approved FIR2022-0072+Fire_Sprinkler_Plan+7.26.2022_11.37.38_AM+3012732See South County
Fire Remarks
PAT) ORCHES DO NOT
REQUIRE PROTECTION
PER NFPA-1 3D 8.3.4. TYP.
1<0 CO E N 0'01 0
PIPING INSTALLED TIGHT TO BEDROOM 1
SPRINKLERS ARE SPACED BOTTOM CHORD OF ATTIC 1 0 '-0 "
TO A MAX OF 20 'x20 ' TRUSSES AND TENTED
PATIO WITHIN DASHED LINE. SEE
DETAILON THIS PAGE.
FAMILY RM
10 '-0 " 9'-0"
loll• (10'MAX)
00
I
o
I �
0 0
0
DE,I Area#: 1 HAZARD: LIGHT
Zme 1 SystEm Typa WET
Q,
V�
Lrcatim LOFT
�4
Qa•I
FIONIng0itllsts: 2
SPRINKLERS ARE SPACED
DEmity: 0 .1 0 REmdeArea 1 9 1
TO A MAX OF 20 'x20 '
ROOF
Flom 4 0 .2gi-n @ 7 6 p2
a
CdaJeticnSefe:y: 4pli .8
BATHROOMS UNDER 55 S.F. DO
V
II�ILl�S 0 gm Hcse�lONe
/'NFPA-13D
NOT REQUIRE PROTECTION PER
8.3.2, TYP.
11 BEDROOM 3
SAUNA
BONUS RM
1 0 '-0 "
10 '-0 '
d16'-10" 9'-4"
ui
o
W.I.C.
lot
•
N 24
33 BATH
1 •
1
1
9,_0
•
4
15-0 1-8 �0
10-6 4
(10'MAX)
4'-0
N LOFT
I
a,
•
1
6-5
10 '-0 =
i
00
10'4
CLOSETS 24 DO
1"UPT
' 02 • DN
UNDER S.F.
ABOVE
1 1 1
NOT REQUIRE PROTECTION
SPRINKLER
PIPING INSTALLED TIGHT TO
UTILITY
2-10 ,•3
4-1 -
PER NFPA-1 3D 8.3.3, TYP.
PROTECTION
BOTTOM CHORD OF ATTIC
o
BATHROOMS UNDER 55
REQUIRED
TRUSSES AND TENTED. SEE
04
E
N
S.F. DO NOT REQUIRE
ABOVE RISER
DETAILON THIS PAGE.
El
®
10 I o
VE
PROTECTION PER
1
OV GE
NFPA-1 3D 8.3.2, TYP.
RISER LOCATION.
CLOSETS UNDER 24 S.F. DO
0 0
E
SEE DETAIL1 ON FP-1
NOT REQUIRE PROTECTION
o
0 0
$,_1
PER NFPA-1 3D 8.3.3, TYP.
BEDROOM 2
•
o
•
1
REMOTE Cn
I
9'-0"
-
AREA #1
rn ENTRY
(10'MAX)
4'-0"
DECK
GARAGE DOES NOT REQUIRE
COVERED PORCH PROTECTION PER NFPA-1 3D 8.3.4
3 CAR GARAGE
1-1 /2" U.G. WATER
0o MAIN FLOOR FIRE PROTECTION PIPING PLAN
SCALE: %8" = 1 '-0 "
GENERALNOTES
1. INTERNATIONALBUILDING CODE (20 1 5)
1 .1 . SPRINKLERED AREA (APPROXIMATE - SEE ARCHITECTURAL PLANS FOR ACTUAL)
MAIN FLOOR = 1 537 S.F.
UPPER FLOOR = 1 883 S.F.
