Temperature Rating: [135'F (57'C) for use with Ordinary Temperature sprinklers][165°F (74'C) for use with Intermediate Temperature sprinklers] 10. Cover plate Finish Note: When Model F1 FIR Series Recessed sprinklers are ordered, the sprin- klers and escutcheons are packaged separately. 7. Reliable ... For Complete Protection Reliable offers a wide selection of sprinkler components. Following are some of the many pre- cision -made Reliable products that guard life and property from fire around the clock. • Automatic sprinklers • Flush automatic sprinklers • Recessed automatic sprinklers • Concealed automatic sprinklers • Adjustable automatic sprinklers • Dry automatic sprinklers • Intermediate level sprinklers • Open sprinklers • Spray nozzles • Alarm valves • Retarding chambers • Dry pipe valves • Accelerators for dry pipe valves • Mechanical sprinkler alarms • Electrical sprinkler alarm switches • Water flow detectors • Deluge valves • Detector check valves • Check valves • Electrical system • Sprinkler emergency cabinets • Sprinkler wrenches • Sprinkler escutcheons and guards • Inspectors test connections • Sight drains • Ball drips and drum drips • Control valve seals • Air maintenance devices • Air compressors • Pressure gauges • Identification signs • Fire department connection The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 100 years. Manufactured by Reliable Automatic Sprinkler Co., Inc. ® Recycled ® (800) 431-1588 Sales Offices Paper neliaul�d () 8-051 Sales Fax Revision lines indicate updated or new data. (914914) 82929-2042 Corporate Offices www.reliablesprinkler.com Internet Address EG. Printed in U.S.A. 12/21 P/N 9999970300 Submittal Information for Spears° Manufacturing Company IIIFI FlameGuard ° CPVC Fire Sprinkler System Date: Job Name: Engineer: Scope: This submittal covers the Spears® FlameGuard® CPVC Fire Sprinkler System suitable for residential and light hazard occupancies in accordance with The National Fire Protection Association (NFPA). The FlameGuard® System shall be sold as a complete system which consists of pipe, fittings and a specially formulated one-step primerless cement intended for use in wet, dry and pre -action systems in residential and light hazard Applications where the operating temperature/pressure does not exceed 175psi @ 150' F. (1.2 MPa @ 66' C) Product Specification: All CPVC fire sprinkler fittings and pipe shall be Spears® FlameGuard®. All solvent cement shall be Spears® FS-5 One -Step, and all thread sealant shall be Spears Blue 75Tm as produced by Spears® Manufacturing Company. All Spears® FlameGuard® CPVC fire sprinkler fittings shall be manufactured in the U.S.A. from a Chlorinated Polyvinyl Chloride (CPVC) compound having a minimum cell classification of 23447 in accordance with ASTM D1784. Fittings shall be manufactured in strict compliance to ASTM F438 or F439, as applicable. All CPVC fire sprinkler piping shall be manufactured in the U.S.A. from a Chlorinated Polyvinyl Chloride (CPVC) compound having a minimum cell classification of 23447 in accordance with ASTM D1784. Piping shall be manufactured in strict compliance to ASTM F442. All CPVC solvent cement shall be a primerless, one-step type manufactured in strict compliance to ASTM F493 and approved for use with CPVC fire sprinkler systems. All CPVC fire sprinkler fittings, pipe and solvent cement shall be listed by Underwriters Laboratories (UL®), Underwriters Laboratories Canada (ULC®) and/or Factory Mutual Research Corporation (FM Global) and/or LPCB for use in residential and light hazard wet, dry and pre -action systems and bear their authorized certification marks. Thread sealant shall be approved by the fitting manufacturer for use with CPVC fire sprinkler products. All CPVC fittings, pipe, solvent cement and thread sealant shall be certified by NSF International as applicable. Pipe and solvent cement shall be certified to UL 2818 GREENGUARD GOLD. Product Marking: FlameGuard® system components shall be orange in color for identification and include required markings and approvals prescribed in ASTM F442 for pipe GSFG-0221 Location: Contractor: and ASTM F438 or F439 for fittings. Pipe and cement shall have GREENGUARD GOLD marking. Installation: Spears® FlameGuard® CPVC Fire Sprinkler System shall carry a working pressure of 175 psi @ 150F (1.2 MPa @ 66' C) and shall be installed in accordance with Spears® Manufacturing Company FlameGuard® CPVC Fire Sprinkler Products Installation Instructions (FG-3) and Addendums. National Fire Protection Association (NFPA) Standards 13, 13D, and 13R must be referenced for design and installation requirements in conjunction with the Installation Instructions and applicable local codes. Installation practices such as pipe support spacing, bracing, allowance for thermal expansion/contraction, solvent cementing and handling and storage shall be in accordance with the manufacturer's instructions and this specification. Buried pipe shall be in accordance with NFPA 24 for supply mains. The piping system shall be joined using a chemically resistant one-step primerless solvent cement joining process conforming to ASTM F493. The system shall be protected from ultra violet (UV) light exposure from the sun or other source and protected from any chemicals that are not compatible with the CPVC materials including but not limited to fire stopping materials, plasticizers, incompatible thread sealants, etc. NOTE: FlameGuard® CPVC piping systems can be leak tested using oil -free compressed air up to 25psi but must also be hydrostatically tested as required per NPFA standard. Referenced Standards: ASTM D1784 — Rigid Vinyl Compounds ASTM F438 — CPVC Schedule 40 Fittings ASTM F439 — CPVC Schedule 80 Fittings ASTM F442 — CPVC SDR Pipe ASTM F493 — Solvent Cements for CPVC Pipe & Fittings NFPA 13, 13D, 13R — National Fire Protection Association Standards NFPA 24 — Installation — Private Fire Service Mains NSF International Standard 14/61 — Potable Water Approvals: NSF° — NSF International Standard 14/61 — Potable Water Underwriters Laboratories — Listing Agency FM Global —Listing Agency UL-GREENGUARD GOLD Certified UL 2818 LPCB — Loss Prevention Council Board 00004 '0000009/Z�Fg §Z0 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 510 CPVC - STEEL - COPPER HANGER SIZE - 3/4" thru 3" pipe. MATERIAL - Carbon Steel. FINISH - Mil. Galvanized. LISTING/APPROVAL - e@n5 203 - EX 4231, EX 2551 FUNCTION - To support horizontal piping - CPVC, Copper or Steel. Hanger in listed mounting positions - Top, Bottom or Side. Also, provides stability on vertical piping. INSTALLATION - Per NFPA 13, 13R, 13D and CPVC manufacturers instructions on top, bottom or side of building element. Space by pipe type. SPECIAL NOTE: When installing on CPVC sprinkler system pipe: Verify that all assembly components are cleaned of any surface oil. FASTENERS - UL Listed per NFPA 13 in WOOD: 3/4" - 3" CPVC pipe - #905 screw - no pre -drill. 3/4" - 3" Copper pipe - #905 screw - no pre -drill. 3/4" - 3" Steel pipe - 1/4"xl1/2" lag screw - no pre -drill. in STEEL - min. 18 GA. 3/4" - 3" CPVC pipe - 1/4" or #14 Tek Screw. 3/4" - 3" Copper pipe - 1/4" or #14 Tek Screw. 3/4" - 3" Steel pipe - 1/4" or #14 Tek Screw. FEATURES * Offset edge eliminates abrasion. * Retainer dimples secure hanger to pipe during installation. * Required AFCON#905 screw has 5/16" hex head - included. ORDERING - Part # and pipe size. *CAN ALSO BE USED TO REPLACE - #500 Pipe Strap #520 Tin Strap Specific AFCONproducts are exclusively designed to be compatible ONLY with other AFCONproducts including parts and fasteners, resulting in a listed sway brace, restrainer or hanger assembly. Be advised the following warranty restriction will apply. DISCLAIMER - AFCON will NOT warrant against the failure of its products when used in combination with other products, parts or systems not manufactured or sold by AFCON. AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damages of any kind, including but not limited to loss of business or profit, when non-AFCON products have been, or are used. 1/08 00004 '0000009/Z�Fg §Z0 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 511 SIDE MOUNT CPVC - COPPER HANGER SIZE - 3/4" thru 2" pipe. MATERIAL - Carbon Steel. FINISH - Mil. Galvanized. LISTING/APPROVAL - e*us 203 - EX 4231, EX 2551 FUNCTION - Hanger on CPVC and Copper pipe. INSTALLATION - Per NFPA 13, 13R, 13D and CPVC manufacturers instructions on top or bottom of beam. Space by pipe type SPECIAL NOTE: When installing on CPVC sprinkler system pipe: Verify that all assembly components are cleaned of any surface oil. FASTENERS - UL Listed per NFPA 13. in WOOD: 3/4" - 2" CPVC pipe - #905 screw - no pre -drill. 3A" - 2" Copper pipe - #905 screw - no pre -drill. in STEEL - min. 18 GA. 3/4" - 2" CPVC pipe - 1/4" or #14 Tek Screw. 3/4" - 2" Copper pipe - 1/4" or #14 Tek Screw. FEATURES * Offset edge eliminates abrasion. * Retainer dimples secure hanger to pipe during installation. * Required AFCON #905 screw has 5/16" hex head - included. ORDERING - Part # and pipe size. Hanger - Wood Stud Side View - For Drawings Below Hanger - Metal Stud Specific AFCONproducts are exclusively designed to be compatible ONLY with other AFCONproducts including parts and fasteners, resulting in a listed sway brace, restrainer or hanger assembly. Be advised the following warranty restriction will apply. DISCLAIMER - AFCON will NOT warrant against the failure of its products when used in combination with other products, parts or systems not manufactured or sold by AFCON. AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damages of any kind, including but not limited to loss of business or profit, when non-AFCON products have been, or are used. 1/08 00004 '0000009/Z�Fg §Z0 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 514 CPVC - COPPER STEEL OFFSET HANGER SIZE - SYSTEM PIPE: 3/4" thru 3" MATERIAL - Carbon Steel. FINISH - Mil. Galvanized.. LISTING/APPROVAL - IWMOU"s 203 - EX 4231, EX 2551 PATENT - No. 6,648,278. FUNCTION - Support horizontal piping: 3/4" -3" CPVC or Copper. • Support horizontal piping: 3/4" - 2" Steel. Size 3/4" - 2" provides listed vertical/lateral restraint and prevents upward movement of pipe that supplies a pendent sprinkler below a ceiling. Stabilize vertical piping. INSTALLATION - Per these instructions includingNFPA 13, 13R, 13D and CPVC manufacturers instructions. Listed 3/4" Install on horizontal or vertical mounting surface. Snap over pipe then squeeze strap back allowing pipe to slide freely. a When #905 threads are exposed in wood, install #906 backing nut. FASTENERS - UL Listed per NFPA 13 WOOD - 3/4" - 3" CPVC pipe - #905 screw- no pre -drill. 