1.2. INSTALLATION STANDARDS:
SPRINKLER SYSTEM DESIGNED AND INSTALLED PER NFPA-1 3D (20 1 3)
2. SPRINKLER PIPE TYPES:
-WET-
2.1 . 1 " BRANCH LINES TO BE SPEARS CPVC PIPING WITH CEMENTED FITTINGS
2.2. 1 " MAIN TO BE SPEARS CPVC PIPING WITH CEMENTED FITTINGS
3. DESIGN CRITERIA
ALLAREAS PROTECTED ACCORDING TO NFPA 1 3D WITH SPRINKLER FLOW DETERMINED BY
REQUIREMENTS SET FOURTH BY NFPA 1 3D AND SPRINKLER HEAD LISTING DATA. PIPING IS SIZED
ACCORDINGLY BY HYDRAULIC CALCULATIONS. REFER TO SPRINKLER HEAD DATA SHEETS FOR DISCHARGE
CRITERIA.
SPRINKLER PROTECTION IS PROVIDED FOR LIVING AREAS AND THE FOLLOWING AREAS PER 1 3D:
• CLOSETS OVER 24 S.F.
• BATHROOMS OVER 55 S.F.
SPRINKLER PROTECTION IS NOT PROVIDED FOR THE FOLLOWING AREAS:
• CLOSETS UNDER 24 S.F. PER 8.3.3
• BATHROOMS UNDER 55 S.F. PER 8.3.2
• PATIOS/PORCHES PER 8.3.4
• ATTIC PER 8.3.5
• GARAGE PER 8.3.4
4. NOTES:
4.1. ALLMATERIALTO BE NEW AND MEET U.L STANDARDS
4.2. HANGERS TO BE INSTALLED IN ACCORDANCE WITH NFPA 13 (20 1 3) - SEE PLAN FOR HANGING REQ.
SYMBOLS USED ON DRAWINGS:
+96" PIPE ELEVATION A.F.F
OH1 ROOM HAZARD CLASSIFICATION (ALLROOMS ARE CONSIDERED LIGHT HAZARD UNLESS
NOTED)
F1 HYDRAULIC CALCULATION JUNCTION POINT
5. SCOPE OF WORK:
5.1. MODERN FIRE PROTECTION WILLBE INSTALLING A NEW SPRINKLER SYSTEM. THERE WILLBE ONE
WET ZONE THAT WILLCOVER THE BUILDING.
5.2. ALLAREAS OF THE BUILDING TO BE INSTALLED AND COVERED IN ACCORDANCE WITH THE LOCAL
AUTHORITY HAVING JURISDICTION AND PER NFPA 1 3D (20 13).
TYPICALWALLSECTION
See South County
Fire Remarks
UPPER F
N U SCALE: Y8" = 1 '-0 "
DECKS DO NOT REQUIRE
PROTECTION PER
N:PPA-13D 8.3.4, TYP.
MASTER RM
1 0 '-0 "
4-2 3-2
CLOSET
m
9'-0"
10'MAX)
MASTER BATH
10 '-0 "
Approved by Fire
08/15/2022 AFM /CFI tte er
Approved set of plans must be on site at the time of
inspection. Failure to provide the approved set may result
in a re -inspection fee. System drain(s) required at riser and
must drain to the exterior. If riser is above lowest grade,
2nd drain required and signage at riser indicating location.
Systems require signage IAW NFPA 13D. Coverage
required to the following areas:
Clothes closets, linen closets and pantries exceeding 24
square feet in area, with the smallest dimension greater the
T and having wall and ceiling surfaces of gypsum board.
Bathrooms more than 55 square feet in area. When fuel
fired equipment is present on covered decks or porches, or
if living space above, at least one quick -response
intermediate temperature sprinkler shall be installed above
the equipment or area under living space.
All fuel fired appliances, except attics if above all living
areas.
LDOR FIRE PROTECTION PIPING PLAN
PIPING RAN TIGHT ON TOP OF BOTTOM
CHORDS OF ATTIC TRUSSES TO KEEP PIPING
AS CLOSE TO WARM SPACE AS POSSIBLE.
THICKNESS MUST BE ADEQUATE TO SUSTAIN
WATER FILLED PIPE @ 40 DEGREES AT ALLTIMES
VISQUEEN TO ACT
AS A THERMAL
BARRIER (BY � INSULATION (BY OTHERS)
OTHERS)
PIPE CLAMP )—B _ LPIPE
WOOD JOIST
STEELSCREW
GYP. BOARD CLG.