3/4" - 2" Copper pipe - #905 screw- no pre -drill. 3/4" - 2" Steel pipe - 1/4"xl 1/2" lag screw - no pre -drill. Thru 5/8" gypsum board - 1/4" x 2" lag screw. STEEL - min. 18 GA. - 3/4" - 3" CPVC pipe - 1/4" or #14 Tek Screw. 3/4" - 2" Copper pipe - 1/4" or #14 Tek Screw. 3/4" - 2" Steel pipe - 1/4" or #14 Tek Screw. CONCRETE: Required minimum load each fastener = 5(wt)+250lbs. 2 FEATURES * 1 1/2" Offset - loose fit allows pipe to slide. * 3/4" and 1" pipe size made with common center -line. * Patented design for superior strength. * Offset edge eliminates abrasion. * AFCON#905 screw included - 5/16" hex head. ORDERING - Part # and pipe size. AFCON#906 backing nut sold separately. #905 #906 1.5000 3.00 o � � M ® Listed Restraint 3/4" thru 2" Specific AFCONproducts are exclusively designed to be compatible ONLY with other AFCONproducts including parts and fasteners, resulting in a listed sway brace, restrainer or hanger assembly. Be advised the following warranty restriction will apply. DISCLAIMER - AFCON will NOT warrant against the failure of its products when used in combination with other products, parts or systems not manufactured or sold by AFCON. AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damages of any kind, including but not limited to loss of business or profit, when non-AFCON products have been, or are used. 9/08 00004 '0000009/Z�Fg §Z0 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 515 CPVC DOUBLE OFFSET HANGER SIZE -SYSTEM PIPE: 3/4" and 1" MATERIAL - Carbon Steel. FINISH - Mil. Galvanized. LISTING/APPROVAL - gu� m 203 - EX 4231 PATENT - No. 6,702,236 FUNCTION - Support/Restrain horizontal CPVC piping. INSTALLATION - Per these instructions including NPFA 13, 13R, 13D and CPVC manufacturers instructions. Install on horizontal or vertical mounting surface. FASTENERS - UL Listed per NFPA 13. WOOD: 3/4" and 1" #904 screw - no pre -drill. FEATURES * Double 1 1/2" offset * Center line matches AFCON #514. * 3/4" and V pipe size have common center -line. * Offset edge eliminates abrasion. * Required AFCON #904 screw included - 3/8" hex head. ORDERING - Part # and pipe size. Specific AFCONproducts are exclusively designed to be compatible ONLY with other AFCONproducts including parts and fasteners, resulting in a listed sway brace, restrainer or hanger assembly. Be advised the following warranty restriction will apply. DISCLAIMER - AFCON will NOT warrant against the failure of its products when used in combination with other products, parts or systems not manufactured or sold by AFCON. AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damages of any kind, including but not limited to loss of business or profit, when non-AFCON products have been, or are used. 3/08 4'�� SYSTEM � SENSOR WFDN Series Waterflow Detector The System Sensor WFDN series is compatible with schedule 7 through 40 steel pipe, for sizes 2 in. through 4 in. and compatible with schedule 10 through 40 steel pipe, sizes 5 in. through 8 in., and can be mounted in a vertical or horizontal position. Features • New directional cover allows installers and inspectors to easily see the direction of flow • UL-listed models are NEMA 4 rated • New cover provides a better seal, is lighter weight, not painted and corrosion resistant • Sealed retard mechanism immune to dust and other contaminants • Less exposed metal reduces shock hazard, plastic cover acts as insulator and is resistant to arcing • Visual switch activation • Audible switch activation (73 dBA) • Field -replaceable timer/switch assembly • Accommodates up to 12 AWG wire • Switch Synchronization activates both alarm panel and local bell or horn strobe • Tamper -resistant cover screws • Improved water sealing • Reduced product weight • Wire -ready terminals • Improved wiring with new terminal block layout • Snap -in optional cover tamper switch • Improved timer repeatability and accuracy Agency Listings C ®U L US O FM LISTED RV APPROVED S739 7770-1653:0231 3051266 The new WFDN Series waterf low detectors from System Sensor consists of a rugged, NEMA 4-rated enclosure that is more damage resistant than previous metal designs. The waterflow detector is designed for both indoor and outdoor use, with the widest available temperature range, from 32°F to 150°F. They are also approved for installation on the widest range of pipe schedules, sizes 2 in. through 4 in. are approved for installation on pipe schedules 7 through 40. UL-listed models are equipped with tamper -resistant cover screws to prevent unauthorized entry. Inside, two sets of SPDT (Form C) synchronized switches are enclosed in a durable terminal block with new layout designed to make wiring easy with wire ready terminals, COM terminals are on a different elevation, large barrier between switches and easy to read raised textured lettering all make wiring easy. An optional cover tamper switch is available, securely snaps into place, no tools required. The WFDN series incorporates a mechanical time delay feature, which minimizes the risk of false alarm due to pressure surges or air trapped in the fire sprinkler system. The larger and easy to turn timer dial makes setting the waterf low detector easy with high contrast pad printed markings. The dial offers three tabs to help with turning, with one larger tab located on the dial position for approximately 60 seconds, a notch is also indicated on the dial to locate approximately 30 seconds making setting the detector in dimmly lit locations easy. The WFDN series is designed for accuracy and repeatability. The detector also offers improved performance during vibration in riser applications where detectors are exposed to a large in rush of water. Waterflow Detector Specifications Vane -type waterflow detectors shall be installed on system piping as designated on the drawing and/or as specified herein. Detectors shall mount on any clear pipe span of the appropriate nominal size, either a vertical upflow or horizontal run, at least 6 in. from any fittings that may change water direction, flow rate, or pipe diameter or no closer than 24 in. from a valve or drain. Detectors shall have a sensitivity in the range of 4 to 10 gallons per minute and a static pressure rating of 450 psi for 2 in. — 8 in. pipes. The detector shall respond to waterflow in the specified direction after a preset time delay that is field adjustable. The delay mechanism shall be a sealed mechanical pneumatic unit with visual and audible indication of actuation. The actuation mechanism shall include a ethylene vinyl acetate vane inserted through a hole in the pipe and connected by a mechanical linkage to the delay mechanism. Outputs shall consist of dual SPDT switches (Form C contacts). Two conduit entrances for standard fittings of commonly used electrical conduit shall be provided on the detectors. A grounding provision is provided. Unless noted, enclosures shall be NEMA 4 listed by Underwriters Laboratories Inc. All detectors shall be listed by Underwriters Laboratories Inc. for indoor or outdoor use. Static Pressure Rating 450 PSI Operating Temperature Range 32°F to 150OF (0°C to 660C) Maximum Surge 18 Feet Per Second (FPS) Enclosure Rating* NEMA 4 — suitable for indoor/outdoor use Triggering Threshold 4-10 GPM Cover Tamper Switch Standard with ULC models, optional for Bandwidth (Flow Rate) UL models, part no. CTS Conduit Entrances Two openings for 1/2 in. conduit. Service Use Automatic Sprinkler: NFPA-13 NEMA 4 rated plugs One or Two Family Dwelling: NFPA 13D Residential Occupancies up to 4 Stories: NFPA 13R National Fire Alarm Code: NFPA-72 Contact Ratings Two sets of SPDT (Form C) Warranty 3 Years 10.0 A, 1/2 HP @ 125/250 VAC 2.5 A @ 6/12/24 VDC Compatible Pipe Steel water pipe, schedule 7 through 40* WFDN Field Wiring Diagram UL-LISTED SSM24-X COMPATIBLE SSV120-X CONTROL PANEL POWER 24VDC OR 120VAC INITIATING SUGGESTED EOL LOOP RESISTOR 1w gglim M j� �{ offim m n ff y 1 READY STATE Ordering Information NOTE: COMMON AND B-NO CONNECTIONS WILL CLOSE WHEN VANE IS DEFLECTED, I.E., WHEN WATER IS FLOWING. DUAL SWITCHES PERMIT APPLICATIONS TO BE COMBINED ON A SINGLE DETECTOR CONTACT RATINGS 125/250VAC 10 AMPS 24VDC 2.5 AMPS SCHEMATIC OF A -NC INDIVIDUAL SWITCH IN COM "NO WATERFLOW CONDITION B-NO BREAK WIREAS SHOWN FOR SUPERVISION OF CONNECTION. DO NOT ALLOW Iff STRIPPED WIRE LEADS TO EXTEND BEYOND SWITCH HOUSING. DO NOT LOOP WIRES. Pipe Size Hole Size Overall Dimensions, Installed U-BOLT NL PIPE SADDLE U-BC OVERALLWIDTH -PIPE DIAMETER+6.4 CM (2.5') Shipping Weights WFD20N WFD20NA 2 in. 11/4 in. 2.6 lbs. WFD25N WFD25NA 21/2 in. 11/4 in. 2.6 lbs. WFD30N WFD30NA 3 in. 2 in. 3.1 lbs. WFD40N WFD40NA 4 in. 2 in. 4.0 lbs. WFD50N WFD50NA 5 in. 2 in. 4.9 lbs. WFD60N WFD60NA 6 in. 2 in. 5.6 lbs. WFD80N WFD80NA 8 in. 2 in. 7.3 lbs. Accessories FS-RT Delay mechanism and switch assembly CTS Tamper -proof switch kit WFDW Tamper -proof wrench for cover * 2 in. - 4 in. rated for use with Schedule 7 through 40 pipe, 6 in. - 8 in. rated for use with Schedule 10 through 40 pipe. ��3825 �� Ohio Avenue • St. Charles, IL 60174 SYSTEM SENSOR Phone: 800 SENS0R2 •Fax: 630 377 6495 www.systemsensor.com ©2016System Sensor. Product sumatioct ochange without product for current product information, including the latest version of this data sheet. rcurre current nonce. version WFDS87903. 11/16 4,�� SYSTEM SSM/SSV Series Alarm Bells System Sensor' SSM and SSV series bells are low current, high decibel notification appliances for use in fire and burglary systems or other signaling applications. Features • Approved for indoor and outdoor use • Low current draw High dB output • Available in six-inch, eight -inch, and ten -inch sizes AC and DC models DC models polarized for use with supervision circuitry • Mount directly to standard four -inch square electrical box indoors SSM and SSV series pre -wired Agency Listings U` <O F M YA �.eMt w MEA LISTED APPROVED 7135-1653125 approved S4011 CS549 7135-1653:100 '1 Reliable Performance. The SSM and SSV series provide loud resonant tones. The SSM series operates on 24VDC and are motor driven, while the SSV series operates on 120VAC utilizing a vibrating mechanism. Simplified Installation. For indoor