NOTES:
• DO NOT INSTALL INSULATION BETWEEN THE SPRINKLER PIPING AND THE CEILING.
• THE VISQUEEN AND INSULATION, PLACED OVER THE SPRINKLER PIPING, IS NECESSARY
TO ACT AS A THERMAL BARRIER.
• ADEQUATE HEATING MUST BE MAINTAINED BY OTHERS, AT ALLTIMES.
TENTING DETAIL
RISER LEGEND
1 . 1-1 /2' UNDERGROUND WATER SERVICE (BY OTHERS)
(FLUSHING & TESTING OF THE UNDERGROUND SHALLBE
COMPLETED PRIOR TO THE SPRINKLER SYSTEM HOOKUP.
UNDERGROUND PAPERS ARE TO BE SUPPLIED TO THE "FP"
CONTRACTOR BY THE G.C.)
2. 1-1 /2' x 1" REDUCER
3. 1 " AMES 20 0 0 B BACKFLOW PREVENTER
4. 1" RISER MANIFOLD w/ FLOW SWITCH, PRESSURE GAUGE, &
TEST AND DRAIN
5. 1 " THREAD X CPVC ADAPTER
6. 1 " TO SYSTEM
7. MAIN DRAIN PIPED TO OUTS"r)E
ALLWIRING/INTERFACING
OF ALARMS BY OTHERS
"ALLPIPING PENETRATING THE
EXTERIOR WALLTO BE GALVANIZED
RISER DETAIL
1 SCALE: 1 " = 1 '-0 "
2
SYM
CNT
POSITION
FINISH
TEMP
K
NPT
SIN
MFG.
MODEL#
ESCUTCHEON
Q
22
PENDENT
WHITE
165
4.9D
1/2"
RAO 616
RELIABLE
RFC
CONCEALED
2
PENDENT
WHITE
212
4.�D
1/2"
RAO 616
RELIABLE
RFC
CONCEALED
®
1
PENDENT
WHITE
286
1 5.60
1/2"
RA1414
RELIABLE
I F1FR56
I EXTENDED
SPRINKLER HEAD LEGEND
el ,,
;e ,Wood
i' ManLE-
i
SAMMY
Scrav
- — _AT Rod
Hagf Rirg
IPS AUTOGRIP HANGER
(SAMMY SCREW)
z "I fel SAMMY
ScreN
i
,
f't
HaT Erg
IPS AUTOGRIP HANGER
(SIDE SAMMY SCREW)
HANGER DETAILS
ManLE-
WOOD SCREW WOOD SCREW
MAIN OR BRANCH `\
LINE NO BLOCK HANGER
CPVC NO BLOCK HANGER
FIR2022-0072
RECEIVED
Aug 03 2022
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
WASHINGTON STATE
CERTIFICATE OF COMPETENCY
FIRE PROTECTION SPRINKLER
SYSTEMS
Jared Reid Van Gammeren
9130-0820-C
II Modern Fire Protection. LLC
N
MODERFP804MA
d
a
Elmo,
�
Expires
�
Slgnatur n
12131122
MAXIMUM DISTANCE BETWEEN HANGERS (FT. —IN.)
NOMINALPIPE SIZE (IN.)
Y4„
Y4"
1 Y2"
2„
2 Y2"
3„
4„
6„
8„
SPEARS CPVC
5-6
6-0
6-6
7-0
8-0
90
10 -0
NA
NA
NA
NFPA 13 HANGER SPACING
FIRE SPRINKLER RISER.
SEE DETAIL1 ON FP-1
0o SITE PLAN
Nl�) SCALE: 1 " = 2 5'-0 "
JOHN TRANG
RESIDENCE
FIFE: 2 %-0 "
1 " WATER METER
37
-75' 1-1 /2" WATER
LINE (BY OTHERS)
FLOW T ES T IN
STATIC: 1 19PS1
RESID: 75 PSI
FLOW: 1743 GPM
DATE: 0 6/13/22
FLOW TEST INFORMA'
PROVIDED BY CITY O
EDMONDS ON 0 6/13/.
ELEV: -29)
�J SCALE: %$" = 1 '-0 "