use, the SSM and SSV series mount to a standard four -inch square electrical box. For outdoor applications, weatherproof back box, model number WBB, is used. The SSM and SSV series come pre -wired, to reduce installation time. The SSM series incorporates a polarized electrical design for use with supervision circuitry. SSM/SSV Specifications Model shall be a SSM or SSV Series alarm bell. Bells shall have underdome strikers and operating mechanisms. Gongs on said bells shall be no smaller than nominal 678710-(specify size) with an operating voltage of 24VDC or 120VAC (specify by part number). Bells shall be suitable for surface or semi -flush mounting. Outdoor surface mounted installations shall be weatherproof (using optional WBB weatherproof electrical box). Otherwise bells shall mount to a standard 4-square electrical box having a maximum projection of 21/2-.. Bells shall be located as shown on the drawings or as determined by the Authority Having Jurisdiction. Bells shall be listed for indoor/outdoor use by Underwriters Laboratories and the California State Fire Marshal, and approved by Factory Mutual and MEA. Operating Temperature Range —31 °F to 140°F Operating Voltage SSM series: 24VDC SSV series:120 VAC Termination Provided with 2 sets of leads for in/out wiring Service Use Fire Alarm, General Signaling, Burglar Alarm Warranty 3 years Electrical Specifications Model Gong Diameter (inches) Nominal Voltage Operating Voltage Limit Maximum Current Sound Output (dBA) SSM24-6 6 Regulated 24VDC 16 to 33VDC DC-31.1 mA/ FWR-53.5mA 82 SSM24-8 8 Regulated 24VDC 16 to 33VDC DC-31.1 mA/ FWR-53.5mA 80 SSM24-10 10 Regulated 24VDC 16 to 33VDC DC-31.1 mA/ FWR-53.5mA 81 SSV120-6 6 Regulated 120VAC 96 to 132VAC 53mA 85 SSV120-8 8 Regulated 120VAC 96to 132VAC 53mA 82 SSV120-10 10 Regulated 120VAC 96 to 132VAC 53mA 82 * Sound output measured at Underwriter Laboratories, as specified in UL464 Ordering Information SSM24-6 SSM24-6A Bell, 6-124VDC, Polarized, 82dBA SSM24-8 SSM24-8A Bell, 8-124VDC, Polarized, 80dBA SSM24-10 SSM24-10A Bell, 10-, 24VDC, Polarized, 81 dBA SSV120-6 SSV120-6A Bell, 6-,120VAC, 85dBA SSV120-8 SSV120-8A Bell, 8-,120VAC, 82dBA SSV120-10 SSV120-10A Bell, 10-1 120VAC, 82dBA WBB Weatherproof back box for SSM and SSV series, when installed outdoors it SYSTEM C2007 System Sensor. 3825 Ohio Avenue • St. Charles, IL 60174 Product specifications subject to change without notice. Visit systemsensorcom for SENSOR' Phone: 800-SENSOR2 • Fax: 630-377-6495 urrentproductinformat -0260-dingth07-#1tversionofthisdatashee. A05-0260-008.4/07•#1676 ES-A-200013 Job Name Contractor Job Location Approval Engineer Contractor's P.O. No. Approval Series 2000B Double Check Valve Assemblies Sizes: 1/2" - 2" Series 2000B Double Check Valve Assemblies are designed to protect drinking water supplies for dangerous cross -connections in accordance with national plumbing codes and water authority requirements for non -health -hazard non -potable service applica- tions such as irrigation, fire line, or industrial processing. These valves meet the requirements of ASSE Std. 1015 and AWWA Std. C510 and are approved by the Foundation for Cross -Connection Control and Hydraulic Research at the University of Southern California. Features • Ease of maintenance with only one cover • Top entry • Replaceable seats and seat discs • Modular construction • Compact design •'/2" — 2" Cast bronze body construction • Top mounted ball valve test cocks • Low pressure drop • No special tools required •'/2" — 1 " have tee handles WAT111,11. It is illegal to use this product in any plumbing system providing water for human consumption, such as drinking or dishwashing, in the United States. Before installing standard material product, consult your local water author- ity, building and plumbing codes. Representative 3/4" 2000B (20mm) 1 —5 2" 2000B HC (50mm) Specifications A Double Check Valve Assembly shall be installed at each not- ed location. The assembly shall consist of two positive seating check modules with captured springs and rubber seat discs. The check module seats and seat discs shall be replaceable. Service of all internal components shall be through a single access cover secured with stainless steel bolts. The assembly shall also include two resilient seated isolation valves and four top mounted, resilient seated test cocks. The assembly shall meet the requirements of ASSE Std. 1015 and AWWA Std. C510. Approved by the Foundation for Cross - Connection Control and Hydraulic Research at the University of Southern California. Assembly shall be an Ames Fire & Waterworks Series 2000B. The information contained herein is not intended to replace the full product installation and safety information available or the experience of a trained product installer. You are required to thoroughly read all installation instructions and product safety information before beginning the installation of this product. Ames Fire & Waterworks product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measure- ments, please contact Ames Fire & Waterworks Technical Service. Ames Fire & Waterworks reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on Ames Fire & Waterworks products previously or subsequently sold. A WATTS Brand Available Models Suffix: B - Quarter turn ball valves LBV - less ball valves SH - stainless steel ball valve handles HC - 21/2" inlet/outlet fire hydrant fitting (2" valve) Pressure — Temperature Temperature Range: 33°F — 140°F (0.5°C — 60°C) Maximum Working Pressure: 175psi (12.1 bar) Dimensions - Weights Standards AWWA Std. C510, IAPMO PS31 4:3AssiFje Approvals Gc U P� o c QL us us 1015 B64.5 3/4" - 2" (LBV Models Only) • Approved by the Foundation for Cross -Connection Control and Hydraulic Research at the University of Southern California. (Excluding all LBV Models) • Horizontal and vertical "flow up" approval on all sizes. Suffix HC — Fire Hydrant Fittings dimension "A" = 231/2" (594mm) SIZE DIMENSIONS WEIGHT in. in. A mm in. B mm in. C mm in. F mm G in. mm H in. mm I in. mm lbs. kgs. 1/2 10 254 4% 117 27/16 62 5 127 3% 85 25/116 59 21/16 52 4.5 2 3/4 111/8 282 4 102 31/8 79 63/s 157 3'/16 87 21/8 54 15/16 33 5 2.3 1 131/4 337 5% 130 4 102 71/2 191 3% 85 111/16 43 111/16 43 12 5.4 11/4 16% 416 5 127 V16 84 91/2 241 5 127 3 76 2 50 15 6.8 11/2 1 163/4 425 1 47/a 124 31/2 89 1 93/4 248 1 513/16 148 1 31/8 79 1 211/6 68 15.86 7.2 2 1 191/2 495 1 61/4 159 1 4 102 1 13% 340 1 61/6 156 1 3'/6 87 1 211/8 68 1 25.75 11.7 Strainer sold separately Capacities As compiled from documented Foundation for Cross - Connection Control and Hydraulic Research at the University of Southern California lab tests. ATypical maximum system flow rate (7.5 feet/sec., 2.3 meters/sec.) kPa psi 11211 A y 83 12 0 69 10 (D 55 8 7 41 6 N 28 4 N 14 2 n 0 0 0 2 4 6 8 10 12 gpm AP 0 7.6 15.2 22.8 30.4 38 45.6 Ipm 5 7.5 10 fps 1.5 2.3 3.0 mps Flow Rate kPa psi H 152 22 0 124 18 96 14 0 H 69 10 . 41 6 a 14 2 31.11 kPa psi 96 14 N 83 12 o 69 10 y 55 8 41 6 y 28 4 L 14 2 0 0 41/wn AP 0 10 20 30 40 50 60 70 80 90 100 110 120 gpm 0 38 76 114 152 190 228 266 304 342 380 418 456 Ipm 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps Flow Rate kPa psi � 1112 83 12 N 69 10 0 55 8 y 41 6 7 28 4 N 14 2 i 0 0 L pp0 10 20 30 40 50 60 70 80 90 100 110 120 gpm 0 38 76 114 152 190 228 266 304 342 380 418 456 Ipm 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps Flow Rate AP 0 5 10 15 26 25 30 35 40 45 50 gpm 0 19 38 57 76 95 114 133 152 171 190 Ipm 7.5 15 fps 2.3 4.6 mps Flow Rate kPa psi y 110 16 0 83 12 y 69 10 3 55 8 N 41 6 28 4 a 14 2 0 5 10 15 20 25 30 35 40 45 50 55 60 gp AP 0 19 38 57 76 95 114 133 152 171 190 209 228 Ip 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps Flow Rate A WATTS Brand ES-A-2000B 1735 kPa psi J a m 211 N 83 12 p 69 10 55 8 41 6 3 N 28 4 i 14 2 0 0 0 25 50 75 100 125 150 175 200 gpm DP 0 95 190 285 380 475 570 665 760 Ipm m 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps Flow Rate USA: Backflow T: (978) 689-6066 • F: (978) 975-8350 • AmesFireWater.com USA: Control Valves T: (713) 943-0688 • F: (713) 944-9445 • AmesFireWater.com Canada: T: (905) 332-4090 • F: (905) 332-7068 • AmesFireWater.ca Latin America: T: (52) 81-1001-8600 • AmesFireWater.com © 2017 Ames Fire & Waterworks FIRE PROTECTION GAUGES Plastic Back and Steel Back oor 0 150 \ 100 SPRINK R 2OO AIR / W _-- 50 250 F _ psi I PRESSURE GAUGE 300 �. FOR FIRE PROTECTION R�• SERVICE x O A GCO ` �� R ...o•® ASSEMBLED IN USA 10.41A ' 6510160: AIR/WATER 300 PSI 6510161: WATER 300 PSI 6510163: AIR 300 PSI 6510162: AIR WITH RETARD 250 PSI d" A SINCE ©1981CO Application: Fluid medium which does not clog connection port or corrode copper alloy. Specifically designed for the fire sprinkler industry. Size: 4" (100 mm) Accuracy ± 3/2/3% of span (ASME B40.1 Grade B) Working Range ASSEMBLED IN U.S.A. Steady: 3/4 of full scale value Fluctuating: 2/3 of full scale value Short time: full scale value Approvals Operating Temperature UL listed (UL-393) Ambient: -40OF to 140°F (-40°C to 60°C) FM approved Media: max. 140OF (+60°C) Meets NFPA 25 Standards Temperature Error Additional error when temperature changes from reference temperature of 68°F Standard Scale (20°C) +0.4% for every 18' F (10°C) rising or falling. Percentage of span. PSI Standard Features Connection Material: copper alloy Lower mount (LM) - not available for 1'/2" size 1/4" NPT limited to wrench flat area Bourdon Tube: Material: copper alloy C-type Movement: Copper alloy, silicone dampened Dia: White plastic with stop pin - black & red lettering Pointer: Black aluminum Case: Black polycarbonate Window Acrylic, ultrasonically welded to case Standard Series • Type 110.10sp Order Options water air/water air System No. Location Spec Section Submitted By Date Approved Paragraph Date ARGCO.com ARGCO Updated 4/28/2022 © ARGCO A ,AGCO.— 800_854_1015 FIRE PROTECTION GAUGES Black Steel Painted Case �rlr i l!l / Qr qufiFrigj. ®� \� 40 5p poi 100saq�K 200 S �30 sawrac 00 7p► ZL eIR �50 250� 300 yp 250 • gEtcco � � •_ 9er�9 i�r�✓ 00}150 �1i2��ii• , ���� 11�1i0+ ll�i� _ rf' 100, zoo 100sp 200 WA 4 �5 a 250= =50 250 100 w 7tr0 Z� ti U� O 6510164STL: AIR/WATER 300 PSI 6510165STL: WATER 300 PSI 6510166STL: AIR 300 PSI 6510166STL: AIR WITH RETARD 250 PSI Application: Fluid medium which does not clog connection port or corrode copper alloy. Specifically designed for the fire sprinkler industry. Size: 4" (100 mm) Accuracy ± 3/2/3% of span (ASME B40.1 Grade B) Working Range Steady: 3/4 of full scale value Fluctuating: 2/3 of full scale value Short time: full scale value Operating Temperature Ambient: -40OF to 140OF (-40°C to 60°C) Media: max. 140OF (+60°C) Temperature Error Additional error when temperature changes from reference temperature of 680F (20'C) +0.4% for every 180 F (10°C) rising or falling. Percentage of span. Standard Features Connection Material: copper alloy Lower mount (LM) - not available for 11/2" size 1/4" NPT limited to wrench flat area Bourdon Tube: Material: copper alloy C-type Movement: Copper alloy, silicone dampened Dia: White plastic with stop pin - black & red lettering Pointer: Black aluminum Case: Black Painted Steel System No. Location Submitted By Date "AR CO SINCE © 1953 1.18" 55' t1/4" NPT ASSEMBLED IN U.S.A. Approvals UL listed (UL-393) FM approved Meets NFPA 25 Standards Standard Scale PSI Window Acrylic, ultrasonically welded to case Standard Series • Type 110.10sp Spec Section Paragraph Approved Date ARGCO.com VARGCO Updated 4/28/2022 © ARGCO I X A-..com aoo_as,_,o,s FIRE PROTECTION GAUGES Plastic Back and Steel Back 114, //3/ 150 � 100 00 SPRINK R 2 AIR / W �50 250� psiARQC0 300 Mg NEMA and IP Ratings for Industrial Instrumentation NEMA Ratings The NEMA Rating system is a standard primarily used in North America for rating enclosures. The table below shows the equivalent IP ratings. NEMA standards meet or exceed the IP ratings listed, but the reverse cannot be assumed. NEMA Description Equiv. Rating IP Rating 1 GENERAL PURPOSE. Intended for use indoors. IP 10 2 GENERAL PURPOSE. Intended for use indoors with additional drip protection. IP 11 GENERAL PURPOSE WEATHER -RESISTANT. Intended for use outdoors with 3 & 3S protection from windblown dust, rain and sleet, and undamaged by the formation of ice. IP 54 GENERAL PURPOSE WEATHER -RESISTANT. Intended for use outdoors with 3R protection from falling rain an sleet, and undamaged by the formation of ice. IP 14 4 & 4X GENERAL PURPOSE WEATHER-PROOF. Intended for use indoors or out doors with IP 65 protection from wash down enUronment and corrosion resistance. GENERAL PURPOSE DUST -TIGHT. Intended for use indoors or outdoors with protection 5 from dust provided by gaskets. IP 52 GENERAL PURPOSE SUBMERSIBLE. Intended for use indoors or outdoors with 6 & 6P protection from occasional submersion. IP 67 HAZARDOUS. Intended for indoor use in Class I, Groups A, B, C, and D environments 7 per NFPA rating system. HAZARDOUS. Intended for indoor or outdoor use in Class I, Groups A, B, C, and D 8 environments per NFPA rating system. HAZARDOUS. Intended for indoor or outdoor use in Class II, Groups E, F, and G 9 environments per NFPA rating system. INDUSTRIAL USE. Intended for use in industrial applications with protection from dust 12 & 12K and non corrosive liquid drip. IP 52 13 INDUSTRIAL USE. Intended for use in industrial applications with protection from dust, IP 54 spraying water, oil and non corrosive liquid drip. ARGCO.com VARrjC0 Updated 4/28/2022 © ARGCO FIRE PROTECTION GAUGES Plastic Back and Steel Back NEMA and IP Ratings for Industrial Instrumentation IP Ratings The IP Rating system (or International Protection Code) is a worldwide standard for rating enclosures. The rating is written as IP-"XY" where X and Y are replaced by the first and second digits as listed in the tables below. Degree of protection from contact or foreign body First Digit grief Description 0 1 No special protection. Generally not used for 2 pressure or temperature instruments. 3 Protected against solid objects > 2.5 mm in diameter 4 Protected against solid objects > 1.0 mm in diameter 5 Dust protected 6 Dust -tight Degree ofwater protection Second Digit Brief Description 0 No special protection. Generally not used for pressure or temperature instruments. 1 Protected against dripping water 2 Protection against dripping water when case is tilted up to 15' 3 Protected against spraying water 4 Protected against splashing water 5 Protected against a water jet 6 Protected against heavy jet spray 7 Protected against limited submersion 8 Protected against continuous submersion ARGCO.com ARGCO Updated 4/28/2022 0 ARGCO ARGCO.com 6GG-asa- G 6 SPEARS° MANUFACTURING COMPANY FS-5 RED 4a mf`�, CP1IS FIRE S0RINIMER PRODUCTS TECHNICAL SPECIFICATIONS Low VOC CPVC Solvent Cement PRODUCT: Spears® F1ameGuard® FS-5 RED One -Step (no primer required) CPVC cement specifically formulated and approved for use with Spears® F1ameGuard® and other approved CPVC Fire Sprinkler Products with interference fit through 3". INTENDED USE: Spears® FS-5 is approved for use with Spears® F1ameGuard® and other approved CPVC Fire Sprinkler Products. See publication FG-3, F1ameGuard® Installation Instructions for additional application details. GENERAL PRODUCT SPECIFICATIONS: COLOR: Red RESIN: CPVC SPECIFIC GRAVITY. 0.985 f 0.04 BROOKFIELD VISCOSITY Heavy Body - Minimum 1600 cP@ 73 f 2°F (23°C +1° C) RELATIVE SET: Fast MAX VOC EMISSIONS: 490 G/L per SCAQMD Rule 1168/316A SHELF LIFE: 2 years from date stamped on the bottom of container. Note: Product usability is limited by the evaporation of the solvents when the container is opened and can cause the cement to thicken and reduce its usefulness. Always seal the can tightly between uses to prevent the solvent from becoming thickened, stringy or jelled. Do not add thinners to change viscosity of thickened cement. Significant changes in cement properties can result. CONFORMANCE STANDARDS AND APPROVALS: • NSF®/ANSI Standard 14 Listed and Certified for compliance to ASTM F493 • NSF®/ANSI Standards 14/61 Listed and Certified for Potable Water, Drain Waste and Vent, and Sewer service use (NSF®-PW, DWV, SW) NSF® Listed and Certified to requirements of the Uniform Plumbing Code (NSF® U.P. Code); NSF® Certified Lead -Free. • FM® and UL® approved for use with Spears® F1ameGuard® and other approved CPVC Fire Sprinkler Products. • Meets SCAQMD Rule 1168/316A for Compliance with LEED® (Leadership in Energy and Environmental Design). Low VOC product credit can be claimed for LEED Green Building Rating System - Indoor Environmental Quality. PACKAGING, SHIPPING & TRANSPORTATION INFORMATION: Can Size Standard Case Ouantity Pint 12 Quart 12 The following is general information for ground shipping, see SDS FS5-6 for additional detail. Proper Shipping Name: Adhesive Exceptions for Quantities < 1 liter Hazard Class: 3 Classification: Limited Quantity Identification Number: UN 1133 49CFR172.315 Marking: Packing Group: II <:> Label Required: Class 3 Flammable Liquid Note: Purchasers who may repackage this product must also conform to all local, state and federal labeling, safety and other regulations. SAFETY & USE PRECAUTIONS: WARNING: CAN CAUSE SERIOUS EYE IRRITATION. HARMFUL IF INHALED. MAY CAUSE DROWSINESS OR DIZZINESS. MAY CAUSE RESPIRATORY IRRITATION. REPEATED EXPOSURE MAY CAUSE SKIN DRYNESS OR CRACKING. KEEP OUT OF REACH OF CHILDREN. Do not take internally. Keep away from heat, spark, open flame, other sources of ignition. Vapors may ignite explosively. Use only in well ventilated area; if not well ventilated, use forced ventilation or NIOSH approved respirator. Avoid breathing vapors. Do not smoke, eat or drink while using. Avoid contact with skin and eyes. Use skin and eye protection. Eye contact may cause injury. Keep container closed when not in use. Contains Tetrahydrofuran (CAS#109-99-9); Methyl Ethyl Ketone (CAS# 78-93-3); Cyclohexanone (CAS# 108-94-1); Acetone (CAS# 67-64-1); CPVC Resin (CAS# 68648-82-8). FIRST AID Contact with eyes: Flush eyes immediately with plenty of water for 15 minutes and seek medical advice immediately. Skin contact: Remove contaminated clothing and shoes. Wash skin thoroughly with soap and water. If irritation develops, seek medical advice. Inhalation: Remove to fresh air. If breathing is stopped, give artificial respiration. If breathing is difficult, give oxygen. Seek medical advice. Ingestion: Rinse mouth with water. Give 1 or 2 glasses of water or milk to dilute. Do not induce vomiting. Seek medical advice immediately. INSTALLATION & INSTALLER TRAINING FS-5 is specialty cement; see Spears® publication FG-3, F1ameGuard® Installation Instructions, for specific details and limitations. Installation instructions are printed on the can label and instructional information is available on Spears® website at www.spearsmfg.com. Certified Installers Training for F1ameGuard® CPVC Fire Sprinkler Systems is also available. Contact Spears® for additional instructional information or formal training. AVOID USE AROUND DRY GRANULATED CALCIUM HYPOCHLORITE While CPVC Fire Sprinkler Systems typically are not disinfected, a fire or explosion may result if dry granular calcium hypochlorite is used to disinfect plastic piping systems that are exposed to organic vapors found in solvent cements, cleaners or primers when a water solution is not used. Calcium hypochlorite is a strong oxidizer and common in Pool & Spa chemicals such as "pool -shock". If required, it is recommended to purify lines by pumping nonvolatile chlorinated water into the piping system. Do not store or use dry granular calcium hypochlorite near solvent cements, cleaners and primers. Refer to Safety Data Sheet (SDS), Spears° publication FS5-6, for more information. LIMITED LIFETIME WARRANTY: Spears® Manufacturing Company warrants all new Solvent Cement and Primer products shall be free from defects in material and workmanship for the specified product shelf life based on the assigned manufactured date on the original product container. If any such product becomes defective under normal use and storage conditions during this warranty period, Spears® will replace the nonconforming solvent cement or primer product without charge. Spears® liability will be limited, without exception, to product replacement. Spears® further warrants properly made solvent cement joints using this product for the life of the system. See Spears® standard Limited Lifetime Warranty for additional detailed information and exclusions. Progressive Products From Spears® Innovation & Technology SPEARS® MANUFACTURING COMPANY • CORPORATE OFFICE rN4,"""'V 15853 Olden St., Sylmar, CA 91342 • PO Box 9203, Sylmar, CA 91392 (818) 364-1611 • www.spearsmfg.com © Copyright 2013 Spears® Manufacturing Company. All Rights Reserved. Printed in the United States of America 10113. FS-5TS-1013